- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Toshiba
- RAV-SM800 AT-E
- Service manual
REFRIGERANT R410A. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E 181 Pages
REFRIGERANT R410A. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E
Add to My manuals181 Pages
Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.
advertisement
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
7. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
(6) When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
7-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc.
by a rupture.
(2) Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant
R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
(4) When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
7-2. Refrigerant Piping Installation
7-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 7-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 30 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Nominal diameter
(2) Joints
1/4
3/8
1/2
5/8
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Table 7-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A
0.80
0.80
0.80
1.00
R22
0.80
0.80
0.80
1.00
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
Table 7-2-2.
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 7-2-3 to 7-
2-6 below.
Nominal diameter
1/4
3/8
1/2
5/8
Table 7-2-2 Minimum thicknesses of socket joints
Reference outer diameter of copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
7-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
(1) Flare Processing Procedures and Precautions a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
– 31 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
ØD
A
Nominal diameter
1/4
3/8
1/2
5/8
Fig. 7-2-1 Flare processing dimensions
Table 7-2-3 Dimensions related to flare processing for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R410A clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
1.5 to 2.0
2.0 to 2.5
2.0 to 2.5
Nominal diameter
1/4
3/8
1/2
5/8
Table 7-2-4 Dimensions related to flare processing for R22
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R22 clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch type
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
Wing nut type
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
1.5 to 2.0
Nominal diameter
1/4
3/8
1/2
5/8
Table 7-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15,88
Thickness
(mm)
0.8
0.8
0.8
1.0
A
9.1
13.2
16.6
19.7
B
Dimension (mm)
C
9.2
13.5
16.0
19.0
6.5
9.7
12.9
16.0
D
13
20
23
25
– 32 – www.ilmalämpöpumput.com
Flare nut
width (mm)
17
22
26
29
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Nominal diameter
1/4
3/8
1/2
5/8
3/4
Table 7-2-6 Flare and flare nut dimensions for R22
Outer diameter Thickness
(mm)
6.35
9.52
12.70
15.88
19.05
(mm)
0.8
0.8
0.8
1.0
1.0
A
9.0
13.0
16.2
19.4
23.3
Dimension (mm)
B C D
9.2
13.5
6.5
9.7
13
20
16.0
19.0
24.0
12.9
16.0
19.2
20
23
34
45 to 46
B A C D
Flare nut width
(mm)
17
22
24
27
36
43 to 45
Fig. 7-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis.
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 7-2-7 shows reference values.
NOTE:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Nominal diameter
1/4
3/8
1/2
5/8
Table 7-2-7 Tightening torque of flare for R410A [Reference values]
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N
• m (kgf
• cm)
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
Tightening torque of torque wrenches available on the market
N
• m (kgf
• cm)
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
– 33 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
7-3. Tools
7-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
(3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
No.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
Used tool
Flare tool
Copper pipe gauge for
adjusting projection margin
Usage
Pipe flaring
Flaring by conventional flare tool
R410A air conditioner installation
Existence of Whether convennew equipment tional equipment for R410A can be used
Yes * (Note 1)
Yes * (Note 1)
Conventional air conditioner installation
Whether new equipment can be used with conventional refrigerant
¡
* (Note 1)
Torque wrench Connection of flare nut
Yes
X X
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder
Leakage detector
Charging cylinder
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
Refrigerant charge
Yes
Yes
Yes
Yes
Yes
(Note 2)
X
X
X
X
X
X
X
¡
¡
X
¡
X
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by attaching vacuum pump adapter.
(2) Torque wrench
(3) Pipe cutter
(4) Reamer
(5) Pipe bender
(6) Level vial
(7) Screwdriver (+, –)
(8) Spanner or Monkey wrench
(9) Hole core drill (Ø65)
(10) Hexagon wrench
(Opposite side 4mm)
(11) Tape measure
(12) Metal saw
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter
(3) Insulation resistance tester
(2) Thermometer
(4) Electroscope
– 34 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
7-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose of the vacuum pump adapter.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
Never charge refrigerant exceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit) (Liquid side)
Opened
(Gas side)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve for charging
Closed
Service port
Electronic balance for refrigerant charging
Fig. 7-4-1 Configuration of refrigerant charging
– 35 – www.ilmalämpöpumput.com
(OUTDOOR unit)
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ]
Gauge manifold
OUTDOOR unit
[ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant cylinder
Electronic balance cylinder ant
Electronic balance
Refriger
Siphon
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies.
Fig. 7-4-2
7-5. Brazing of Pipes
7-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
When performing brazing again at time of servicing, use the same type of brazing filler.
7-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler's surface tension, the brazing filler adheres better to the treated metal.
– 36 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
(2) Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
•
Noncorrosive flux
Generally, it is a compound of borax and boric acid.
It is effective in case where the brazing temperature is higher than 800°C.
•
Activated flux
Most of fluxes generally used for silver brazing are this type.
It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used brazing filler/flux
7-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas
(N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.
Apply a seal onto the clearance between the piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
When the Nitrogen gas is flowing, be sure to keep the piping end open.
Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m
³
/Hr or 0.02 MPa (0.2kgf/ cm
²
) by means of the reducing valve.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
Piping material
Used brazing filler
Used flux
Copper - Copper Phosphor copper Do not use
Copper - Iron
Iron - Iron
Silver
Silver
Paste flux
Vapor flux
M
Flow meter
Stop valve
Nitrogen gas cylinder
From Nitrogen cylinder
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
Remove the flux after brazing.
Pipe
Rubber plug
Nitrogen gas
Fig. 7-5-1 Prevention of oxidation during brazing
– 37 – www.ilmalämpöpumput.com
advertisement
Key Features
- 4-Way Air Discharge Cassette Type
- Concealed Duct Type
- High-Wall Type
- Flexible Type
- R410A Refrigerant
- Turbo Fan
- Energy Consumption Effect Ratio
- Compressor Thermo
- Pulse Motor Valve
- Wired Remote Controller
Frequently Answers and Questions
What are the different types of indoor units available?
What is the standard capacity of the units?
What is the sound level of the outdoor unit?
Related manuals
advertisement
Table of contents
- 3 SPECIFICATIONS
- 12 AIR DUCTING WORK
- 13 CONSTRUCTION VIEWS (EXTERNAL VIEWS)
- 20 SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
- 22 WIRING DIAGRAM
- 28 SPECIFICATIONS OF ELECTRICAL PARTS
- 30 REFRIGERANT R410A
- 38 CONTROL BLOCK DIAGRAM
- 48 CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
- 65 TROUBLESHOOTING
- 88 REPLACEMENT OF SERVICE INDOOR P.C. BOARD
- 92 SETUP AT LOCAL SITE AND OTHERS
- 103 ADDRESS SETUP
-
108
TROUBLESHOOTING
- 135 DETACHMENTS
- 168 EXPLODED VIEWS AND PARTS LIST