Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
13. ADDRESS SETUP
13-1. Address Setup
<Address setup procedure>
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted while automatic address works. (Approx. 4 to 5 minutes)
Setup of line address of outdoor unit, indoor unit address, and group address
Completion of cabling work
Do you arbitrarily set the indoor unit address?
YES
(MANUAL)
Connect one remote controller with one indoor unit (1 : 1) tentatively with communication cable.
NO
NO
Is refrigerant line 1 line?
YES
NO
Is group control performed?
YES (To AUTO address mode)
Do you change setting after automatic setting at the first time?
YES
Turn on power of outdoor unit.
Set to all indoor units one by one.
Turn on power of outdoor unit.
Turn on power of outdoor unit.
After completion of address setup, change is to arbitral address/group manually.
address finishes within
4 to 5 minutes.
END
•
When the following addresses are not stored in the neutral memory (IC10) on the indoor P.C. board, a test run operation cannot be performed. (Unfixed data at shipment from factory)
Line address
Indoor unit address
Group address
Item code
12
13
14
Data at shipment
0099
0099
0099
Setup data range
0001 (No. 1 unit) to 0030 (No. 30 unit)
0001 (No. 1 unit) to 0030 (No. 30 unit)
Max. value of indoor units in the identical refrigerant line (Double twin = 4)
0000 : Individual (Indoor units which are not controlled in a group)
0001 : Master unit (1 indoor unit in group control)
0002 : Sub unit (Indoor units other than master unit in group control)
–
103
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
13-2. Address Setup & Group Control
<Terminology>
Indoor unit No.
: N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64)
Group address : 0 = Individual (Not group control)
1 = Master unit in group control
2 = Sub unit in group control
Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from the remote controllers and sub indoor units. (* It has no relation with an indoor unit which communicates serially with the outdoor units.)
The operation mode and setup temperature range are displayed on the remote controller
LCD. (Except sir direction adjustment of flap)
Sub unit (= 2) : Indoor units other than master unit in group operation
Basically, sub units do not send/receive signals to/from the remote controllers.
(Except errors and response to demand of service data)
13-2-1. System configuration
1. Single 2. Single group operation
Outdoor
Indoor
1-1
Individual
(Master/Sub)
Remote controller
2-1
Sub
1-1
Sub
4-1
Master
3-1
Sub
8-1
Sub
13-2-2. Automatic address example from unset address (No miscabling)
1. Standard (One outdoor unit)
1) Single
2) Gr operation
(Multiple outdoor units = Miltiple indoor units only with serial communication)
1-1
Individual
(Master/Sub)
2-1
Sub
1-1
Sub
4-1
Master
8-1
Sub
Max. 8 units
Only turning on source power supply (Automatic completion)
–
104
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
13-3. Address Setup
In case that addresses of the indoor units will be determined prior to piping work after cabling work
(Manual setting from remote controller)
<Address setup procedure>
•
Set an indoor unit per a remote controller.
•
Turn on power supply.
1
Push
SET
+ + buttons simultaneously for 4 seconds or more.
2
(
←
Line address) Using the temperature setup
/ buttons, set
12
to the item code.
3
Using timer time / buttons, set the line address.
4
Push
SET
button. (OK when display goes on.)
5
(
←
Indoor unit address) Using the temperature setup
/ buttons, set
13
to the item code.
6
Using timer time / buttons, set 1 to the line address.
7
Push
SET
button. (OK when display goes on.)
8
(
←
Group address) Using the temperature setup
/ buttons, set
14
to the item code.
9
Using timer time / buttons, set
0000
to Individual,
0001
to Master unit, and
0002
to sub unit.
10
Push
SET
button. (OK when display goes on.)
11
Push button.
Setup completes.
(The status returns to the usual stop status.)
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Line address 1
Indoor unit address 1
Group address 1
Group address
Individual : 0000
Master unit : 0001
Sub unit : 0002
OUT
IN
2
1
2
OUT
IN
For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit cable.
In case of group control
SET DATA
UNIT No.
R.C.
No.
3, 6, 9
END
1
11
SET CL
UNIT
2, 5, 8
4, 7, 10
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
END
–
105
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy n
Confirmation of indoor unit No. position
1. To know the indoor unit addresses though position of the indoor unit body is recognized
•
In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
1
Push button if the unit stops.
2
Push button.
Unit No.
1-1
is displayed on LCD.
(It disappears after several seconds.)
The displayed unit No. indicate line address and indoor unit address.
(When other indoor units are connected to the identical remote controller (Group control unit), other unit numbers are also displayed every pushing button.
SET CL
UNIT No.
UNIT
2
CODE No.
<Operation procedure>
1 2
END
1
Operation
2. To know the position of indoor unit body by address
•
To confirm the unit No. in the group control
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are successively displayed, and fan, flap, and drain pump of the corresponding indoor unit are turned on. (Follow to the procedure during operation)
1
Push and buttons simultaneously for 4 seconds or more.
•
Unit No.
ALL
is displayed.
•
Fans and flaps of all the indoor units in the group control operate.
2
Every pushing button, the unit numbers in the group control are successively displayed.
•
The unit No. displayed at the first time indicates the master unit address.
•
Fan and flap of the selected indoor unit only operate.
3
Push button to finish the procedure. All the indoor units in the group control stop.
1
3
SET DATA
SET CL
<Operation procedure>
1 2 3
END
UNIT No.
R.C.
No.
UNIT
2
–
106
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
RAV-SM800AT-E LED display when SW800 : Bit 1, 2, 3, 4 OFF
•
When multiple errors are detected, the latest error is displayed.
•
While LED displays
〇
(go on), there is the main cause of error in control at CDB side and it stops abnormally.
•
While LED displays
◎
(flash), there is the main cause of error in control at IPDU side and it stops abnormally.
•
For an error in case thermo operation, the communication is interrupted on the serial circuit. If continuing the case thermo operation, serial sending to the indoor unit is interrupted and a serial communication error is output.
CDB side
No.
Item
4
5
6
1
2
3
7
TE sensor error
TD sensor error
TS sensor error
TO sensor error
Discharge temp error
Out DC fan error
Communication error between IPDU
(Abnormal stop)
8 High-pressure release operation
IPDU side
9
10
11
12
13
14
15
16
EEPROM error
Communication error between IPDU
(No abnormal stop)
G-Tr short-circuit protection
Detection circuit error
Current sensor error
Phase missing detection
Comp lock error
Comp breakdown
〇
: Go on,
●
: Go off,
◎
: Flash (5 Hz)
Table A
Check code
B type
1B
1E
1A
18
19
18
1C
21
—
—
—
14
16
17
17
1D
1F
LED display
D800 D801 D802 D803
(Red) (Yellow) (Yellow) (Yellow)
〇
〇
●
●
●
〇
●
〇
●
〇
〇
〇
●
●
〇
●
〇
〇
●
●
●
●
●
●
〇 ● ● 〇
●
〇
●
◎
●
◎
●
●
◎
〇
〇
●
●
◎
◎
●
●
●
●
●
〇
●
●
●
●
◎
◎
〇
〇
〇
●
●
●
◎
●
●
–
107
– www.ilmalämpöpumput.com