Annexe. Schneider Electric SW ABILIT.CBS/SPACELYNK/BMS

Annexe. Schneider Electric SW ABILIT.CBS/SPACELYNK/BMS

Add to My manuals
32 Pages

Schneider Electric SW ABILIT.CBS/SPACELYNK/BMS enables system integrators to develop customized applications that can access system data, control devices, and create new visualizations. It provides a secure and reliable way to connect to Schneider Electric devices and systems, and to create custom applications that can be tailored to the specific needs of a building or facility.

Some of the possible use cases for Schneider Electric SW ABILIT.CBS/SPACELYNK/BMS include:

  • Monitor and control HVAC systems
  • Monitor and control lighting systems
  • Monitor and control security systems
  • Monitor and control energy consumption

advertisement

Annexe. Schneider Electric SW ABILIT.CBS/SPACELYNK/BMS | Manualzz

10.2

Annexe

BACnet ID

12541

12544

12545

12546

12547

12548

12549

12550

12551

12552

12553

12554

Modbus TCP register EXW register description

0x30FD

0x3100

0x3101

0x3102

0x3103

0x3104

0x3105

0x3106

0x3107

0x3108

GLT Gateway State

0 Gateway error (0=ok, 1=error). Read by the EXW-P-C

1 Gateway has been initialized (0=not initialized, 1=initialized). Set by the EXW-P-C

2 – 15 Reserved

System state A

0 Operating mode (0=charging, 1=operational)

1 Emergency lighting blocked (0=no, 1=yes)

2 Mains operation (0=no, 1=yes)

3 Battery operation (0=no, 1=yes)

4 Cumulative failure (0=no, 1=yes)

5 Charger (0=not active, 1=active)

6 Deep discharge (0=no, 1=yes)

7 Active (mains) / mod. stand-by (0=no, 1=yes)

8 Critical circuit (0=closed, 1=open)

9 – 15 Reserved

System state B

0 – 15 Reserved

Fault memory A (fault: 0=inactive, 1=active)

0 Maintenance required (0=no, 1=yes)

1 Battery earth fault (0=OK, 1=battery earth fault detected)

2 Battery fuse (0=OK, 1=fuse has blown)

3 Battery current (0=OK, 1=invalid range)

4 Battery voltage (0=OK, 1=invalid range)

5 Battery center voltage (0=OK, 1= valid range)

6 DCM / MLD fault

7 LDM / MCHG fault

8 IOM / MSWC fault

9 SAM / MMO fault

10 Fan failure

11 Luminary fault (collective luminary monitoring faults)

12 Current fault (collective current monitoring faults)

13 Circuit fault (collective circuit faults)

14 – 15 Reserved

Fault memory B

0 – 15 Reserved

Fault memory C

0 – 15 Reserved

Fault memory D

0 – 15 Reserved

Subsystem faults (1 to 16)

0 Subsystem 1 (0=OK, 1=errors present)

...

15 Subsystem 16 (0=OK, 1=errors present)

Subsystem faults (17 to 32)

0 Subsystem 17 (0=OK, 1=errors present)

...

15 Subsystem 32 (0=OK, 1=errors present)

Battery voltage (Resolution 0.1V) (signed int)

0x3109 Battery center voltage (Resolution 0.1V) (signed int)

0x310A Battery current (Resolution 0.1V) (signed int)

Table 4: Objects list (part 1/2)

AN019_v1-1_EXW-P-C_connected_to SBO_via spaceLYnk

Page 30 / 32

BACnet ID

12555

12556

12557

Modbus TCP register EXW register description

0x310B Mains voltage L1 (Resolution 0.1V) (signed int)

0x310C

0x310D

Mains voltage L2 (Resolution 0.1V) (signed int)

Mains voltage L3 (Resolution 0.1V) (signed int)

12558

12560

12561

12800

12801

12802 … 12806

12809 … 12814

12817 … 12822

12825 … 12830

12833 … 12838

12841 … 12846

12849 … 12944

0x310E

0x3110

0x3111

0x3200

0x3201

0x3202 … 0x3206

0x3209 … 0x320E

0x3211 … 0x3216

0x3219 … 0x321E

0x3221 … 0x3226

0x3229 … 0x322E

0x3231 … 0x3290

Mains voltage N (Resolution 0.1V) (signed int)

Temperature cabinet (Resolution 0.1°C) (signed int)

Temperature battery (Resolution 0.1°C) (signed int)

First and last installed circuit

0..7 First circuit number (1..96)

8..15 Last circuit number (1..96)

Circuit 1 to 16 installed

0 Circuit 1 (0=empty, 1=installed)

1 Circuit 2 (0=empty, 1=installed)

...

15 Circuit 16 (0=empty, 1=installed)

Circuit 17 to 96 installed

Bit 3202.0: circuit 17, etc. (0=empty, 1=installed)

Circuit 1 to 96 Operation mode

0=maintained mode (BS), 1=non-maintained mode (DS)

Circuit 1 to 96 Faults

Bit 3211.0: faults on circuit 1, etc. (0=OK, 1=Fault: fuse blown or earth fault)

Circuit 1 to 96: Fuse state

Bit 3219.0: fuse state on circuit 1, etc. (0=OK, 1=fuse has blown)

Circuit 1 to 96: Earth fault

Bit 3221.0: earth fault on circuit 1, etc. (0=OK, 1=earth fault)

Circuit 1 to 96: Current monitoring faults (on circuit level)

Bit 3229.0: current fault on circuit 1, etc. (0=OK, 1=current fault)

Circuit 1 to 96: Circuit power

Measured power during the last test (resolution 1W)

Register 3231: circuit 1, etc.

Circuit 1 to 96: Luminary faults (collective fault on 13138 … 13143 0x3352 … 0x3357

13145 … 13146 0x3359 … 0x335A circuit level)

Bit 3352.0: luminary faults on circuit 1, etc. (0=no faults, 1=faults)

Circuit 1: Luminary failure (on luminary level 1-20)

Bit 3359.0: lamp 1, Bit 3359.1: Lamp 2, ... Bit 335A.3: Lamp 20 (0=OK, 1=fault)

… 13147 … 13334 0x335B … 0x3416

13335 … 13336 0x3417 … 0x3418

13501 … 13522 0x34BD … 0x34D2

13544 … 13545

13546

13548 … 13549

0x34E8 … 0x34E9

0x34EA

0x34EC … 0x34ED

Circuit 96: Luminary failure (on luminary level 1-20)

(Bit 3417.0: lamp 1, Bit 3417.1: lamp 2, ...Bit 3418.3: lamp 20)

System name (43 chars) (22 registers)

System number (32 bit) (2 registers)

NLSR firmware version (16 bit)

System IP address (32 bit) (2 registers)

Table 5: Objects list (part 2/2)