4 Operating instructions. Atlas Copco HiLight H4 Kd ESF
Advertisement
Advertisement
00_00_HiLight H4_EN.book Page 27 Monday, April 18, 2016 2:10 PM
4 Operating instructions
In your own interest, always strictly observe all relevant safety instructions.
Do not operate the light tower in excess of the limitations mentioned in the Technical Specifications.
Local rules concerning the setting up of low voltage power installations
(below 1000 V) must be respected when connecting site distribution panels, switch gear or loads to the light tower generator.
At each start-up and at any time a new load is connected, the earthing and protections (GB trip and earth leakage relay) of the light tower must be verified. Earthing must be done either by the earth pin or, if available, by an existing, suitable earthing installation. The protective system against excessive contact voltage is not effective unless a suitable earthing is made.
4.1
Before starting
– Perform all daily checks and maintenance as
specified in the “Maintenance schedule” on page 39.
– With the light tower standing level, check the engine oil level and top up if necessary. The oil level must be between the min and max levels on the engine oil level dipstick.
– Check the fuel level and top up if necessary. It is recommended to fill the tank after the day’s operation to prevent water vapour in a nearly empty tank from condensing.
– Check the tightness of all bolts and nuts. For
torque values, see “Critical bolt connections” on page 75.
– Check that circuit breaker Q1 is switched off.
– Check that the fuses have not tripped and that the emergency stop is in the OUT position.
– Check that the load is switched off.
4.2
Operating the light tower
Carefully read and follow in sequence all the operating instructions in the Engine's manual as well as those contained in this manual!
4.2.1
Before the engine is started
1. Before starting the engine, check that all the automatic switches (general ELCB, sockets protection and lamp circuit breakers) are in the
OFF position (1).
X1
0
1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
X2
GE
ON
P8
1
2
2. If the optional External power input (230 VAC) is installed, select the desired operating mode with
- 27 -
00_00_HiLight H4_EN.book Page 28 Monday, April 18, 2016 2:10 PM
4.2.2
Starting the engine
1. Put starter switch S20 in position I (ON) (1) to power the Lc1003™ module.
2. Push the START button (2) on the Lc1003™ module.
The pre-heater indicator (3) is lit. Auto preheating starts and the engine will start after preheating.
3. Once the machine starts, the controller will check that all functioning conditions are OK. If there is any failure (low oil pressure, high coolant temperature, etc...), the controller will display a signal.
4.2.3
Positioning the floodlights
1. Check that the glass panes of the lights (1) are in good condition.
1 2
3. Loosen the handle at the side of the floodlight (3) and adjust the inclination of the floodlight.
3
X1
X2
0
1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
2
1
3
2. Check the tightness of the nuts on top of the lamps
(2). Torque if necessary.
4. Tighten the handle again when the floodlight is in the desired position.
5. Proceed with the extension of the mast as described below.
- 28 -
00_00_HiLight H4_EN.book Page 29 Monday, April 18, 2016 2:10 PM
4.2.4
Extending the mast
If the Mast Down option is provided, the mast can only be extended if the handbrake is engaged. For more
details on this option see “Auto mast down system” on page 64.
1. Check that the emergency push button has not been pushed. (If it has been pushed, a message will appear on the display.)
2. Check whether the plastic spacers on top of the mast sections (1) are in good condition. Replace if necessary.
X1
X2
0
1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
4. Use the UP (4) and DOWN (5) buttons on the control panel to extend and adjust the mast to the desired height up to the red indication on the mast
(6) (max 9 metres).
2
3
4
5
4.2.5
Rotating the mast
1. Unlock the locking pin (1) of the mast (located on its rotating base) and rotate the light tower using the mast handles (2) to further adjust the light beam. The mast can be rotated through 340°.
2
1
2. Lock the mast again using its locking pin (1).
1
3. Switch ON the main circuit breaker Q1 (2) and make sure all other breakers are switched OFF (3).
6
Do not extend the mast at a wind speed stronger than 80 km/h.
- 29 -
00_00_HiLight H4_EN.book Page 30 Monday, April 18, 2016 2:10 PM
4.2.6
Switching on/off the floodlights
4.2.6.1
Switching on the floodlights manually
1. Make sure the mast is up and in the desired
operating position. See section 4.2.4.
2. Switch ON the 4 circuit breakers (Q2-5) (1).
4. Wait for the lights to heat up. - this will take about
10 minutes.
4.2.6.2
Switching off the floodlights manually
To switch the lights off manually, follow the procedure described below and proceed to lower the mast.
5. Push the START button on the Lc1003™ module
(1) to shut down the lamps.
6. Place the 4 automatic switches (Q2-5) (2) in their
OFF position.
2
0
1
X1
X2
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
1
0
1
1
X1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
3. Push the AUTO button on the Lc1003™ module
(2) to ignite the lamps.
In sequence, every 20 seconds one lamp will ignite automatically.
When the light tower is connected to
the mains (“External power input
(230 VAC), with battery charger”
option, S10 in position 2) all lights will ignite at the same time, as soon as circuit breakers Q2-Q5 are switched ON.
X2
GE
ON
P8
2
7. Wait for the lamps to cool down - this will take about 10 minutes.
- 30 -
Once the floodlights are switched
OFF (Q2-5 switches in the OFF position), do not to switch them ON again until the cooling-off time is over. The lamps will only ignite, after complete cool down!
00_00_HiLight H4_EN.book Page 31 Monday, April 18, 2016 2:10 PM
4.2.6.3
Switching on/off the floodlights automatically
Only applicable with timer or
1. Make sure the mast is up and in the desired
operating position. See section 4.2.4.
2. Put the starter switch S20 in position REMOTE
(1).
3. Switch ON the 4 circuit breakers (Q2-5) (2).
When the light tower is connected to
the mains (“External power input
(230 VAC), with battery charger”
option, S10 in position 2) all lights will ignite at the same time, as soon as circuit breakers Q2-Q5 are switched ON.
4.2.7
Lowering the mast
1. If the floodlights are not to be used again, lower the mast using the DOWN button on the control panel (1).
X1
X2
0
1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
3
1
2
4. Push the AUTO button on the Lc1003™ module
(3) to activate AUTO mode.
The floodlights will ignite/switch off automatically depending on the luminosity
(optional Photocell) or a set time schedule.
X1
X2
0
1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
1
Mind your head while lowering the mast!
- 31 -
When lowering the mast, check that the power cord on the mast (spiral cable) collapses freely into its holder and does not become pinched or tangled!
2
00_00_HiLight H4_EN.book Page 32 Monday, April 18, 2016 2:10 PM
4.2.8
Stopping the engine
Follow the instructions below to switch the engine off correctly:
1. Lower the mast. See section 4.2.7.
2. Disconnect the electrical appliances connected to the socket (1).
3. Push the STOP button on the Lc1003™ module
(2) to go into cool down.
4. After cool down, which takes approx. 30 sec., put the starter switch S20 in position O (OFF) (3).
5. Place all the automatic switches in their OFF position (4).
6. If the optional External power input (230 VAC) is installed, switch S10 to O (OFF) (5). See also
“External power input (230 VAC), with battery charger” on page 66.
Should an emergency arise, it is also possible to stop the machine by pressing the EMERGENCY 'STOP' button (6). If the light tower has been stopped in this way, the emergency stop button must be released by rotating it clockwise, for next operation.
6
0
1
X1
X2
0
1
Q1
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
2
3
4
5
1
- 32 -
00_00_HiLight H4_EN.book Page 33 Monday, April 18, 2016 2:10 PM
4.3
Connecting appliances
Keep in mind that this machine is a light tower, not a generator set!
1. Start the engine. See section 4.2.2.
2. Wait 3 or 4 minutes before connecting the appliances to allow the engine to warm up enough. Then plug in the socket (X1) (1).
1
X1
X2
0
1
Q1
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
3. Make sure that a correct voltage is displayed.
4. Switch on circuit breaker Q6.
5. Switch on your appliance.
Power is limited to 10 Amps!
2
6. If the breaker Q6 (2) trips (10 A), adjust the load until it falls within the maximum power limit allowed.
If the 4 lamps are switched ON and the load of the socket is exceeded, an
Under voltage alarm will be triggered and the engine will shutdown.
7. Make sure that the load does not exceed the nominal power of the generating set as indicated in the technical data sheet and guaranteed with a tolerance of ± 5% when the engine has run in.
For derating values, check the derating table on
8. Make sure the load does not exceed the nominal current capacity of the socket or the cable connected to it.
Avoid long low-load periods
(< 30%). In this case, an output drop and higher oil consumption of the engine could occur. Refer to
9. Only connect the light tower directly to the mains, if the optional External power input (230 VAC) is installed. In this case use the X2 socket (3). See
also “External power input (230 VAC), with battery charger” on page 66.
3
X1
X2
0
1
Q1 Q2 Q3 Q4 Q5 Q6
Q1
40A/30mA
Q2 Q3 Q4 Q5 Q6
GE
ON
P8
To correctly disconnect the appliances from the light tower generator, first position the switch to
OFF to isolate the electric load and only then remove the plug.
10. Stop the engine. See section 4.2.8.
- 33 -
00_00_HiLight H4_EN.book Page 34 Monday, April 18, 2016 2:10 PM
4.4
Setting the Lc1003™ controller
Controller settings should only be performed by a qualified technician.
2
4.4.1
Push button and LED functions
Following push buttons are used on the
Lc1003™:
3
4
5
1
4
1 2 3
STOP: Is used to activate Stop/Reset mode. When pressing the STOP button, the generator will unload
(Light Output 1, 2, 3 & 4 becomes inactive (if used)), the fuel supply deenergises and the engine shuts down.
Pressing the STOP button will also clear any alarm conditions for which the triggering criteria have been removed.
5
AUTO: Is used to activate Auto mode.
It is also used for floodlight operation:
– switch on the floodlights manually (S20: ON)
– switch on/off the floodlights automatically, in REMOTE mode (S20: REMOTE)
START: Is used to start the unit in
Manual mode.
It is also used to switch off the floodlights manually (S20: ON).
UP: Is used for navigating the instrumentation, event log and configuration screens and to go to the previous parameter level.
DOWN: Is used for navigating the instrumentation, event log and configuration screens and to go to the next parameter level.
Following Leds are used on the Lc1003™:
1
2
3
Stop
Auto
Start
1 2 3
LED indicates that the unit is in Stop/
Reset Mode.
LED indicates that the unit is in Auto
Mode.
LED indicates that the unit is in
Manual/Start Mode.
- 34 -
00_00_HiLight H4_EN.book Page 35 Monday, April 18, 2016 2:10 PM
4.4.2
Module display
4.4.2.1
Home page
The home page is the page displayed when no other page has been selected:
1
2
3
4
7
1 Instrumentation icon
2 Active configuration
3 FPE/Auto run
4 Light output icons
5 Alarm icon
6 Mode icon
7 Instrumentation and Unit e.g. voltage reading
5
6
4.4.3
Icon overview
4.4.3.1
Instrumentation icons
Display Description
The default home page which displays Generator voltage and the
Auto Run icon
Generator voltage and frequency instrumentation screen
Current and load instrumentation screen
Engine speed instrumentation screen
Hours run instrumentation screen
Battery voltage instrumentation screen
Oil pressure instrumentation screen
Coolant temperature instrumentation screen
Fuel sender instrumentation screen
Display Description
Appears when the event log is being displayed
Current time held in the unit
The current value of the scheduler run time and duration
ECU diagnostic trouble codes
Oil Filter maintenance timers
Air Filter maintenance timers
Fuel Filter maintenance timers
- 35 -
00_00_HiLight H4_EN.book Page 36 Monday, April 18, 2016 2:10 PM
4.4.3.2
Active configuration
Display Description
Appears when the main configuration is selected.
Appears when the alternative configuration is selected.
4.4.3.3
Front panel editor (FPE) / Auto Run icons
Display Description
Appears when a remote start input is active
Appears when a low battery run is active
Appears when a scheduled run is active
4.4.3.4
Mode icons
Display Description
Appears when the engine is at rest and the unit is in stop mode.
Appears when the engine is at rest and the unit is in auto mode.
Appears when the engine is at rest and the unit is waiting for a manual start.
Appears when a timer is active, for example cranking time, crank rest etc.
Appears when the engine is running, and all timers have expired, either on or off load.
The animation speed is reduced when running in idle mode.
Appears when the unit is in the front panel editor.
Appears when a USB connection is made to the controller.
Appears if either the configuration file or engine file becomes corrupted.
4.4.3.5
Light output icons
Display Description
Appears when the corresponding light output has been configured and is not active.
Appears when the corresponding light output has been configured and is active.
Appears when a timer to delay the light output activating or deactivating is in progress
4.4.3.6
Alarm icons
To indicate the alarm that is currently active on the controller, an icon is displayed in the Alarm Icon section.
For an overview of all controller alarms, see “Solving controller alarms” on page 56.
- 36 -
00_00_HiLight H4_EN.book Page 37 Monday, April 18, 2016 2:10 PM
4.4.4
Navigation menu
To enter the navigation menu, press both the UP and
DOWN buttons simultaneously.
To navigate to the desired page, select the corresponding icon by pressing the UP and DOWN button and press the AUTO (Accept) button to enter.
If the AUTO button is not pressed, the display automatically returns to the home page.
Display Description
Home and generator voltage and frequency instrumentation
Generator current and load instrumentation
1
2
3
Display
Event Log
Description
4.4.5
Event log
The Lc1003™ module’s event log contains a list of the last 15 record electrical trip or shutdown events and the engine hours at which they occurred.
Once the log is full, any subsequent electrical trip or shutdown alarms over writes the oldest entry in the log. Hence, the log always contains the most recent shutdown alarms. The module logs the alarm, along with the engine running hours.
4
5
6
To view the event log:
1. Press the UP and DOWN buttons simultaneously to display the navigation menu.
2. Once entered, cycle to the event log section (1) and enter.
3. To view the event log, repeatedly press the UP or
DOWN buttons until the LCD screen displays the desired event.
4. Continuing to press the UP or DOWN buttons will cycle through the past alarms.
5. To exit the event log, press the UP and DOWN buttons simultaneously.
4.4.6
Setting the Lc1003™ timer
The Lc1003™ controller provides a basic scheduler that allows the operator to set a detailed time schedule following which the igniting of the floodlights can be programmed.
To set the Lc1003™ timer, follow the flow on the next page.
i
Engine instrumentation
Module information
Engine DTCs (Diagnostic Trouble
Codes) if active
1 Icon to indicate that the event log is currently display
2 Number of event displayed out
3 Light output status
4 The engine hours at which the event occurred
5 Icon to indicate the electrical trip or shutdown alarm that has been recorded
6 Current operating state of the module
- 37 -
00_00_HiLight H4_EN.book Page 38 Monday, April 18, 2016 2:10 PM
Menu flow:
Configuration Parameters – Scheduler
901 Enable Scheduler
902 Schedule Run On or
Off Load
On (1),
Off (0)
On (1),
Off (0)
903 Schedule Period
904 Scheduler (1)
Start Time
905 Scheduler (1)
Start Day
906 Scheduler (1)
Start Week
Weekly (0),
Monthly (1)
0:00:00
0
(1=Monday)
1,2,3,4
907 Scheduler (1) Duration 0:00:00
908 Scheduler (2)
Start Time
0:00:00
...
- 38 -

Download
Advertisement