LIST OF CODED ERRORS. CHAUVIN ARNOUX C.A 6456
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
7. LIST OF CODED ERRORS
Er10
Er18
Er 22
Er24
Error code
Er02
Er03
Er04
Er05
Er06
Er07
Er08
Meaning
Incorrect wiring or connection error: L and PE reversed
Incorrect wiring or connection error: L missing
U
F
voltage too high on earth electrode (danger): measurement STOPPED
The calculation (current measured by the probe) by (the measured voltage) is too low
The current measured by the probe is too unstable
Earth potential too high (potential danger): measurement STOPPED
Untimely interruption of the current during the measurement of Z too high
LN
or Z
LPE
(earth fault breaker tripped?) - Probable cause: reversal of conductors N and PE or the installation leakage current is
Voltage too high on the voltage probe (danger): measurement STOPPED
Current probe not connected
RH + RE or parasitic voltages are too high in 2P/3P measurement (the voltage exceeds the safety limit in terms of contact voltage).
Backup memory full (action: delete stored data)
8. TO ORDER
C.A 6456 earth and loop tester
Delivered in a carrying bag containing:
- 1 measuring cable for Euro mains socket,
- 1 measuring cable, 3 separate leads,
- 3 crocodile clips (red, yellow, and white),
- 3 contact pins (red, yellow, and white),
- 1 pouch with neck strap
- 1 optical communication cable
- data processing software program
- 6 LR6 batteries (1.5V)
- 1 user manual
P01123512
C.A 6456 + T P01123513
Same as above + a earth kit comprising two rods, three cables on reels, terminated by clips
(red, 30m; blue, 30m; green, 10m) and a mallet
ACCESSORIES
- C172 current probe
- MN20 current probe
- serial printer
- Earth kit
P01120310
P01120440
P01102903
P01101823
41
07 - 2013
Code 689909B02 - Ed. 2
DEUTSCHLAND - Chauvin-Arnoux GmbH
Straßburger Str. 34 - 77694 Kehl / Rhein
Tél : 7851 99 26-0 - Fax : 7851 99 26-60
ESPAÑA - Chauvin-Arnoux Ibérica S.A.
C/ Roger de Flor N°293 - Planta 1 - 08025 BARCELONA
Tél : 902 20 22 26 - Fax : 934 59 14 43
ÖSTERREICH - Chauvin-Arnoux Ges.m.b.H
Slamastrasse 29 / 2 / 4 - 1230 WIEN
Tél : 161 61 961 - Fax : 161 61 961 61
SWEDEN - Chauvin-Arnoux Mätsystem AB
Sjöflygvägen 35 - Box 4501 - 18304 TÄBY
Tél : 850 52 68 00 - Fax : 850 52 68 10
ITALIA - A.M.R.A. SPA
Via Sant’ Ambrogio, 23/25
20050 BAREGGIA DI MACHERIO (MI)
Tél : 039 245 75 45 - Fax : 039 481 561
SCHWEIZ - Chauvin-Arnoux AG
Moosacherstrasse 15 - 8804 AU / ZH
Tél : 44 727 75 55 - Fax : 44 727 75 56
LIBAN - Chauvin-Arnoux Middle East
P.O. BOX 60-154 - 1241 2020 JAL EL DIB
Tél : 18 90 425 - Fax : 18 90 424
CHINA Shanghai Pujiang Enerdis Inst. CO. LTD
3F 3Rd Buildind - N381 Xiang De Road - 200081 - SHANGHAI
Tél : 21 65 21 51 96 - Fax : 21 65 21 61 07
USA - Chauvin-Arnoux Inc - d.b.a AEMC Instruments
200 Foxborough Blvd. - Foxborough - MA 02035
Tél : (508) 698-2115 - Fax : (508) 698-2118
UNITED KINGDOM - Chauvin-Arnoux Ltd
Unit 1 Nelson Court - Flagship Square - Shaw Cross Business
Park - DEWSBURY - 99132 WEST YORSHIRE WF 127TH
Tél : 1 924 460 494 - Fax : 1 924 455 328
http://www.chauvin-arnoux.com
190, rue Championnet - 75876 PARIS Cedex 18 - FRANCE
Tél. +33 (0)1 44 85 44 85 - Fax +33 (0)1 46 27 73 89 - [email protected]
Export : Tél. +33 (0)1 44 85 44 38 - Fax +33 (0)1 46 27 95 59 - [email protected]
advertisement
Related manuals
advertisement
Table of contents
- 4 PRESENTATION
- 5 1.1 Environmental conditions
- 5 1.2 Compliance with standards
- 5 1.3 Power supply
- 6 DESCRIPTION
- 9 GENERAL USE
- 9 3.1 Automatic checks
- 10 3.2 Instrument configuration (SET-UP)
- 11 3.3 Compensation of the leads
- 13 3.4 Recording measurement results (MEM)
- 13 3.5 Recalling recorded values (MR)
- 14 3.6 Erasing recorded values
- 15 3.7 Printing measurement results (PRINT)
- 15 3.8 Printing recorded values (PRINT MEM)
- 16 MEASUREMENTS
- 16 4.1 Voltage measurement
- 21 4.2 2P and 3P earth measurement
- 25 4.3 Earth measurement in live condition (REARTH)
- 32 4.4 3-wire loop measurement (Z LOOP)
- 35 4.5 2-wire loop measurement (Z LINE)
- 40 MAINTENANCE
- 40 6.1 Replacing the batteries
- 40 6.2 Storage
- 40 6.3 Cleaning
- 40 6.4 Metrological verification
- 40 6.5 Warranty
- 40 6.6 Customer service
- 40 6.7 Repair
- 41 LIST OF CODED ERRORS
- 41 TO ORDER