RPA Parallel System
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
RPA Parallel System
(option)
The RPA PARALLEL SYSTEM is entered any time the “ RPA ” key is pressed.
This screen is only displayed when the RPA
Parallel System is available (option).
The LCD screen will provide some information on the RPA Parallel System.
In this mode the keys perform the following functions:
Shows the main screen MEASURES.
See Section 6.2.
Note! During IEMi Operation Mode, the “Percent Load” information is computed based on on-line Units only.
Shows the main screen EVENTS.
See Section 6.3.
Shows the main screen SETUP.
See Section 6.4.
Shows the main screen COMMANDS.
See Section 6.5.
Return to HOME screen.
Key to reset general alarm and buzzer.
Shows the screen for the next RPA Parallel System Units
Shows the screen of the previous RPA Parallel System Units.
52/86
RECT
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
Description of the RPA Parallel System screen’s main elements
Rectifier green color = On / grey color = Off
CHRG / BST Battery Charger / Booster green color = On / grey color = Off
INV Inverter green color = On / grey color = Off
BYP Automatic Bypass green color = On / grey color = Off
UPS1÷6
M
Number of UPS in the RPA Parallel System
Master Unit of the RPA System Parallel
Input Utility status (for RECT – Rectifier and BYP - Bypass)
Battery status (for CHRG – Battery Charger)
Green color = On / Grey color = Off
Q1 Load output switch
Q2 Manual Bypass switch
(only if provided by customer)
Open
Closed
Examples of the main RPA Parallel System Unit status situations
Open
Closed
UPS with Load supplied by Inverter or
On-line UPS in IEMi Operation Mode
UPS with Load supplied by Automatic Bypass
UPS with Load supplied by Battery
UPS in stand-by in an
Redundant RPA Parallel System or
Stand-by UPS in IEMi Operation Mode
UPS in eBoost Operation Mode
UPS with Load supplied by Manual Bypass
(only if provided by customer)
advertisement
Related manuals
advertisement
Table of contents
- 6 Safety rules
- 8 Safety symbols and warnings
- 8 Cyber security
- 9 Layout
- 9 Layout TLE Scalable Series 40 to
- 10 Introduction
- 11 Description
- 12 Block diagram and main elements
- 13 Operation modes
- 13 Normal VFI Operation Mode (Voltage Frequency Independent)
- 13 SEM Operation Mode (Super Eco Mode)
- 14 Utility Failure Operation
- 14 Utility Recovery Operation
- 15 Automatic Bypass
- 16 RPA Parallel System operation
- 16 Introduction to the RPA Parallel System
- 17 Features of RPA Parallel System
- 17 System control
- 17 Synchronization
- 17 Load sharing
- 18 IEMi Operation Mode (option)
- 19 UPS paralleled on the same Battery
- 20 Service and technical support
- 20 Warranty
- 21 Recycling instructions
- 22 Control Panel
- 23 LCD screen
- 23 Home screen
- 24 Description of the selection keys
- 25 Description of the signaling LEDs
- 28 Measures
- 32 Events
- 34 Events (alarms and messages)
- 34 Alarms list
- 38 Messages list
- 41 Setup
- 47 Commands
- 51 RPA Parallel System
- 53 Operation
- 54 Procedures for single TLE Scalable Series 40 to
- 54 Initial start-up of the TLE Scalable Series 40 to
- 58 Complete UPS shut-down
- 59 Restore to normal operation after “System shutdown” with Load not supplied
- 60 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 61 Procedures single TLE Scalable Series 40 to 150 functioning as Frequency Converter
- 61 Initial Start-up of the TLE Scalable Series 40 to 150 as Frequency Converter
- 65 Complete shut-down of the TLE Scalable Series 40 to 150 as Frequency Converter
- 66 Restore to normal operation after “System shutdown” with Load not supplied
- 67 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 68 Procedures for TLE Scalable Series 40 to 150 RPA Parallel System
- 68 TLE Scalable Series 40 to 150 RPA Parallel System start-up
- 73 Separate a UPS Unit from the RPA Parallel System (System Redundancy)
- 75 Reconnect a UPS Unit to RPA Parallel System
- 77 Complete RPA Parallel System shut-down
- 78 Restore to normal operation after “System shutdown” with Load not supplied
- 80 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 82 Options
- 82 Connectivity options
- 82 Options in UPS cabinet
- 82 Options in additional cabinets
- 83 Maintenance
- 83 Service check
- 83 Fans and ventilation
- 83 Other components with limited lifetime
- 84 Battery
- 84 UPS room conditions and temperature
- 84 Preventive maintenance program
- 85 Notes
- 85 Notes Form