SETUP AT LOCAL SITE AND OTHERS. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E

SETUP AT LOCAL SITE AND OTHERS. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E

Add to My manuals
181 Pages

Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.

advertisement

SETUP AT LOCAL SITE AND OTHERS. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E | Manualzz

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12. SETUP AT LOCAL SITE AND OTHERS

12-1. Indoor Unit

12-1-1. Test Run Setup on Remote Controller

<Wired remote controller>

1. When pushing button on the remote controller for 4 seconds or more,

TEST

is displayed on LC display.

Then push button.

• “

TEST

is displayed on LC display during operation of Test Run.

During Test Run, temperature cannot be adjusted but air volume can be selected.

In heating and cooling operation, a command to fix the Test Run frequency is output.

Detection of error is performed as usual. However, do not use this function except case of Test Run because it applies load on the unit.

2. Use either heating or cooling operation mode for [TEST].

NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after operation has stopped.

3. After a Test Run has finished, push button again and check that [TEST] on LC display has gone off.

(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote controller.)

<Wireless remote controller> (Option for 4-way air discharge cassette type)

1. Turn off power of the unit.

Remove the adjuster attached with sensors from the ceiling panel. For removing, refer to the Installation manual attached to the ceiling panel. (Be careful to handle the adjuster because cables are connected to the sensor.) Remove the sensor cover from the adjuster. (1 screw)

2. Change ON of Bit [1: TEST] of the sensor P.C. board switch [S003] to OFF.

Mount the sensor cover and mount the adjuster with sensor to the ceiling panel.

Turn on power of the unit.

3. Push button on the wireless remote controller and select [COOL] or [HEAT] operation mode using

button. (All the display lamps of sensors on the wireless remote controller flash during Test Run.)

Do not perform Test Run operation in other modes than [HEAT] / [COOL] mode.

Detection of error is performed as usual.

4. After Test Run operation, push button to stop the operation.

5. Turn off power of the unit.

Return Bit [1] of the sensor P.C. board switch [S003] to the original position. (ON

OFF)

Mount the adjuster with sensors to the ceiling panel.

Sensor cover

Adjust corner cap

S003

Bit 1 : OFF to ON

ON

Sensor P.C. board

92

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-1-2. Setup to Select Function

<Procedure> Use this function while the indoor unit stops.

1

Push

SET

, , and buttons concurrently for 4 seconds or more.

The unit No. displayed at the first time indicates the indoor unit address of the master unit in the group control.

In this time, fan and flap of the selected indoor unit operate.

2

Every pushing button, the indoor unit numbers in the group control are displayed successively.

In this time, fan and flap of the selected indoor unit only operate.

3

Using the set temperature / buttons, set the item code (DN).

4

Using the timer time / buttons, select the setup data.

5

Push

SET

button. (OK if display goes on.)

To change the selected indoor unit, proceed to

2

.

To change the item to be set, proceed to

3

.

6

Pushing button returns the status to usual stop status.

SET DATA

UNIT No.

R.C.

No.

6

4

1

SET CL

UNIT

5 2

<Operation procedure>

1 2 3 4 5 6

END

3

93

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

Item No. (DN) table (Selection of function)

DN Item

01 Filter sign lighting time

02 Dirty state of filter

0000 : None

0002 : 2500H

0004 : 10000H

0000 : Standard

Description

0001 : 150H

0003 : 5000H

0005 : Clogged sensor used

0001 : High degree of dirt

(Half of standard time)

0064 : No.64 unit

At shipment

According to type

0000 : Standard

03 Central control address

0001 : No.1 unit

0099 : Unfixed

06 Heating suction temp shift

0000 : No shift

0002 : +2

°

C to to

0001 : +1

°

C

0010 : -10

°

C

(Up to recommendation + 6)

0099 : Unfixed

0002 : +2

°

C

(Floor type 0000: 0

°

C)

0F Cooling only 0000 : Heat pump 0001 : Cooling only

(No display of [AUTO] [HEAT])

0000 : Shared for cooling/ heating

10 Type

11 Indoor unit capacity 0000 : Unfixed

12 Line address

0000 : (Air discharge cassette 1) 0001 : (Air discharge cassette 4) to 0037

0001 : No.1 unit

0001 to 0034

0030 : No.30 unit

According to model type

13 Indoor unit address 0001 : No.1 unit to to

According to capacity type

0099 : Unfixed

14 Group address

0064 : No.64 unit

0001 : Master of group

0099 : Unfixed

0099 : Unfixed

19 Flap type

(Adjustment of air direction)

0000 : Individual

0002 : Sub of group

0000 : No flap

0004 : 4-way

0001 : Swing only According to type

0003 : 3 deg

(Ts±1.5)

1E Temp difference of automatic cooling/ heating mode selection COOL

HEAT, HEAT

COOL

0000 : 0 deg to 0010 : 10 deg

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

28 Automatic reset of power failure

0000 : None 0001 : Reset

2A Option

0000 : None

2b Thermo output selection (T10

ƒ

)

2E Option

0000 : Indoor thermo ON 0001 : Output of outdoor comp-ON receiving

0002 : Default

0000: Thermo. ON

0000 : Default

30

31

32

40

Option

Option

Sensor selection

Option

0000 : Body TA sensor 0001 : Remote controller sensor

0000 : Default

0000 : Default

0000 : Body sensor

0003 : Default

5d High ceiling selection

(Air volume selection)

0000 : Standard filter

0001 : Oil guard, Super-long life, Optical regenerative deodorization

0003 : High performance (65%), High performance (90%),

High antibacterial performance (65%)

0000 : Available (Operable) 0001 : Unavailable (Operation prohibited)

0000 : Standard

0000 : Available 60 Timer set

(Wired remote controller)

8b Correction of high heat feeling

0000 : None 0001 : Correction 0000 : None

94

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-1-3. Cabling and Setting of Remote Controller Control

2-remote controller control (Controlled by two remote controllers)

One or multiple indoor units are controlled by two remote controllers.

(Max. 2 remote controllers are connectable.)

• 1 indoor unit is controlled by 2

Remote controller

Remote controller switch (Master) switch (Sub)

remote controllers

Sold separately Sold separately

A B

Indoor unit

1 2 3

Remote controller cables (Procured locally)

Terminal block for remote controller cables

1 2 3

Outdoor u nit

(Setup method)

One or multiple indoor units are controlled by two remote controllers.

(Max. 2 remote controllers are connectable.)

Rear side of remote controller P.C. board

<Wired remote controller>

How to set wired remote controller to sub remote controller

Insert the remote controller address connector provided on the rear side of the remote controller switch P.C. board into Sub in exchange for Master.

Remote controller address connector

Master remote controller

Sub remote controller

<Wireless remote controller>

How to set wireless remote controller to sub remote controller

Change OFF of Bit [3: Remote controller Sub/

Master] of switch S003 to ON.

Sensor cover

Adjust corner cap

[Operation]

1. The operation contents can be changed by Last-push-priority.

2. Use a timer on either Master remote controller or Sub remote controller.

95

– www.ilmalämpöpumput.com

S003

Bit 1 : OFF to ON

ON

Sensor P.C. board

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-1-4. Monitor Function of Remote Controller Switch

n

Call of sensor temperature display

<Contents>

Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling the service monitor mode from the remote controller.

<Procedure>

1

Push + buttons simultaneously for 4 seconds or more to call the service monitor mode.

The service monitor goes on, the master indoor unit

No. is displayed, and then temperature of the item

code

00

is displayed.

2

Push the temperature setup / buttons to select the sensor No. (Item code) of the sensor to be monitored.

The sensor numbers are described below:

4

1

SET DATA

SET CL

UNIT No.

R.C.

No.

UNIT

3

<Operation procedure>

1 2 3 4

Returned to usual display

2

Indoor unit data

Item code

00

01

02

03

04

Data name

Room temp (under control) *1

Room temp (remote controller)

Indoor suction temp

Indoor coil temp (TCJ)

Indoor coil temp (TC)

Outdoor unit data

Item code

60

61

62

63

64

65

Data name

Heat exchanger temp TE

Outside temp TO

Discharge temp TD

Suction temp TS

Heat sink temp THS

*1 Only master unit in group control

3

The temperature of indoor units and outdoor unit in a group control can be monitored by pushing

button to select the indoor unit to be monitored.

4

Pushing button returns the display to usual display.

96

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy n

Calling of error history

<Contents>

The error contents in the past can be called.

<Procedure>

1

Push + buttons simultaneously for 4 seconds or more to call the service check mode.

Service Check goes on, the item code

01

is displayed, and then the content of the latest alarm is displayed. The number and error contents of the indoor unit in which an error occurred are displayed.

2

In order to monitor another error history, push the set temperature / buttons to change the error history No. (Item code).

Item code

01

(Latest)

Item code

04

(Old)

NOTE : Four error histories are stored in memory.

3

Pushing button returns the display to usual display.

<Requirement>

Do not push button, otherwise all the error histories of the indoor unit are deleted.

3

SET DATA

UNIT No.

R.C.

No.

SET CL

UNIT

1

<Operation procedure>

1 2 3

Returned to usual display

2

(Group control operation)

In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.

The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to setting on the remote controller.

<System example>

OUT OUT OUT

IN

1-1

IN

Master

2-1

IN

3-1

Remote controller

OUT

IN

4-1

OUT

IN

7-1

Max. 8 units

(1) Display range on remote controller

The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the master unit is reflected on the remote controller.

(2) Address setup

Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic address.

If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the system is rebooted and the automatic address setting will be judged again.

1) Connect 3 In/Out cables surely.

2) Check line address/indoor address/group address of the unit one by one.

3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the unit No. is not duplicated with one of another unit.

97

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-2. Network Adapter

Model name: TCB-PCNT20E

12-2-1. Function

A network adapter is an optional P.C. board to connect the indoor unit to AI net (Central control remote controller).

12-2-2. Microcomputer Block Diagram

Remote controller

Indoor unit

Optional communication P.C. board

CN41

Indoor control

P.C. board

CN309

AC220-

240V

CN02

Remote controller communication circuit

MCU

Terminal block

(A.B)

Power transformer

AC14V

CN01

5V power supply

5V

Network address setup switch

AI-NET communication circuit

CN03

Terminal block

(X.Y)

EEPROM

Central control remote controller

Network

Communication units: Total 64 units

Communication distance: 1km

12-2-3. Network Address Setup Switch (SW01)

4

5

6

7

8

No.

1

2

3

LSB

Central control address

MSB

Item

Setup availability from remote controller

Setup contents

1 2 3 4 5 6

××× × × ×

: No.1 unit

〇×× × × × : No.2 unit

:

×

: Switch OFF

: Switch OFF

〇〇〇 〇 〇 ×

: No.63 unit

〇〇〇 〇 〇 〇 : No.64 unit

Switch OFF : Setup available from remote controller

Switch ON : Setup unavailable from remote controller

12-2-4. LED Display Specification

LED No.

D01 (Red)

D02 (Red)

D03 (Red)

D04 (Red)

Function

Communication status: Remote controller

Communication status: Center

Operation status of air conditioner

Air conditioner error

Go on

During communication

During communication

Running

Error

Go off

No communication (including communication error)

No communication (including communication error)

Stop

Normal

* For positions of LED, refer to P.C. board external view.

– 98 – www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-2-5. Communication Cable Specifications

No.

1

2

Communication circuit

Remote controller communication side

AI NET side

Cable

Cable type

Cable dia.

Cable length

Cable

Cable type

Cable dia.

Cable length

Communication cable specifications

Neutral 2-cable type

CVV (JIS C3401) Controlling vinyl insulation vinyl seal cable

VCTF (JIS C3306) Vinyl cab tire round type cord

VCT (JIS C3401) 600V vinyl cab tire cable

VVR (JIS C3401) Vinyl insulation seal cable round type

MVVS Cable with net shielding for instrumentation

CPEVS Shielded polyethylene insulation vinyl seal cable

0.5 to 2.0 mm²

Total cable length Max. 500m

(Up to 400m when there is wireless remote controller in group)

Neutral 2-cable type

MVVS Cable with net shielding for instrumentation

1.25 mm²

500 m, 2.0 mm²

1 km

Total cable length : Up to 500m when using 1.25mm² cable,

Up to 1000m when using 2.0mm² cable

12-2-6. Cable Connection

<Network cable connection>

• Install a network adapter per 1 group of the group control (including single unit control). Also install a network adapter to one of the indoor units in the group control.

Central control remote controller

X Y

Network adapter

Indoor unit

Indoor unit

Indoor control

P.C. board

A B

Indoor control

P.C. board

A B

Indoor unit

Indoor control

P.C. board

A B

Indoor unit

Indoor control

P.C. board

A B

X Y

Network adapter

Indoor unit

Indoor unit

Indoor control

P.C. board

A B

Indoor control

P.C. board

A B

Remote controller

Connectable indoor units per group: Up to 8 units

(1-remote controller system*)

* In case of 2-remote controllers system,

the connectable indoor units are up to 7 units.

– 99 – www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-3. How to Set an Address Number

When connecting indoor units to the central control remote controller by using a network adapter, it is required to set up a network address No.

The network address No. should be agreed with the line No. of the central control remote controller.

When the unit was shipped from the factory, the network address has been set to 1.

The following two methods to set the network address are provided.

1. How to set from the remote controller at indoor unit side

* This method is effective only when

‡

of set switch SW01 on the network adapter P.C. board is turned off.

<Procedure> Set the network address while the unit stops.

1

Push + buttons for 4 seconds or more.

In the group control, the unit No

RLL

is displayed, and then all the indoor units in the group control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)

(Keep status of

RLL

display without pushing button.)

3

For the individual remote controller which is not included in a group control, the line address and the indoor unit address are displayed.

2

Specify the item code

03

using the temperature setup /

buttons.

3

Using the timer time / buttons, select the setup data.

1

5

SET DATA

SET CL

4

Fig. 1

UNIT No.

R.C.

No.

UNIT

Table 1

The setup data are shown in the right table (Table 1).

4

Push

SET

button. (OK if display goes on)

To change the item to be set, return to

2

.

5

Push button.

The status returns to the usual stop status.

Setup data

0001

0002

0003

:

0064

0099

Network address No.

1

2

3

:

64

Unset (Setup at shipment from factory)

2

2. How to set by the switch on the network adapter P.C. board

When the remote controller cannot be found or when you don

’ t want to change setting of the network address

No. from the remote controller, use the setup switch SW01 on the network adapter P.C. board (Network address

No. setup switch) to set the address No.

<Procedure>

(1) Turn off the power.

Invalid address No. setup from remote controller

No. setup switch

(2) Turn

‡

of the address No. setup switch SW01 to ON side. Accordingly the address No. set on the remote controller is invalidated. (See Fig. 2.)

ON

1 2 3 4 5 6 7

ON side

OFF side

(Numeral side)

(3) Set the network address No. with combination of ON and OFF of

†

to



of the address No. setup switch

SW01. The relation between combination of ON/OFF and address No. is described in Table 2. The right figure (Fig. 3) shows an example of case that the address No. is set to 16.

Address No. setup

SW01

Fig. 2

Setup example of address No. 16

ON

When the network address No. has been changed, be sure to turn of power of the central control remote controller again or to reset the remote controller using the reset hole on the operation panel of the central control remote controller.

1 2 3 4 5 6 7

ON side

OFF side

(Numeral side)

Fig. 3

100

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

20

21

22

17

18

19

23

24

13

14

15

16

10

11

12

29

30

31

25

26

27

28

32

Address No.

01

02

03

07

08

09

04

05

06

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

Table 2 Network address No. setup table (SW01)

52

53

54

49

50

51

55

56

45

46

47

48

42

43

44

61

62

63

57

58

59

60

64

Address No.

33

34

35

39

40

41

36

37

38

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

〇 : ON side

× : OFF side

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

×

Requirement in Service

When using this product as service part to replace the network adapter P.C. board, be sure to match the setup of the setup switch SW01 (Network address No. setup switch) on the network adapter P.C. board with the P.C.

board setup before replacement.

101

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

12-4. Display and Operation of Main Remote Controller and Central Control Remote

Controller

1. Turn on all the power supplies of the air conditioner, and then turn on power of the central control remote controller (Line 16 RBC-SXC1P, Line 64 TCB-SC641). If both power supplies are simultaneously turned on or if they are turned on reversely, the check code [97] may be temporarily displayed on the central remote controller. When settings of connecting cables and central control address are correct, the connected air conditioner is displayed on the central control remote controller.

2. As shown in the following table, there is difference of LCD between main remote controller (RBC-AMT21) and the central control remote controller and also there are restriction and others of operation.

1

2

3

4

5

6

Item

Air volume selection

Air speed selection in FAN mode

Air speed selection in DRY mode

Air direction adjustment

[SPEED] [AUTO]

[SPEED]

[HH]

[H]

[L]

[HH]

Contents

Main remote controller Central control remote controller

[VOL]

[VOL]

[AUTO]

[H]

[M]

[L]

[FIX]

[VOL] [SPEED]

[HH]

[H]

[L]

[SPEED] [AUTO]

[HH]

[H]

[L]

[VOL]

[AUTO]

[H]

[M]

[L]

[AUTO]

[SWING] and air direction adjustment

(No display)

[LOUVER]

Display of air speed selection differs.

In duct type

Cautions

Air speed becomes [H] and [FIX].

When handling main remote controller, [AUTO] is not displayed. If [AUTO] is selected at center side,

[AUTO] is displayed on the main remote controller.

In this time, the air speed becomes [HH].

On the central remote controller, only [AUTO] is displayed. The display on the main remote controller changes to [AUTO] by changing the setup temperature/louver, and the air speed is automatically selected.

On the central remote controller, only [LOUVER] is displayed. It is displayed while flap is swinging, and the setup operation of [LOUVER] becomes selection of swing ON/OFF.

To set up the air direction, use the main remote controller.

In a model type without air direction adjustment

Check button Test run (4 seconds)

Manual operation for

[LOUVER]

Check code display and check reset (3 seconds)

Check code 3-digits display (alphabet + 2-digits numeral)

2-digits display (alphabet or numeral)

The function of long-pushing operation for the check button differs. If the check reset operation on the central remote controller is performed during operation of air conditioner, the operation stops once, and then the operation restarts. (Error of air conditioner is cleared.)

Display of check code differs.

Ex. : Float switch operation

Main side: [P10]

Center side: [0b]

3. When using the remote controller together with the former one (RBC-AM1, AT1), the display on the main remote controller differs if [Last-push priority/Center/Operation Prohibited] is selected from the central control remote controller.

Item

1 Last-push priority

2 Center

3 Operation prohibited

New remote controller

(RBC-AMT21)

(No display)

Contents

Former remote controller

(RBC-AM1, AT1)

(No display)

[CENTER] goes on [CENTER] goes on

[CENTER] flashes

Remarks

All the settings and ON/OFF operations are available.

The setup contents on the central control remote controller are fixed, and only ON/OFF operation and timer setup operation are available on the main remote controller.

The setup contents on the central control remote controller are fixed, and the air conditioner stops.

Operation from the main remote controller is unavailable.

102

– www.ilmalämpöpumput.com

advertisement

Key Features

  • 4-Way Air Discharge Cassette Type
  • Concealed Duct Type
  • High-Wall Type
  • Flexible Type
  • R410A Refrigerant
  • Turbo Fan
  • Energy Consumption Effect Ratio
  • Compressor Thermo
  • Pulse Motor Valve
  • Wired Remote Controller

Frequently Answers and Questions

What are the different types of indoor units available?
The indoor units are available in 4-Way Air Discharge Cassette Type, Concealed Duct Type, High-Wall Type, and Flexible Type.
What is the standard capacity of the units?
The standard capacity of the units varies depending on the model. Refer to the specifications section for detailed information.
What is the sound level of the outdoor unit?
The sound level of the outdoor unit is measured in an anechoic chamber and is typically between 45 and 50 dB(A).