SETUP AT LOCAL SITE AND OTHERS. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E 181 Pages
SETUP AT LOCAL SITE AND OTHERS. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E
Add to My manuals181 Pages
Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.
advertisement
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12. SETUP AT LOCAL SITE AND OTHERS
12-1. Indoor Unit
12-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. When pushing button on the remote controller for 4 seconds or more,
“
TEST
”
is displayed on LC display.
Then push button.
• “
TEST
”
is displayed on LC display during operation of Test Run.
•
During Test Run, temperature cannot be adjusted but air volume can be selected.
•
In heating and cooling operation, a command to fix the Test Run frequency is output.
•
Detection of error is performed as usual. However, do not use this function except case of Test Run because it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after operation has stopped.
3. After a Test Run has finished, push button again and check that [TEST] on LC display has gone off.
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote controller.)
<Wireless remote controller> (Option for 4-way air discharge cassette type)
1. Turn off power of the unit.
Remove the adjuster attached with sensors from the ceiling panel. For removing, refer to the Installation manual attached to the ceiling panel. (Be careful to handle the adjuster because cables are connected to the sensor.) Remove the sensor cover from the adjuster. (1 screw)
2. Change ON of Bit [1: TEST] of the sensor P.C. board switch [S003] to OFF.
Mount the sensor cover and mount the adjuster with sensor to the ceiling panel.
Turn on power of the unit.
3. Push button on the wireless remote controller and select [COOL] or [HEAT] operation mode using
button. (All the display lamps of sensors on the wireless remote controller flash during Test Run.)
•
Do not perform Test Run operation in other modes than [HEAT] / [COOL] mode.
•
Detection of error is performed as usual.
4. After Test Run operation, push button to stop the operation.
5. Turn off power of the unit.
Return Bit [1] of the sensor P.C. board switch [S003] to the original position. (ON
→
OFF)
Mount the adjuster with sensors to the ceiling panel.
Sensor cover
Adjust corner cap
S003
Bit 1 : OFF to ON
ON
Sensor P.C. board
–
92
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-1-2. Setup to Select Function
<Procedure> Use this function while the indoor unit stops.
1
Push
SET
, , and buttons concurrently for 4 seconds or more.
The unit No. displayed at the first time indicates the indoor unit address of the master unit in the group control.
In this time, fan and flap of the selected indoor unit operate.
2
Every pushing button, the indoor unit numbers in the group control are displayed successively.
In this time, fan and flap of the selected indoor unit only operate.
3
Using the set temperature / buttons, set the item code (DN).
4
Using the timer time / buttons, select the setup data.
5
Push
SET
button. (OK if display goes on.)
•
To change the selected indoor unit, proceed to
2
.
•
To change the item to be set, proceed to
3
.
6
Pushing button returns the status to usual stop status.
SET DATA
UNIT No.
R.C.
No.
6
4
1
SET CL
UNIT
5 2
<Operation procedure>
1 2 3 4 5 6
END
3
–
93
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Item No. (DN) table (Selection of function)
DN Item
01 Filter sign lighting time
02 Dirty state of filter
0000 : None
0002 : 2500H
0004 : 10000H
0000 : Standard
Description
0001 : 150H
0003 : 5000H
0005 : Clogged sensor used
0001 : High degree of dirt
(Half of standard time)
0064 : No.64 unit
At shipment
According to type
0000 : Standard
03 Central control address
0001 : No.1 unit
0099 : Unfixed
06 Heating suction temp shift
0000 : No shift
0002 : +2
°
C to to
0001 : +1
°
C
0010 : -10
°
C
(Up to recommendation + 6)
0099 : Unfixed
0002 : +2
°
C
(Floor type 0000: 0
°
C)
0F Cooling only 0000 : Heat pump 0001 : Cooling only
(No display of [AUTO] [HEAT])
0000 : Shared for cooling/ heating
10 Type
11 Indoor unit capacity 0000 : Unfixed
12 Line address
0000 : (Air discharge cassette 1) 0001 : (Air discharge cassette 4) to 0037
0001 : No.1 unit
0001 to 0034
0030 : No.30 unit
According to model type
13 Indoor unit address 0001 : No.1 unit to to
According to capacity type
0099 : Unfixed
14 Group address
0064 : No.64 unit
0001 : Master of group
0099 : Unfixed
0099 : Unfixed
19 Flap type
(Adjustment of air direction)
0000 : Individual
0002 : Sub of group
0000 : No flap
0004 : 4-way
0001 : Swing only According to type
0003 : 3 deg
(Ts±1.5)
1E Temp difference of automatic cooling/ heating mode selection COOL
→
HEAT, HEAT
→
COOL
0000 : 0 deg to 0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
28 Automatic reset of power failure
0000 : None 0001 : Reset
2A Option
0000 : None
2b Thermo output selection (T10
)
2E Option
0000 : Indoor thermo ON 0001 : Output of outdoor comp-ON receiving
0002 : Default
0000: Thermo. ON
0000 : Default
30
31
32
40
Option
Option
Sensor selection
Option
0000 : Body TA sensor 0001 : Remote controller sensor
0000 : Default
0000 : Default
0000 : Body sensor
0003 : Default
5d High ceiling selection
(Air volume selection)
0000 : Standard filter
0001 : Oil guard, Super-long life, Optical regenerative deodorization
0003 : High performance (65%), High performance (90%),
High antibacterial performance (65%)
0000 : Available (Operable) 0001 : Unavailable (Operation prohibited)
0000 : Standard
0000 : Available 60 Timer set
(Wired remote controller)
8b Correction of high heat feeling
0000 : None 0001 : Correction 0000 : None
–
94
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-1-3. Cabling and Setting of Remote Controller Control
2-remote controller control (Controlled by two remote controllers)
One or multiple indoor units are controlled by two remote controllers.
(Max. 2 remote controllers are connectable.)
• 1 indoor unit is controlled by 2
Remote controller
Remote controller switch (Master) switch (Sub)
remote controllers
Sold separately Sold separately
A B
Indoor unit
1 2 3
Remote controller cables (Procured locally)
Terminal block for remote controller cables
1 2 3
Outdoor u nit
(Setup method)
One or multiple indoor units are controlled by two remote controllers.
(Max. 2 remote controllers are connectable.)
Rear side of remote controller P.C. board
<Wired remote controller>
How to set wired remote controller to sub remote controller
Insert the remote controller address connector provided on the rear side of the remote controller switch P.C. board into Sub in exchange for Master.
Remote controller address connector
Master remote controller
Sub remote controller
<Wireless remote controller>
How to set wireless remote controller to sub remote controller
Change OFF of Bit [3: Remote controller Sub/
Master] of switch S003 to ON.
Sensor cover
Adjust corner cap
[Operation]
1. The operation contents can be changed by Last-push-priority.
2. Use a timer on either Master remote controller or Sub remote controller.
–
95
– www.ilmalämpöpumput.com
S003
Bit 1 : OFF to ON
ON
Sensor P.C. board
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-1-4. Monitor Function of Remote Controller Switch
n
Call of sensor temperature display
<Contents>
Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling the service monitor mode from the remote controller.
<Procedure>
1
Push + buttons simultaneously for 4 seconds or more to call the service monitor mode.
The service monitor goes on, the master indoor unit
No. is displayed, and then temperature of the item
code
00
is displayed.
2
Push the temperature setup / buttons to select the sensor No. (Item code) of the sensor to be monitored.
The sensor numbers are described below:
4
1
SET DATA
SET CL
UNIT No.
R.C.
No.
UNIT
3
<Operation procedure>
1 2 3 4
Returned to usual display
2
Indoor unit data
Item code
00
01
02
03
04
Data name
Room temp (under control) *1
Room temp (remote controller)
Indoor suction temp
Indoor coil temp (TCJ)
Indoor coil temp (TC)
Outdoor unit data
Item code
60
61
62
63
64
65
Data name
Heat exchanger temp TE
Outside temp TO
Discharge temp TD
Suction temp TS
—
Heat sink temp THS
*1 Only master unit in group control
3
The temperature of indoor units and outdoor unit in a group control can be monitored by pushing
button to select the indoor unit to be monitored.
4
Pushing button returns the display to usual display.
–
96
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy n
Calling of error history
<Contents>
The error contents in the past can be called.
<Procedure>
1
Push + buttons simultaneously for 4 seconds or more to call the service check mode.
Service Check goes on, the item code
01
is displayed, and then the content of the latest alarm is displayed. The number and error contents of the indoor unit in which an error occurred are displayed.
2
In order to monitor another error history, push the set temperature / buttons to change the error history No. (Item code).
Item code
01
(Latest)
→
Item code
04
(Old)
NOTE : Four error histories are stored in memory.
3
Pushing button returns the display to usual display.
<Requirement>
Do not push button, otherwise all the error histories of the indoor unit are deleted.
3
SET DATA
UNIT No.
R.C.
No.
SET CL
UNIT
1
<Operation procedure>
1 2 3
Returned to usual display
2
(Group control operation)
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.
The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to setting on the remote controller.
<System example>
OUT OUT OUT
IN
1-1
IN
Master
2-1
IN
3-1
Remote controller
OUT
IN
4-1
OUT
IN
7-1
Max. 8 units
(1) Display range on remote controller
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the master unit is reflected on the remote controller.
(2) Address setup
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic address.
If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the system is rebooted and the automatic address setting will be judged again.
1) Connect 3 In/Out cables surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the unit No. is not duplicated with one of another unit.
–
97
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-2. Network Adapter
Model name: TCB-PCNT20E
12-2-1. Function
A network adapter is an optional P.C. board to connect the indoor unit to AI net (Central control remote controller).
12-2-2. Microcomputer Block Diagram
Remote controller
Indoor unit
Optional communication P.C. board
CN41
Indoor control
P.C. board
CN309
AC220-
240V
CN02
Remote controller communication circuit
MCU
Terminal block
(A.B)
Power transformer
AC14V
CN01
5V power supply
5V
Network address setup switch
AI-NET communication circuit
CN03
Terminal block
(X.Y)
EEPROM
Central control remote controller
Network
Communication units: Total 64 units
Communication distance: 1km
12-2-3. Network Address Setup Switch (SW01)
4
5
6
7
8
No.
1
2
3
LSB
Central control address
MSB
Item
Setup availability from remote controller
Setup contents
1 2 3 4 5 6
××× × × ×
: No.1 unit
〇×× × × × : No.2 unit
:
×
〇
: Switch OFF
: Switch OFF
〇〇〇 〇 〇 ×
: No.63 unit
〇〇〇 〇 〇 〇 : No.64 unit
Switch OFF : Setup available from remote controller
Switch ON : Setup unavailable from remote controller
12-2-4. LED Display Specification
LED No.
D01 (Red)
D02 (Red)
D03 (Red)
D04 (Red)
Function
Communication status: Remote controller
Communication status: Center
Operation status of air conditioner
Air conditioner error
Go on
During communication
During communication
Running
Error
Go off
No communication (including communication error)
No communication (including communication error)
Stop
Normal
* For positions of LED, refer to P.C. board external view.
– 98 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-2-5. Communication Cable Specifications
No.
1
2
Communication circuit
Remote controller communication side
AI NET side
Cable
Cable type
Cable dia.
Cable length
Cable
Cable type
Cable dia.
Cable length
Communication cable specifications
Neutral 2-cable type
CVV (JIS C3401) Controlling vinyl insulation vinyl seal cable
VCTF (JIS C3306) Vinyl cab tire round type cord
VCT (JIS C3401) 600V vinyl cab tire cable
VVR (JIS C3401) Vinyl insulation seal cable round type
MVVS Cable with net shielding for instrumentation
CPEVS Shielded polyethylene insulation vinyl seal cable
0.5 to 2.0 mm²
Total cable length Max. 500m
(Up to 400m when there is wireless remote controller in group)
Neutral 2-cable type
MVVS Cable with net shielding for instrumentation
1.25 mm²
≤
500 m, 2.0 mm²
≤
1 km
Total cable length : Up to 500m when using 1.25mm² cable,
Up to 1000m when using 2.0mm² cable
12-2-6. Cable Connection
<Network cable connection>
• Install a network adapter per 1 group of the group control (including single unit control). Also install a network adapter to one of the indoor units in the group control.
Central control remote controller
X Y
Network adapter
Indoor unit
Indoor unit
Indoor control
P.C. board
A B
Indoor control
P.C. board
A B
Indoor unit
Indoor control
P.C. board
A B
Indoor unit
Indoor control
P.C. board
A B
X Y
Network adapter
Indoor unit
Indoor unit
Indoor control
P.C. board
A B
Indoor control
P.C. board
A B
Remote controller
Connectable indoor units per group: Up to 8 units
(1-remote controller system*)
* In case of 2-remote controllers system,
the connectable indoor units are up to 7 units.
– 99 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-3. How to Set an Address Number
When connecting indoor units to the central control remote controller by using a network adapter, it is required to set up a network address No.
•
The network address No. should be agreed with the line No. of the central control remote controller.
•
When the unit was shipped from the factory, the network address has been set to 1.
The following two methods to set the network address are provided.
1. How to set from the remote controller at indoor unit side
* This method is effective only when
of set switch SW01 on the network adapter P.C. board is turned off.
<Procedure> Set the network address while the unit stops.
1
Push + buttons for 4 seconds or more.
In the group control, the unit No
RLL
is displayed, and then all the indoor units in the group control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)
(Keep status of
RLL
display without pushing button.)
3
For the individual remote controller which is not included in a group control, the line address and the indoor unit address are displayed.
2
Specify the item code
03
using the temperature setup /
buttons.
3
Using the timer time / buttons, select the setup data.
1
5
SET DATA
SET CL
4
Fig. 1
UNIT No.
R.C.
No.
UNIT
Table 1
The setup data are shown in the right table (Table 1).
4
Push
SET
button. (OK if display goes on)
•
To change the item to be set, return to
2
.
5
Push button.
The status returns to the usual stop status.
Setup data
0001
0002
0003
:
0064
0099
Network address No.
1
2
3
:
64
Unset (Setup at shipment from factory)
2
2. How to set by the switch on the network adapter P.C. board
When the remote controller cannot be found or when you don
’ t want to change setting of the network address
No. from the remote controller, use the setup switch SW01 on the network adapter P.C. board (Network address
No. setup switch) to set the address No.
<Procedure>
(1) Turn off the power.
Invalid address No. setup from remote controller
No. setup switch
(2) Turn
of the address No. setup switch SW01 to ON side. Accordingly the address No. set on the remote controller is invalidated. (See Fig. 2.)
ON
1 2 3 4 5 6 7
ON side
OFF side
(Numeral side)
(3) Set the network address No. with combination of ON and OFF of
to
of the address No. setup switch
SW01. The relation between combination of ON/OFF and address No. is described in Table 2. The right figure (Fig. 3) shows an example of case that the address No. is set to 16.
Address No. setup
SW01
Fig. 2
Setup example of address No. 16
ON
When the network address No. has been changed, be sure to turn of power of the central control remote controller again or to reset the remote controller using the reset hole on the operation panel of the central control remote controller.
1 2 3 4 5 6 7
ON side
OFF side
(Numeral side)
Fig. 3
–
100
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
20
21
22
17
18
19
23
24
13
14
15
16
10
11
12
29
30
31
25
26
27
28
32
Address No.
01
02
03
07
08
09
04
05
06
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
〇
×
〇
×
×
〇
×
①
×
〇
〇
×
〇
×
×
×
×
〇
×
〇
〇
〇
〇
×
×
〇
〇
〇
〇
×
〇
×
×
〇
×
×
〇
〇
〇
×
②
×
×
×
〇
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
⑥
×
×
×
×
〇
〇
〇
〇
〇
〇
〇
〇
〇
×
×
〇
〇
〇
〇
〇
〇
〇
×
×
×
×
×
×
×
×
×
×
⑤
×
×
×
×
×
〇
〇
×
×
×
×
×
×
〇
〇
×
〇
〇
〇
〇
〇
〇
〇
〇
〇
×
〇
〇
〇
×
×
×
④
×
×
×
×
〇
×
×
〇
〇
〇
×
×
×
〇
〇
×
〇
〇
〇
×
×
〇
×
〇
〇
〇
×
×
×
×
×
〇
③
×
×
〇
〇
Table 2 Network address No. setup table (SW01)
52
53
54
49
50
51
55
56
45
46
47
48
42
43
44
61
62
63
57
58
59
60
64
Address No.
33
34
35
39
40
41
36
37
38
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
×
〇
〇
×
〇
×
×
〇
×
①
×
〇
〇
×
〇
×
×
×
×
〇
×
〇
〇
〇
〇
×
×
〇
〇
〇
〇
×
〇
×
×
〇
×
×
〇
〇
〇
×
②
×
×
×
〇
×
〇
〇
×
×
×
×
×
×
〇
〇
×
〇
〇
〇
〇
〇
〇
〇
〇
〇
×
〇
〇
〇
×
×
×
④
×
×
×
×
〇 : ON side
× : OFF side
〇
〇
〇
〇
〇
〇
〇
〇
〇
×
×
〇
〇
〇
〇
〇
〇
〇
×
×
×
×
×
×
×
×
×
×
⑤
×
×
×
×
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
〇
⑥
〇
〇
〇
〇
〇
×
×
〇
〇
〇
×
×
×
〇
〇
×
〇
〇
〇
×
×
〇
×
〇
〇
〇
×
×
×
×
×
〇
③
×
×
〇
〇
Requirement in Service
When using this product as service part to replace the network adapter P.C. board, be sure to match the setup of the setup switch SW01 (Network address No. setup switch) on the network adapter P.C. board with the P.C.
board setup before replacement.
–
101
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-4. Display and Operation of Main Remote Controller and Central Control Remote
Controller
1. Turn on all the power supplies of the air conditioner, and then turn on power of the central control remote controller (Line 16 RBC-SXC1P, Line 64 TCB-SC641). If both power supplies are simultaneously turned on or if they are turned on reversely, the check code [97] may be temporarily displayed on the central remote controller. When settings of connecting cables and central control address are correct, the connected air conditioner is displayed on the central control remote controller.
2. As shown in the following table, there is difference of LCD between main remote controller (RBC-AMT21) and the central control remote controller and also there are restriction and others of operation.
1
2
3
4
5
6
Item
Air volume selection
Air speed selection in FAN mode
Air speed selection in DRY mode
Air direction adjustment
[SPEED] [AUTO]
[SPEED]
[HH]
[H]
[L]
[HH]
Contents
Main remote controller Central control remote controller
[VOL]
[VOL]
[AUTO]
[H]
[M]
[L]
[FIX]
[VOL] [SPEED]
[HH]
[H]
[L]
[SPEED] [AUTO]
[HH]
[H]
[L]
[VOL]
[AUTO]
[H]
[M]
[L]
[AUTO]
[SWING] and air direction adjustment
(No display)
[LOUVER]
Display of air speed selection differs.
In duct type
Cautions
Air speed becomes [H] and [FIX].
When handling main remote controller, [AUTO] is not displayed. If [AUTO] is selected at center side,
[AUTO] is displayed on the main remote controller.
In this time, the air speed becomes [HH].
On the central remote controller, only [AUTO] is displayed. The display on the main remote controller changes to [AUTO] by changing the setup temperature/louver, and the air speed is automatically selected.
On the central remote controller, only [LOUVER] is displayed. It is displayed while flap is swinging, and the setup operation of [LOUVER] becomes selection of swing ON/OFF.
To set up the air direction, use the main remote controller.
In a model type without air direction adjustment
Check button Test run (4 seconds)
Manual operation for
[LOUVER]
Check code display and check reset (3 seconds)
Check code 3-digits display (alphabet + 2-digits numeral)
2-digits display (alphabet or numeral)
The function of long-pushing operation for the check button differs. If the check reset operation on the central remote controller is performed during operation of air conditioner, the operation stops once, and then the operation restarts. (Error of air conditioner is cleared.)
Display of check code differs.
Ex. : Float switch operation
Main side: [P10]
Center side: [0b]
3. When using the remote controller together with the former one (RBC-AM1, AT1), the display on the main remote controller differs if [Last-push priority/Center/Operation Prohibited] is selected from the central control remote controller.
Item
1 Last-push priority
2 Center
3 Operation prohibited
New remote controller
(RBC-AMT21)
(No display)
Contents
Former remote controller
(RBC-AM1, AT1)
(No display)
[CENTER] goes on [CENTER] goes on
[CENTER] flashes
Remarks
All the settings and ON/OFF operations are available.
The setup contents on the central control remote controller are fixed, and only ON/OFF operation and timer setup operation are available on the main remote controller.
The setup contents on the central control remote controller are fixed, and the air conditioner stops.
Operation from the main remote controller is unavailable.
–
102
– www.ilmalämpöpumput.com
advertisement
Key Features
- 4-Way Air Discharge Cassette Type
- Concealed Duct Type
- High-Wall Type
- Flexible Type
- R410A Refrigerant
- Turbo Fan
- Energy Consumption Effect Ratio
- Compressor Thermo
- Pulse Motor Valve
- Wired Remote Controller
Frequently Answers and Questions
What are the different types of indoor units available?
What is the standard capacity of the units?
What is the sound level of the outdoor unit?
Related manuals
advertisement
Table of contents
- 3 SPECIFICATIONS
- 12 AIR DUCTING WORK
- 13 CONSTRUCTION VIEWS (EXTERNAL VIEWS)
- 20 SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
- 22 WIRING DIAGRAM
- 28 SPECIFICATIONS OF ELECTRICAL PARTS
- 30 REFRIGERANT R410A
- 38 CONTROL BLOCK DIAGRAM
- 48 CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
- 65 TROUBLESHOOTING
- 88 REPLACEMENT OF SERVICE INDOOR P.C. BOARD
- 92 SETUP AT LOCAL SITE AND OTHERS
- 103 ADDRESS SETUP
-
108
TROUBLESHOOTING
- 135 DETACHMENTS
- 168 EXPLODED VIEWS AND PARTS LIST