Dimensional Data

Parallel Fan-Powered Terminal Units

PARALLEL COOLING ONLY (VPCF)

FAN

SIZE

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

INLET SIZE

AVAILABILITY

(NOMINAL Ø")

5", 6", 8", 10"

6", 8", 10", 12"

8", 10", 12", 14"

10", 12", 14"

10", 12", 14", 16"

10", 12", 14", 16"

INLET SIZE

AVAILABILITY

(NOMINAL Ømm)

127 mm, 152 mm, 203 mm, 254 mm

152 mm, 203 mm, 254 mm, 305 mm

203 mm, 254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm, 406 mm

254 mm, 305 mm, 356 mm, 406 mm

H

15.50" (394 mm)

17.50" (445 mm)

21.50" (546 mm)

W

40.00" (1016 mm)

L

30.00" (762 mm)

32.50" (826 mm)

40.00" (1016 mm)

DISCHARGE DIMENSIONS

A

19.25" (489 mm)

B

14.00" (356 mm)

16.00" (406 mm)

20.00" (508 mm)

UNIT WT

WT LBS

(kg)

78 (35)

96 (43)

97 (44)

111 (50)

117 (53)

125 (57)

4.

Optional Attenuator

Field Installed

9.

Actuator, Controller and

Fan Controls located in this area

2.

9.

Actuator, Controller and

Fan Controls located in this area

40.00"

(1016 mm)

Airflow

Plenum Inlet

(Valves 5"-14")

(Valve 16")

4.00"

(102 mm)

2.00"

(51 mm)

Flow Ring tubing

20.00"

(508 mm)

Primary

Airflow

Valve 5"

6.50"

(165 mm)

Air

Valve

4.00"

(102 mm)

18.875" Max.

(479 mm)

9.

5.50" Max.

(140 mm)

B

11.30" Max.

(287 mm)

9.

Airflow

Discharge Outlet

A

W back draft damper

Optional Attenuator

Field Installed

L

5.

Panel slides for Motor access

TOP VIEW

5.

20.00"

(508 mm)

DISCHARGE VIEW

30.00"

(762 mm)

H

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 20" x 1"

(356 mm x 508 mm x 25 mm)

Attn. Weight

Wt Lbs

(kg)

46 (21)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

48 (22)

54 (25)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet

clearance for unducted installations.

2. Filter location with optional Attenuator.

3. Attenuator-factory assembled, field installed.

4. See Installation Documents for exact hanger bracket location.

5. For Motor access, remove bottom screw on hanger brackets

to slide panel as shown in drawing.

6. When Attenuator option selected, water coil ships mounted

to attenuator.

7. Air valve centered between top and bottom panel.

8. All high & low voltage controls have same-side NEC

jumpback clearance. (Left-hand shown, right-hand/mirror

image optional.)

9. Maximum dimensions for controls area shown. Configurations

and types of control boxes vary according to control type

selected. See "Enclosure Details" for specific layout.

10. Graphic shown is for left-hand electrical. Right-hand electrical

is a mirror image.

VAV-PRC012-EN 103

Dimensional Data

PARALLEL HOT WATER (VPWF)

FAN

SIZE

INLET SIZE

AVAILABILITY

(NOMINAL Ø")

02SQ

5", 6", 8", 10"

03SQ

04SQ

05SQ

6", 8", 10", 12"

8", 10", 12", 14"

10", 12", 14"

06SQ

07SQ

10", 12", 14", 16"

10", 12", 14", 16"

INLET SIZE

AVAILABILITY

(NOMINAL Ømm)

127 mm, 152 mm, 203 mm, 254 mm

152 mm, 203 mm, 254 mm, 305 mm

203 mm, 254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm, 406 mm

254 mm, 305 mm, 356 mm, 406 mm

H

W

15.50" (394 mm)

17.50" (445 mm)

40.00" (1016 mm)

21.50" (546 mm)

L

30.00" (762 mm)

32.50" (826 mm)

40.00" (1016 mm)

DISCHARGE DIMENSIONS

A

19.25" (489 mm)

B

UNIT WT

WT LBS

(kg)

14.00" (356 mm)

78 (35)

16.00" (406 mm)

96 (43)

97 (44)

111 (50)

20.00" (508 mm) 117 (53)

125 (57)

4.

Optional Attenuator

Field Installed

104

9.

Actuator, Controller and

Fan Controls located in this area

(Valves 6"-14")

(Valve 16")

4.00"

(102 mm)

2.00"

(51 mm)

Flow Ring tubing

18.875" Max.

(479 mm)

9.

5.50" Max.

(140 mm)

B

11.30" Max.

(287 mm)

2.

40.00"

(1016 mm)

20.00"

(508 mm)

Water

Coil

Airflow

Plenum Inlet

Coil

Connection

6.30"

(160 mm)

9.

Actuator, Controller and

Fan Controls located in this area

20.00"

(508 mm)

Primary

Airflow

Valve 5"

6.50"

(165 mm)

Air

Valve

4.00"

(102 mm)

Airflow

Discharge Outlet

W back draft damper

Optional Attenuator

Field Installed

L

5.

Panel slides for Motor access

TOP VIEW

5.

20.00"

(508 mm)

30.00"

(762 mm)

H

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 20" x 1"

(356 mm x 508 mm x 25 mm)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

Attn. Weight

Wt Lbs

(kg)

46 (21)

48 (22)

54 (25)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance

for unducted installations.

2. Filter location with optional Attenuator.

3. Attenuator-factory assembled, field installed.

4. See Installation Documents for exact hanger bracket location.

5. For Motor access, remove bottom screw on hanger

brackets to slide panel as shown in drawing.

6. When Attenuator option selected, water coil ships

mounted to attenuator.

7. Air valve centered between top and bottom panel.

8. All high & low voltage controls have same-side NEC

jumpback clearance. (Left-hand shown, right-hand/mirror

image optional.)

9. Maximum dimensions for controls area shown.

9.

A

DISCHARGE VIEW

VAV-PRC012-EN

Dimensional Data

PARALLEL WITH HOT WATER ON DISCHARGE (VPWF)

FAN

SIZE

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

INLET SIZE

AVAILABILITY

(NOMINAL Ø")

5", 6", 8", 10"

6", 8", 10", 12"

8", 10", 12", 14"

10", 12", 14"

10", 12", 14", 16"

10", 12", 14", 16"

INLET SIZE

AVAILABILITY

(NOMINAL Ømm)

127 mm, 152 mm, 203 mm, 254 mm

152 mm, 203 mm, 254 mm, 305 mm

203 mm, 254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm, 406 mm

254 mm, 305 mm, 356 mm, 406 mm

H

15.50" (394 mm)

17.50" (445 mm)

21.50" (546 mm)

W

40.00" (1016 mm)

L

30.00" (762 mm)

32.50" (826 mm)

40.00" (1016 mm)

DISCHARGE DIMENSIONS

A

20.00" (508 mm)

B

14.00" (356 mm)

16.00" (406 mm)

20.00" (508 mm)

UNIT WT

(kg)

78 (35)

96 (43)

97 (44)

111 (50)

117 (53)

125 (57)

4.

Optional Attenuator

Field Installed

8.

Actuator, Controller and

Fan Controls located in this area

2.

40.00"

(1016 mm)

Airflow

Plenum Inlet

8.

Actuator, Controller and

Fan Controls located in this area

(Valves 5"-14")

(Valve 16")

4.00"

(102 mm)

2.00"

(51 mm)

Flow Ring tubing

20.00"

(508 mm)

Primary

Airflow

Valve 5"

6.50"

(165 mm)

Air

Valve

4.00"

(102 mm)

18.875" Max.

(479 mm)

8.

5.50" Max.

(140 mm)

6.30"

(160 mm)

Airflow

Discharge Outlet

Water

Coil

20.00"

(508 mm)

W

B

11.30" Max.

(287 mm)

8.

A

VAV-PRC012-EN

30.00"

(762 mm)

Optional Attenuator

Field Installed

L

5.

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 20" x 1"

(356 mm x 508 mm x 25 mm)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

Attn. Weight

Wt. Lbs.

(kg)

46 (21)

48 (22)

54 (25)

Panel slides for Motor access

TOP VIEW

5.

20.00"

(508 mm)

H

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet

clearance for unducted installations.

2. Filter location with optional Attenuator.

3. Attenuator-factory assembled, field installed.

4. See Installation Documents for exact hanger bracket location.

5. For Motor access, remove bottom screw on hanger brackets

to slide panel as shown in drawing.

6. Air valve centered between top and bottom panel.

7. All high & low voltage controls have same-side NEC

jumpback clearance. (Left-hand shown, right-hand/mirror

image optional.)

8. Maximum dimensions for controls area shown.

DISCHARGE VIEW

105

Dimensional Data

106 VAV-PRC012-EN

Dimensional Data

VAV-PRC012-EN 107

Dimensional Data

PARALLEL ELECTRIC HEAT (VPEF)

FAN

SIZE

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

INLET SIZE

AVAILABILITY

(NOMINAL Ø")

5", 6", 8", 10"

6", 8", 10", 12"

8", 10", 12", 14"

10", 12", 14"

10", 12", 14", 16"

10", 12", 14", 16"

INLET SIZE

AVAILABILITY

(NOMINAL Ømm)

127 mm, 152 mm, 203 mm, 254 mm

152 mm, 203 mm, 254 mm, 305 mm

203 mm, 254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm

254 mm, 305 mm, 356 mm, 406 mm

254 mm, 305 mm, 356 mm, 406 mm

H

15.50" (394 mm)

17.50" (445 mm)

21.50" (546 mm)

W

40.00" (1016 mm)

L

30.00" (762 mm)

32.50" (826 mm)

40.00" (1016 mm)

DISCHARGE DIMENSIONS

A

20.00" (508 mm)

B

14.00" (356 mm)

16.00" (406 mm)

20.00" (508 mm)

UNIT WT

WT LBS

(kg)

120 (54)

96 (43)

138 (63)

141 (64)

178 (80)

186 (84)

5.

Optional Attenuator

Field Installed

108

9.

Actuator, Controller and

Fan Controls located in this area

18.875" Max.

(479 mm)

9.

4.00"

(102 mm)

Flow Ring tubing

20.00"

(508 mm)

Primary

Airflow

Valve 5"

6.50"

(165 mm)

Air

Valve

4.00"

(102 mm)

22.00"

(559 mm)

5.50" Max.

(140 mm)

B

11.30" Max.

(287 mm)

9.

2.

9.

Actuator, Controller and

Fan Controls located in this area

40.00"

(1016 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

30.00"

(762 mm)

L

4.

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 20" x 1"

(356 mm x 508 mm x 25 mm)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

Attn. Weight

Wt. Lbs.

(kg)

46 (21)

48 (22)

54 (25)

Heater

Airflow

Discharge Outlet

W

6.00"

(152 mm)

4.

Panel slides for Motor access

TOP VIEW

20.00"

(508 mm)

H

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Filter location with optional Attenuator.

3. Attenuatory factory assembled, field installed.

4. For motor access, remove bottom screws on hanger brackets

to slide panel as shown in drawing.

5. See Installation Documents for exact hanger bracket location.

6. Air valve centered between top and bottom panel.

7. Heating coil uninsulated. External insulation may be field

supplied and installed as required.

8. All high & low voltage controls have same side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

Maximum dimensions for controls area shown.

and types of control boxes vary according to control type

selected. See "Enclosure Details" for specific layout.

A

DISCHARGE VIEW

VAV-PRC012-EN

Dimensional Data

Series Fan-Powered Terminal Units

SERIES COOLING ONLY (VSCF) WITHOUT ATTENUATOR

FAN

SIZE

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø

INCHES

4, 5, 6, 8, 10

6, 8, 10, 12

6, 8, 10, 12, 14

10, 12, 14

10, 12, 14, 16

10, 12, 14, 16

INLET SIZE

AVAILABILITY

NOMINAL Ø

(mm)

104, 127, 152, 203, 254

152, 203, 254, 305

152, 203, 254, 305, 356

254, 305, 356

254, 305, 356, 406

254, 305, 356, 406

H

15.50" (394 mm)

17.50" (445 mm)

21.50" (546 mm)

W L

DISCHARGE DIMENSIONS

A B

C D

Unit Wt

Lbs

(kg)

22.00" (559 mm)

24.00" (610 mm)

30.00" (762 mm)

34.00" (864 mm)

40.00" (1016 mm)

12.00" (305 mm)

19.00" (483 mm)

14.00" (356 mm)

16.00" (406 mm)

24.00" (610 mm)

18.00" (457 mm)

5.00" (127 mm)

2.50" (64 mm)

3.00" (76 mm)

.65" (17 mm)

.75" (19 mm)

78 (35)

85 (39)

86 (39)

1.66" (42 mm)

100 (45)

117 (53)

125 (57)

2.

7.

Airflow

Plenum Inlet

TOP VIEW

Filter

5.50" Max.

(140 mm)

11.30" Max.

(287 mm)

7.

(Valves 4"-14")

4.00"

(102 mm)

Flow Ring

Tubing

W

Primary

Airflow

Air

Valve

Valves 4" & 5"

6.50"

(165 mm)

4.00"

(102 mm)

18.875" Max.

(479 mm)

7.

Actuator, Controller and

Fan Controls located in this area

L

Airflow

Discharge Outlet

Panel slides for Motor access

B

H

D

4.

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 14" x 1"

(356 mm x 356 mm x 25 mm)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. See Installation Documents for exact hanger bracket location.

3. Air valve centered between top and bottom panel.

4. For motor access, remove bottom screw on hanger brackets

to slide panel as shown in drawing.

5. Attenuator option not available with this unit layout.

6. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

types of control boxes vary according to control types selected.

A C

DISCHARGE VIEW

VAV-PRC012-EN 109

Dimensional Data

110 VAV-PRC012-EN

Dimensional Data

NARROW CORRIDOR DESIGN SERIES COOLING (VSCF) WITHOUT ATTENUATOR

VAV-PRC012-EN

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet

clearance for unducted installations.

2. See installation Documents for exact hanger bracket location.

3. Air valve centered between top and bottom panel.

4. For Motor access, remove bottom screw on hanger

brackets to slide panel as shown in drawing.

5. Attenuator option not available with this unit layout.

6. All high & low voltage controls have same-side NEC

jumpback clearance. (unit shown w/left hand high &

low voltage box connections [high voltage inlet facing].

Right hand connections available.)

7. Maximum dimensions for controls are shown.

111

Dimensional Data

112 VAV-PRC012-EN

Dimensional Data

SERIES HOT WATER (VSWF) WITHOUT ATTENUATOR

FAN

SIZE

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø

INCHES

4, 5, 6, 8, 10

6, 8, 10, 12

6, 8, 10, 12, 14

10, 12, 14

10, 12, 14, 16

10, 12, 14, 16

INLET SIZE

AVAILABILITY

NOMINAL Ø

(mm)

104, 127, 152, 203, 254

152, 203, 254, 305

152, 203, 254, 305, 356

254, 305, 356

254, 305, 356, 406

254, 305, 356, 406

H W L

DISCHARGE DIMENSIONS

A

B

C D E

Unit Wt

Lbs

(kg)

15.50" (394 mm)

17.50" (445 mm)

22.00" (559 mm)

24.00" (610 mm)

21.50" (546 mm)

30.00" (762 mm)

34.00" (864 mm)

40.00" (1016 mm)

12.00" (305 mm)

19.00" (483 mm)

24.00" (610 mm)

14.00" (356 mm)

16.00" (406 mm)

5.00" (127 mm)

2.50" (64 mm)

18.00" (457 mm)

3.00" (76 mm)

.65" (17 mm)

.75" (19 mm)

1.66" (42 mm)

6.75" (171 mm)

10.75" (273 mm)

6.75" (171 mm)

78 (35)

85 (39)

86 (39)

100 (45)

117 (53)

125 (57)

2.

W

(Valves 4"-14")

4.00"

(102 mm)

2.00"

(Valve 16") (51 mm)

Flow Ring

Tubing

Primary

Airflow

Air

Valve

Valves 4" & 5"

6.50"

(165 mm)

4.00"

(102 mm)

18.875" Max.

(479 mm)

9.

Actuator, Controller and

Fan Controls located in this area

L

9.

Airflow

Plenum Inlet

4.

Filter

3.00" x 7.00"

(76 mm x 178 mm)

Coil Access

Coil Connection

TOP VIEW

5.50" Max.

(140 mm)

11.30" Max.

(287 mm)

9.

Water Coil

Airflow

Discharge Outlet

Panel slides for Motor access

E

B

H

D

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 14" x 1"

(356 mm x 356 mm x 25 mm)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. See Installation Documents for exact hanger bracket location.

3. Air valve centered between top and bottom panel.

4. For motor access, remove bottom screw on hanger brackets

to slide panel as shown in drawing.

5. Attenuator option not available with this unit layout.

6. Heating coil uninsulated. External insulation may be field-

supplied and installed as required.

7. Rotate coil 180 for right-hand coil connection.

8. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

Maximum dimensions for controls area shown.

types of control boxes vary according to control types selected. See

"Enclosure Details" for specific layout.

A

C

DISCHARGE VIEW

VAV-PRC012-EN 113

Dimensional Data

114 VAV-PRC012-EN

Dimensional Data

NARROW CORRIDOR DESIGN SERIES HOT WATER (VSWF) WITHOUT ATTENUATOR

VAV-PRC012-EN

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet

clearance for unducted installations.

2. See Installation Documents for exact hanger

bracket location.

3. Air valve centered between top and bottom panel.

4. For motor access, remove bottom screw on

hanger brackets to slide panel as shown in drawing.

5. Attenuator option not available with this unit layout.

6. Heating coil un-insulated. External insulation may be

field supplied and installed as required.

7. Rotate coil 180° for right hand coil connection.

8. All high & low voltage controls have same-side NEC

jumpback clearance. (unit shown w/left hand high &

low voltage box connections [high voltage inlet facing].

Right hand connections available.)

9. Maximum dimensions for controls area shown.

115

Dimensional Data

116 VAV-PRC012-EN

COIL INFORMATION FOR SERIES 1-ROW COIL

Dimensional Data

VAV-PRC012-EN 117

Dimensional Data

COIL INFORMATION FOR SERIES 2-ROW COILS

118 VAV-PRC012-EN

Dimensional Data

SERIES ELECTRIC (VSEF) WITHOUT ATTENUATOR

FAN

SIZE

INLET SIZE

AVAILABILITY

NOMINAL Ø

INCHES

4, 5, 6, 8, 10 02SQ

03SQ

04SQ

05SQ

6, 8, 10, 12

6, 8, 10, 12, 14

10, 12, 14

06SQ 10, 12, 14, 16

07SQ

10, 12, 14, 16

INLET SIZE

AVAILABILITY

NOMINAL Ø

(mm)

104, 127, 152, 203, 254

152, 203, 254, 305

152, 203, 254, 305, 356

254, 305, 356

254, 305, 356, 406

254, 305, 356, 406

H

15.50" (394 mm)

17.50" (445 mm)

21.50" (546 mm)

W

30.00" (762 mm)

L

22.00" (559 mm)

24.00" (610 mm)

34.00" (864 mm)

40.00" (1016 mm)

DISCHARGE DIMENSIONS

A

B

C

D

12.00" (305 mm) 10.00" (254 mm)

12.00" (305 mm)

16.00" (406 mm)

19.00" (483 mm)

14.00" (356 mm)

5.00" (127 mm)

4.00" (102 mm)

18.00" (457 mm)

4.00" (102 mm) 22.00" (559 mm)

10.00" (254 mm)

5.50" (140 mm)

25.00" (635 mm)

E

18.50" (470 mm)

17.00" (432 mm)

Unit Wt

Lbs

(kg)

78 (35)

85 (39)

86 (39)

100 (45)

117 (53)

125 (57)

2.

W

(Valves 4"-14")

(Valve 16")

4.00"

(102 mm)

2.00"

(51 mm)

Flow Ring

Tubing

Primary

Airflow

Air

Valve

Valves 4" & 5"

6.50"

(165 mm)

4.00"

(102 mm)

18.875" Max.

(479 mm)

8.

Airflow

Plenum Inlet

Fans

02SQ

Fans

03SQ–05SQ

Fans

06SQ–07SQ

Filter

1.00"

(25 mm)

2.00"

(51 mm)

0.60"

(15 mm)

TOP VIEW

E

6.20"

(157 mm)

5.50" Max.

(140 mm)

11.30" Max.

(287 mm)

8.

DISCHARGE VIEW

Electric

Heater

Airflow

Discharge Outlet

D

A

Panel slides for Motor access

L

8.

Actuator, Controller and

Fan Controls located in this area

4.

Fan Size

02SQ

03SQ

04SQ

05SQ

06SQ

07SQ

Filter Size

14" x 14" x 1"

(356 mm x 356 mm x 25 mm)

16" x 20" x 1"

(406 mm x 508 mm x 25 mm)

20" x 20" x 1"

(508 mm x 508 mm x 25 mm)

C

B

Fans

02SQ

Fans

03SQ–05SQ

Fans

06SQ–07SQ

1.50"

(38 mm)

1.50"

(38 mm)

3.00"

(76 mm)

H

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. See Installation Documents for exact hanger bracket location.

3. Air valve centered between top and bottom panel.

4. For motor access, remove bottom screw on hanger brackets

to slide panel as shown in drawing.

5. Attenuator option not available with this unit layout.

6. Heating coil uninsulated. External insulation may be field-

supplied and installed as required.

7. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

Maximum dimensions for controls area shown.

types of control boxes vary according to control types selected. See

"Enclosure Details" for specific layout.

VAV-PRC012-EN 119

Dimensional Data

120 VAV-PRC012-EN

Dimensional Data

VAV-PRC012-EN 121

Dimensional Data

122 VAV-PRC012-EN

Dimensional Data

Low Height Parallel Fan-Powered Terminal Units

LOW-HEIGHT PARALLEL COOLING (LPCF) FAN SIZES 08SQ & 09SQ

FAN

INLET SIZE

AVAILABILITY

SIZE NOMINAL Ø (INCHES)

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

08SQ

09SQ

5, 6, 8

6, 8

127, 152, 203

152, 203

DISCHARGE DIMENSIONS

H W L

A

11.00" (279 mm) 40.00" (1016 mm) 30.00" (762 mm) 19.25" (489 mm)

B

9.5" (241 mm)

09SQ

8 x 14 203 x 356

D

4.00" (102 mm)

3.25" (83 mm)

UNIT WT

WT LBS

(kg)

69 (31.3)

74 (33.6)

83 (37.7)

Optional Attenuator

Field Installed

17.50"

(445 mm)

5.00"

(127 mm)

H

10.50"

(267 mm)

5.

Actuator, Controller and

Fan Controls located in this area

5.

Actuator, Controller and

Fan Controls located in this area

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.00

(102 mm)

Airflow

Discharge Outlet

A

W

32.00"

(813 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

18.00"

(457 mm)

Rectangular Damper

8" x 14"

(203 mm X 356 mm)

Rectangular Damper Detail

5.

Actuator, Controller and

Fan Controls located in Enclosure

7.

L

Fan Size

08SQ

09SQ

Filter Size

10" x 20" x 1"

(254 mm x 508 mm x 25 mm)

Attn Wt

Wt. Lbs.

(kg)

10 (4.5)

TOP VIEW

B

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted

installations.

2. Flanged discharge outlet accepts up to 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Air valve centered between top and bottom panel.

5. Control box enclosure provided with all control types.

6. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

DISCHARGE VIEW

VAV-PRC012-EN 123

Dimensional Data

LOW-HEIGHT PARALLEL COOLING (LPCF) FAN SIZE 10SQ

FAN

SIZE

10SQ

10SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

8

8 x 14

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

203

203 x 356

H W

11.50" (292 mm)

40.00" (1016 mm)

DISCHARGE DIMENSIONS

L

A

B

50.00" (1270 mm) 19.25" (489 mm)

10.00" (254 mm)

D

4.00" (102 mm)

3.25" (83 mm)

UNIT WT

WT LBS

(kg)

90 (41)

92 (42)

4.

124

Flow Ring tubing

20.00"

(508 mm)

D

Primary

Airflow

Air

Valve

4.00

(102 mm)

18.875" Max.

(479 mm)

20.00"

(508 mm)

L

6.

Actuator, Controller and

Fan Controls located in this area

4.

Rectangular Damper

8" x 14"

(203 mm X 356 mm)

Rectangular Damper Detail

6.

Actuator, Controller and

Fan Controls located in this area

6.

5.50" Max.

(140 mm)

B

11.30" Max.

(287 mm)

6.

Airflow

Discharge Outlet

W

TOP VIEW

Fan Size

10SQ

Filter Size

10" x 20" x 1"

(254 mm x 508 mm x 25 mm)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. See Installation Documents for exact hanger bracket location.

5. Air valve centered between top and bottom panel.

6. Maximum dimensions for controls area shown.

H

A

DISCHARGE VIEW

VAV-PRC012-EN

Dimensional Data

LOW-HEIGHT PARALLEL HOT WATER (LPWF) FAN SIZES 08SQ & 09SQ

FAN

SIZE

INLET SIZE

AVAILABILITY

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES) NOMINAL Ø (mm)

08SQ

09SQ

09SQ

5, 6, 8

6, 8

8 x 14

127, 152, 203

152, 203

203 x 356

H W

11.00" (279 mm) 40.00" (1016 mm)

DISCHARGE DIMENSIONS

L

30.00" (762 mm)

A

B

19.25" (483 mm) 9.50" (241 mm)

D

UNIT WT

WT LBS

(kg)

4.00" (102 mm) 98 (44.5)

103 (46.7)

3.25" (83 mm) 112 (50.8)

Optional Attenuator

Field Installed

17.50"

(445 mm)

5.00"

(127 mm)

5.

Actuator, Controller and

Fan Controls located in this area

5.

Actuator, Controller and

Fan Controls located in this area

32.00"

(813 mm)

20.00"

(508 mm)

6.80"

(173 mm)

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.00

(102 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

18.00"

(457 mm)

7.

L

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

Rectangular Damper Detail

5.

Actuator, Controller and

Fan Controls located in Enclosure

Fan Size

08SQ

09SQ

Filter Size

10" x 20" x 1"

(254 mm x 508 mm x 25 mm)

Attn Wt

Wt Lbs

(kg)

10 (4.5)

H

10.50"

(267 mm)

Airflow

Discharge Outlet

W

B

TOP VIEW

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Air valve centered between top and bottom panel.

5. Control box enclosure provided with all control types.

6. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

A

DISCHARGE VIEW

VAV-PRC012-EN 125

Dimensional Data

126 VAV-PRC012-EN

Dimensional Data

PARALLEL LOW-HEIGHT HOT WATER (LPWF) COIL ON DISCHARGE

FAN SIZES 08SQ & 09SQ

FAN

SIZE

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

H W L

DISCHARGE DIMENSIONS

08SQ

09SQ

09SQ

5, 6, 8

6, 8

8 X 14

127, 152, 203

152, 203

203 X 356

11.00" (279 mm) 40.00" (1016 mm) 30.00" (762 mm)

A

20.00" (508 mm)

B

10.00" (254 mm)

D

UNIT WT

WT LBS

(kg)

4.00" (102 mm) 98 (44.5)

103 (46.7)

3.25" (83 mm) 112 (50.8)

Optional Attenuator

Field Installed

5.

Actuator, Controller and

Fan Controls located in this area 5.

Actuator, Controller and

Fan Controls located in this area

17.50"

(445 mm)

5.00"

(127 mm)

32.00"

(813 mm)

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.00

(102 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

18.00"

(457 mm)

7.

L

Rectangular Damper

8" x 14"

(203 mm X 356 mm)

Rectangular Damper Detail

5.

Actuator, Controller and

Fan Controls located in Enclosure

Fan Size

08SQ

09SQ

Filter Size

10" x 20" x 1"

(254 mm x 508 mm x 25 mm)

Attn Wt

Wt Lbs

(kg)

10 (4.5)

H

10.50"

(267 mm)

6.80"

(173 mm)

20.00"

(508 mm)

Airflow

Discharge Outlet

W

A

B

TOP VIEW

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Air valve centered between top and bottom panel.

5. Control box enclosure provided with all control types.

6. All high & low voltage controls have same-side NEC jumpback clearance.

(Left-hand shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

DISCHARGE VIEW

VAV-PRC012-EN 127

Dimensional Data

Coil Information For Low Height Parallel Inlet-1 Row

Size Inlet/Fan

08SQ

09SQ

10SQ

Coil Connection 1-Row

3/8" (10 mm) O.D.

3/8" (10 mm) O.D.

.375" (10 mm) O.D.

A

9" (229 mm)

9" (229 mm)

9.00" (229 mm)

B

2 7/8" (71 mm)

2 7/8" (71 mm)

2.80" (71 mm)

L

20" (508 mm)

20" (508 mm)

20.00" (508 mm)

H

10" (254 mm)

10" (254 mm)

10.00" (254 mm)

L

OUTLET

A

AIR FLOW

H

INLET

AIR FLOW

B

7/8"

[22mm]

Fan Size

08SQ

09SQ

10SQ

Internal Volume Gal (L)

0.07 (16.7)

0.07 (16.7)

0.07 (.27)

Operating Weight Lbs (Kg)

9.7 (4.4)

9.7 (4.4)

9.7 (4.4)

Notes:

1. Location of coil connections is determined by facing air steam. R.H. Coil connections shown, L.H. not available.

2. Coil furnished with stub sweet connections.

128 VAV-PRC012-EN

Dimensional Data

Coil Information For Low Height Parallel Plenum Inlet 2-Row Coil

Fan Size

08SQ

09SQ

10SQ

Coil Connection 2 Row

7/8" (22 mm) O.D.

7/8" (22 mm) O.D.

.875" (22 mm) O.D.

A

6 1/4" (157 mm)

6 1/4" (157 mm)

6.20" (157 mm)

B

2 1/8" (55 mm)

2 1/8" (55 mm)

2.18" (55 mm)

L

20" (508 mm)

20" (508 mm)

20.00" (508 mm)

H

10" (254 mm)

10" (254 mm)

10.00" (254 mm)

VAV-PRC012-EN

Fan Size

08SQ

09SQ

10SQ

Internal Volume Gal (L)

0.16 (39.0)

0.16 (39.0)

0.16 (.61)

Operating Weight Lbs (Kg)

13.7 (6.2)

13.7 (6.2)

13.7 (6.2)

Notes:

1. Location of coil connections is determined by facing air steam. R.H. Coil connections shown, L.H. not available.

2. Coil furnished with female sweat connections.

3.

0.85" lip NOT on 08SQ or 09SQ units.

129

Dimensional Data

Coil Information For Low Height Parallel Discharge 1-Row Coil

Fan Size

08SQ

09SQ

Coil Connection

3/8" (10 mm) O.D.

3/8" (10 mm) O.D.

A B L H W

9.00" (229 mm) 1.65" (42 mm) 20.00" (508 mm) 10.00" (254 mm) 6.75" (171 mm)

9.00" (229 mm) 1.65" (42 mm) 20.00" (508 mm) 10.00" (254 mm) 6.75" (171 mm)

130

Fan Size

08SQ

09SQ

Internal Volume Gal (L)

0.07 (.28)

0.07 (.28)

Operating Weight Lbs (Kg)

9.7 (4.4)

9.7 (4.4)

Notes:

1. Location of coil connections is determined by facing air stream. L.H. Coil connections shown, R.H. opposit.

2. Coil furnished with stub sweat connections.

3. Coil is rotated to achieve opposite hand connection. Note: Water inlet is always on the bottom and outlet on the top.

4. Access Panel is standard.

VAV-PRC012-EN

Dimensional Data

Coil Information For Low Height Parallel Discharge 2 Row Coil

Fan Size

08SQ

09SQ

Coil Connection

7/8" (22 mm) O.D.

7/8" (22 mm) O.D.

A

6.25" (159 mm)

6.25" (159 mm)

B

2.00 (51 mm)

2.00 (51 mm)

L H

20.00" (508 mm) 10.00" (254 mm)

20.00" (508 mm) 10.00" (254 mm)

W

6.75" (171 mm)

6.75" (171 mm)

VAV-PRC012-EN

Fan Size

08SQ

09SQ

Internal Volume Gal (L)

0.17 (.64)

0.17 (.64)

Operating Weight Lbs (Kg)

13.7 (6.2)

13.7 (6.2)

Notes:

1. Location of coil connections is determined by facing air stream. L.H. Coil connections shown, R.H. opposite.

2. Coil furnished with stub sweat connections.

3. Use port at bottom for inlet and port at top for outlet. For 2-row coils, always plumb in counter flow orientation: Left hand unit's water inlet on bottom, and outlet on the top. Right hand unit’s water inlet on top and outlet on bottom.

4. Access Panel is standard.

131

Dimensional Data

LOW-HEIGHT PARALLEL ELECTRIC HEAT (LPEF) FAN SIZES 08SQ & 09SQ

FAN

INLET SIZE

AVAILABILITY

SIZE NOMINAL Ø (INCHES)

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

08SQ

5, 6, 8 127, 152, 203

DISCHARGE DIMENSIONS

H

11.00" (279 mm)

W L

A

B

40.00" (1016 mm) 30.00" (762 mm) 19.00" (483 mm)

9.50" (241 mm)

09SQ

6, 8

152, 203

D

UNIT WT

WT LBS

(kg)

4.00" (102 mm) 104 (47.2)

109 (49.4)

09SQ

8 x 14 203 x 356

3.25" (83 mm) 118 (53.5)

Optional Attenuator

Field Installed

132

5.00"

(127 mm)

20.00"

(508 mm)

5.

Actuator, Controller and

Fan Controls located in Enclosure

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.00

(102 mm)

32.00"

(813 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

18.00"

(457 mm)

17.50"

(445 mm)

7.

L

Heater

Airflow

Discharge Outlet

6.00"

(152 mm)

TOP VIEW

W

H

10.50"

(267 mm)

B

5.

Actuator, Controller and

Fan Controls located in Enclosure

Rectangular Damper

8" x 14"

(203 mm X 356 mm)

Rectangular Damper Detail

Fan Size

08SQ

09SQ

5.

Actuator, Controller and

Fan Controls located in Enclosure

Filter Size

10" x 20 " x 1"

(254 mm x 508 mm x 25 mm)

Atten Wt

Lbs

(kg)

10 (4.5)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Air valve centered between top and bottom panel.

5. Control box enclosure provided with all control types.

6. All high & low voltage controls have same-side NEC jumpback clearance. (Left-hand

shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

A

DISCHARGE VIEW

VAV-PRC012-EN

LOW-HEIGHT PARALLEL ELECTRIC (LPEF) FAN SIZE 10SQ

Dimensional Data

VAV-PRC012-EN 133

Dimensional Data

Low Height Series Fan-Powered Terminal Units

LOW-HEIGHT SERIES COOLING ONLY (LSCF) FAN SIZES 08SQ & 09SQ

FAN

SIZE

08SQ

09SQ

09SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø (inches)

5, 6, 8

6, 8

8 x 14

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

H

11.00" (279 mm)

127, 152, 203

152, 203

203 x 355

DISCHARGE DIMENSIONS

W L

26.00" (660 mm)

A B

40.00" (1016 mm)

18.00" (457 mm) 10.00" (254 mm)

D

Unit Wt

Lbs

(kg)

4.00" (102 mm)

4.50" (114 mm)

86 (39)

96 (44)

105 (47)

Optional Attenuator

Field Installed

134

17.50"

(445 mm)

5.00"

(127 mm)

10.50"

(267 mm)

TOP VIEW

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.

Actuator, Controller and

Fan Controls located in Enclosure

32.00"

(813 mm)

Optional Attenuator

Field Installed

Air

Valve

4.00

(102 mm)

Airflow

Plenum Inlet

18.00"

(457 mm)

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

W

Airflow

Discharge Outlet

L

B

7.

4.

Actuator, Controller and

Fan Controls located in Enclosure

Rectangular Damper Detail

4.

Actuator, Controller and

Fan Controls located in Enclosure

Fan Size

08SQ

09SQ

Filter Size

10" x 10" x 1"

(254 mm x 254 mm x 25 mm)

Atten Wt

Lbs

(kg)

10 (4.5)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Control box enclosure provided with all control types.

5. Air valve centered between top and bottom panel.

6. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

H

DISCHARGE VIEW

A

1.00"

(25 mm)

VAV-PRC012-EN

Dimensional Data

LOW-HEIGHT SERIES COOLING (LSCF) FAN SIZE 10SQ

FAN

SIZE

10SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

8

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

203

H W L

11.00" (279 mm) 48.00" (1219 mm)

36.00" (914 mm)

DISCHARGE DIMENSIONS

C

A B

38.00" (965 mm)

10.00" (254 mm)

4.00" (102 mm)

D

UNIT WT

WT LBS

(kg)

20.00" (508 mm) 120 (54)

10SQ 8 x 14

203 x 356

17.50" (445 mm) 130 (59)

Optional Attenuator

Field Installed

2. Optional Attenuator

Field Installed

8.

Actuator, Controller and

Fan Controls located in Enclosure

8.

Actuator, Controller and

Fan Controls located in Enclosure

2.

18.00"

(457 mm)

32.00"

(813 mm)

Optional Attenuator

Field Installed

D

Airflow

Plenum Inlet

Primary

Airflow

C

32.00"

(813 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

17.50"

(445 mm)

5.00"

(127 mm)

Rectangular Damper Detail

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

L

9.

Fan Size

10SQ

Filter Size

10" x 16" x 1"

(254 mm x 406 mm x 25 mm)

Atten Wt

Lbs

(kg)

20 (9)

H B

10.50"

(267 mm)

W

Airflow

Discharge Outlet

TOP VIEW

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Filter location with optional Attenuator.

3. Attenuator-factory assembled, field installed.

4. Air valve centered between top and bottom panel.

5. Heating coil uninsulated. External insulation may be field

supplied and installed as required.

6. All high & low voltage controls have same-side NEC jumback

clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Bottom Access panel standard.

8. Control box enclosure provided with all control types.

9. Flange adds 2" to width and length of unit.

A

DISCHARGE VIEW

VAV-PRC012-EN 135

Dimensional Data

LOW-HEIGHT SERIES HOT WATER (LSWF) FAN SIZES 08SQ & 09SQ

FAN

SIZE

08SQ

09SQ

09SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

5, 6, 8

6, 8

8 x 14

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

127, 152, 203

152, 203

203 x 355

H

11.00" (279 mm)

DISCHARGE DIMENSIONS

W L

26.00" (660 mm) 40.00" (1016 mm)

A

18.00" (457 mm)

B

10.00" (254 mm)

D

4.00" (102 mm)

4.50" (114 mm)

Unit Wt

Lbs

(kg)

95 (43)

105 (48)

114 (52)

Optional Attenuator

Field Installed

136

17.50"

(445 mm)

5.00"

(127 mm)

10.50"

(267 mm)

TOP VIEW

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.

Actuator, Controller and

Fan Controls located in Enclosure

32.00"

(813 mm)

Optional Attenuator

Field Installed

Air

Valve

4.00

(102 mm)

Airflow

Plenum Inlet

18.00"

(457 mm)

L

4.

Actuator, Controller and

Fan Controls located in Enclosure

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

Rectangular Damper Detail

4.

Actuator, Controller and

Fan Controls located in Enclosure

Fan Size

08SQ

09SQ

Filter Size

10" x 10" x 1"

(254 mm x 254 mm x 25 mm)

Atten Wt

Lbs

(kg)

10 (4.5)

6.80"

(173 mm)

8.

Water

Coil

Airflow

Discharge Outlet

W

DISCHARGE VIEW

A

B

1.00"

(25 mm)

H

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm)

duct flange.

3. Bottom Access panel standard.

4. Control box enclosure provided with all control types.

5. Air valve centered between top and bottom panel.

6. Heating coil uninsulated. External insulation may be field

supplied and installed as required.

7. All high & low voltage controls have same-side NEC

jumpback clearance. (Left-hand shown, right-hand/mirror

image optional.)

8. Flange adds 2" to width and length of unit.

VAV-PRC012-EN

Dimensional Data

LOW-HEIGHT SERIES HOT WATER (LSWF) FAN SIZE 10SQ

FAN

SIZE

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

10SQ 8

10SQ 8 x 14

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

203

DISCHARGE DIMENSIONS

H W L C

11.00" (279 mm)

A B

48.00" (1219 mm) 36.00" (914 mm) 38.00" (965 mm) 10.00" (254 mm) 4.00" (102 mm)

203 x 356

D

20.00" (508 mm)

UNIT WT

WT LBS

(kg)

136 (62)

17.50" (445 mm) 146 (66)

Optional Attenuator

Field Installed

2.

Optional Attenuator

Field Installed

8.

Actuator, Controller and

Fan Controls located in Enclosure

8.

Actuator, Controller and

Fan Controls located in Enclosure

18.00"

(457 mm)

32.00"

(813 mm)

Optional Attenuator

Field Installed

D

Airflow

Plenum Inlet

10.50"

(267 mm)

17.50"

(445 mm)

5.00"

(127 mm)

2.

Primary

Airflow

C

32.00"

(813 mm)

Optional Attenuator

Field Installed

Airflow

Plenum Inlet

W

Airflow

Discharge Outlet

TOP VIEW

B

L

9.

6.80"

(173 mm)

Rectangular Damper Detail

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

Fan Size

10SQ

Filter Size

8.

Actuator, Controller and

Fan Controls located in Enclosure

10" x 16" x 1"

(254 mm x 406 mm x 25 mm)

Atten Wt

Lbs

(kg)

20 (9)

H

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Filter location with optional Attenuator.

3. Attenuator-factory assembled, field installed.

4. Air valve centered between top and bottom panel.

5. Heating coil uninsulated. External insulation may be field

supplied and installed as required.

6. All high & low voltage controls have same-side NEC

jumpback clearance. (Left-hand shown, right-hand/mirror

image optional.)

7. Bottom Access panel standard.

8. Control box enclosure provided with all control types.

9. Flange adds 2" to width and length of unit.

A

DISCHARGE VIEW

VAV-PRC012-EN 137

Dimensional Data

138 VAV-PRC012-EN

Dimensional Data

VAV-PRC012-EN 139

Dimensional Data

LOW-HEIGHT SERIES ELECTRIC HEAT (LSEF) FAN SIZES 08SQ & 09SQ

FAN

SIZE

08SQ

09SQ

09SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

5, 6, 8

6, 8

8 x 14

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

127, 152, 203

152, 203

203 x 355

H

11.00" (279 mm)

W

26.00" (660 mm)

DISCHARGE DIMENSIONS

L

A

40.00" (1016 mm) 14.00" (356 mm)

B

9.00" (229 mm)

D

4.00" (102 mm)

4.50" (114 mm)

Unit Wt

Lbs

(kg)

101 (45.8)

111 (50.3)

120 (54.4)

Optional Attenuator

Field Installed

140

17.50"

(445 mm)

5.00"

(127 mm)

10.50"

(267 mm)

20.00"

(508 mm)

D

Primary

Airflow

Valve 5"

6.50"

(165 mm)

4.

Actuator, Controller and

Fan Controls located in Enclosure

32.00"

(813 mm)

Optional Attenuator

Field Installed

Air

Valve

4.00

(102 mm)

Airflow

Plenum Inlet

18.00"

(457 mm)

Electric

Heater

Airflow

Discharge Outlet

20.00"

(508 mm)

A

4.

Actuator, Controller and

Fan Controls located in Enclosure

L

8.

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

Rectangular Damper Detail

Fan Size

08SQ

09SQ

Filter Size

4.

Actuator, Controller and

Fan Controls located in Enclosure

10" x 10" x 1"

(254 mm x 254 mm x 25 mm)

Atten Wt

Lbs

(kg)

10 (4.5)

B

TOP VIEW

H

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

2. Flanged discharge outlet accepts up to 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Control box enclosure provided with all control types.

5. Air valve centered between top and bottom panel.

6. Heating coil uninsulated. External insulation may be field supplied and

installed as required.

7. All hight & low voltage controls have same-side NEC jumpback clearance.

(Left-hand shown, right-hand/mirror image optional.)

8. Flange adds 2" to width and length of unit.

DISCHARGE VIEW

VAV-PRC012-EN

Dimensional Data

LOW-HEIGHT SERIES ELECTRIC (LSEF) FAN SIZE 10SQ

FAN

SIZE

10SQ

INLET SIZE

AVAILABILITY

NOMINAL Ø (INCHES)

8

INLET SIZE

AVAILABILITY

NOMINAL Ø (mm)

203

H W

11.00" (279 mm) 48.00" (1219 mm)

10SQ

8 x14 203 x 356

L

36.00" (914 mm)

DISCHARGE DIMENSIONS

A

B

19.00" (483 mm) 9.50" (241 mm)

C

4.00" (102 mm)

D

UNIT WT

WT LBS

(kg)

20.00" (508 mm) 145 (65.8)

17.50" (445 mm)

155 (70.3)

Optional Attenuator

Field Installed

18.00"

(457 mm)

17.50"

(445 mm)

5.00"

(127 mm)

32.00"

(813 mm)

Optional Attenuator

Field Installed

D

Airflow

Plenum Inlet

2.

Optional Attenuator

Field Installed

8.

Actuator, Controller and

Fan Controls located in Enclosure

8.

Actuator, Controller and

Fan Controls located in Enclosure

2.

Primary

Airflow

C

Airflow

Plenum Inlet

32.00"

(813 mm)

Optional Attenuator

Field Installed

W

L

9.

Rectangular Damper Detail

Rectangular Damper

8" x 14"

(203 mm x 356 mm)

8.

Actuator, Controller and

Fan Controls located in Enclosure

Fan Size

10SQ

Filter Size

10" x 16" x 1"

(254 mm x 406 mm x 25 mm)

Atten Wt (Qty 2)

Lbs

(kg)

20 (9.1)

24.00"

(610 mm)

Heater

Plenum Area

11.00"

(279 mm)

8.00"

(203 mm)

Airflow

Discharge Outlet

TOP VIEW

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for

unducted installations.

2. Filter location with optional Attenuator.

3. Attenuator-factory assembled, field installed.

4. Air valve centered between top and bottom panel.

5. Heating coil uninsulated. External insulation may be field supplied

and installed as required.

6. All high & low voltage controls have same-side NEC jumpback

clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Bottom Access panel standard.

8. Control box enclosure provided with all control types.

9. Flange adds 2" to width and length of unit.

H B

10.50"

(267 mm)

A

DISCHARGE VIEW

VAV-PRC012-EN 141