Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.

advertisement

AIR DUCTING WORK. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E | Manualzz

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

2. AIR DUCTING WORK

2-1. Static Pressure Characteristics of Each Model

Fig. 1 RAV-SM560BT-E

70% (570m

³

/h)

Standard air volume : 840m

³

/h

12

11

10

9

8

7

6

5

4

3

2

1

0

500

110% (925m

³

/h)

570 600

70% (800m

³

/h)

700 800

Air volume (m

³

/hr.)

Fig. 2 RAV-SM800BT-E

Standard air volume : 1140m

³

/h

900 925 1000

110% (1255m

³

/h)

7

6

5

4

3

2

1

0

700

12

11

10

9

8

800 900 1000 1100

Air volume (m

³

/hr.)

1200 1255 1300

– 12 – www.ilmalämpöpumput.com

advertisement

Key Features

  • 4-Way Air Discharge Cassette Type
  • Concealed Duct Type
  • High-Wall Type
  • Flexible Type
  • R410A Refrigerant
  • Turbo Fan
  • Energy Consumption Effect Ratio
  • Compressor Thermo
  • Pulse Motor Valve
  • Wired Remote Controller

Frequently Answers and Questions

What are the different types of indoor units available?
The indoor units are available in 4-Way Air Discharge Cassette Type, Concealed Duct Type, High-Wall Type, and Flexible Type.
What is the standard capacity of the units?
The standard capacity of the units varies depending on the model. Refer to the specifications section for detailed information.
What is the sound level of the outdoor unit?
The sound level of the outdoor unit is measured in an anechoic chamber and is typically between 45 and 50 dB(A).

Related manuals