Maintenance. ABB TLE Scalable UL Series UPS 86 Pages
Maintenance. ABB TLE Scalable UL Series UPS
advertisement
83/86
9 Maintenance
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
Note!
All maintenance and service works must be performed by an ABB Service Technician only!
9.1
Maintenance
A UPS system, like other electrical equipment, needs periodic preventive maintenance.
A regular maintenance check of your installation guarantees higher reliability of your safe power supply.
ABB recommends to perform the first service within 12 months from the commissioning date or within 18 months from delivery date.
Subsequent services to perform every 12 months .
Preventive maintenance work on the UPS can be done only by an ABB Service Technician.
We therefore recommend you sign a Maintenance and Service contract with the local ABB Service Center organization.
9.1.1
Service check
If this lamp lights up during normal operation, the Unit has not been serviced for the last 20,000 hours by an ABB
Service Technician .
Some components of the UPS which need periodic maintenance, if not replaced, could cause a reliability reduction of the supply system.
We highly recommend that you contact your ABB Service Center for preventive maintenance work.
Note!
Never ignore a Service Check alarm!
Failure to perform mandatory preventative maintenance on components documented in the UPS product manual may result in thermal damage to the equipment, its surroundings and an increased risk of personnel injury.
Refer to Section 9.1.2 to 9.1.6 for this important detail.
9.1.2
Fans and ventilation
We recommend a periodic cleaning of the ventilation channels and grids on the UPS system, in order to guarantee proper air circulation in the Unit and in the Battery.
The fans eventually wear out and must be substituted when a UPS alarm is triggered, in order to ensure the reliability of the UPS.
9.1.3
Other components with limited lifetime
Various components, such as the DC and AC filter capacitors and the lithium Battery on the “Control board”
(memory saving), must be systematically replaced in order to maintain the UPS’S reliability.
The substitution of these components is Signaled by a UPS alarm going off.
advertisement
Related manuals
advertisement
Table of contents
- 6 Safety rules
- 8 Safety symbols and warnings
- 8 Cyber security
- 9 Layout
- 9 Layout TLE Scalable Series 40 to
- 10 Introduction
- 11 Description
- 12 Block diagram and main elements
- 13 Operation modes
- 13 Normal VFI Operation Mode (Voltage Frequency Independent)
- 13 SEM Operation Mode (Super Eco Mode)
- 14 Utility Failure Operation
- 14 Utility Recovery Operation
- 15 Automatic Bypass
- 16 RPA Parallel System operation
- 16 Introduction to the RPA Parallel System
- 17 Features of RPA Parallel System
- 17 System control
- 17 Synchronization
- 17 Load sharing
- 18 IEMi Operation Mode (option)
- 19 UPS paralleled on the same Battery
- 20 Service and technical support
- 20 Warranty
- 21 Recycling instructions
- 22 Control Panel
- 23 LCD screen
- 23 Home screen
- 24 Description of the selection keys
- 25 Description of the signaling LEDs
- 28 Measures
- 32 Events
- 34 Events (alarms and messages)
- 34 Alarms list
- 38 Messages list
- 41 Setup
- 47 Commands
- 51 RPA Parallel System
- 53 Operation
- 54 Procedures for single TLE Scalable Series 40 to
- 54 Initial start-up of the TLE Scalable Series 40 to
- 58 Complete UPS shut-down
- 59 Restore to normal operation after “System shutdown” with Load not supplied
- 60 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 61 Procedures single TLE Scalable Series 40 to 150 functioning as Frequency Converter
- 61 Initial Start-up of the TLE Scalable Series 40 to 150 as Frequency Converter
- 65 Complete shut-down of the TLE Scalable Series 40 to 150 as Frequency Converter
- 66 Restore to normal operation after “System shutdown” with Load not supplied
- 67 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 68 Procedures for TLE Scalable Series 40 to 150 RPA Parallel System
- 68 TLE Scalable Series 40 to 150 RPA Parallel System start-up
- 73 Separate a UPS Unit from the RPA Parallel System (System Redundancy)
- 75 Reconnect a UPS Unit to RPA Parallel System
- 77 Complete RPA Parallel System shut-down
- 78 Restore to normal operation after “System shutdown” with Load not supplied
- 80 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 82 Options
- 82 Connectivity options
- 82 Options in UPS cabinet
- 82 Options in additional cabinets
- 83 Maintenance
- 83 Service check
- 83 Fans and ventilation
- 83 Other components with limited lifetime
- 84 Battery
- 84 UPS room conditions and temperature
- 84 Preventive maintenance program
- 85 Notes
- 85 Notes Form