TROUBLESHOOTING <WALL TYPE>. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E

Add to My manuals
181 Pages

Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.

advertisement

TROUBLESHOOTING <WALL TYPE>. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E | Manualzz

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14. TROUBLESHOOTING <WALL TYPE>

14-1. Summary of Troubleshooting

<Wired remote controller type>

1. Before troubleshooting

1) Required tools/instruments

+ and

screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch

Tester, thermometer, pressure gauge, etc.

2) Confirmation points before check



The following operations are normal.

a) Compressor does not operate.

Is not 3-minutes delay (3 minutes after compressor OFF)?

Does not thermostat turn off?

Does not timer operate during fan operation?

Is not detected an overflow error?

Is not outside high-temperature operation controlled in heating operation?

b) Indoor fan does not rotate.

Does not cool air discharge preventive control work in heating operation?

c) Outdoor fan does not rotate or air speed changes.

Does not high-temperature release operation control work in heating operation?

Does not outside low-temperature operation control work in cooling operation?

Is not defrost operation performed?

d) ON/OFF operation cannot be performed from remote controller.

Is not during emergency operation?

Is not the control operation performed from outside/remote side?

‚

Did you return the cabling to the initial positions?

ƒ

Are connecting cables of indoor unit and remote controller correct?

2. Troubleshooting procedure

When a trouble occurred, check the parts along with the following procedure.

Trouble

Confirmation of check code display

Check defective position and parts.

NOTE :

For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the remote controller and the signal line to shield cables.

108

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

(a) Outline of Judgment

A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.

<Judgment by flashing display on the indoor unit display part>

The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part.

Remote controller code

Block display

Operation lamp display flashes. (1Hz)

00 Operation lamp display flashes. (5Hz)

01

02

03

Operation/timer lamp displays flash. (5Hz)

Operation/defrost lamp displays flash. (5Hz)

Operation/timer/defrost lamp displays flash. (5Hz)

——

Contents of self-diagnosis

Power failure (In power ON)

Indoor P.C. board

Inter-unit cables/transmission system

Outdoor P.C. board

Cycle system, etc.

——

Check code

——

0b to 0F, 11, 12, b5, b6

04

14 to 19, 1A, 1C

1d, 1E, 1F, 21

1b, 8b

(b) Self-diagnosis by check code on the remote controller

Refer to

Judgment of error mode by check code on the remote controller

.

<Wireless remote controller type>

1. Before troubleshooting

1) Required tools/instruments

+ and

screwdrivers, spanners, radio cutting pliers, nippers, etc.

Tester, thermometer, pressure gauge, etc.

2) Confirmation points before check



The following operations are normal.

a) Compressor does not operate.

Is not 3-minutes delay (3 minutes after compressor OFF)?

Does not thermostat turn off?

Does not timer operate during fan operation?

Is not outside high-temperature operation controlled in heating operation?

b) Indoor fan does not rotate.

Does not cool air discharge preventive control work in heating operation?

c) Outdoor fan does not rotate or air volume changes.

Does not high-temperature release operation control work in heating operation?

Does not outside low-temperature operation control work in cooling operation?

Is not defrost operation performed?

d) ON/OFF operation cannot be performed from remote controller.

Is not forced operation performed?

Is not the control operation performed from outside/remote side?

‚

Did you return the cabling to the initial positions?

ƒ

Are connecting cables between indoor unit and receiving unit correct?

109

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

2. Troubleshooting procedure

When a trouble occurred, check the parts along with the following procedure.

Trouble

Confirmation of check code by service mode

Check defective position and parts.

NOTE :

For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cable of the signal line to shield cable.

(a) Outline of Judgment

A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.

<Judgment by flashing display on the indoor unit display part>

The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part

(Sensors).

Remote controller code

Block display

Operation lamp display flashes. (1Hz)

00

01

Operation lamp display flashes. (5Hz)

Operation/timer lamp displays flash. (5Hz)

02

03

Contents of self-diagnosis

Power failure (In power ON)

Indoor P.C. board

Inter-unit cables/transmission system

Operation/defrost lamp displays flash. (5Hz) Outdoor P.C. board

Operation/timer/defrost lamp displays flash. (5Hz)

——

Cycle system, etc.

——

Check code

——

0b to 0F, 11, 12, b5, b6

04

14 to 19, 1A, 1C

1d, 1E, 1F, 21

1b, 8b

(b) Self-diagnosis by check code on the remote controller

In the wireless type models, the self-diagnosis for the protective circuit operation is performed by handling the remote controller. First change the operation mode of the remote controller, and then perform the selfdiagnosis by the displayed contents of the remote controller and the existence of operation lamp flashing

(5Hz) and buzzer sound (Pi, Pi, Pi). During self-diagnosis operation, the timer lamp usually flashes (5Hz).



Selection of remote controller operation mode

1) Selection of service mode

Push the select button at lower side of the wireless remote controller with a tip of pencil, etc. for approx. 3 seconds or more. In this time, check that [00] is displayed on the room temp. display part and other displays go off.

2) Selection of normal mode

Push the reset button at lower side of the wireless remote controller with a tip of pencil, etc. In this time, check that [

AM

] display on the time display part flashes.

‚

Cautions in service

1) After service work, be sure to push the reset button to return the mode to normal mode.

2) After service by the check codes, turn off the power switch once and then turn on the switch to return the stored memory in microcomputer to the initial status.

110

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

(c) Self-diagnosis with remote controller

With the indoor unit control, self-diagnosis of protective circuit action can be done by turning the remote controller operation into service mode, operating the remote controller, observing the remote controller indicators and checking whether TIMER lamp flashes (5 Hz).

NOTE :

• To perform this self-diagnosis, the remote controller with the service code of 43069666 is required.

<How to select remote control operation mode>

1. Selecting service mode

Push the switch button provided on rear bottom of the wireless remote control with a tip of pencil for more than 3 seconds. Make sure the setting temperature

“ ”

is displayed on the display and other display is turned off.

2. Selecting ordinary mode

Push the all clear button (ACL) on the rear bottom of the wireless remote controller with a tip of pencil for more than 3 seconds. Make sure the operation mode display, wind volume display, clock display and setting temperature display are turned on and

:

of the clock display is flashing.

<Cautions when doing service>

1. After completion of servicing, always push the all clear (ACL) button to return the operation mode to the normal mode.

2. After completion of servicing by the check code, turn off the power once and then turn on the power to reset memorized contents of the microcomputer to the initial status.

All clear button

Switch for selecting service mode

ACL CLOCK

ACL CLOCK

(Rear bottom of remote control)

Rear bottom cover

111

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

<Self-diagnosis by check codes>

1. The self-diagnosis by the check codes is conducted under the block displays.

2. Remote controller key operation under the service mode is conducted by ON/OFF or TEMP. The remote controller display by each key operation is varied as shown below. Two digit number is displayed in a hexadecimal number.

3. The self-diagnosis by the check codes is conducted with procedures shown below.

1) Enter the service mode and make sure the off timer display of the remote controller shows

“ ”

.

2) Operate the

ON/OFF

key and make sure the timer lamp on the display section is flashing (5 Hz).

3) At the same time, also make sure the operation lamp is also flashing. This shows that the protection circuit on the indoor P.C. board is working.

4) Operate the TEMP. key and make sure the remote controller display shows “ ” and flashing of the operation lamp. If the operation lamp is flashing, it shows the protection circuits for connecting cable is working or thermal fuse is blown.

5) In the same way, operate the TEMP. key so that the display is increased one by one to continue checks by the self-diagnosis as shown in the next table. From

“ ”

up to “ ” check operations of protection circuits for each block, and

“ ”

to

“ ”

check operations of the typical protection circuits.

Operating key

ON/OFF

Indication after operation

TEMP. (Up)

TEMP. (Down)

AUTO

LOUVER

SET

LOUVER

1 is added to data before operation.

(Example)

1 is subtracted from data before operation.

(Example)

10 is subtracted from data before operation.

(Example)

Data before operation is directly transferred.

(Example)

“ ” “

” “

” “

112

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14-2. Troubleshooting with CHECK Display of Remote Controller

14-2-1. In case of main remote controller/sub-remote controller A

RBC-AM1E RBC-AS1E

1. Operation for CHECK display

When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is displayed at the right side of the set up TEMP. display section, and the check data of 2 errors/faults x 16 units is displayed in the set up temp. display section.

If there is a filter display, the indoor unit No. which sends the filter signal is displayed at the right side of the set up temp. display section, and then the check code is displayed as described above.

(1 display for 3 seconds)

F A N

CHECK ADDRESS

UNIT

1 2

H E AT AU TO

CENTRAL

FILTER

PREHEA

DEFROST

L O U V E R

M A N UA L

MODE

FILTER CHECK

ON/OFF

LCD display “STANDBY” is present.

• When phase-sequence of power wiring is incorrect

• When combination of indoor units is over capacity

• Indoor unit with command excepted by operation mode select switch

• When there is an indoor unit which stopped with the indoor overflow alarm “0b”.

• Indoor unit with cooling operation command excepted by heating priority control

RESET switch

Push the switch in the hole with pin.

The remote controller resets the power supply.

(All data is cleared.)

CHECK switch

Push for 0.5 seconds to display CHECK code.

Push for 3 seconds to reset indoor microprocessor.

(While indoor microprocessor is locked by ALL STOP alarm)

Push for 10 seconds to clear check data.

113

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

2. Reading of CHECK monitor display

<7 segment display>

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Hexadecimal notation

Decimal notation

<Display on CHECK monitor>

CHECK

1 2

UNIT

FILTER

FILTER sign

Indoor unit No.

CHECK code

<FILTER data>

(Example)

Case that Filter signal is sent from No.1 and No.16 units under group operation

UNIT

FILTER

UNIT

FILTER

<CHECK data>

(Example)

Room temp.sensor of No.1 is defective.

In No.16, first the heat exchanger sensor has failed.

Next, interconnection wire (serial signal line) of indoor/outdoor is defective.

CHECK

1

UNIT CHECK

1

UNIT CHECK

2

UNIT

(Example) There is no check data.

CHECK

114

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14-2-2. Remote controller with timer

RBC-AM1E

1. Operation for CHECK display

When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is displayed in the set up temp. display section, and check code is displayed in the TIME display section.

If FILTER display (air filter cleaning sign) is present, the indoor unit No. which sends the filter signal is displayed in the set up temp. display section, and then the check code is displayed. (1 display for 3 seconds)

LCD display STANDBY is present.

• When phase-sequence of power wiring is incorrect

• When combination of indoor units is over capacity.

• Indoor unit with command excepted by operation mode select switch

• When there is an indoor unit which stopped with the indoor overflow alarm “0b”.

• Indoor unit with cooling operation command excepted by heating priority control

MODE

FAN ONLY

COOL

HEAT

FAN

AUTO

HIGH

MED

LOW

FIX

PREHEAT

DEFROST

OPERATION

STANDBY

FILTER

TEMP

UNIT

CHECK

DEMAND

C

F

LOUVER

MANUAL

TIMER CONT.OFF ON ADDRESS

AFTER H M

REMOTE CONTROLLER

MODE

TIMER ADJUST

CHECK FILTER

ON/OFF

(This display is for remote control with timer.)

CHECK switch

Push for 0.5 seconds to display CHECK code.

Push for 3 seconds to reset indoor microprocessor.

(While indoor microprocessor is locked by ALL STOP alarm)

Push for 10 seconds to clear check data.

RESET switch

Push the switch in the hole with pin.

The remote controller resets initialized.

(All data is cleared.)

115

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

2. Reading of CHECK monitor display

<7 segment display>

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Hexadecimal notation

Decimal notation

<FILTER data>

(Example)

Filter signal is sent from No.1 and No.15 units under grouping operation

UNIT

CHECK

FILTER

UNIT

CHECK

FILTER

<CHECK data>

Unit No.

UNIT

CHECK

Check code detected at first Check code detected at last

(Example)

Room temp.sensor of No.1 is defective.

In No.15, first the indoor heat exchanger sensor has failed.

Next, interconnection wire (bus communication line) of indoor/outdoor is defective.

(Example)

There is no check data.

UNIT

CHECK

UNIT

CHECK CHECK

After 3 seconds

116

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14-2-3. Central remote controller

1. Operation for CHECK display

When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data is displayed in the UNIT No. display section, and the check code is displayed in the set up temp. display section.

ON

MONITOR

SET

ZONE

ALL UNIT

ON

OFF

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64

CENTER

LOCKED

MODE

FAN ONLY

COOL

DRY

HEAT

AUTO

AUX. TYPE

TIMER No.

FAN

AUTO

HIGH

MED.

LOW

FIX

LOUVER

MANUAL

STANDBY

FILTER

TEMP.

CHECK

1 C

2

MONITOR/SET ALL/ZONE ZONE UNIT ON CENTER/LOCKED MODE TEMP.

FILTER RESET CHECK

ZONE SET/ENTER SELECT OFF TIMER ON

FAN LOUVER

CHECK switch

Push for 0.5 seconds to display CHECK code.

Push for 3 seconds to reset indoor microprocessor.

(While indoor microprocessor is locked by ALL STOP alarm)

Push for 10 seconds to clear check data.

RESET switch

Push the switch in the hole with pin.

The remote controller resets initialized.

(All data is cleared.)

2. Reading of CHECK monitor display

<7 segment display>

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Hexadecimal notation

Decimal notation

<Display on CHECK monitor>

Unit line No. (Network address No.)

MONITOR

SET

ZONE

ALL UNIT

ON

OFF

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64

CENTER

LOCKED

MODE

FAN ONLY

COOL

DRY

HEAT

AUTO

AUX. TYPE

TIMER No.

FAN

AUTO

HIGH

MED.

LOW

FIX

TEMP.

1

2

LOUVER

MANUAL

STANDBY

FILTER

CHECK

C

Check code detected at first

Check code detected at last

<CHECK data>

(Example)

There is no check data.

UNIT

TEMP.

CHECK

(Example)

In No.1 unit, first the interconnection wire (bus communication line) of indoor/outdoor has failed.

Next, the room temp. sensor is defective.

For No.16 unit, the high pressure switch at the inverter unit side operates.

UNIT UNIT UNIT

TEMP.

CHECK

1

TEMP.

CHECK

2

TEMP.

CHECK

1

117

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14-3. Check Code Table

Error mode detected by indoor unit (1)

Block display

[MODE]

[TIMER] lamp

5Hz flash

[MODE] lamp

5Hz flash

Check code

*

Operation of diagnostic function

Cause of operation

Status of air conditioner

Error in other cycles

Indoor heat exchanger temp

(TC) does not vary after start of cooling/heating operation.

Coming-off, disconnection or short of indoor temp sensor

(TA)

Coming-off, disconnection or short of indoor temp sensor

(TC)

Operation continues

Operation continues

Operation continues

Condition

Judgment and measures

The serial signal is not output from outdoor unit to indoor unit.

Miscabling of inter-unit cables

Defective serial sending circuit on outdoor P.C. board

Defective serial receiving circuit on outdoor P.C. board

Compressor case thermo operation

Operation continues

Displayed when error is detected

1. Outdoor unit does not completely operate.

Inter-unit cable check, correction of miscabling

Outdoor P.C. board check, P.C. board cables check

Compressor case thermo check

2. In normal operation

When outdoor sending serial LED

(Green) flashes, the receiving serial

LED (Orange) also flashes. : Indoor

P.C. board (Main P.C. board) check

When the receiving serial LED

(Orange) does not flash: Outdoor P.C.

board check

BUS communication circuit error

* BUS communication was interrupted over the specified time.

Operation continues

(According to remote controller of indoor unit)

Displayed when error is detected

1. Communication line check, miscabling check

Power supply check for central controller (Central control remote controller, etc.) and indoor unit

2. Communication check (XY terminal)

3. Indoor P.C. board check

4. Central controller check

(Communication P.C. board)

Network address miss-setting

Addresses of central controllers (Central control remote controller, etc.) are duplicated.

Operation continues

Displayed when error is detected

1. Check central control system network address setting. (SW02)

2. Indoor P.C. board check

3. Central controller check

(Communication P.C. board)

Error in 4-way valve system

Indoor heat exchanger temperature rise after start of cooling operation.

Indoor heat exchanger temperature fall after start of heating operation.

Operation continues

Displayed when error is detected

1. Check 4-way valve.

2. Check 2-way valve and non-return valve.

3. Check indoor heat exchanger sensor

(TC).

4. Check indoor P.C. board (Main P.C.

board).

Displayed when error is detected

1. Compressor case thermo operation

2. Coming-off of detection part of indoor heat exchanger sensor

3. Check indoor heat exchanger sensor

(TC).

4. Check indoor P.C. board (Main P.C.

board).

Displayed when error is detected

1. Check indoor temp sensor (TA).

2. Check indoor P.C. board (Main P.C.

board).

Displayed when error is detected

1. Check indoor temp sensor (TC).

2. Check indoor P.C. board (Main P.C.

board).

Coming-off, disconnection or short of indoor temp sensor

(TCJ)

Operation continues

Displayed when error is detected

1. Check indoor temp sensor (TCJ).

2. Check indoor P.C. board (Main P.C.

board).

*

: No display in the setting at shipment

118

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

Error mode detected by indoor unit (1)

Block display

[MODE] lamp

5Hz flash

Check code

Operation of diagnostic function

Cause of operation

Status of air conditioner

Error in indoor fan system

Revolutions frequency error of fan

All stop

Condition

Judgment and measures

Displayed when error is detected

1. Check indoor fan motor connector circuit (CN210).

2. Check indoor fan.

3. Check indoor P.C. board (Main P.C.

board).

Displayed when error is detected

1. Check indoor P.C. board

(EEPROM and peripheral circuits)

(Main P.C. board).

Error in indoor unit or other positions

1. EEPROM access error

Operation continues

Outside error input

Detected by input voltage level from outside devices

Operation continues

Outside interlock input

Detected by input voltage level from outside devices

All stop

Displayed when error is detected

Displayed when error is detected

1. Check outside devices.

2. Check indoor P.C. board (Main P.C.

board).

Error mode detected by indoor unit (2)

Check code

Operation of diagnostic function

Cause of operation

Status of air conditioner

Condition

Serial return signal is not sent from No. 1 indoor unit to remote controller.

Miscabling of inter-unit cable between remote controller and indoor unit

Miss-setting of indoor unit No.

(Group address)

ON/OFF

Judgment and measures

Displayed when error is detected

1. Indoor unit does not completely operate.

Check inter-unit cable.

Check indoor P.C. board. (Main/Sub P.C. boards)

Check remote controller.

2. In normal operation

Check setting of indoor unit No.

(SW01) (Sub P.C. board)

Check remote controller.

119

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

Error mode detected by outdoor unit

Check code

Operation of diagnostic function

Cause of operation

Status of air conditioner

Inverter over-current protective circuit operates.

(For a short time)

All stop

Condition

Judgment and measures

Displayed when error is detected

1. Inverter immediately stops even if restarted.

Compressor rare short

2. Check IPDU.

Cabling error

Error on current detection circuit

Current value is high at AC side even while compressor stops.

Phase of power supply is missed.

Coming-off, disconnection or short of outdoor temp sensor

All stop

All stop

Displayed when error is detected

1. Compressor immediately stops even if restarted.

: Check IPDU.

2. Phase-missing operation of power supply

Check power voltage of R, S, T.

Coming-off, disconnection or short of outdoor temp sensor

Compressor drive output error

Tin thermistor temp, Tin error

(IPDU heat sink temp. is high.)

Communication error between

IPDU

Connector coming-off between CDB and IPDU

All stop

All stop

Compressor does not rotate.

(Over-current protective circuit works when constant time passed after activation of compressor.)

All stop

Discharge temp error

Discharge temp over specified value was detected.

All stop

Displayed when error is detected

1. Check outdoor temp sensor (TE, TS).

2. Check CDB.

Displayed when error is detected

1. Check outdoor temp sensor (TD).

2. Check CDB.

Displayed when error is detected

1. Abnormal overload operation of refrigerating cycle

2. Loosening of screws and contact error of IPDU and heat sink

3. Cooling error of heat sink

4. Check cabling of CDB and IPDU.

Displayed when error is detected

Displayed when error is detected

1. Compressor error (Compressor lock, etc.)

: Replace compressor.

2. Cabling trouble of compressor (Phase missing)

1. Check refrigerating cycle. (Gas leak)

2. Error of electron control valve

3. Check pipe sensor (TD).

Displayed when error is detected

1. Check power voltage. (AC200V±20V)

2. Overload operation of refrigerating cycle

3. Check current detection circuit at AC side.

Compressor breakdown

Operation frequency lowered and stops though operation had started.

All stop

High-voltage protection error by TE sensor

TE temp over specified value was detected.

All stop

DC outdoor fan motor error

IDC operation or lock was detected by DC outdoor fan driving.

All stop

Error on IPDU position detection circuit

Coming-off, disconnection or short of outdoor temp sensor

All stop

Operation continues

Displayed when error is detected

Displayed when error is detected

1. Overload operation of refrigerating cycle

2. Check outdoor temp sensor (TE).

1. Position detection error

2. Over-current protection circuit operation of outdoor fan drive unit

Check CDB.

Refer to Judgment of outdoor fan.

Displayed when error is detected

1. Position detection circuit operates even if driving by removing 3P connector of compressor.

Replace IPDU.

Displayed when error is detected

1. Check outdoor temp sensor (TO).

2. Check P.C. board.

120

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14-4. Troubleshooting for Each Check Code

[1A error]

Are connections of CN301 and

CN300 of CDB correct?

YES

Does the fan rotate without trouble when handling the fan with hands under condition of removing CN301 and CN300 from CDB?

YES

NO

The status that the resistance values between leads below are 50 to 80 for 40W motor (ICF-140-43) and 25 to 55 for 60W motor (ICF-140-63-1) is normal.

NO of motor winding of connector (CN301)

YES

The status that there is

5k to 20k resistance values between of motor position detection of connector

(CN300, CN302) is normal.

YES

NO

CN301

CN300

For RAV-SM560AT-E, CN300 changes to

CN301, and CN301 to CN300, respectively.

Normal fan motor Defective fan motor

(CDB error)

NOTE :

However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.

When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

Objective P.C. board

Fan motor winding

Motor position detection

RAV-SM560AT-E

Control P.C. board

CN300

CN301

RAV-SM800AT-E

CDB P.C. board

CN301

CN300

121

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[04 error]

NO

Does outdoor unit operate?

YES

Are 1, 2, 3 inter-unit cables normal?

YES

NO

Correct inter-unit cable.

Are connections of connectors normal?

YES

NO

Correct connection of connector.

Is DC310 to 340V applied between terminals of electrolytic capacitor of IPDU main circuit?

YES

* For RAV-SM560AT-E, check case thermo.

NO

Replace IPDU.

* For RAV-SM560AT-E, replace control P.C. board.

Is DC310 to 340V power supplied to CDB?

(CN03)

YES

NO

Replace IPDU.

NO

Does LED (D05) (Orange) on indoor main P.C. board flash?

YES

Is case thermo

(CN500) connected?

YES

NO

Correct connection of connector.

Does case thermo operate?

YES

NO

Check CDB.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

Check CDB.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

Check main indoor main P.C. board

(MCC-1370A).

Defect Replace

Check/Correct charged refrigerant amount.

* For RAV-SM560AT-E, replace control P.C. board.

122

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[08 error]

Check and replace

2-way valve, check valve, or electron expansion valve.

Is operation of

4-way valve normal?

YES

NO

NO

Is flow of refrigerant by

2-way valve, check valve, or electron expansion valve normal?

YES

Is 200V applied to

4-way valve coil terminal in heating operation?

NO

YES

Check 4-way valve.

Is circuit cable normal?

YES

NO

Check and correct circuit.

NO

Are characteristics of TC sensor resistance value normal?

* Refer to Characteristics-2.

YES

Replace TC sensor.

Check indoor main P.C. board

(MCC-1370A) and sub P.C. board (MCC-1370B).

Defect Replace

* For RAV-SM560AT-E, check control P.C. board.

Check CDB P.C. board.

YES

NO

Check CDB P.C. board.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

In cooling operation, if high pressure is abnormally raised, [08 error] may be displayed. In this case, remove cause of pressure up and then check again referring to the item [21 error].

[0C error]

Is connection of TA sensor connector

(Indoor main P.C. board CN04) normal?

YES

NO

Are characteristics of

TA sensor resistance value normal?

YES

NO

* Refer to Characteristics-1.

Check indoor P.C. board

(MCC-1370A).

Defect Replace

Correct connection of connector.

Replace TA sensor.

123

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[0d error]

Is connection of TC sensor connector

(Indoor P.C. board CN05) normal?

YES

NO

Are characteristics of

TC sensor resistance value normal?

YES

NO

* Refer to Characteristics-2.

Check indoor P.C. board

(MCC-1370A).

Defect Replace

Correct connection of connector.

Replace TC sensor.

[0F error]

Is connection of TCJ sensor connector

(Indoor P.C. board CN20) normal?

YES

NO

Are characteristics of

TCJ sensor resistance value normal?

YES

NO

* Refer to Characteristics-2.

Check indoor P.C. board

(MCC-1370A).

Defect Replace

Correct connection of connector.

Replace TCJ sensor.

124

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[99 error]

Is inter-unit cable of

A, B and C normal?

YES

NO

Is there no disconnection or contact error of connector?

NO

YES

Is individual (1 : 1) operation?

NO

YES

NO

Is unit set to No.1?

YES

NO

Are not No.1 unit duplicated?

YES

NO

Does indoor unit operate?

YES

Correct inter-unit cable of remote controller.

Correct connection of connector.

Check circuit cables.

Does LED (Green) on indoor main P.C. board flash?

(D13)

NO

YES

Set the unit to No.1.

Avoid duplication of unit No.1 setting.

Check remote controller P.C. board.

Defect Replace

Check indoor main P.C. board

(MCC-1370A).

Defect Replace

125

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[11 error]

Turn off the breaker once.

Turn on the breaker after approx. 10 seconds.

Does fan stop when operation stopped?

YES

NO

Is DC1V or more voltage applied between 5 + and 3

of the motor connector (CN210)?

YES

Start the operation with cooling mode [L (Low)].

NO

Does the fan rotate?

YES

Is DC280V or more voltage applied between 1 + and 3

of the motor connector (CN210)?

YES

(Connection status of motor)

Is DC15V or more voltage applied between 4 + and 3

of the motor connector (CN210)?

YES

Change the cooling mode to [H (High)].

NO

NO

Stop the operation and turn off the breaker.

After removing motor connector, turn on the breaker again and then stop the operation from remote controller.

NO

Is fan speed raised?

YES

Is DC15V voltage applied between 4 + and 3

of the motor connector (CN210)?

YES

Is DC1V or more voltage applied between 5 + and 3

of the motor connector (CN210) when changing the operation mode (except HEAT)?

(Check within approx. 15 seconds after operation has started.)

NO

YES

NO

Stop the operation and disconnect the receptacle. After removing motor connector, connect receptacle again and then stop the operation from remote controller.

NO

Normal fan motor

NO

Is DC1V or more voltage applied between 5 + and 3

of the motor connector (CN210) when changing the operation mode (except HEAT)?

(Check within approx. 15 seconds after operation has started.)

YES

NO

Does the cross flow fan rotate normally when handled with hands?

YES

Does 0 to 5V voltage

(revolutions return signal) generate between 6 + and 3

of the motor connector (CN210) when rotating the cross flow fan with hands under condition of operation-stop?

YES

Repair bering of the cross flow fan.

NO

126

– www.ilmalämpöpumput.com

Replace indoor fan motor.

Replace indoor main P.C. board

(MCC-1370A).

Replace indoor main P.C. board

(MCC-1370A).

Replace indoor fan motor.

Replace indoor main P.C. board

(MCC-1370A).

Replace indoor fan motor.

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[11 error]

Indoor fan starts rotating by inserting receptacle.

[Check output voltage (DC) of P.C. board fan motor.]

Measure the voltages of the motor connector

CN210 Pin 3 (GND (minus): Black) and Pin 5 (V line (plus): Yellow) under condition that indoor fan rotates.

DC1.0V or less DC1.0V or more

Defective indoor main P.C. board

(MCC-1370A)

Defective indoor fan motor

DC

CN210

Yellow

Black

P.C. board

6 (Blue)

5 (Yellow)

4 (White)

3 (Black)

2 –

1 (Red)

[12 error]

Is there no turbulence of power supply?

YES

Check indoor main P.C. board (MCC-1370A).

Defect Replace

NO

Check power voltage. Improve line.

Check and eliminate noise, etc.

– 127 – www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[14 error]

Is power voltage normal?

YES

NO

Improve the power supply line.

YES

Are connections of cabling/connector normal?

YES

NO

* For RAV-SM560AT-E, check RY01 on the control P.C. board.

Check and correct circuit cables.

Correct connection of connector.

Check and correct reactor connection.

Does RY01 relay of

IPDU operate?

NO

YES

Is not

14

errors output when an operation is performed by removing 3P connector of compressor?

YES

* Single-phase type is not provided to RAV-SM560AT-E.

NO

Replace IPDU.

Is not AC fuse fused?

NO

* Replace control P.C. board of RAV-SM560AT-E.

Replace IPDU.

* Replace control P.C. board of RAV-SM560AT-E.

Is compressor normal?

YES

NO

Check IPDU.

Defect Replace

Check rare short of compressor trouble.

Defect Replace

[16 error]

Are connections of cable/connector normal?

YES

NO

NO

Is compressor normal?

YES

YES

Is not earthed?

NO

Is not winding shorted?

(Is resistance between windings 0.6 to 1.2 ?)

NO

YES

YES

Is not winding opened?

NO

Check and correct circuit cabling such as cabling to compressor.

Compressor error Replace

Compressor error Replace

Compressor error Replace

Check IPDU P.C. board.

Defect Replace

128

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[18 error]

Are connections of

TE/TS sensor connectors of

CDB CN604/CN605 normal?

YES

NO

Correct connection of connector.

Are characteristics of TE/TS sensor resistance values normal?

YES

* (For RAV-SM560AT-E, CN600 TE sensor and CN603 TS sensor)

NO

Replace TE and TS sensors.

* Refer to Characteristics-3.

Check CDB.

Defect Replace

* For RAV-SM560AT-E, replace the control P.C. board

[19 error]

Is connection of TD sensor connector of CDB CN600 normal?

YES

Are characteristics of TD sensor resistance value normal?

YES

NO

Correct connection of connector.

* For RAV-SM560AT-E, CN601 on control P.C. board

NO

Replace TD sensor.

Check control P.C. board.

Defect Replace

* Refer to Characteristics-4.

[1C error] * Except RAV-SM560AT-E

Are connections of

CDB CN800 and CDB IPDU CN06 connectors normal?

YES

NO

Was the error just after power ON determined?

NO

YES

Are cabling/connector normal?

YES

NO

Correct connection of connector.

Check cabling between IPDU and CDB and connector.

IPDU P.C. board error

Defect Replace

Is there no abnormal overload?

NO

YES

NO

Is IPDU P.C. board come to closely contact with heat sink?

YES

Improve and eliminate the cause.

Correct mounting.

IPDU P.C. board error

Defect Replace

129

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[1d error]

NO

Is power voltage normal?

YES

Are connections of cable/connector normal?

YES

NO

NO

Is compressor normal?

YES

Improve power line.

Check and correct circuit cabling such as cabling to compressor

(phase missing) and connector.

Is there no slackened refrigerant?

YES

NO

Does electron expansion valve normally operate?

YES

NO

Compressor lock Replace

Check TE and TS sensors. Replace

Check electron expansion valve. Replace

Check IPDU and CDB.

Defect Replace

* For RAV-SM560AT-E, check control P.C. board.

Defect Replace

[1E error]

Is protective control such as discharge temprelease control normal?

YES

NO

Are connections of cable/connector normal?

YES

NO

Correct the cabling and connection of connector.

Check parts. Defect Replace

Is charged refrigerant amount normal?

YES

NO

YES

Is not abnormal overload?

NO

NO

Are characteristics of

TD sensor resistance value normal?

YES

* Refer to Characteristics-4.

Check and correct the charged refrigerant amount.

Improve and delete the cause

Replace TD sensor.

Check CDB.

Defect Replace

[1F error]

Is power voltage normal?

YES

Is not abnormal overload?

NO

Is the circuit detected by current sensor normal?

YES

* For RAV-SM560AT-E, check control P.C. board.

NO

YES

NO

Improve power line.

Improve and delete the cause.

Check and correct circuit cables.

Check IPDU.

Defect Replace

* For RAV-SM560AT-E, check control P.C. board.

130

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

[21 error] [ ] LCD flash

Is high-voltage protective operation by

TE sensor normal?

YES

NO

Is connection of cabling connector normal?

YES

NO

Correct connection of cabling connector.

Check TE sensor.

Defect Replace

Does cooling outdoor fan normally operate?

YES

NO

Is connection of connector normal?

YES

NO

Correct connection of connector.

NO

Is fan motor normal?

YES

Replace fan motor.

NO

Check TE, TC, TS sensors.

Does electron control valve normally operate?

YES

Do not TD and TO sensors come off the detection part?

NO

YES

Replace electron expansion valve.

Correct coming-off.

Are characteristics of

TD, TO, TC sensor resistance values normal?

YES

NO

Replace TD, TO, and TC sensors.

* Refer to Characteristics-3 and 4.

Check charged refrigerant amount.

Check liquid/gas valves.

Check abnormal overload.

Check CDB.

Defect Replace

* For RAV-SM560AT-E, check control P.C. board.

131

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

14-5. Simple Check Method for Main Parts

14-5-1. Indoor unit

No.

Part name Check procedure

1 Temperature sensor (Ta)

Heat exchanger sensor (Tc)

Heat exchanger sensor (Tcj)

Measure the resistance value with tester by removing the connector.

(Normal temperature)

Normal value

10 k

to 20 k

Refer to Characteristics table.

2 Louver motor

MP35EA12

Measure the resistance value of each winding coil with tester.

(Under normal temperature 25

°

C)

Brown

Red

Orange

Yellow

Pink

Blue

1

2

3

4

5

6

1

2

3

4

5

6

Position

Between 1 and 2

Between 1 and 3

Between 1 and 4

Between 1 and 5

Resistance value

130 ± 40

3 Indoor fan motor

(ICF-340-30-1) lMeasure the resistance value of each winding coil with tester.

lFor P.C. board side, proceed to [11 error] of

Troubleshooting procedure for each check code

.

Position

Between

ƒ

(Black) and



(Red)

Between

ƒ

(Black) and

„

(White)

Between

ƒ

(Black) and

…

(Yellow)

Between

ƒ

(Black) and

†

(Blue)

Resistance value

(M

)

27 to 47 k

140 to 280 k

(M

)

Red 1 1

Black 3

White

Yellow

4

5

Blue 6

3

4

5

6

1

3

4

5

6

1

2

3

4

5

6

132

– www.ilmalämpöpumput.com

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

Relational graph of temperature sensor resistance value and temperature

Resistance

(k )

10

20

0

10 20

40

TA sensor

Caracteristics-1

30

Resistance

(k )

20

30 40

Temperature [ C]

50

TC, TCJ sensor

Caracteristics-2

10

0

10 0 10 20 30 40 50 60 70

Temperature [ C]

20

TE, TO, TS sensor

200

Caracteristics-3

Resistance

(k )

(10 C or lower)

100

Resistance

(k )

(10 C or higher)

10

0

200

-10 0 10 20 30 40

Temperature [ C]

50 60 70

0

TD sensor

Caracteristics-4

Resistance

(k )

(50 C or lower)

100

20

Resistance

(k )

(50 C or higher)

10

0 0

50

Temperature [ C]

100

133

– www.ilmalämpöpumput.com

100

50

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy

Resistance

(K )

200

150

Caracteristics-5

TH sensor

Resistance

(K )

(10 C or higher)

20

15

10

5

30

20

10 0 10 20 30 40

Temperature [

º

C]

50 60 70 80 90 100

134

– www.ilmalämpöpumput.com

advertisement

Key Features

  • 4-Way Air Discharge Cassette Type
  • Concealed Duct Type
  • High-Wall Type
  • Flexible Type
  • R410A Refrigerant
  • Turbo Fan
  • Energy Consumption Effect Ratio
  • Compressor Thermo
  • Pulse Motor Valve
  • Wired Remote Controller

Frequently Answers and Questions

What are the different types of indoor units available?
The indoor units are available in 4-Way Air Discharge Cassette Type, Concealed Duct Type, High-Wall Type, and Flexible Type.
What is the standard capacity of the units?
The standard capacity of the units varies depending on the model. Refer to the specifications section for detailed information.
What is the sound level of the outdoor unit?
The sound level of the outdoor unit is measured in an anechoic chamber and is typically between 45 and 50 dB(A).

Related manuals