Performance Data. Trane Fan-Powered Low-Height Parallel 234 Pages
Performance Data. Trane Fan-Powered Low-Height Parallel
advertisement
Performance Data
Parallel Fan-Powered Terminal Units
Table 4.
Primary airflow control factory setting-I-P
Control Type
Direct Digital
Control/ UCM
Air Valve
Size (in.)
10
12
14
16
5
6
8
Maximum
Valve Cfm
350
500
900
1400
2000
3000
4000
Maximum
Controller Cfm
40-350
60-500
105-900
165-1400
240-2000
320-3000
420-4000
Pneumatic with
Volume
Regulator
10
12
14
16
5
6
8
350
500
900
1400
2000
2885
3785
63-350
73-500
134-900
215-1400
300-2000
408-2887
536-3789
Note:
Maximum airflow must be greater than or equal to minimum airflow.
Minimum
Controller Cfm
0, 40-350
0, 60-500
0, 105-900
0, 165-1400
0, 240-2000
0, 320-3000
0, 420-4000
0, 63-350
0, 73-500
0, 134-900
0, 215-1400
0, 300-2000
0, 408-2887
0, 536-3789
Constant Volume
Cfm
40-350
60-500
105-900
165-1400
240-2000
320-3000
420-4000
63-350
73-500
134-900
215-1400
300-2000
408-2887
536-3789
Table 5.
Primary airflow control factory settings – SI
Control Type
Air Valve
Size (in.)
Maximum
Valve L/s
Maximum
Controller L/s
Direct Digital
Control/ UCM
10
12
14
16
5
6
8
165
236
425
661
944
1416
1888
19-165
28-236
50-425
77-661
111-944
151-1416
198-1888
Pneumatic with
Volume
Regulator
5
6
8
10
12
14
16
165
236
425
661
944
1362
1787
30-165
35-236
63-425
102-661
141-944
193-1363
253-1788
Note:
Maximum airflow must be greater than or equal to minimum airflow.
Minimum
Controller L/s
0, 19-350
0, 28-236
0, 50-425
0, 77-661
0, 111-944
0, 151-1416
0, 198-1888
0, 30-165
0, 35-236
0, 63-425
0, 102-661
0, 141-944
0, 193-1363
0, 253-1788
Constant
Volume L/s
19-350
28-236
50-425
77-661
111-944
151-1416
198-1888
30-165
35-236
63-425
102-661
141-944
193-1363
253-1788
Table 6.
Unit air pressure drop – in. wg (I-P)
Fan/Inlet Size Airflow Cfm Cooling Only Fan/Inlet Size Airflow Cfm Cooling Only
02SQ-05
02SQ-06
60
200
350
500
0.01
0.05
0.17
0.35
05SQ-10
Note:
Unit pressure drops do not include hot water coil or attenuator pressure drops.
02SQ-08
40
150
250
350
105
350
600
900
0.01
0.03
0.08
0.17
0.01
0.03
0.09
0.21
04SQ-14
05SQ-12
320
1200
2100
3000
165
550
950
1400
240
750
1350
2000
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.05
0.01
0.01
0.01
0.01
24 VAV-PRC012-EN
Performance Data
VAV-PRC012-EN
Table 6.
Unit air pressure drop – in. wg (I-P) (continued)
Fan/Inlet Size Airflow Cfm Cooling Only
02SQ-10
03SQ-06
165
550
950
1400
60
200
350
500
0.01
0.01
0.01
0.01
0.01
0.06
0.19
0.40
03SQ-08
03SQ-10
03SQ-12
04SQ-08
04SQ-10
04SQ-12
105
350
600
900
165
550
950
1400
240
750
1350
2000
105
350
600
900
165
550
950
1400
240
750
1350
2000
0.01
0.03
0.08
0.20
0.01
0.01
0.02
0.05
0.01
0.01
0.01
0.01
0.01
0.03
0.08
0.20
0.01
0.01
0.02
0.05
0.01
0.01
0.01
0.01
Fan/Inlet Size Airflow Cfm Cooling Only
05SQ-14
06SQ-10
320
1200
2100
3000
165
550
950
1400
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
06SQ-12
06SQ-14
06SQ-16
07SQ-10
07SQ-12
07SQ-14
07SQ-16
240
750
1350
2000
320
1200
2100
3000
420
1600
2800
4000
165
550
950
1400
240
750
1350
2000
320
1200
2100
3000
420
1600
2800
4000
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
Note:
Unit pressure drops do not include hot water coil or attenuator pressure drops.
Table 7.
Coil air pressure drop – in. wg (I-P)
Fan Size
02SQ
Airflow Cfm
100
200
300
400
500
1-Row HW (in. wg)
0.00
0.01
0.01
0.02
0.02
03SQ
04SQ
05SQ
06SQ
07SQ
250
500
750
1000
1250
1400
600
900
1200
1500
1800
2000
Note:
HW Coil Only pressure drops do not include unit pressure drop.
0.01
0.02
0.04
0.07
0.10
0.12
0.02
0.04
0.06
0.09
0.12
0.15
2-Row HW (in. wg)
0.00
0.01
0.02
0.03
0.05
0.04
0.07
0.11
0.16
0.22
0.27
0.02
0.04
0.08
0.13
0.19
0.23
25
Performance Data
26
Table 8.
Attenuator air pressure drop (I-P)
Fan Size Plenum Cfm Attenuator
02SQ
03SQ
50
250
500
750
1000
1200
50
200
350
500
650
750
04SQ
50
300
600
900
1200
1450
Note:
Plenum cfm = (Fan cfm)
0.00
0.00
0.00
0.00
0.01
0.06
0.00
0.00
0.01
0.02
0.04
0.06
0.00
0.01
0.02
0.03
0.05
0.06
Table 9.
Attenuator air pressure drop (SI)
Fan Size
02SQ
03SQ
04SQ
24
142
283
425
566
684
Note:
Plenum cfm = (Fan cfm)
24
118
236
354
472
566
24
94
165
236
307
354
Plenum L/s Attenuator
0
0
2
0
0
14
0
0
2
5
10
14
5
8
0
3
11
14
Table 10. Coil air pressure drop – Pa (SI)
Fan Size
02SQ
03SQ
04SQ
05SQ
Airflow L/s
118
236
354
472
590
661
200
300
400
500
600
1-Row HW (Pa)
2
5
10
17
25
31
0
1
2
4
6
Fan Size
05SQ
06SQ
07SQ
Plenum Cfm
50
300
600
900
1200
1550
50
500
900
1300
1650
1900
50
500
1000
1500
2000
2500
Attenuator
0.00
0.01
0.03
0.06
0.10
0.14
0.00
0.00
0.02
0.06
0.13
0.24
0.00
0.01
0.04
0.08
0.15
0.25
Fan Size
05SQ
06SQ
07SQ
Plenum L/s Attenuator
24
236
425
613
779
897
24
142
283
425
566
731
24
236
472
708
944
1180
0
2
7
15
26
35
0
1
5
15
32
61
0
2
9
21
38
62
2-Row HW (Pa)
4
11
21
33
47
57
1
3
5
8
12
VAV-PRC012-EN
Performance Data
Table 10. Coil air pressure drop – Pa (SI)
06SQ
07SQ
900
1200
1500
1800
2150
2500
Note:
HW Coil Only pressure drops do not include unit pressure drop.
Table 11. Unit air pressure drop-Pa (SI)
Fan/Inlet Size
02SQ-05
02SQ-06
02SQ-08
02SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-08
04SQ-10
04SQ-12
Airflow L/s
50
165
283
425
78
260
448
661
113
354
637
944
50
165
283
425
78
260
448
661
113
354
637
944
19
71
118
165
28
94
165
236
50
165
283
425
78
260
448
661
28
94
165
236
Cooling Only
2
2
6
13
2
2
2
2
2
6
21
49
2
6
21
49
2
2
6
13
2
2
2
2
2
13
41
86
2
8
23
51
2
2
2
3
2
7
20
41
2
15
48
99
5
9
15
22
30
36
Fan/Inlet Size Airflow L/s
04SQ-14
05SQ-10
05SQ-12
05SQ-14
06SQ-10
06SQ-12
06SQ-14
06SQ-16
07SQ-10
07SQ-12
07SQ-14
07SQ-16
113
354
637
944
151
566
991
1416
198
755
1321
1888
78
260
448
661
113
354
637
944
151
566
991
1416
198
755
1321
1888
151
566
991
1416
78
260
448
661
113
354
637
944
151
566
991
1416
78
260
448
661
Note:
Unit pressure drops do not include hot water coil or attenuator pressure drops.
10
18
28
41
56
67
Cooling Only
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
6
13
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
VAV-PRC012-EN 27
Performance Data
Pa In. wg
150 0.60
Parallel 02SQ—PSC
125 0.50
100 0.40
75 0.30
50
0.20
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note:
When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa
199
In. wg
0.80
174 0.70
150
0.60
125 0.50
100 0.40
75
0.30
50
0.20
25 0.10
200
94
25 0.10
100
47
200
94
300
142
400
189
Airflow
500
236
600
283
700
330
Cfm
L/s
Pa In. wg
199 0.80
174
0.70
150 0.60
125 0.50
100
0.40
75 0.30
50
0.20
25 0.10
200
94
300
142
400
189
500
236
Parallel Fan Size 03SQ—PSC
600
283
700
330
Airflow
800
378
900
425
1000
472
1100
519
1200
566
1300
Cfm
614
L/s
Parallel 04SQ—PSC
400
189
600
283
800
378
Airflow
1000
472
1200
566
1400
661
1600
Cfm
755
L/s
28 VAV-PRC012-EN
Performance Data
Pa In. wg
199
0.80
174 0.70
150 0.60
125
0.50
100
0.40
75 0.30
50
0.20
25 0.10
300
142
500
236
700
330
Parallel 05SQ—PSC
900
425
1100
519
Airflow
1300
614
1500
708
1700
802
Cfm
L/s
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note:
When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
199 0.80
174
0.70
150 0.60
125 0.50
100 0.40
75 0.30
50 0.20
25 0.10
400
189
600
283
Parallel 06SQ—PSC
800
378
1000
472
1200
566
1400
661
Airflow
1600
755
1800
850
2000
944
2200
Cfm
1038 L/s
Pa In. wg
199 0.80
174
0.70
150 0.60
125 0.50
100 0.40
75
0.30
50 0.20
25 0.10
500
236
Parallel 07SQ—PSC
700
330
900
425
1100
519
1300
614
1500
708
Airflow
1700
802
1900
897
2100
991
2300
1086
Cfm
L/s
VAV-PRC012-EN 29
Performance Data
Pa In. wg
125 0.50
100 0.40
75
0.30
VPxF 03SQ—ECM
50
0.20
25 0.10
100
47
200
94
300
142
400
189
500
236
600
283
Airflow
700
330
800
378
900
425
1000
472
1100
519
Cfm
L/s
Pa In. wg
125 0.50
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
100 0.40
75 0.30
50
0.20
25 0.10
200
94
400
189
Pa In. wg
125 0.50
VPxF 04SQ—ECM
600
283
800
378
Airflow
1000
472
1200
566
1400
661
1600
Cfm
755
L/s
VPxF 05SQ—ECM
30
100 0.40
75
0.30
50
0.20
25 0.10
200
94
400
189
600
283
800
378
1000
472
1200
566
Airflow
1400
661
1600
755
1800
850
2000
944
Cfm
L/s
VAV-PRC012-EN
Performance Data
Pa In. wg
125 0.50
VPxF 06SQ—ECM
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
100 0.40
75
0.30
50 0.20
25 0.10
400 600
283
800
378
1000
472
1200
566
1400
661
Airflow
1600
755
1800
850
2000
944
2200
1038
Cfm
L/s
Table 12. Heating capacity (MBh) - fan size 02SQ (I-P)
Rows Gpm
Water
Pressure
Drop (ft)
1-Row
Capacity
MBH
2-Row
Capacity
MBH
1.0
2.0
3.0
4.0
5.0
0.5
1.0
2.0
3.0
4.0
5.0
0.22
0.76
2.65
5.54
9.39
14.17
1.30
4.41
9.08
15.18
22.66
100
-
9.20
9.79
10.01
10.12
10.19
9.97
10.29
10.40
10.45
10.48
150
-
11.49
12.50
12.87
13.07
13.19
13.83
14.58
14.83
14.95
15.03
200
-
13.14
14.52
15.04
15.32
15.49
17.07
18.39
18.83
19.05
19.18
250
-
14.45
16.17
16.84
17.19
17.41
19.81
21.78
22.46
22.80
23.00
Airflow (Cfm)
300
-
15.56
17.60
18.39
18.82
19.09
22.13
24.82
25.76
26.23
26.52
350
-
16.52
18.87
19.79
20.29
20.60
24.13
27.56
28.77
29.40
29.78
400
-
17.38
20.02
21.07
21.64
22.00
25.85
30.03
31.54
32.32
32.80
Notes:
1. Fouling Factor = 0.0005 °F ft² h/Btu.
2. Capacity based on 70°F entering air temperature and 180°F entering water temperature.
450
-
18.16
21.09
22.26
22.90
23.30
27.35
32.27
34.09
35.04
35.62
500
-
18.93
22.08
23.38
24.09
24.54
28.67
34.31
36.45
37.56
38.25
550
-
19.64
23.02
24.44
25.22
25.71
29.83
36.18
38.63
39.92
40.72
600
-
20.30
23.90
25.44
26.29
26.83
30.86
37.90
40.67
42.13
43.03
VAV-PRC012-EN 31
Performance Data
Table 13. Heating capacity (MBh) - fan sizes 03SQ–05SQ (I-P)
1-Row
Capacity
MBH
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
2-Row
Capacity
MBH
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
Rows Gpm
Water
Pressure
Drop (ft)
0.35
1.28
2.74
4.72
7.20
10.18
13.64
17.59
22.03
26.94
0.28
1.02
2.22
3.85
5.92
8.41
11.32
14.65
18.40
22.57
Airflow (Cfm)
150 300 450 600 750 900 1050 1200 1350 1500 1650
-
15.08
15.36
15.50
15.59
15.64
15.68
15.71
15.74
15.76
-
13.14
13.62
13.88
14.04
14.14
14.22
14.28
14.33
14.37
-
25.87
27.00
27.57
27.92
28.15
28.31
28.44
28.54
28.62
-
18.63
19.69
20.27
20.64
20.89
21.08
21.22
21.33
21.42
-
33.70
35.94
37.11
37.83
38.31
38.66
38.93
39.13
39.30
-
22.21
23.78
24.65
25.21
25.59
25.88
26.10
26.28
26.42
-
39.58
42.99
44.82
45.97
46.74
47.31
47.74
48.08
48.35
-
25.01
27.05
28.20
28.95
29.46
29.85
30.15
30.38
30.57
-
47.77
53.40
56.57
58.59
59.99
61.02
61.81
62.44
62.95
-
29.41
32.34
34.03
35.14
35.92
36.50
36.95
37.31
37.60
-
44.13
48.69
51.20
52.78
53.87
54.67
55.28
55.76
56.15
-
27.36
29.86
31.28
32.21
32.85
33.34
33.71
34.01
34.25
-
53.20
60.74
65.13
67.99
70.00
71.49
72.64
73.55
74.30
-
33.00
36.63
38.84
40.31
41.35
42.13
42.73
43.22
43.62
-
50.73
57.36
61.15
63.60
65.32
66.58
67.55
68.32
68.95
-
31.30
34.58
36.54
37.82
38.73
39.41
39.94
40.36
40.71
-
57.08
66.21
71.68
75.30
77.87
79.80
81.29
82.48
83.45
-
35.94
40.31
42.99
44.80
46.10
47.08
47.85
48.46
48.97
-
55.29
63.66
68.60
71.85
74.15
75.86
77.19
78.24
79.10
-
34.54
38.52
40.98
42.62
43.80
44.67
45.36
45.91
46.36
-
58.63
68.46
74.42
78.39
81.23
83.36
85.01
86.33
87.42
-
37.23
41.99
44.86
46.85
48.28
49.36
50.21
50.89
51.45
Table 14. Heating capacity (MBh) - fan sizes 06SQ & 07SQ (I-P)
Rows Gpm
Water
Pressure
Drop (ft)
1-Row
Capacity
MBH
2-Row
Capacity
MBH
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0.5
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0.11
0.36
1.24
2.57
4.32
6.49
9.04
11.99
0.68
2.24
4.57
7.59
11.29
15.64
20.61
Airflow (Cfm)
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
-
-
32.17
35.12
36.78
37.86
38.61
39.17
-
51.03
56.65
59.73
61.67
63.00
63.97
-
-
33.60
36.76
38.60
39.79
40.63
41.25
-
53.38
59.74
63.27
65.51
67.05
68.18
-
-
34.93
38.31
40.32
41.63
42.55
43.23
-
55.46
62.53
66.50
69.04
70.79
72.07
-
-
36.17
39.77
41.95
43.38
44.38
45.13
-
57.32
65.06
69.46
72.28
74.24
75.69
-
-
37.34
41.16
43.51
45.05
46.14
46.95
-
58.98
67.37
72.18
75.29
77.45
79.05
-
-
38.43
42.50
45.01
46.66
47.83
48.70
-
60.47
69.48
74.69
78.08
80.44
82.19
-
-
39.47
43.81
46.44
48.21
49.46
50.40
-
61.83
71.42
77.02
80.67
83.24
85.14
-
-
40.45
45.07
47.82
49.70
51.04
52.04
-
63.07
73.20
79.18
83.09
85.86
87.90
-
-
41.38
46.27
49.14
51.14
52.56
53.62
-
64.20
74.86
81.19
85.36
88.31
90.51
-
-
42.27
47.42
50.42
52.53
54.04
55.16
-
65.24
76.40
83.08
87.50
90.63
92.96
-
-
43.12
48.53
51.68
53.88
55.47
56.66
-
66.20
77.83
84.84
89.50
92.81
95.28
Water Coil Performance Notes (I-P)
1.
Fouling Factor = 0.0005.
2. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed
140°F when mounted on plenum inlet.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
LAT
=
EAT
+
--------------------------------------
WTD
=
EWT LWT
=
------------------------
32 VAV-PRC012-EN
VAV-PRC012-EN
Performance Data
4. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer to correction factors for different entering conditions.
5. For premium coils (.020” wall), water side pressure drop increases 17% and water velocity increases 7% for fixed GPM.
Table 15. Temperature correction factors for water pressure drop (ft)
Average Water Temperature
Correction Factor
200
0.970
190
0.985
180
1.000
170
1.020
160
1.030
150
1.050
140
1.080
130
1.100
120
1.130
110
1.150
Table 16. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air
Correction Factor
40
0.355
50
0.446
60
0.537
70
0.629
80
0.722
90
0.814
100
0.907
110
1.000
120
1.093
130
1.187
Table 17. Heating capacity (kW) - fan size 02SQ (SI)
Rows
1-Row
Capacity kW
2-Row
Capacity kW
L/s
0.03
0.06
0.13
0.19
0.25
0.32
0.06
0.13
0.19
0.25
0.32
Water
Pressure
Drop
(kPa)
0.66
2.26
7.91
16.57
28.08
42.34
3.89
13.19
27.13
45.38
67.73
47
-
2.69
2.87
2.93
2.97
2.99
2.92
3.02
3.05
3.06
3.07
71
-
3.37
3.66
3.77
3.83
3.87
4.05
4.27
4.35
4.38
4.40
Airflow (L/s)
94 118 142 165 189 212 236 260
-
3.85
4.26
4.41
4.49
4.54
5.00
5.39
5.52
5.58
5.62
-
4.24
4.74
4.93
5.04
5.10
5.80
6.38
6.58
6.68
6.74
-
4.56
5.16
5.39
5.52
5.59
6.49
7.27
7.55
7.69
7.77
-
4.84
5.53
5.80
5.95
6.04
7.07
8.08
8.43
8.62
8.73
-
5.09
5.87
6.18
6.34
6.45
7.58
8.80
9.24
9.47
9.61
-
5.32
6.18
6.52
6.71
6.83
8.02
9.46
9.99
10.27
10.44
-
5.55
6.47
6.85
7.06
7.19
8.40
10.06
10.68
11.01
11.21
-
5.76
6.75
7.16
7.39
7.53
8.74
10.60
11.32
11.70
11.93
283
-
5.76
6.75
7.16
7.39
7.53
8.74
10.60
11.32
11.70
11.93
Table 18. Heating capacity (kW) - fan sizes 03SQ–05SQ (SI)
Rows
1-Row
Capacity kW
2-Row
Capacity kW
L/s
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.57
0.63
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.57
0.63
Water
Pressure
Drop (kPa)
1.06
3.83
8.20
14.11
21.52
30.42
40.78
52.59
65.84
80.52
0.82
3.06
6.63
11.51
17.68
25.13
33.83
43.79
55.00
67.45
Airflow (L/s)
71 142 212 283 354 425 495 566 637 708 779
-
7.58
7.91
8.08
8.18
8.25
8.30
8.33
8.36
8.39
-
5.46
5.77
5.94
6.05
6.12
6.18
6.22
6.25
6.28
-
4.42
4.50
4.54
4.57
4.58
4.60
4.61
4.61
4.62
-
3.85
3.99
4.07
4.11
4.15
4.17
4.19
4.20
4.21
-
16.20
18.66
20.11
21.06
21.73
22.23
22.62
22.93
23.18
-
10.12
11.29
12.01
12.49
12.84
13.09
13.29
13.46
13.59
-
15.59
17.80
19.09
19.92
20.51
20.95
21.29
21.56
21.77
-
9.67
10.74
11.38
11.81
12.12
12.35
12.52
12.67
12.78
-
14.87
16.81
17.92
18.64
19.14
19.51
19.80
20.02
20.21
-
9.17
10.14
10.71
11.08
11.35
11.55
11.71
11.83
11.93
-
14.00
15.65
16.58
17.17
17.58
17.88
18.12
18.30
18.45
-
8.62
9.48
9.97
10.30
10.53
10.70
10.83
10.93
11.02
-
12.93
14.27
15.01
15.47
15.79
16.02
16.20
16.34
16.45
-
8.02
8.75
9.17
9.44
9.63
9.77
9.88
9.97
10.04
-
11.60
12.60
13.14
13.47
13.70
13.87
13.99
14.09
14.17
-
7.33
7.93
8.27
8.48
8.64
8.75
8.83
8.90
8.96
-
9.88
10.53
10.88
11.09
11.23
11.33
11.41
11.47
11.52
-
6.51
6.97
7.22
7.39
7.50
7.58
7.65
7.70
7.74
-
16.73
19.40
21.01
22.07
22.82
23.39
23.82
24.17
24.46
-
10.53
11.81
12.60
13.13
13.51
13.80
14.02
14.20
14.35
-
16.73
19.40
21.01
22.07
22.82
23.39
23.82
24.17
24.46
-
10.53
11.81
12.60
13.13
13.51
13.80
14.02
14.20
14.35
33
Performance Data
Table 19. Heating capacity (kW) - fan sizes 06SQ & 07SQ (SI)
Rows L/s
1-Row
Capacity kW
0.03
0.06
0.13
0.19
0.25
0.32
0.38
0.44
2-Row
Capacity kW
0.06
0.13
0.19
0.25
0.32
0.38
0.44
Water
Pressure
Drop
(kPa)
0.33
1.09
3.71
7.68
12.92
19.39
27.04
35.84
2.02
6.70
13.65
22.70
33.76
46.74
61.61
Airflow (L/s)
425 472 519 566 613 661 708 755 802 849 897
-
-
9.43
10.29
10.78
11.10
11.32
11.48
-
-
9.85
10.77
11.31
11.66
11.91
12.09
-
-
10.24
11.23
11.82
12.20
12.47
12.67
-
-
10.60
11.66
12.30
12.71
13.01
13.23
-
-
10.94
12.06
12.75
13.20
13.52
13.76
-
-
11.26
12.46
13.19
13.67
14.02
14.27
-
-
11.57
12.84
13.61
14.13
14.50
14.77
-
-
11.86
13.21
14.01
14.57
14.96
15.25
-
-
12.13
13.56
14.40
14.99
15.40
15.72
-
-
12.39
13.90
14.78
15.40
15.84
16.17
-
-
12.39
13.90
14.78
15.40
15.84
16.17
-
14.96
16.60
17.51
18.07
18.46
18.75
-
15.64
17.51
18.54
19.20
19.65
19.98
-
16.25
18.33
19.49
20.23
20.75
21.12
-
16.80
19.07
20.36
21.18
21.76
22.18
-
17.28
19.74
21.15
22.06
22.70
23.17
-
17.72
20.36
21.89
22.88
23.58
24.09
-
18.12
20.93
22.57
23.64
24.39
24.95
-
18.48
21.45
23.20
24.35
25.16
25.76
-
18.82
21.94
23.80
25.02
25.88
26.52
-
19.12
22.39
24.35
25.64
26.56
27.24
-
19.12
22.39
24.35
25.64
26.56
27.24
Water Coil Performance Notes (SI)
1.
Fouling Factor = 0.0005.
2. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed
60°C when mounted on plenum inlet.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
LAT
=
EAT
+ -----------------------------
WTD=EWT-LWT=kW/(4.19) L/s
4. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different entering conditions.
5. For premium coils (.020” wall), water side pressure drop increases 17% and water velocity increases 7% for fixed GPM.
Table 20. Temperature correction factors for water pressure drop (kPa)
Average Water Temperature
Correction Factor
93
0.970
88
0.985
82
1.000
77
1.020
71
1.030
66
1.050
60
1.080
54
1.100
49
1.130
43
1.150
Table 21. Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air
Correction Factor
22
0.355
27
0.446
33
0.537
38
0.629
44
0.722
50
0.814
55
0.907
61
1.000
67
1.093
72
1.187
34 VAV-PRC012-EN
Performance Data
Series Fan-Powered Terminal Units
Table 22. Primary airflow control factory settings – I-P
Control Type
Air Valve Size
(in.)
Maximum
Valve Cfm
Maximum
Controller Cfm
Direct Digital
Control/UCM
4
5
6
8
10
12
14
16
4
5
6
8
225
350
500
900
1400
2000
3000
4000
225
350
500
900
25-225
40-350
60-500
105-900
165-1400
240-2000
320-3000
420-4000
38-225
63-350
73-500
134-900
Pneumatic with
Volume Regulator
10
12
14
16
1400
2000
2885
3785
215-1400
300-2000
408-2887
536-3789
Note:
Maximum airflow must be greater than or equal to minimum airflow.
Minimum
Controller Cfm
0, 25-225
0, 40-350
0, 60-500
0, 105-900
0, 165-1400
0, 240-2000
0, 320-3000
0, 420-4000
0, 38-225
0, 63-350
0, 73-500
0, 134-900
0, 215-1400
0, 300-2000
0, 408-2887
0, 536-3789
Table 23. Primary airflow control factory settings – SI
Control Type
Air Valve Size
(in.)
Maximum
Valve L/s
Maximum
Controller L/s
Direct Digital
Control/UCM
Pneumatic with
Volume
Regulator
10
12
14
16
6
8
4
5
10
12
14
16
6
8
4
5
106
165
236
425
661
944
1416
1888
106
165
236
425
661
944
1362
1787
12-106
19-165
28-236
50-425
77-661
111-944
151-1416
198-1888
18-106
30-165
35-236
63-425
102-661
141-944
193-1363
253-1788
Note:
Maximum airflow must be greater than or equal to minimum airflow.
Minimum
Controller L/s
0, 12-106
0, 19-165
0, 28-236
0, 50-425
0, 77-661
0, 111-944
0, 151-1416
0, 198-1888
0, 18-106
0, 30-165
0, 35-236
0, 63-425
0, 102-661
0, 141-944
0, 193-1363
0, 253-1788
Constant
Volume L/s
12-106
19-165
28-236
50-425
77-661
111-944
151-1416
198-1888
18-106
30-165
35-236
63-425
102-661
141-944
193-1363
253-1788
Constant
Volume Cfm
25-225
40-350
60-500
105-900
165-1400
240-2000
320-3000
420-4000
38-225
63-350
73-500
134-900
215-1400
300-2000
408-2887
536-3789
VAV-PRC012-EN 35
Performance Data
Table 24. Unit air pressure drop – in. wg (I-P)
Fan/Inlet Size
2SQ-04
2SQ-05
Airflow Cfm
200
225
200
250
300
350
Unit
0.03
0.03
0.03
0.04
0.06
0.09
2SQ-06
2SQ-08
2SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-06
200
300
400
500
0.03
0.11
0.24
0.44
0.01
0.07
0.16
0.32
0.16
0.29
0.35
0.48
0.10
0.15
0.34
0.45
0.05
0.16
0.31
0.49
0.01
0.05
0.10
0.16
0.01
0.02
0.06
0.11
250
550
850
1200
250
550
850
1200
330
400
450
500
250
300
400
500
250
500
700
900
200
400
550
700
200
400
550
700
0.03
0.06
0.12
0.19
Note:
Unit pressure drops do not include hot water coil or attenuator pressure drops.
Fan/Inlet Size
04SQ-12
04SQ-14
05SQ-10
05SQ-12
05SQ-14
6SQ-10
6SQ-12
6SQ-14
6SQ-16
7SQ-10
Airflow Cfm
330
750
1150
1550
330
750
1150
1550
700
1350
2000
2600
850
1000
1200
1400
700
1150
1600
2000
700
1350
2000
2600
400
900
1400
1900
700
950
1200
1400
400
750
1100
1400
400
900
1400
1900
0.01
0.04
0.19
0.41
0.01
0.05
0.12
0.22
0.01
0.01
0.12
0.27
0.01
0.04
0.19
0.41
0.01
0.09
0.26
0.53
0.01
0.03
0.12
0.22
0.01
0.08
0.22
0.39
0.01
0.09
0.28
0.58
Unit
0.02
0.11
0.28
0.51
0.02
0.11
0.26
0.48
36 VAV-PRC012-EN
Performance Data
Table 24. Unit air pressure drop – in. wg (I-P) (continued)
Fan/Inlet Size
04SQ-08
04SQ-10
Airflow Cfm
330
500
700
900
330
700
1050
1400
Unit
0.04
0.12
0.25
0.44
0.02
0.12
0.29
0.54
Note:
Unit pressure drops do not include hot water coil or attenuator pressure drops.
Fan/Inlet Size
7SQ-12
7SQ-14
7SQ-16
Airflow Cfm
850
1200
1600
2000
850
1550
2250
3000
850
1550
2250
3000
Table 25. Coil air pressure drop – in. wg (I-P)
Fan
Size
02SQ
03SQ
04SQ
Airflow
Cfm
200
300
400
500
600
250
500
750
1000
1250
1500
1-Row HW
(in. wg)
0.01
0.02
0.04
0.06
0.08
0.01
0.02
0.05
0.08
0.12
0.16
2-Row HW
(in. wg)
0.03
0.05
0.08
0.11
0.15
0.02
0.05
0.10
0.15
0.22
0.30
Fan Size Airflow Cfm
05SQ
400
700
1000
1250
1500
1750
1-Row HW
(in. wg)
0.01
0.04
0.07
0.10
0.14
0.19
06SQ
07SQ
600
1000
1500
2000
2500
3000
0.02
0.04
0.08
0.13
0.19
0.27
Note:
HW Coil Only pressure drops do not include unit pressure drop.
2-Row HW
(in. wg)
0.03
0.08
0.13
0.19
0.26
0.34
0.04
0.08
0.15
0.23
0.34
0.47
Table 26. Attenuator air pressure drop (I-P)
Fan Size Plenum Cfm Attenuator
02SQ
03SQ
50
150
350
550
750
950
50
250
500
750
1000
1200
0.00
0.00
0.02
0.05
0.10
0.16
0.00
0.00
0.02
0.06
0.13
0.21
04SQ
50
300
600
900
1200
1500
0.00
0.02
0.07
0.14
0.24
0.35
Note:
Plenum cfm = (Fan cfm) – (Min. valve cfm)
Fan Size Plenum Cfm
05SQ
06SQ
07SQ
50
300
650
1000
1300
1650
50
500
900
1300
1700
2100
50
800
1200
1600
2000
2400
Attenuator
0.00
0.01
0.05
0.14
0.28
0.52
0.00
0.00
0.02
0.07
0.17
0.36
0.00
0.01
0.05
0.14
0.30
0.58
Unit
0.01
0.02
0.12
0.27
0.01
0.07
0.27
0.59
0.01
0.07
0.27
0.59
VAV-PRC012-EN 37
Performance Data
Table 27. Attenuator air pressure drop (SI)
Fan Size Plenum L/s Attenuator
02SQ
03SQ
04SQ
24
118
236
354
472
566
24
71
165
260
354
448
24
142
283
425
566
708
Note:
Plenum cfm = (Fan cfm) – (Min. valve cfm)
0
1
5
15
32
52
0
1
4
12
24
40
0
5
18
36
59
88
Fan Size
05SQ
06SQ
07SQ
Plenum L/s Attenuator
24
236
425
613
802
991
24
142
307
472
613
779
24
378
566
755
944
1133
0
1
4
16
42
90
0
2
12
36
70
129
0
3
12
34
75
144
Table 28. Coil air pressure drop – Pa (SI)
Fan
Size
02SQ
03SQ
04SQ
Airflow
L/s
250
400
500
600
700
118
236
354
472
590
708
1-Row HW
(Pa)
3
6
10
14
20
2
6
12
19
29
40
2-Row HW
(Pa)
7
12
19
28
38
5
13
24
38
55
75
Fan Size
Airflow L/ s
05SQ
189
330
472
590
708
826
06SQ
07SQ
850
1300
1700
2150
2550
3000
Note:
HW coil only pressure drops do not include unit pressure drop.
1-Row HW
(Pa)
4
9
17
25
35
47
4
9
19
31
47
66
2-Row HW
(Pa)
8
19
33
48
65
85
9
19
36
58
85
117
38 VAV-PRC012-EN
Performance Data
Table 29. Unit air pressure drop-Pa (SI)
Fan/Inlet Size
2SQ-04
2SQ-05
2SQ-06
2SQ-08
2SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-06
04SQ-08
Airflow Cfm
94
189
260
330
94
189
260
330
118
142
189
236
118
236
330
425
94
106
94
118
142
165
94
142
189
236
118
260
401
566
118
260
401
566
156
189
212
236
156
236
330
425
Unit
25
38
85
112
2
12
24
39
2
5
14
39
12
41
76
123
7
9
7
11
16
22
7
16
29
46
8
28
59
110
4
17
40
79
40
73
88
119
10
29
63
109
04SQ-10
156
330
495
661
5
30
73
135
04SQ-12
156
354
543
731
5
28
69
127
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
Fan/Inlet Size
04SQ-14
05SQ-10
05SQ-12
05SQ-14
6SQ-10
6SQ-12
6SQ-14
6SQ-16
7SQ-10
7SQ-12
7SQ-14
7SQ-16
Airflow Cfm
330
543
755
944
330
637
944
1227
330
637
944
1227
401
472
566
661
401
566
755
944
401
731
1062
1416
401
731
1062
1416
156
354
543
731
189
354
519
661
189
425
661
897
189
425
661
897
330
448
566
661
VAV-PRC012-EN
Unit
2
3
31
68
2
9
47
101
2
9
47
101
2
12
2
8
31
55
5
27
65
120
1
20
55
98
2
23
71
144
2
21
65
131
55
2
5
31
68
2
18
67
147
2
18
67
147
39
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note:
When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
40
Pa In. wg
150
0.60
125
0.50
100
0.40
75
0.30
50
0.20
25
0.10
0
0.00
100
47
200
94
Series 02SQ—PSC
300
142
400
189
Airflow
500
236
600
283
700
330
800
378
Cfm
L/s
Pa In. wg
199 0.80
174 0.70
150 0.60
125 0.50
100
0.40
Series 03SQ—PSC
75
0.30
50
0.20
25 0.10
0
0.00
200
94
300
142
400
189
500
236
600
283
700
330
800
378
Airflow
900
425
1000
472
1100
519
1200
566
1300
614
1400
Cfm
661
L/s
Pa In. wg
199 0.80
174 0.70
150 0.60
125 0.50
100 0.40
75 0.30
50 0.20
Series 04SQ—PSC
25 0.10
0 0.00
300
142
400
189
500
236
600
283
700
330
800
378
900 1000 1100 1200 1300 1400 1500 1600 1700
Cfm
425 472 519 566 614 661 708 755 802
L/s
Airflow
VAV-PRC012-EN
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note:
When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
VAV-PRC012-EN
Pa
In. wg
199 0.80
174 0.70
150 0.60
125 0.50
100 0.40
75 0.30
50
0.20
25
0.10
0
0.00
300
142
500
236
700
330
Series 05SQ—PSC
900
425
1100
519
Airflow
1300
614
1500
708
1700
802
1900
897
2100
Cfm
991
L/s
Pa In. wg
199 0.80
Series 06SQ—PSC
174 0.70
150 0.60
125 0.50
100
0.40
75
0.30
50 0.20
25 0.10
0 0.00
400
189
600
283
800
378
1000 1200
472 566
1400
661
1600 1800
755
850
2000 2200
944 1038
2400
1133
2600 2800
1227
1322
Cfm
L/s
Airflow
Pa In. wg
199 0.80
174 0.70
150 0.60
125 0.50
100
0.40
75 0.30
50 0.20
25 0.10
Series 07SQ—PSC
0 0.00
800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400
Cfm
378 472 566 661 755 850 944 1038 1133
1227 1322
1416 1510
1605
L/s
Airflow
41
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
42
Pa In. wg
125 0.50
100 0.40
75
0.30
50
0.20
25
0.10
VSxF Size 03SQ—ECM
0 0.00
100
47
200
94
300
142
400
189
500
236
600
283
700
330
Airflow
800
378
900
425
1000
472
1100
519
1200
Cfm
566
L/s
Pa In. wg
125
0.50
100 0.40
75 0.30
50
0.20
25
0.10
0 0.00
200
94
400
189
VSxF 04SQ—ECM
600
283
800
378
Airflow
1000
472
1200
566
1400
661
1600
Cfm
755
L/s
Pa In. wg
125
0.50
100 0.40
75 0.30
50
0.20
25 0.10
VSxF 05SQ—ECM
0 0.00
300
142
500
236
700
330
900
425
1100
519
Airflow
1300
614
1500
708
1700
802
1900
897
2100
Cfm
991
L/s
VAV-PRC012-EN
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa
125
In. wg
0.50
100 0.40
75 0.30
50 0.20
25 0.10
VSxF 06SQ—ECM
0 0.00
600
283
800
378
1,000
472
1,200
566
1,400
661
1,600
755
Airflow
1,800
850
2,000
944
2,200
1038
2,400
1133
2,600
Cfm
1227
L/s
Table 30. Heating capacity (MBh) - fan size 02SQ (I-P)
Rows
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Gpm
1.0
2.0
3.0
4.0
5.0
0.50
1.0
2.0
3.0
4.0
5.0
Water
Pressure
Drop (ft)
0.16
0.53
1.85
3.85
6.51
9.79
1.00
3.42
7.05
11.82
17.68
150
-
9.14
9.94
10.25
10.41
10.51
12.59
13.42
13.71
13.86
13.94
200
-
10.34
11.40
11.80
12.02
12.15
15.23
16.60
17.08
17.33
17.48
250
-
11.34
12.63
13.14
13.41
13.58
17.40
19.34
20.04
20.40
20.62
Table 31. Heating capacity (MBh) - fan sizes 03SQ 04SQ (I-P)
Rows
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Gpm
6.0
7.0
8.0
9.0
10.0
1.0
2.0
3.0
4.0
5.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Water
Pressure
Drop (ft)
0.27
1.01
2.19
3.81
5.85
8.32
11.20
14.50
18.22
22.35
0.39
1.41
3.01
5.16
7.84
11.06
14.81
19.07
200
-
15.03
15.70
16.06
16.29
16.45
16.56
16.65
16.72
16.78
-
18.93
19.46
19.72
19.88
19.98
20.06
20.12
300
-
18.19
19.23
19.80
20.16
20.41
20.59
20.73
20.84
20.93
-
25.58
26.72
27.30
27.65
27.88
28.05
28.18
400
-
20.63
22.00
22.76
23.24
23.58
23.82
24.01
24.17
24.29
-
30.93
32.79
33.75
34.34
34.74
35.02
35.24
550
-
23.57
25.41
26.44
27.11
27.57
27.91
28.18
28.39
28.56
-
37.20
40.20
41.80
42.79
43.47
43.96
44.34
300
-
12.20
13.73
14.34
14.66
14.87
19.21
21.73
22.66
23.14
23.44
Airflow (Cfm)
350
-
12.97
14.73
15.43
15.81
16.05
20.74
23.84
25.00
25.62
25.99
400
-
13.67
15.66
16.45
16.89
17.17
22.06
25.71
27.12
27.86
28.32
Airflow (Cfm)
700
-
26.00
28.29
29.59
30.43
31.02
31.46
31.80
32.08
32.30
-
41.99
46.12
48.38
49.81
50.79
51.50
52.05
850
-
28.09
30.81
32.38
33.40
34.12
34.66
35.07
35.41
35.68
-
45.78
50.97
53.88
55.73
57.01
57.96
58.68
450
-
14.32
16.52
17.41
17.90
18.21
23.19
27.39
29.03
29.90
30.44
1000
-
29.99
33.08
34.91
36.11
36.96
37.59
38.08
38.48
38.80
-
48.85
55.02
58.54
60.81
62.40
63.57
64.46
500
-
14.93
17.33
18.32
18.87
19.21
24.19
28.90
30.77
31.77
32.40
1150 1300
-
31.71
35.15
37.23
38.60
39.58
40.31
40.88
41.34
41.71
-
51.38
58.45
62.56
65.23
67.10
68.49
69.57
-
33.27
37.05
39.38
40.93
42.03
42.86
43.51
44.03
44.46
-
53.52
61.41
66.05
69.11
71.26
72.87
74.11
550
-
15.51
18.10
19.18
19.78
20.17
25.07
30.27
32.37
33.50
34.21
600
-
16.05
18.82
20.01
20.66
21.08
25.85
31.52
33.84
35.10
35.89
1450 1600
-
34.68
38.83
41.38
43.10
44.34
45.26
45.99
46.57
47.05
-
55.34
63.98
69.14
72.55
74.98
76.79
78.19
-
35.97
40.51
43.26
45.15
46.51
47.54
48.34
48.99
49.52
-
56.92
66.24
71.88
75.63
78.31
80.32
81.88
700
-
17.02
20.18
21.56
22.32
22.81
27.19
33.72
36.46
37.96
38.92
VAV-PRC012-EN 43
Performance Data
Table 32. Heating capacity (MBh) - fan size 05SQ (I-P)
Rows
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Gpm
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Water
Pressure
Drop (ft)
0.39
1.39
2.96
5.08
7.72
10.90
14.59
18.79
0.29
1.08
2.33
4.03
6.18
8.76
11.79
15.24
350
-
29.95
31.40
32.14
32.58
32.87
33.08
33.24
-
21.67
23.02
23.76
24.23
24.55
24.79
24.97
500
-
37.69
40.36
41.74
42.59
43.16
43.57
43.88
-
25.25
27.14
28.20
28.87
29.34
29.69
29.95
650
-
43.62
47.58
49.69
51.00
51.88
52.53
53.02
-
28.09
30.49
31.85
32.72
33.34
33.79
34.14
800
-
48.30
53.51
56.37
58.16
59.39
60.28
60.96
-
30.49
33.38
35.03
36.10
36.86
37.42
37.85
Airflow (Cfm)
1000 1200 1400 1600 1800 2000
-
53.17
59.95
63.77
66.21
67.90
69.14
70.09
-
33.30
36.75
38.78
40.11
41.05
41.75
42.29
-
56.95
65.16
69.90
72.97
75.11
76.69
77.91
-
35.79
39.71
42.12
43.71
44.83
45.67
46.33
-
59.97
69.45
75.05
78.72
81.30
83.22
84.70
-
37.96
42.39
45.14
46.98
48.29
49.28
50.05
-
62.43
73.07
79.45
83.68
86.69
88.93
90.66
-
39.88
44.89
47.92
50.01
51.50
52.63
53.51
-
64.49
76.15
83.26
88.02
91.42
93.97
95.95
-
41.61
47.17
50.48
52.81
54.50
55.76
56.76
-
66.24
78.82
86.60
91.85
95.63
98.47
100.69
-
43.17
49.26
52.91
55.44
57.30
58.71
59.82
2150
-
44.25
50.73
54.64
57.30
59.30
60.82
62.01
-
67.38
80.59
88.84
94.45
98.49
101.54
103.93
Table 33. Heating capacity (MBh) - fan size 06SQ & 07SQ (I-P)
Rows
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Gpm
1.0
2.0
3.0
4.0
5.0
6.0
0.5
1.0
2.0
3.0
4.0
5.0
6.0
Water
Pressure
Drop (ft)
0.12
0.40
1.37
2.83
4.76
7.13
9.93
0.77
2.58
5.27
8.78
13.07
18.13
700
-
-
31.21
33.81
35.27
36.20
36.85
-
47.79
52.10
54.37
55.77
56.71
900
-
-
34.50
37.76
39.61
40.80
41.64
-
54.01
60.08
63.38
65.44
66.85
Airflow (Cfm)
1100 1300 1500 1700 1900
-
-
37.47
41.19
43.42
44.87
45.90
-
58.79
66.51
70.82
73.55
75.43
-
-
40.06
44.25
46.86
48.57
49.78
-
62.56
71.79
77.06
80.45
82.80
-
-
42.33
47.10
50.00
51.97
53.36
-
65.61
76.21
82.39
86.40
89.22
-
-
44.37
49.74
52.91
55.12
56.70
-
68.13
79.96
86.98
91.60
94.86
-
-
46.21
52.17
55.63
58.07
59.83
-
70.25
83.19
91.00
96.18
99.86
2100
-
-
47.89
54.40
58.24
60.84
62.79
-
72.05
86.00
94.54
100.26
104.34
2300
-
-
49.43
56.49
60.68
63.46
65.59
-
73.60
88.47
97.69
103.91
108.37
2500
-
-
50.85
58.43
62.97
66.00
68.24
-
74.95
90.65
100.51
107.20
112.03
2700
-
-
52.16
60.24
65.14
68.41
70.77
-
76.14
92.61
103.06
110.19
115.36
Water Coil Notes (I-P)
1.
Fouling Factor = 0.0005.
2. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD):
LAT
=
EAT
+
------------------------------------
WTD
=
EWT LWT
=
------------------------
44
3. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer to correction factors for different entering conditions.
Table 34. Temperature correction factors for water pressure drop (ft)
Average Water Temperature
Correction Factor
200
0.970
190
0.985
180
1.000
170
1.020
160
1.030
150
1.050
140
1.080
130
1.100
120
1.130
110
1.150
VAV-PRC012-EN
Performance Data
Table 35. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air
Correction Factor
40
0.355
50
0.446
60
0.537
70
0.629
80
0.722
90
0.814
100
0.907
110
1.000
120
1.093
130
1.187
Table 36. Heating capacity (kW) - fan size 02SQ (SI)
Rows
1-Row
Capacity kW
2-Row
Capacity kW
L/s
0.03
0.06
0.13
0.19
0.25
0.32
0.06
0.13
0.19
0.25
0.32
Water
Pressure
Drop (kPa)
0.47
1.59
5.52
11.51
19.45
29.27
3.00
10.21
21.07
35.33
52.84
71
-
2.68
2.91
3.00
3.05
3.08
3.69
3.93
4.02
4.06
4.09
94
-
3.03
3.34
3.46
3.52
3.56
4.46
4.86
5.01
5.08
5.12
118
-
3.32
3.70
3.85
3.93
3.98
5.10
5.67
5.87
5.98
6.04
Table 37. Heating capacity (kW) - fan sizes 03SQ 04SQ(SI)
Rows
1-Row
Capacity kW
2-Row
Capacity kW
L/s
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.57
0.63
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
Water
Pressure
Drop (kPa)
0.81
3.02
6.56
11.39
17.49
24.86
33.49
43.36
54.46
66.80
1.18
4.22
8.99
15.41
23.45
33.07
44.26
57.00
142
-
5.33
5.64
5.80
5.91
5.98
6.03
6.08
6.11
6.13
-
7.50
7.83
8.00
8.10
8.17
8.22
8.26
94
-
4.40
4.60
4.71
4.77
4.82
4.85
4.88
4.90
4.92
-
5.55
5.70
5.78
5.83
5.86
5.88
5.90
189
-
6.04
6.45
6.67
6.81
6.91
6.98
7.04
7.08
7.12
-
9.07
9.61
9.89
10.06
10.18
10.26
10.33
260
-
6.91
7.45
7.75
7.94
8.08
8.18
8.26
8.32
8.37
-
10.90
11.78
12.25
12.54
12.74
12.88
12.99
142
-
3.58
4.02
4.20
4.30
4.36
5.63
6.37
6.64
6.78
6.87
165
-
3.80
4.32
4.52
4.63
4.71
6.08
6.99
7.33
7.51
7.62
Airflow (L/s)
189
-
4.01
4.59
4.82
4.95
5.03
6.46
7.54
7.95
8.16
8.30
212
-
4.20
4.84
5.10
5.25
5.34
6.80
8.03
8.51
8.76
8.92
330
-
7.62
8.29
8.67
8.92
9.09
9.22
9.32
9.40
9.47
-
12.31
13.52
14.18
14.60
14.88
15.09
15.25
Airflow (L/s)
401
-
8.23
9.03
9.49
9.79
10.00
10.16
10.28
10.38
10.46
-
13.42
14.94
15.79
16.33
16.71
16.99
17.20
472
-
8.79
9.70
10.23
10.58
10.83
11.02
11.16
11.28
11.37
-
14.32
16.12
17.16
17.82
18.29
18.63
18.89
755
-
10.16
11.38
12.13
12.63
12.99
13.27
13.48
13.65
13.79
-
16.22
18.75
20.26
21.26
21.97
22.50
22.92
684
-
10.16
11.38
12.13
12.63
12.99
13.27
13.48
13.65
13.79
-
16.22
18.75
20.26
21.26
21.97
22.50
22.92
613
-
9.75
10.86
11.54
11.99
12.32
12.56
12.75
12.90
13.03
-
15.68
18.00
19.36
20.25
20.89
21.36
21.72
543
-
9.29
10.30
10.91
11.31
11.60
11.81
11.98
12.12
12.22
-
15.06
17.13
18.33
19.12
19.67
20.07
20.39
236
-
4.38
5.08
5.37
5.53
5.63
7.09
8.47
9.02
9.31
9.50
260
-
4.55
5.30
5.62
5.80
5.91
7.35
8.87
9.49
9.82
10.03
283
-
4.70
5.52
5.86
6.06
6.18
7.58
9.24
9.92
10.29
10.52
330
-
4.70
5.52
5.86
6.06
6.18
7.58
9.24
9.92
10.29
10.52
VAV-PRC012-EN 45
Performance Data
Table 38. Heating capacity (kW) - fan size 05SQ(SI)
Rows
1-Row
Capacity kW
2-Row
Capacity kW
L/s
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
Water
Pressure
Drop (kPa)
1.16
4.16
8.85
15.17
23.09
32.57
43.60
56.16
0.87
3.22
6.95
12.04
18.46
26.20
35.23
45.57
165
-
8.78
9.20
9.42
9.55
9.63
9.70
9.74
-
6.35
6.75
6.96
7.10
7.19
7.26
7.32
236
-
11.05
11.83
12.23
12.48
12.65
12.77
12.86
-
7.40
7.95
8.26
8.46
8.60
8.70
8.78
307
-
12.78
13.94
14.56
14.95
15.21
15.39
15.54
-
8.23
8.94
9.33
9.59
9.77
9.90
10.01
Table 39. Heating capacity (kW) - fan sizes 06SQ & 07SQ (SI)
Rows
1-Row
Capacity kW
2-Row
Capacity kW
L/s
0.06
0.13
0.19
0.25
0.32
0.38
0.03
0.06
0.13
0.19
0.25
0.32
0.38
Water
Pressure
Drop (kPa)
0.36
1.20
4.10
8.46
14.22
21.30
29.68
2.31
7.71
15.74
26.24
39.08
54.19
330
-
-
9.15
9.91
10.34
10.61
10.80
-
14.01
15.27
15.94
16.34
16.62
425
-
-
10.11
11.07
11.61
11.96
12.20
-
15.83
17.61
18.58
19.18
19.59
519
-
-
10.98
12.07
12.73
13.15
13.45
-
17.23
19.49
20.75
21.55
22.11
613
-
-
11.74
12.97
13.73
14.23
14.59
-
18.33
21.04
22.58
23.58
24.27
378
-
14.16
15.68
16.52
17.04
17.40
17.67
17.87
-
8.94
9.78
10.27
10.58
10.80
10.97
11.09
472
-
15.58
17.57
18.69
19.41
19.90
20.26
20.54
-
9.76
10.77
11.37
11.76
12.03
12.24
12.40
Airflow (L/s)
566
-
16.69
19.10
20.48
21.38
22.01
22.48
22.83
-
10.49
11.64
12.34
12.81
13.14
13.39
13.58
661
-
17.57
20.35
21.99
23.07
23.83
24.39
24.82
-
11.12
12.42
13.23
13.77
14.15
14.44
14.67
Airflow (L/s)
708
-
-
12.41
13.80
14.66
15.23
15.64
-
19.23
22.33
24.14
25.32
26.15
802
-
-
13.00
14.58
15.51
16.15
16.62
-
19.97
23.43
25.49
26.85
27.80
897
-
-
13.54
15.29
16.30
17.02
17.54
-
20.59
24.38
26.67
28.19
29.27
755
-
18.30
21.41
23.28
24.52
25.41
26.06
26.57
-
11.69
13.16
14.04
14.66
15.09
15.42
15.68
849
-
18.90
22.32
24.40
25.80
26.79
27.54
28.12
-
12.19
13.82
14.79
15.48
15.97
16.34
16.63
944
-
19.41
23.10
25.38
26.92
28.03
28.86
29.51
-
12.65
14.44
15.51
16.25
16.79
17.21
17.53
991
-
-
14.03
15.94
17.07
17.83
18.40
-
21.11
25.20
27.71
29.38
30.58
1085 1180 1274
-
-
14.49
16.55
17.78
18.60
19.22
-
21.57
25.93
28.63
30.45
31.76
-
-
14.90
17.12
18.46
19.34
20.00
-
21.97
26.57
29.46
31.42
32.83
-
-
14.90
17.12
18.46
19.34
20.00
-
21.97
26.57
29.46
31.42
32.83
1015
-
19.41
23.10
25.38
26.92
28.03
28.86
29.51
-
12.65
14.44
15.51
16.25
16.79
17.21
17.53
Water Coil Notes (SI)
1.
Fouling Factor = 0.0005.
2. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
LAT
=
EAT
+ -----------------------------
WTD
=
EWT LWT
= kW
3. Capacity based on 21°C entering air temperature and 82°Centering water temperature. Refer to correction factors for different entering conditions.
Table 40. Temperature correction factors for water pressure drop (kPa)
Average Water Temperature
Correction Factor
93
0.970
88
0.985
82
1.000
77
1.020
71
1.030
66
1.050
60
1.080
54
1.100
49
1.130
43
1.150
Table 41. Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air
Correction Factor
22
0.355
27
0.446
33
0.537
38
0.629
44
0.722
50
0.814
55
0.907
61
1.000
67
1.093
72
1.187
46 VAV-PRC012-EN
Performance Data
Low Height Parallel Fan-Powered Terminal Units
Table 42. Primary airflow control factory settings – I-P
Control Type
Direct Digital Control/
UCM
Pneumatic with
Volume Regulator
Analog Electronic
Air Valve Size
(in.)
5
6
8
8x14
5
6
8
8x14
5
6
8
8x14
Maximum Valve
Cfm
350
500
900
2200
350
500
900
2100
350
500
900
2200
Maximum
Controller Cfm
40-350
60-500
105-900
200-2200
63-350
73-500
134-900
297-2100
82-350
120-500
210-900
440-2200
Table 43. Primary airflow control factory settings – SI
Control Type
Direct Digital Control/
UCM
Pneumatic with Volume
Regulator
Air Valve Size
(in.)
5
6
8
8x14
5
6
8
8x14
Maximum Valve
L/s
165
236
425
1038
165
236
425
991
Analog Electronic
5
6
8
8x14
165
236
425
1038
Note:
Maximum airflow must be greater than or equal to minimum airflow.
Maximum
Controller L/s
19-165
28-236
50-425
104-1038
30-165
35-236
63-425
140-991
39-165
57-236
100-425
208-1038
Table 44. Unit air pressure drop – in. wg (I-P)
Fan/Inlet Size
08SQ-05
08SQ-06
08SQ-08
09SQ-06
Airflow Cfm
150
200
250
350
200
300
400
500
400
600
800
900
200
300
400
500
Cooling Only Unit
(in. wg)
0.01
0.02
0.03
0.05
0.01
0.04
0.06
0.09
0.01
0.09
0.16
0.20
0.01
0.04
0.06
0.09
Notes:
1. Units with Electric Coils per fan size add 0.01" (3 Pa) to cooling only value.
2. HW Coil only pressure drops are just for the heating coil.
Fan/Inlet Size
09SQ-08
09SQ-8x14
10SQ-08
10SQ-8x14
Minimum Controller
Cfm
0, 40-350
0, 60-500
0, 105-900
0, 220-2200
0, 63-350
0, 73-500
0, 134-900
0, 297-2100
0, 82-310
0, 120-360
0, 210-660
0, 440-1475
Minimum Controller
L/s
0, 19-165
0, 28-236
0, 50-425
0, 104-1038
0, 30-165
0, 35-236
0, 63-425
0, 140-991
0, 39-146
0, 57-170
0, 100-311
0, 208-696
Constant Volume
Cfm
40-350
60-500
105-900
220-2200
63-350
73-500
134-900
297-2100
82-310
120-360
210-660
440-1475
Constant Volume
L/s
19-165
28-236
50-425
104-1038
30-165
35-236
63-425
140-991
39-146
57-170
100-311
208-696
Airflow Cfm Cooling Only Unit
(in. wg)
400
600
800
900
700
1100
1500
1900
400
600
800
900
725
1000
1200
1450
0.01
0.09
0.16
0.20
0.10
0.25
0.47
0.75
0.01
0.09
0.18
0.24
0.18
0.36
0.53
0.78
VAV-PRC012-EN 47
Performance Data
Table 45. Unit air pressure drop – Pa (SI)
Inlet/Fan Size
08SQ-05
08SQ-06
08SQ-08
09SQ-06
Airflow L/s
71
94
118
165
200
142
189
236
189
283
378
425
94
142
189
236
Cooling Only
Unit (Pa)
2
5
7
13
0.01
10
16
24
2
21
40
51
2
10
16
24
Notes:
1. Units with Electric Coils per fan size add 0.01" (3 Pa) to cooling only value.
2. HW Coil only pressure drops are just for the heating coil.
Table 46. Coil air pressure drop in. wg (I-P)
Fan Size Airflow Cfm 1-Row HW
(in. wg)
2-Row HW
(in. wg)
08SQ
09SQ
250
400
550
700
850
100
200
300
400
450
0.00
0.01
0.02
0.03
0.04
0.01
0.03
0.05
0.08
0.11
0.01
0.02
0.04
0.06
0.07
0.03
0.06
0.10
0.15
0.20
10SQ
725
800
900
1000
1100
1150
0.09
0.11
0.13
0.16
0.19
0.20
0.17
0.20
0.24
0.29
0.33
0.35
Note:
HW Coil Only pressure drops do not include unit pressure drop.
Inlet/Fan Size
09SQ-08
09SQ-8x14
10SQ-08
10SQ-8x14
Airflow L/s
189
283
378
425
330
519
708
897
189
283
378
425
345
475
565
685
Cooling Only
Unit (Pa)
2
21
40
51
26
63
116
185
2
23
45
59
47
91
131
195
Pa (SI)
Fan Size Airflow L/s 1-Row HW
(Pa)
08SQ
09SQ
10SQ
118
189
260
330
401
47
94
142
189
212
342
375
425
475
520
543
3
7
12
19
27
4
7
1
2
9
22
26
33
40
46
49
2-Row HW (Pa)
7
15
25
36
51
2
5
10
15
18
43
49
60
72
82
87
Table 47. Attenuator air pressure drop
Fan Size
08SQ
09SQ
10SQ
(I-P)
Plenum Cfm
150
250
350
450
350
500
650
800
Attenuator
not available
0.01
0.03
0.05
0.07
0.05
0.08
0.13
0.18
48
Fan Size
08SQ
09SQ
10SQ
(SI)
Plenum L/s
71
118
165
212
165
236
307
378
Attenuator
not available
0.01
0.01
0.02
0.02
0.02
0.03
0.04
0.05
VAV-PRC012-EN
Performance Data
Performance Data Fan Curves
LPCF and LPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
150 0.60
125
0.50
100 0.40
75 0.30
50 0.20
25 0.10
150
71
200
94
Low-Height Parallel 08SQ—PSC
250
118
300
142
350
165
Airflow
400
189
450
212
500
236
550
Cfm
260
L/s
Pa In. wg
199 0.80
174
0.70
150
0.60
125 0.50
100
0.40
75
0.30
50 0.20
25 0.10
400
189
Pa In. wg
199
0.80
174 0.70
150 0.60
125
0.50
100 0.40
75 0.30
50 0.20
25 0.10
300
142
500
236
Low-Height Parallel 09SQ—PSC
500
236
600
273
700
330
Airflow
800
378
Low-Height Parallel 10SQ—PSC
900
425
700
330
1000
472
Cfm
L/s
900
425
Airflow
1100
519
1300
614
1500
708
Cfm
L/s
VAV-PRC012-EN 49
Performance Data
LPCF and LPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
125 0.50
100 0.40
LPxF 08SQ—ECM
75 0.30
50 0.20
25
0.10
50
24
150
71
250
118
Airflow
350
165
LPxF 09SQ—ECM
450
212
Cfm
L/s
Pa In. wg
125 0.50
100 0.40
75
0.30
50
0.20
25
0.10
200
94
300
142
400
189
500
236
600
283
Airflow
700
330
800
378
900
425
1000
472
1100
Cfm
519
L/s
50 VAV-PRC012-EN
Performance Data
Table 48. Heating capacity (MBh) - fan sizes 08SQ & 09SQ (I-P)
Rows
1-Row
Capacity MBH
2-Row
Capacity MBH
Gpm
0.5
1.0
1.5
2.0
2.5
1.0
2.0
3.0
4.0
5.0
Water
Pressure
Drop (ft)
0.80
2.67
5.43
9.02
13.39
0.89
3.02
6.24
10.47
15.66
100
7.73
8.58
8.90
9.06
9.17
9.36
9.74
9.86
9.92
9.96
200
10.43
12.15
12.83
13.20
13.43
15.49
16.83
17.29
17.53
17.67
300
12.20
14.51
15.52
16.07
16.43
19.69
22.20
23.11
23.59
23.88
400
13.50
16.37
17.69
18.42
18.89
22.72
26.42
27.82
28.56
29.01
Airflow (Cfm)
500
14.51
17.98
19.56
20.47
21.06
25.00
29.83
31.72
32.73
33.36
600
15.33
19.42
21.21
22.30
23.00
26.79
32.65
35.02
36.29
37.10
700
16.03
20.69
22.72
23.97
24.79
28.23
35.03
37.85
39.39
40.36
800
16.63
21.82
24.15
25.51
26.45
29.41
37.06
40.32
42.11
43.24
900
17.15
22.85
25.46
26.95
28.00
30.41
38.83
42.49
44.52
45.81
Table 49. Heating capacity (MBh) - fan size 10SQ (I-P)
Rows
1-Row Capacity
MBH
2-Row Capacity
MBH
Gpm
1.5
2.0
3.0
4.0
5.0
0.7
1.0
1.5
2.0
2.5
Water
Pressure
Drop (ft)
1.51
2.80
5.69
9.45
14.03
1.85
3.07
6.32
10.58
15.80
700
18.46
20.69
22.72
23.97
24.79
32.51
35.03
37.85
39.39
40.36
800
19.31
21.82
24.15
25.51
26.45
34.20
37.06
40.32
42.11
43.24
900
20.07
22.85
25.46
26.95
28.00
35.65
38.83
42.49
44.52
45.81
Airflow (Cfm)
1000
20.75
23.78
26.67
28.32
29.46
36.90
40.38
44.42
46.68
48.13
1100
21.37
24.64
27.79
29.62
30.83
38.01
41.76
46.15
48.62
50.22
1200
21.93
25.43
28.84
30.84
32.14
38.98
42.99
47.71
50.39
52.13
1240
22.14
25.72
29.24
31.30
32.66
39.34
43.44
48.29
51.06
52.84
Water Coil Notes (I-P)
Note: Fouling Factor = 0.0005.
Note: The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed
140°F when mounted on plenum inlet.
Note: The following equations may be used in calculating Leaving Air Temperature (LAT) and
Water Temperature Difference (WTD).
LAT
=
EAT
+ --------------------------------------
VAV-PRC012-EN
WTD
=
EWT LWT
= ------------------------
Note: Capacity based on 70°F entering air temperature and 180°F entering water temperature.
Refer to correction factors for different entering conditions.
Table 50.
Temperature correction factors for water pressure drop (WPD)
Average Water Temperature 200 190 180 170 160 150 140 130 120 110
Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150
Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air 40 50 60 70 80 90 100 110 120 130
Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
51
Performance Data
Table 51. Heating capacity (kW) - fan sizes 08SQ & 09SQ (SI)
Rows
1-Row Capacity kW
2-Row Capacity kW
L/s
0.03
0.06
0.09
0.13
0.16
0.06
0.13
0.19
0.25
0.32
Water Pressure
Drop (kPa)
2.39
7.98
16.24
26.97
40.04
2.65
9.03
18.65
31.29
46.82
47
2.27
2.51
2.61
2.66
2.69
2.74
2.85
2.89
2.91
2.92
94
3.06
3.56
3.76
3.87
3.94
4.54
4.93
5.07
5.14
5.18
142
3.58
4.25
4.55
4.71
4.81
5.77
6.51
6.77
6.91
7.00
Table 52. Heating capacity (kW) - fan size 10SQ (SI)
Rows
1-Row Capacity kW
2-Row Capacity kW
L/s
0.04
0.06
0.09
0.13
0.16
0.09
0.13
0.19
0.25
0.32
Water Pressure
Drop (kPa)
4.51
8.37
17.02
28.25
41.94
5.53
9.19
18.89
31.61
47.22
330
5.41
6.06
6.66
7.03
7.27
9.53
10.27
11.09
11.54
11.83
378
5.66
6.40
7.08
7.48
7.75
10.02
10.86
11.82
12.34
12.67
189
3.96
4.80
5.18
5.40
5.54
6.66
7.74
8.15
8.37
8.50
Airflow (L/s)
236 283
4.25
5.27
5.73
6.00
6.17
7.33
8.74
9.30
9.59
9.78
4.49
5.69
6.22
6.54
6.74
7.85
9.57
10.26
10.64
10.87
425
5.88
6.70
7.46
7.90
8.21
10.45
11.38
12.45
13.05
13.43
Airflow (L/s)
472
6.08
6.97
7.81
8.30
8.63
10.82
11.84
13.02
13.68
14.10
519
6.26
7.22
8.14
8.68
9.03
11.14
12.24
13.52
14.25
14.72
330
4.70
6.06
6.66
7.03
7.27
8.27
10.27
11.09
11.54
11.83
566
6.43
7.45
8.45
9.04
9.42
11.42
12.60
13.98
14.77
15.28
378
4.87
6.40
7.08
7.48
7.75
8.62
10.86
11.82
12.34
12.67
585
6.49
7.54
8.57
9.17
9.57
11.53
12.73
14.15
14.96
15.49
Water Coil Notes (SI)
1.
Fouling Factor = 0.0005.
2. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed
60°C when mounted on plenum inlet.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
LAT
=
EAT
+ -----------------------------
425
5.03
6.70
7.46
7.90
8.21
8.91
11.38
12.45
13.05
13.43
WTD
=
EWT LWT
=
----------------------------------
4. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different entering conditions.
Table 53.
Temperature correction factors for water pressure drop (kPa)
Average Water Temperature 93 88 82 77 71 66 60 54 49 43
Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150
Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air 22 27 33 38 44 50 55 61 67 72
Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
52 VAV-PRC012-EN
Performance Data
Low Height Series Fan-Powered Terminal Units
Table 54. Primary airflow control factory settings-I-P
Control Type
Direct Digital Control/UCM
Air Valve Size
(in.)
Maximum Valve
Cfm
5
6
8
8x14
350
500
900
2200
Pneumatic with Volume
Regulator
Analog Electronic
5
6
8
8x14
5
6
8
8x14
350
500
900
2100
350
500
900
2200
Maximum Controller
Cfm
40-350
60-500
105-900
200-2200
63-350
73-500
134-900
297-2100
82-350
120-500
210-900
440-2200
Minimum Controller
Cfm
0, 40-350
0, 60-500
0, 105-900
0, 220-2200
0, 63-350
0, 73-500
0, 134-900
0, 297-2100
0, 82-310
0, 120-360
0, 210-660
0, 440-1475
Constant Volume
Cfm
40-350
60-500
105-900
220-2200
63-350
73-500
134-900
297-2100
82-310
120-360
210-660
440-1475
Table 55. Primary airflow control factory settings-SI
Control Type
Air Valve Size
(in.)
Maximum
Valve L/s
Direct Digital Control/ UCM
Pneumatic with Volume Regulator
Analog Electronic
5
6
8
8x14
5
6
8
8x14
5
6
8
8x14
165
236
425
1038
165
236
425
991
165
236
425
1038
Note:
Maximum airflow must be greater than or equal to minimum airflow.
Maximum Controller
L/s
Minimum Controller L/ s
19-165
28-236
50-425
104-1038
30-165
35-236
63-425
140-991
39-165
57-236
100-425
208-1038
0, 19-165
0, 28-236
0, 50-425
0, 104-1038
0, 30-165
0, 35-236
0, 63-425
0, 140-991
0, 39-146
0, 57-170
0, 100-311
0, 208-696
Table 56. Unit air pressure drop
Fan/Inlet Size
08SQ-05
08SQ-06
08SQ-08
09SQ-06
in. wg (I-P)
Airflow Cfm
150
250
350
150
275
400
500
150
275
400
500
350
400
450
500
Cooling Only
0.01
0.03
0.11
0.02
0.14
0.35
0.58
0.01
0.05
0.13
0.21
0.17
0.26
0.37
0.50
Fan/Inlet Size
08SQ-05
08SQ-06
08SQ-08
09SQ-06
Pa (SI
Airflow L/s
71
118
165
71
130
189
236
71
130
189
236
165
189
212
236
19-165
28-236
50-425
104-1038
30-165
35-236
63-425
140-991
39-146
57-170
100-311
208-696
Cooling Only
3
14
32
52
2
9
28
5
34
86
143
43
66
93
124
VAV-PRC012-EN 53
Performance Data
Table 56. Unit air pressure drop (continued)
09SQ-08
09SQ-8x14
10SQ-08
10SQ-8x14
in. wg (I-P)
400
600
750
900
600
700
900
1050
400
600
800
600
900
1100
1500
0.08
0.38
0.84
0.21
0.50
0.77
1.47
0.08
0.24
0.40
0.61
0.18
0.27
0.51
0.73
Table 57. Coil air pressure drop in.wg (I-P)
Fan
Size Airflow Cfm
1-Row HW (in. wg)
2-Row HW (in. wg)
08SQ
09SQ
100
200
300
400
500
400
550
700
850
1000
0.00
0.01
0.02
0.03
0.05
0.03
0.06
0.09
0.13
0.18
0.01
0.03
0.05
0.07
0.10
0.07
0.12
0.17
0.24
0.32
10SQ
400
800
1200
1600
2000
0.01
0.03
0.06
0.11
0.16
0.02
0.07
0.12
0.20
0.29
Note:
HW Coil Only pressure drops do not include unit pressure drop.
Table 58. Attenuator air pressure drop
Fan Size
08SQ
09SQ
10SQ
(I-P)
Plenum Cfm
150
250
350
450
350
500
650
800
400
700
1000
1300
1600
Attenuator
0.02
0.04
0.06
0.09
0.06
0.10
0.15
0.22
0.02
0.05
0.09
0.14
0.20
54
09SQ-08
8x14-09SQ
10SQ-08
10SQ-8x14
Fan Size
08SQ
09SQ
10SQ
(SI)
Plenum L/s
71
118
165
212
165
236
307
378
189
330
472
614
755
Pa (SI
189
283
354
425
283
330
425
495
189
283
378
283
425
519
708
Pa (SI)
Fan Size Airflow L/s 1-Row HW (Pa) 2-Row HW (Pa)
08SQ
09SQ
10SQ
189
260
330
401
472
47
94
142
189
236
189
378
566
755
944
9
15
23
33
44
5
9
1
3
13
3
8
16
27
40
18
29
43
0
80
3
6
11
18
25
6
16
31
50
72
Attenuator
0.01
0.01
0.02
0.03
0.02
0.03
0.05
0.06
0.01
0.02
0.03
0.04
0.06
VAV-PRC012-EN
20
94
209
51
124
191
367
21
59
100
151
44
66
126
182
Performance Data
LSCF and LSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note:
When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
199 0.80
174 0.70
150
0.60
125
0.50
100
0.40
75 0.30
50 0.20
25 0.10
0 0.00
150
71
200
94
Low-Height Series 08SQ—PSC
250
118
300
142
350
165
Airflow
400
189
450
212
500
236
550
260
600
Cfm
283
L/s
Pa In. wg
199
0.80
174 0.70
150
0.60
125 0.50
100
0.40
75
0.30
50 0.20
25 0.10
0
0.00
300
142
Low-Height Series 09SQ—PSC
400
189
500
236
600
283
700
330
Airflow
800
378
900
425
1000
472
1100
Cfm
519
L/s
Pa In. wg
199
0.80
174
0.70
150
0.60
125 0.50
100 0.40
75
0.30
50 0.20
25 0.10
0
0.00
300
142
Low-Height Series 10SQ—PSC
500
236
700
330
900
425
1100
519
1300
614
Airflow
1500
708
1700
802
1900
897
2100
991
2300
Cfm
1086
L/s
VAV-PRC012-EN 55
Performance Data
LSCF and LSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
56
Pa In. wg
125
0.50
100
0.40
75 0.30
50 0.20
25 0.10
LSxF 08SQ—ECM
0
0.00
50
24
Pa In. wg
125 0.50
100
47
150
71
200
94
250
118
300
142
Airflow
LSxF 09SQ—ECM
350
165
400
189
450
212
500
236
Cfm
L/s
100 0.40
75
0.30
50 0.20
25 0.10
0
0.00
200
94
300
142
400
189
500
236
600
283
Airflow
700
330
800
378
900
425
1000
472
Cfm
L/s
Pa In. wg
125 0.50
100 0.40
75
0.30
50
0.20
LSxF 10SQ—ECM
25 0.10
0 0.00
300
142
500
236
700
330
900
425
1100
519
Airflow
1300
614
1500
708
1700
802
1900
Cfm
897
L/s
VAV-PRC012-EN
Performance Data
Table 59. Heating capacity (MBh) - fan sizes 08SQ & 09SQ (I-P)
Rows
1-Row Capacity
MBH
2-Row Capacity
MBH
Gpm
1.0
2.0
3.0
4.0
5.0
6.0
1.0
2.0
3.0
4.0
5.0
Water
Pressure
Drop (ft)
0.15
0.58
1.27
2.24
3.48
4.98
0.76
2.60
5.39
9.06
13.57
100
-
-
7.92
8.08
8.17
8.24
9.04
9.45
9.59
9.66
9.70
200
-
-
11.16
11.48
11.69
11.83
14.59
15.95
16.43
16.68
16.83
300
-
-
13.45
13.94
14.25
14.47
18.26
20.70
21.60
22.08
22.37
400
-
-
15.34
15.98
16.39
16.69
20.87
24.34
25.68
26.40
26.85
Airflow (Cfm)
500
-
-
16.97
17.76
18.28
18.65
22.83
27.24
29.01
29.96
30.56
600
-
-
18.42
19.36
19.99
20.43
24.35
29.61
31.78
32.96
33.71
700
-
-
19.73
20.82
21.54
22.06
25.57
31.59
34.14
35.54
36.43
800
-
-
20.92
22.16
22.98
23.58
26.58
33.28
36.17
37.78
38.80
900
-
-
22.01
23.39
24.32
24.99
27.42
34.74
37.95
39.75
40.90
1000
-
-
23.02
24.54
25.57
26.31
28.14
36.02
39.53
41.51
42.78
Table 60. Heating capacity (MBh) - fan size 10SQ (I-P)
Rows
1-Row Capacity
MBH
2-Row Capacity
MBH
Gpm
1.0
2.0
4.0
6.0
8.0
10.0
1.0
2.0
3.0
4.0
5.0
Water
Pressure
Drop (ft)
0.16
0.61
2.32
5.09
8.91
13.77
1.29
4.31
8.84
14.77
22.03
450
-
-
25.05
26.10
26.66
27.02
28.40
33.46
35.30
36.25
36.83
600
-
-
28.61
30.00
30.76
31.23
32.18
39.56
42.41
43.91
44.83
750
-
-
31.67
33.40
34.34
34.95
34.87
44.37
48.23
50.30
51.58
Airflow (Cfm)
900 1050 1200 1350 1500 1650 1800 1950
-
-
34.39
36.45
37.59
38.32
-
-
36.86
39.26
40.59
41.44
-
-
39.12
41.85
43.38
44.36
-
-
41.23
44.28
46.00
47.11
-
-
43.18
46.57
48.48
49.72
-
-
45.02
48.73
50.83
52.20
-
-
46.75
50.77
53.07
54.56
-
-
48.41
52.71
55.20
56.83
36.88
48.27
53.10
55.72
57.37
38.43
51.49
57.23
60.40
62.41
39.66
54.19
60.78
64.48
66.84
40.66
56.50
63.88
68.08
70.78
41.49
58.49
66.61
71.28
74.30
42.19
60.23
69.03
74.15
77.48
42.79
61.76
71.20
76.74
80.36
43.30
63.13
73.16
79.09
82.99
Water Coil Notes
1.
Fouling Factor = 0.0005.
2. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
LAT
=
EAT
+
--------------------------------------
WTD
=
EWT LWT
= ------------------------
3. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer to correction factors for different entering conditions.
Table 61. Temperature correction factors for water pressure drop (ft)
Average Water Temperature
Correction Factor
200 190 180 170 160 150 140 130 120 110
0.970 0.985
1.000 1.020 1.030 1.050 1.080 1.100
1.130
1.150
Table 62. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air
Correction Factor
40 50 60 70 80 90 100 110 120 130
0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
VAV-PRC012-EN 57
Performance Data
Table 63. Heating capacity (kW) - fan size 08SQ & 09SQ (SI)
Rows
1-Row Capacity kW
2-Row Capacity kW
L/s
0.06
0.13
0.19
0.25
0.32
0.38
0.06
0.13
0.19
0.25
0.32
Water Pressure
Drop (kPa)
0.44
1.72
3.81
6.71
10.40
14.90
2.27
7.78
16.11
27.08
40.58
47
-
-
2.32
2.37
2.39
2.41
2.65
2.77
2.81
2.83
2.84
94
-
-
3.27
3.36
3.42
3.47
4.28
4.67
4.82
4.89
4.93
142
-
-
3.94
4.08
4.18
4.24
5.35
6.07
6.33
6.47
6.56
189
-
-
4.50
4.68
4.80
4.89
6.12
7.13
7.53
7.74
7.87
-
-
4.97
5.21
5.36
5.47
6.69
7.98
8.50
8.78
8.96
Airflow (L/s)
236 283 330
-
-
5.40
5.67
5.86
5.99
7.14
8.68
9.31
9.66
9.88
-
-
5.78
6.10
6.31
6.47
7.49
9.26
10.00
10.41
10.68
378
-
-
6.13
6.49
6.74
6.91
7.79
9.75
10.60
11.07
11.37
425
-
-
6.45
6.86
7.13
7.32
8.04
10.18
11.12
11.65
11.99
472
-
-
6.75
7.19
7.49
7.71
8.25
10.56
11.58
12.16
12.54
Table 64. Heating capacity (kW) - fan size 10SQ (SI)
Rows
1-Row Capacity kW
2-Row Capacity kW
L/s
0.06
0.13
0.25
0.38
0.50
0.63
0.06
0.13
0.19
0.25
0.32
Water
Pressure Drop
(kPa)
0.48
1.82
6.93
15.22
26.64
41.16
3.84
12.90
26.43
44.15
65.84
212
-
-
7.34
7.65
7.81
7.92
8.32
9.81
10.35
10.62
10.79
283
-
-
8.38
8.79
9.01
9.15
9.43
11.59
12.43
12.87
13.14
354
-
-
9.28
9.79
10.07
10.24
10.22
13.00
14.14
14.74
15.12
425
-
-
10.08
10.68
11.02
11.23
10.81
14.15
15.56
16.33
16.81
495
-
-
10.80
11.50
11.90
12.15
11.26
15.09
16.77
17.70
18.29
Airflow (L/s)
566
-
-
11.47
12.27
12.71
13.00
11.62
15.88
17.81
18.90
19.59
637
-
-
12.08
12.98
13.48
13.81
11.92
16.56
18.72
19.95
20.74
708
-
-
12.66
13.65
14.21
14.57
12.16
17.14
19.52
20.89
21.78
779
-
-
13.19
14.28
14.90
15.30
12.36
17.65
20.23
21.73
22.71
849
-
-
13.70
14.88
15.55
15.99
12.54
18.10
20.87
22.49
23.55
920
-
-
13.70
14.88
15.55
15.99
12.54
18.10
20.87
22.49
23.55
Water Coil Notes
1.
Fouling Factor = 0.0005.|
2. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
LAT
=
EAT
+
WTD
=
EWT LWT
=
kW
4.19
Lls
3. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different entering conditions.
Table 65. Temperature correction factors for water pressure drop (kPa)
Average Water Temperature
Correction Factor
93 88 82 77 71 66 60 54 49 43
0.970 0.985
1.000 1.020 1.030
1.050
1.080 1.100 1.130 1.150
Table 66. Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air
Correction Factor
22 27 33 38 44 50 55 61 67 72
0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
58 VAV-PRC012-EN
advertisement
Related manuals
advertisement
Table of contents
- 5 Features and Benefits
- 13 Agency Certifications
- 15 Model Number Descriptions
- 17 Selection Procedure
- 17 Air Valve Selection
- 17 Heating Coil Selection
- 18 Fan Size and Selection
- 18 Acoustics
- 19 Selection Example—Parallel With Hot Water Heat
- 22 Selection Example—Series With Hot Water Heat and ECM
- 24 Performance Data
- 24 Parallel Fan-Powered Terminal Units
- 32 Water Coil Performance Notes (I-P)
- 34 Water Coil Performance Notes (SI)
- 35 Series Fan-Powered Terminal Units
- 44 Water Coil Notes (I-P)
- 46 Water Coil Notes (SI)
- 47 Low Height Parallel Fan-Powered Terminal Units
- 49 Performance Data Fan Curves
- 53 Low Height Series Fan-Powered Terminal Units
- 59 Electrical Data
- 59 Parallel Fan-Powered Terminal Units
- 63 Series Fan-Powered Terminal Units
- 68 Low Height Parallel Fan-Powered Terminal Units
- 70 Low Height Series Fan-Powered Terminal Units
- 73 Fan-Powered Parallel
- 74 Fan-Powered Series
- 75 Low Height Parallel Fan-Powered
- 75 Low-Height Series Fan-Powered
- 76 Acoustics Data
- 76 Parallel Fan-Powered Terminal Units
- 85 Series Fan-Powered Terminal Units
- 92 Low Height Parallel Fan-Powered Terminal Units
- 98 Low Height Series Fan-Powered Terminal Units
- 103 Dimensional Data
- 103 Parallel Fan-Powered Terminal Units
- 109 Series Fan-Powered Terminal Units
- 123 Low Height Parallel Fan-Powered Terminal Units
- 128 Coil Information For Low Height Parallel Inlet-1 Row
- 129 Coil Information For Low Height Parallel Plenum Inlet 2-Row Coil
- 130 Coil Information For Low Height Parallel Discharge 1-Row Coil
- 131 Coil Information For Low Height Parallel Discharge 2 Row Coil
- 134 Low Height Series Fan-Powered Terminal Units
- 142 Mechanical Specifications: Fan-Powered
- 147 DDC Controls
- 147 Control Logic
- 148 DDC Remote Heat Control Options
- 152 Tracer™ UC400 and UC210 Programmable BACnet Controllers
- 152 General Features and Benefits
- 154 Trane DDC VAV Controller Logic
- 157 Flow Tracking Control
- 158 Tracer™ Programmable BACnet Controller — Unit Control Module
- 159 Specifications
- 160 Trane LonMark DDC VAV Controller
- 160 Introduction
- 160 General Features and Benefits
- 162 Trane DDC VAV Controller Logic
- 165 Flow Tracking Control
- 166 LonMark™ Direct Digital Controller—Unit Control Module
- 166 Specifications
- 169 Direct Digital Controller—Unit Control Module
- 169 Specifications
- 170 Wireless Comm Interface (WCI)
- 171 Dimensions
- 171 Specifications
- 172 Wireless Receiver/Wireless Zone Sensor
- 172 Specifications
- 173 DDC Zone Sensor
- 173 Specifications
- 174 CO2 Wall Sensor and Duct CO2 Sensor
- 174 Specifications
- 176 DDC Zone Sensor with LCD
- 176 Specifications
- 177 Zone Occupancy Sensor
- 177 Specifications
- 178 Factory or Field Wired Auxiliary Temperature Sensor
- 178 Specifications
- 178 Control Relay
- 178 Specifications
- 179 Two-Position Water Valve
- 179 Specifications
- 180 Proportional Water Valve
- 180 Specifications
- 181 Differential Pressure Transducer
- 181 Specifications
- 182 Transformers
- 182 Specifications
- 183 Trane Actuator – 90 Second at 60 Hz Drive Time
- 183 Specifications
- 184 Belimo Actuator – 95 Second Drive Time
- 184 Specifications
- 185 Trane Spring Return Actuator
- 185 Specifications
- 186 VariTrane DDC Retrofit Kit
- 186 Retrofit Kit Actuator
- 186 Specifications
- 187 Silicon-Controlled Rectifier (SCR)
- 188 Pneumatic Controls
- 188 3011 Pneumatic Volume Regulator
- 189 3501 Pneumatic Volume Regulator
- 190 Pneumatic Damper Actuator
- 191 Reversing Relay
- 192 Signal Limiter
- 203 Controls Specifications
- 203 Fan Speed Control
- 203 Direct Digital Controls (DDC)
- 206 Pneumatic Controls
- 207 Options
- 207 DDC Retrofit Kit (VRTO)
- 207 Retrofit Kit Options
- 207 Other Options Available
- 208 Application Considerations
- 208 VAV System
- 208 No Heat
- 208 Central Heat
- 209 Terminal Heat
- 209 VariTrane VAV Terminal Units
- 210 VAV Terminal Unit Types
- 211 Parallel vs. Series
- 211 Comparison of Parallel and Series Models
- 211 Typical Application of Parallel Units
- 211 Typical Application of Series Units
- 213 Low-Temperature Air
- 213 Benefits of Low-Temperature Air
- 213 System Operation
- 214 Considerations for VAV products
- 216 Energy Savings & System Controls
- 216 Electrically Commutated Motor
- 216 Fan-Pressure Optimization
- 217 Ventilation Reset
- 218 Control Types
- 218 Direct Digital Control (DDC) Systems
- 218 Pneumatic Control Systems
- 219 DDC Controls Basic Information
- 219 Pneumatic Controls Basic Information
- 219 Room Thermostats
- 220 Pneumatic Volume Regulators
- 221 Flow Measurement and Control
- 221 Flow Measurement
- 222 Accuracy
- 223 Air Density Effects
- 224 Reheat Options
- 225 Electric Reheat
- 226 Insulation
- 226 Acoustics
- 230 Duct Design
- 231 Best Practices
- 231 Common Mistakes
- 232 Unit Conversions
- 233 Additional VAV System and Product References