- Industrial & lab equipment
- Measuring, testing & control
- CHAUVIN ARNOUX
- C.A 6456
- User manual
- 42 Pages
4.4 3-wire loop measurement (Z LOOP). CHAUVIN ARNOUX C.A 6456
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
4.4
WIRE LOOP MEASUREMENT (Z LOOP)
4.4.1
DESCRIPTION OF THE FUNCTION
In a TT network, measurement of loop impedance LPE is a rapid and practical way of checking a earth resistance without planting auxiliary rods.
In this case, the measurement includes the earthing resistance of the power supply transformer of the installation and the resistance of the distribution cables. It is therefore a high earth measurement, and any error is on the safe side.
In TT and TN networks, this function can also be used to check and size the protective systems in place by a rapid and easy measurement of the loop impedances between L and PE, L and N, and N and PE. This function can also be used to calculate the corresponding short-circuit currents (sizing of fuses and circuit breakers).
Note that the instrument allows measurement of loop impedance LPE behind 30mA circuit-breakers without causing them to trip (principle patented by Chauvin Arnoux).
In an IT network, use the instrument's "ZLINE" function.
The measurement principle is the same as for an earth measurement in a live condition.
When the TEST key is pressed, the instrument :
- checks that the amplitude and frequency of the voltages present are correct,
- measures the voltage between the TEST key and terminal PE,
- interchanges L and N internally if the 2 conductors are reversed in the socket,
- generates a current (high or low according to the user's selection) between terminals L and PE,
- measures loop impedances Z
Note: the measurement of Z
LN
LN
, Z
LPE
, et Z
NPE
.
does not trip the earth fault breakers even with high currents.
32
4.4.2
PREPARATION FOR THE MEASUREMENT (CONNECTION))
=> If necessary, in SET-UP mode:
- set threshold voltage U
L
(see § 3.2),
- the type of compensation of the measuring cables (see § 3.3))
- set the alarm threshold Z
L
or R
L
- possibly, select a value of U
REF
(see § 4.2.2)
to be used for the calculation of the short-circuit current :
PUSH btn
2 nd
>
88.88
direction of alarm (> or<)
88.88
location of decimal point
88.88
MORE x3 setting of the values of each of the 4 digits, selected by successive presses on the
keys
PUSH btn
- possibly, select a value of U
REF
to be used for the calculation of the short-circuit current:
PUSH btn
MORE x4
U ref
MEAS
I k selection of voltage :
MEAS/230/400/127 or MEAS/220/380/110
MORE x3
PUSH btn
- the current generated for the measurement in low current mode (see § 4.2.2),
- set the number of measurements to be counted to smooth the measurement (see § 3.2)
=> Set the switch to the ZLOOP position,
=> Activate the alarm by pressing the ALARM key ,
=> Connect the line power plug or the 3 separate cables to the installation to be tested,
33
=> Compensate the measuring cables (see § 3.3),
2 nd 5
=> high ( ) for a greater accuracy:
- if no tripping of a earth fault breaker is foreseen (measurement made upstream of the RCDs),
- if the earth fault breaker concerned is short-circuited for greater accuracy,
=> low ( ) otherwise for a rapid check
The connection diagrams are the same as for earth measurements in a live condition, but without the voltage or current probe (see § 4.2.2).
4.4.3
MEASUREMENT PROCEDURE
The instrument first checks the resistance of the rod and measures the voltage between PE and earth, then measures voltages U
LN
, U
LPE
, U
NPE
.
If these values are correct, pressing the TEST key starts the measurement: as soon as the result is available, it is displayed.
Note: for measurements on three-phase systems, the loop impedance must be measured between each phase conductor, the neutral conductor, and the protective conductor.
4.4.4
MEASUREMENT RESULTS
After the measurement, the measured values and complementary results can be consulted using the and keys.
(The quantities accessible before the measurement is made are described above, in § 4.1.4.)
Initial display
Initial display
R
LPE
Z
LPE
MORE
(1 st press)
L
LPE
Z
LPE
MORE
(2 nd press)
U
REF
I
KLPE
MORE
(3 nd press)
Hz
U
LPE
MORE
(4 nd press)
----
Z
L ALARM
MORE
(5 nd press)
R
∆
PE
U
L
(1 st press)
R
LN
Z
LN
L
Z
LN
LN
U
I
REF
KLN
Hz
U
LN
Z
----
L ALARM
R
U
∆ L
L
(2 nd press)
R
NPE
Z
NPE
L
Z
NPE
NPE
I
U
REF
KNPE
Hz
U
NPE
Z
----
L ALARM
R
U
L
N
Note : In non-trip mode the inductive component is not measurable due to the weak test current. The values
L
LPE
, L
NPE
, Z
NPE
, are not displayed (display shows - - - -). The value L
LPE
is displayed in the L
LN
field .
4.4.5
CHARACTERISTICS
4.4.5.1 Measurement ranges and accuracy
Particular reference conditions :
- nominal voltage of the installation = 90 to 550V,
- nominal frequency of use = 15.3 to 65Hz,
- inductive part < 0.1 x the resistive part of the impedance measured.
The characteristics of loop measurements with 3 wires, with ( ) or without tripping ( ) are the same as those of earth measurements in a live condition, with or without tripping, respectively: see § 4.3.5.1.
34
advertisement
Related manuals
advertisement
Table of contents
- 4 PRESENTATION
- 5 1.1 Environmental conditions
- 5 1.2 Compliance with standards
- 5 1.3 Power supply
- 6 DESCRIPTION
- 9 GENERAL USE
- 9 3.1 Automatic checks
- 10 3.2 Instrument configuration (SET-UP)
- 11 3.3 Compensation of the leads
- 13 3.4 Recording measurement results (MEM)
- 13 3.5 Recalling recorded values (MR)
- 14 3.6 Erasing recorded values
- 15 3.7 Printing measurement results (PRINT)
- 15 3.8 Printing recorded values (PRINT MEM)
- 16 MEASUREMENTS
- 16 4.1 Voltage measurement
- 21 4.2 2P and 3P earth measurement
- 25 4.3 Earth measurement in live condition (REARTH)
- 32 4.4 3-wire loop measurement (Z LOOP)
- 35 4.5 2-wire loop measurement (Z LINE)
- 40 MAINTENANCE
- 40 6.1 Replacing the batteries
- 40 6.2 Storage
- 40 6.3 Cleaning
- 40 6.4 Metrological verification
- 40 6.5 Warranty
- 40 6.6 Customer service
- 40 6.7 Repair
- 41 LIST OF CODED ERRORS
- 41 TO ORDER