CONTROL BLOCK DIAGRAM. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E 181 Pages
CONTROL BLOCK DIAGRAM. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E
Add to My manuals181 Pages
Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.
advertisement
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
8. CONTROL BLOCK DIAGRAM
8-1. Indoor Control Circuit
Max. 8 units are connectable.*1
*1 Max. 7 units when network adapters
are attached
*2 Network adapters are attached to only
one unit.
*3 Weekly timer is not connectable to the
sub remote controller.
Central control remote controller
(Option)
Main (Sub) master remote controller
Display
LCD
Display
LED
CPU
Remote controller communication circuit
Function setup
Key switch
DC5V
Power circuit
CN2 CN1
* 3
Weekly timer
Display
LCD
LCD driver
Power circuit
DC5V
CPU
Secondary battery
Option
Y
X
Indoor unit
#1
Network adapter (Option)
Network adapter
P.C. board
(MCC-1401)
Remote controller communication circuit
AI NET communication circuit
DC5V
Power circuit
CPU
H8/3687
Switch setup
Indoor control P.C. board (MCC-1402)
DC20V
DC12V
DC5V
A B
Remote controller communication circuit
EEPROM
Humidifier relay output
Heater relay output
Driver
CPU
H8/3039
TA sensor
TC sensor
TCJ sensor
Function setup
Key switch
Option
#2
A B
#3
A B
Same as the left
*
2
Same as the left
*
2
Transformer
Float input
Louver motor
Drain pump
Indoor fan motor
DC280V
Power circuit
CPU
TMP88CH
47FG
(TMP88PH
47FG)
Fan motor control circuit
Outside output
Run
Warning
Ready
Thermo. ON
Cool
Heat
Fan
AC synchronous signal input circuit
Serial send/ receive circuit
1 2 3 1 2 3
Outdoor unit
Outdoor unit
1 2 3
1 2 3
Outdoor unit
Optional only for 4-way air discharge cassette type models
Wireless remote controller kit
Sensor P.C. board (MCC-1418)
Power circuit
DC5V
Remote controller communication circuit
Buzzer
CPU
Temporary operation SW
Function setup SW
Receive circuit Display LED
– 38 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
8-2. Control Specifications
No.
1
Item
When power supply is reset
Outline of specifications
1) Distinction of outdoor units
When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result.
2) Setting of speed of the indoor fan/setting whether to adjust air direction or not.
(Only 4-way models)
Based on EEPROM data, speed of the indoor fan or setting whether to adjust air direction or not is selected.
Remarks
Air speed/
Air direction adjustment
2 Operation mode selection
1) Based on the operation mode selecting command from the remote controller, the operation mode is selected.
Remote controller command
STOP
FAN
COOL
DRY
HEAT
AUTO
Outline of control
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
• COOL/HEAT operation mode is automatically selected by Ta and Ts for operation.
Ta
( C)
+1.5
COOL
(COOL ON)
Tsc or Tsh
(COOL OFF)
-1.5
HEAT
1) Judge the selection of COOL/HEAT mode as shown in the figure above.
When 10 minutes passed after thermostat had been turned off, the heating operation (Thermo
OFF) is exchanged to cooling operation if Tsh exceeds +1.5 or more.
(COOL OFF) and (COOL ON) in the figure indicate an example.
When 10 minutes passed after thermostat had been turned off, the cooling operation (Thermo
OFF) is exchanged to heating operation if Tsc exceeds –1.5 or less.
2) For the automatic capacity control after judgment of
COOL/HEAT, refer to item 4.
3) For the temperature correction of room temperature control in automatic heating operation, refer to item 3.
Ta : Room temperature
Ts : Setup temperature
Tsc : Setup temperature in cooling operation
Tsh : Setup temperature
+ Room temperature control temperature compensation
– 39 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
3
Item
Room temperature control
Outline of specifications
1) Adjustment range Remote controller setup temperature (°C)
COOL/
DRY
Heating operation
Auto operation
Wired type
Wireless type
*
18 to 29
18 to 30
18 to 29
16 to 30
18 to 29
17 to 27
*
: Only for 4-way air discharge cassette type
2) Using the item code 06, the setup temperature in heating operation can be compensated.
Setup data
Setup temp.
compensation
0
+0°C
2
+2°C
4
+4°C
6
+6°C
Setting at shipment
Setup data 2
Remarks
Shift of suction temperature in heating operation
4 Automatic capacity control
(GA control)
1) Based on the difference between Ta and Ts, the operation frequency is instructed to the outdoor unit.
5 Air speed selection
1) Operation with (HH), (H), (L), or [AUTO] mode is performed by the command from the remote controller.
2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts.
HH > H > L > LL
<COOL>
Ta ( C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
-0.5
HH
(HH)
H (HH)
H (HH)
L(H)
L(H)
L(H)
L(L)
A
B
C
D
E
F
G
• Controlling operation in case when thermo of remote controller works is same as a case when thermo of the body works.
• If the air speed has been changed once, it is not changed for 3 minutes. However when the air volume is exchanged, the air speed changes.
• When cooling operation has started, the air speed selects a downward slope, that is, the high position.
• If the temperature is just on the difference boundary, the air speed does not change.
• Mode in the parentheses indicates one in automatic cooling operation.
– 40 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
5
Item
Air speed selection
(Continued)
Outline of specifications Remarks
<HEAT>
Ta ( C)
(-0.5)
–
1.0
(0) Tsh
(+0.5) +1.0
(+1.0)
+2.0
(+1.5) +3.0
(+2.0) +4.0
L(L)
L(H)
H(H)
H
(HH)
HH
(HH)
E
D
C
B
A
Value in the parentheses indicates one when thermostat of the remote controller works.
Value without parentheses indicates one when thermostat of the body works.
•
If the air speed has been changed once, it is not changed for 1 minute. However when the air speed is exchanged, the air speed changes.
•
When heating operation has started, the air speed selects a upward slope, that is, the high position.
•
If the temperature is just on the difference boundary, the air speed does not change.
•
Mode in the parentheses indicates one in automatic heating operation.
•
In Tc
≥
60
°
C, the air speed increases by 1 step.
<Operation of duct only>
Standard High ceiling
Tap
COOL HEAT COOL HEAT
UL
L
L+
M
M+
H
UL
L
L+
M
M+
H
UL
L
L+
H
UL
L
L+
M+,M M+,M
H
F7
F6
F5
F4
F3
F2
F1
FD
FD
FB
FA
F9
F8
SM560 SM800
Revolutions per minute (rpm)
320
320
330
320
330
340
350
360
370
400
410
420
360
370
380
410
440
450
440
480
530
580
480
500
540
580
Tc: Indoor heat exchanger sensor temperature
3) In heating operation, the mode changes to [UL] if thermostat is turned off.
4) If Ta
≥
25
°
C when heating operation has started and when defrost operation has been cleared, it operates with HIGH (H) mode or (HH) for 1 minute from when Tc has entered in E zone of cool air discharge preventive control (Item 6).
5) In automatic cooling/heating operation, the revolution frequency of [HH] is set larger than that in the standard cooling/heating operation. However the revolution frequency is restricted in the automatic heating operation as shown in the following figure.
[PRE-HEAT] display
Tc
( C)
47
42
F5 F4
F5
–
41
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
6
Item
Cool air discharge preventive control
Outline of specifications Remarks
1) In heating operation, the indoor fan is controlled based on the detected temperature of Tc sensor or Tcj sensor.
As shown below, the upper limit of the
Tc
Tcj
( C)
32
HH revolution frequency is determined.
30
H
L
E zone
28
UL
D zone
26
OFF
20
16
C zone
B zone
A zone
In D or E zone, the priority is given to setup of air volume exchange.
In A and B zones,
[PRE-HEAT] is displayed.
7 Freeze preventive control
(Low temperature release)
1) The cooling operation (including Dry operation) is performed as follows based on the detected temperature of Tc sensor or Tcj sensor.
When [J] zone is detected for 6 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [J] zone.
In [K] zone, time counting is interrupted and the operation is held.
When [I] zone is detected, the timer is cleared and the operation returns to the normal operation.
If the commanded frequency becomes S0 because the operation continues in [J] zone, the return temperature
A is raised from 5
°
C to 12
°
C until [I] zone is detected and the indoor fan operates with [M] mode.
( C)
5 I A
K
Tcj : Indoor heat exchanger sensor temperature
2
J
8
In heating operation, the freeze-preventive control works if 4-way valve is not exchanged and the condition is satisfied. (However the temperature for J zone dashing control is changed from 2
°
C to
–
5
°
C.)
High-temp release control
1) The heating operation is performed as follows based on the detected temperature of Tc sensor or Tcj sensor.
•
When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [M] zone.
•
In [N] zone, the commanded frequency is held.
•
When [L] zone is detected, the commanded frequency is returned to the original value by approx.
6Hz every 60 seconds.
Setup at shipment
Control temp (°C)
A B
Tc ( C)
Tcj
A
M
N
56 (54) 52 (52)
B
L
NOTE :
When the operation has started or when Tc or Tcj became lower than 30
°
C after start of the operation, temperature is controlled between values in parentheses of A and B.
Same when thermostat is turned off.
–
42
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
9
Item Outline of specifications
Drain pump control
(For the duct, when the drain-up kit
(sold separately) is mounted)
1) In cooling operation (including Dry operation), the drain pump is usually operated.
2) If the float switch operates while drain pump operates, the compressor stops, the drain pump continues the operation, and a check code is output.
3) If the float switch operates while drain pump stops, the compressor stops and the drain pump operates. If the float switch keeps operating for approx.
4 minutes, a check code is output.
Remarks
Check code [P10]
10 After-heat elimination
When heating operation stops, the indoor fan operates with LOW mode for approx. 30 seconds.
11 Flap control
(For 4-way air discharge cassette type only)
1) Flap position setup
• When the flap position is changed, the position moves necessarily to downward discharge position once to return to the set position.
• The flap position can be set up in the following operation range.
In cooling/dry operation In heating/fan operation
• In group twin/triple operation, the flap positions can be set up collectively or individually.
2) Swing setup
• The swinging position can be moved in the following operation range.
All modes
• In group twin/triple operation, the swinging positions can be set up collectively or individually.
3) When the unit stops or when a warning is output, the flap automatically moves downward.
4) While the heating operation is ready, the flap automatically moves upward.
Warning :
A check code is displayed on the remote controller, and the indoor unit stops.
(Excluding [F08] and
[L31])
– 43 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
Item
12 Frequency fixed operation
(Test run)
Outline of specifications
<In case of wired remote controller>
1. When pushing [CHECK] button for 4 seconds or more,
[TEST] is displayed on the display screen and the mode enters in Test run mode.
2. Push [ON/OFF] button.
3. Using [MODE] button, change the mode from [COOL] to [HEAT].
•
Do not use other mode than [COOL]/[HEAT] mode.
•
During test run operation, the temperature cannot be adjusted.
•
An error is detected as usual.
•
A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the operation. (Display in the display part is same as the procedure in item 1).)
5. Push [CHECK] button to clear the test run mode.
([TEST] display in the display part disappears and the status returns to the normal stop status.)
<In case of wireless remote controller>
(Option for 4-way air discharge cassette type only)
1. Turn off the power of the set.
Remove the adjuster with sensors from the ceiling panel.
2. Turn Bit [1: TEST] of sensor P.C. board switch [S003] from OFF to ON.
Attach the sensor P.C. board cover and mount the adjuster with sensors to the ceiling panel.
Turn on the power of the set.
3. Push [ON/OFF] button of the wireless remote controller and set the operation mode to [COOL] or [HEAT] using
[MODE] button.
(During test run operation, all the display lamps of wireless remote controller sensors flash.)
•
Do not use other mode than [COOL]/[HEAT] mode.
•
An error is detected as usual.
•
A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the operation.
5. Turn off the power of the set.
Turn Bit [1: TEST] of sensor P.C. board switch [S003] from ON to OFF.
Mount the adjuster with sensors to the ceiling panel.
Remarks
13 Filter sign display
(Except wireless type)
1) The operation time of the indoor fan is calculated, the filter reset signal is sent to the remote controller when the specified time (2500H) has passed, and it is displayed on LCD.
2) When the filter reset signal has been received from the remote controller, time of the calculation timer is cleared. In this case, the measurement time is reset if the specified time has passed, and display on LCD disappears.
[FILTER] goes on.
–
44
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
14
15
Item
Central control mode selection
Energy-save control
(By connected outdoor unit)
16 Max. frequency cut control
Outline of specifications
1) Setting at the central controller side enables to select the contents which can be operated on the remote controller at indoor unit side.
2) RBC-AMT21
[Last push priority] :
The operation contents can be selected from both remote controller and central controller of the indoor unit side, and the operation is performed with the contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the remote controller at indoor unit side.
[Operation Prohibited] :
It cannot be operated on the remote controller at indoor unit side. (Stop status is held.)
Remarks
(No display)
[CENTER] goes on.
[CENTER] goes on.
In a case of wireless type, the display lamp does not change.
However, contents which can be operated are same.
The status set in [CENTER]/
[Operation Prohibited] mode is notified with the receiving sound
“
Pi, Pi, Pi, Pi, Pi
”
(5 times).
1) Selecting [AUTO] mode enables an energy-saving to be operated.
2) The setup temperature is shifted (corrected) in the range not to lose the comfort ability according to input values of various sensors.
3) Data (Input value room temp. Ta, Outside temp. To, Air volume, Indoor heat exchanger sensor temp. Tc) for
20 minutes are taken the average to calculate correction value of the setup temperature.
4) The setup temperature is shifted every 20 minutes, and the shifted range is as follows.
In cooling time : +1.5 to
–
1.0K
In heating time :
–
1.5 to +1.0K
1) This control is operated by selecting [AUTO] operation mode.
2) COOL operation mode: the frequency is controlled according to the following
Ta( C) Normal control
+4 figure if
To < 28
°
C.
+3
Max. frequency is restricted to approximately the rated cooling frequency
Tsc
3) HEAT operation mode: the frequency is controlled according to the right
Ta( C)
Tsh figure if
To > 15
°
C.
–
3
Max. frequency is restricted to approximately the rated heating frequency
–
4
Normal control
17 DC motor
(For 4-way air discharge cassette type only)
1) When the fan operation has started, positioning of the stator and the rotor are performed.
(Moves slightly with tap sound)
2) The motor operates according to the command from the indoor controller.
NOTES :
•
When the fan rotates while the air conditioner stops due to entering of outside air, etc, the air conditioner may operated while the fan motor stops.
•
When a fan locking is found, the air conditioner stops, and an error is displayed.
Check code [P12]
–
45
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
DC fan output
Microcomputer operation LED
EEPROM
Network adapter power supply
Indoor/Outdoor inter-unit cable
DC fan return
Float SW
Louver
Optional output
TA sensor
CHK
DISP
EXCT
TC sensor
Outside error input
TCJ sensor
Remote controller power LED
Remote controller inter-unit cable www.ilmalämpöpumput.com
Drain pump output
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Indoor/Outdoor inter-unit cable
Power transformer output
Power transformer input (AC11V,14V,20V)
Microcomputer operation LED
Louver
Drain pump output
Network adapter power supply
Fan output EXCT Float SW
TA sensor
TCsensor
TCJ sensor
Outside error input
Remote controller inter-unit cable
CHK
DISP www.ilmalämpöpumput.com
Remote controller power LED
HA
Optional output
advertisement
Key Features
- 4-Way Air Discharge Cassette Type
- Concealed Duct Type
- High-Wall Type
- Flexible Type
- R410A Refrigerant
- Turbo Fan
- Energy Consumption Effect Ratio
- Compressor Thermo
- Pulse Motor Valve
- Wired Remote Controller
Frequently Answers and Questions
What are the different types of indoor units available?
What is the standard capacity of the units?
What is the sound level of the outdoor unit?
Related manuals
advertisement
Table of contents
- 3 SPECIFICATIONS
- 12 AIR DUCTING WORK
- 13 CONSTRUCTION VIEWS (EXTERNAL VIEWS)
- 20 SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
- 22 WIRING DIAGRAM
- 28 SPECIFICATIONS OF ELECTRICAL PARTS
- 30 REFRIGERANT R410A
- 38 CONTROL BLOCK DIAGRAM
- 48 CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
- 65 TROUBLESHOOTING
- 88 REPLACEMENT OF SERVICE INDOOR P.C. BOARD
- 92 SETUP AT LOCAL SITE AND OTHERS
- 103 ADDRESS SETUP
-
108
TROUBLESHOOTING
- 135 DETACHMENTS
- 168 EXPLODED VIEWS AND PARTS LIST