ADDRESS SETUP. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E

Add to My manuals
181 Pages

Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.

advertisement

ADDRESS SETUP. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E | Manualzz

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

13. ADDRESS SETUP

13-1. Address Setup

<Address setup procedure>

When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted while automatic address works. (Approx. 4 to 5 minutes)

Setup of line address of outdoor unit, indoor unit address, and group address

Completion of cabling work

Do you arbitrarily set the indoor unit address?

YES

(MANUAL)

Connect one remote controller with one indoor unit (1 : 1) tentatively with communication cable.

NO

NO

Is refrigerant line 1 line?

YES

NO

Is group control performed?

YES (To AUTO address mode)

Do you change setting after automatic setting at the first time?

YES

Turn on power of outdoor unit.

Set to all indoor units one by one.

Turn on power of outdoor unit.

Turn on power of outdoor unit.

After completion of address setup, change is to arbitral address/group manually.

address finishes within

4 to 5 minutes.

END

When the following addresses are not stored in the neutral memory (IC10) on the indoor P.C. board, a test run operation cannot be performed. (Unfixed data at shipment from factory)

Line address

Indoor unit address

Group address

Item code

12

13

14

Data at shipment

0099

0099

0099

Setup data range

0001 (No. 1 unit) to 0030 (No. 30 unit)

0001 (No. 1 unit) to 0030 (No. 30 unit)

Max. value of indoor units in the identical refrigerant line (Double twin = 4)

0000 : Individual (Indoor units which are not controlled in a group)

0001 : Master unit (1 indoor unit in group control)

0002 : Sub unit (Indoor units other than master unit in group control)

103

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

13-2. Address Setup & Group Control

<Terminology>

Indoor unit No.

: N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64)

Group address : 0 = Individual (Not group control)

1 = Master unit in group control

2 = Sub unit in group control

Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from the remote controllers and sub indoor units. (* It has no relation with an indoor unit which communicates serially with the outdoor units.)

The operation mode and setup temperature range are displayed on the remote controller

LCD. (Except sir direction adjustment of flap)

Sub unit (= 2) : Indoor units other than master unit in group operation

Basically, sub units do not send/receive signals to/from the remote controllers.

(Except errors and response to demand of service data)

13-2-1. System configuration

1. Single 2. Single group operation

Outdoor

Indoor

1-1

Individual

(Master/Sub)

Remote controller

2-1

Sub

1-1

Sub

4-1

Master

3-1

Sub

8-1

Sub

13-2-2. Automatic address example from unset address (No miscabling)

1. Standard (One outdoor unit)

1) Single

2) Gr operation

(Multiple outdoor units = Miltiple indoor units only with serial communication)

1-1

Individual

(Master/Sub)

2-1

Sub

1-1

Sub

4-1

Master

8-1

Sub

Max. 8 units

Only turning on source power supply (Automatic completion)

104

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

13-3. Address Setup

In case that addresses of the indoor units will be determined prior to piping work after cabling work

(Manual setting from remote controller)

<Address setup procedure>

Set an indoor unit per a remote controller.

Turn on power supply.

1

Push

SET

+ + buttons simultaneously for 4 seconds or more.

2

(

Line address) Using the temperature setup

/ buttons, set

12

to the item code.

3

Using timer time / buttons, set the line address.

4

Push

SET

button. (OK when display goes on.)

5

(

Indoor unit address) Using the temperature setup

/ buttons, set

13

to the item code.

6

Using timer time / buttons, set 1 to the line address.

7

Push

SET

button. (OK when display goes on.)

8

(

Group address) Using the temperature setup

/ buttons, set

14

to the item code.

9

Using timer time / buttons, set

0000

to Individual,

0001

to Master unit, and

0002

to sub unit.

10

Push

SET

button. (OK when display goes on.)

11

Push button.

Setup completes.

(The status returns to the usual stop status.)

(Example of 2-lines cabling)

(Real line: Cabling, Broken line: Refrigerant pipe)

Line address 1

Indoor unit address 1

Group address 1

Group address

Individual : 0000

Master unit : 0001

Sub unit : 0002

OUT

IN

2

1

2

OUT

IN

For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit cable.

In case of group control

SET DATA

UNIT No.

R.C.

No.

3, 6, 9

END

1

11

SET CL

UNIT

2, 5, 8

4, 7, 10

<Operation procedure>

1 2 3 4 5 6 7 8 9 10 11

END

105

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy n

Confirmation of indoor unit No. position

1. To know the indoor unit addresses though position of the indoor unit body is recognized

In case of individual operation (Wired remote controller : indoor unit = 1 : 1)

(Follow to the procedure during operation)

<Procedure>

1

Push button if the unit stops.

2

Push button.

Unit No.

1-1

is displayed on LCD.

(It disappears after several seconds.)

The displayed unit No. indicate line address and indoor unit address.

(When other indoor units are connected to the identical remote controller (Group control unit), other unit numbers are also displayed every pushing button.

SET CL

UNIT No.

UNIT

2

CODE No.

<Operation procedure>

1 2

END

1

Operation

2. To know the position of indoor unit body by address

To confirm the unit No. in the group control

(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)

<Procedure>

The indoor unit numbers in the group control are successively displayed, and fan, flap, and drain pump of the corresponding indoor unit are turned on. (Follow to the procedure during operation)

1

Push and buttons simultaneously for 4 seconds or more.

Unit No.

ALL

is displayed.

Fans and flaps of all the indoor units in the group control operate.

2

Every pushing button, the unit numbers in the group control are successively displayed.

The unit No. displayed at the first time indicates the master unit address.

Fan and flap of the selected indoor unit only operate.

3

Push button to finish the procedure. All the indoor units in the group control stop.

1

3

SET DATA

SET CL

<Operation procedure>

1 2 3

END

UNIT No.

R.C.

No.

UNIT

2

106

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

RAV-SM800AT-E LED display when SW800 : Bit 1, 2, 3, 4 OFF

When multiple errors are detected, the latest error is displayed.

While LED displays

(go on), there is the main cause of error in control at CDB side and it stops abnormally.

While LED displays

(flash), there is the main cause of error in control at IPDU side and it stops abnormally.

For an error in case thermo operation, the communication is interrupted on the serial circuit. If continuing the case thermo operation, serial sending to the indoor unit is interrupted and a serial communication error is output.

CDB side

No.

Item

4

5

6

1

2

3

7

TE sensor error

TD sensor error

TS sensor error

TO sensor error

Discharge temp error

Out DC fan error

Communication error between IPDU

(Abnormal stop)

8 High-pressure release operation

IPDU side

9

10

11

12

13

14

15

16

EEPROM error

Communication error between IPDU

(No abnormal stop)

G-Tr short-circuit protection

Detection circuit error

Current sensor error

Phase missing detection

Comp lock error

Comp breakdown

: Go on,

: Go off,

: Flash (5 Hz)

Table A

Check code

B type

1B

1E

1A

18

19

18

1C

21

14

16

17

17

1D

1F

LED display

D800 D801 D802 D803

(Red) (Yellow) (Yellow) (Yellow)

〇 ● ● 〇

107

– www.ilmalämpöpumput.com

advertisement

Key Features

  • 4-Way Air Discharge Cassette Type
  • Concealed Duct Type
  • High-Wall Type
  • Flexible Type
  • R410A Refrigerant
  • Turbo Fan
  • Energy Consumption Effect Ratio
  • Compressor Thermo
  • Pulse Motor Valve
  • Wired Remote Controller

Frequently Answers and Questions

What are the different types of indoor units available?
The indoor units are available in 4-Way Air Discharge Cassette Type, Concealed Duct Type, High-Wall Type, and Flexible Type.
What is the standard capacity of the units?
The standard capacity of the units varies depending on the model. Refer to the specifications section for detailed information.
What is the sound level of the outdoor unit?
The sound level of the outdoor unit is measured in an anechoic chamber and is typically between 45 and 50 dB(A).

Related manuals