73/86 TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
7.3.2
Separate a UPS Unit from the RPA Parallel System (System Redundancy)
Note!
Make sure that “SEM - Super Eco Mode” Operation Mode is disabled before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before starting this procedure.
Note!
The Load is powered by the UPS RPA Parallel System.
One UPS Unit of the RPA Parallel System has to be turned OFF, while the Load is shared between the other Units supplying the Parallel Bus.
The Control Bus cable connecting J1A - J2A and J1B - J2B cannot be connected or disconnected after the system has been powered ON.
Initial status:
Load supplied by all Inverters of the RPA Parallel
System.
1. Disconnect the Inverter performing the “Inverter OFF” command on the Unit to separate.
1 - Perform the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF .
2 - Repeat the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF .
With Redundant System, performing the “Inverter OFF” command the Inverter shuts down and it will stay OFF.
Performing the “Inverter OFF” command the Load is transferred to the Utility and the Inverter remains operating, it means the system is not redundant.
In this case is not possible to switch-OFF one Unit without transferring the Load on Mains.
• Load supplied by Inverter(s) of the other Unit(s) of the RPA Parallel System.
Synoptic diagram of the Unit to separate
2. Open “Q1 - UPS Output switch” (Pos. O) on the Unit to separate.
• LED ALARM is lit.
Synoptic diagram of other Units
Synoptic diagram of the Unit to separate Synoptic diagram of other Units
Continue →
74/86 TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
3. Perform the command “Module shutdown” on the Unit to separate only when the symbol Q1 in the Synoptic Diagram is shown open.
Perform the command “Module shutdown” through the screen:
Commands 1 / Module shutdown / SHUTDOWN .
Synoptic diagram of the Unit to separate Synoptic diagram of other Units
4. Disconnect the Battery on the Unit to separate by opening the “ Battery Cabinet Breaker ” (Pos. O).
Press “MUTE” key to reset Acoustical Alarm. LED ALARM remains lit.
Synoptic diagram of the Unit to separate Synoptic diagram of other Units
Note!
Before performing the next procedure (5) wait 5 minutes for DC-link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link 1 and DC-link 2 voltage has reached 10Vdc.
5. Disconnect the Utility supply on the Unit to separate.
LCD display is OFF
Synoptic diagram of the Unit to separate
End of Procedure
Synoptic diagram of other Units
Danger!
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Note!
For any further intervention contact your ABB Service Center.
advertisement
Related manuals
advertisement
Table of contents
- 6 Safety rules
- 8 Safety symbols and warnings
- 8 Cyber security
- 9 Layout
- 9 Layout TLE Scalable Series 40 to
- 10 Introduction
- 11 Description
- 12 Block diagram and main elements
- 13 Operation modes
- 13 Normal VFI Operation Mode (Voltage Frequency Independent)
- 13 SEM Operation Mode (Super Eco Mode)
- 14 Utility Failure Operation
- 14 Utility Recovery Operation
- 15 Automatic Bypass
- 16 RPA Parallel System operation
- 16 Introduction to the RPA Parallel System
- 17 Features of RPA Parallel System
- 17 System control
- 17 Synchronization
- 17 Load sharing
- 18 IEMi Operation Mode (option)
- 19 UPS paralleled on the same Battery
- 20 Service and technical support
- 20 Warranty
- 21 Recycling instructions
- 22 Control Panel
- 23 LCD screen
- 23 Home screen
- 24 Description of the selection keys
- 25 Description of the signaling LEDs
- 28 Measures
- 32 Events
- 34 Events (alarms and messages)
- 34 Alarms list
- 38 Messages list
- 41 Setup
- 47 Commands
- 51 RPA Parallel System
- 53 Operation
- 54 Procedures for single TLE Scalable Series 40 to
- 54 Initial start-up of the TLE Scalable Series 40 to
- 58 Complete UPS shut-down
- 59 Restore to normal operation after “System shutdown” with Load not supplied
- 60 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 61 Procedures single TLE Scalable Series 40 to 150 functioning as Frequency Converter
- 61 Initial Start-up of the TLE Scalable Series 40 to 150 as Frequency Converter
- 65 Complete shut-down of the TLE Scalable Series 40 to 150 as Frequency Converter
- 66 Restore to normal operation after “System shutdown” with Load not supplied
- 67 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 68 Procedures for TLE Scalable Series 40 to 150 RPA Parallel System
- 68 TLE Scalable Series 40 to 150 RPA Parallel System start-up
- 73 Separate a UPS Unit from the RPA Parallel System (System Redundancy)
- 75 Reconnect a UPS Unit to RPA Parallel System
- 77 Complete RPA Parallel System shut-down
- 78 Restore to normal operation after “System shutdown” with Load not supplied
- 80 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 82 Options
- 82 Connectivity options
- 82 Options in UPS cabinet
- 82 Options in additional cabinets
- 83 Maintenance
- 83 Service check
- 83 Fans and ventilation
- 83 Other components with limited lifetime
- 84 Battery
- 84 UPS room conditions and temperature
- 84 Preventive maintenance program
- 85 Notes
- 85 Notes Form