- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Toshiba
- RAV-SM800 AT-E
- Service manual
TROUBLESHOOTING <WALL TYPE>. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E 181 Pages
TROUBLESHOOTING <WALL TYPE>. Toshiba RAV-SM560 BT-E, RAV-SM560 XT-E, RAV-SM560 KRT-E, RAV-SM800 AT-E, RAV-SM800 KRT-E, RAV-SM800 BT-E, RAV-SM800 XT-E, RAV-SM560 UT-E, RAV-SM560 AT-E, RAV-SM800 UT-E
Add to My manuals181 Pages
Below you will find brief information for RAV-SM560 AT-E, RAV-SM800 AT-E, RAV-SM560 UT-E, RAV-SM800 UT-E, RAV-SM560 BT-E, RAV-SM800 BT-E, RAV-SM560 KRT-E, RAV-SM800 KRT-E, RAV-SM560 XT-E, RAV-SM800 XT-E. These split-system air conditioners are designed to provide comfortable indoor temperatures in residential and commercial settings. The units are available in a range of capacities to suit different needs and come with various features for optimal performance and energy efficiency.
advertisement
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14. TROUBLESHOOTING <WALL TYPE>
14-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
•
+ and
–
screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch
•
Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
The following operations are normal.
a) Compressor does not operate.
•
Is not 3-minutes delay (3 minutes after compressor OFF)?
•
Does not thermostat turn off?
•
Does not timer operate during fan operation?
•
Is not detected an overflow error?
•
Is not outside high-temperature operation controlled in heating operation?
b) Indoor fan does not rotate.
•
Does not cool air discharge preventive control work in heating operation?
c) Outdoor fan does not rotate or air speed changes.
•
Does not high-temperature release operation control work in heating operation?
•
Does not outside low-temperature operation control work in cooling operation?
•
Is not defrost operation performed?
d) ON/OFF operation cannot be performed from remote controller.
•
Is not during emergency operation?
•
Is not the control operation performed from outside/remote side?
Did you return the cabling to the initial positions?
Are connecting cables of indoor unit and remote controller correct?
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble
→
Confirmation of check code display
→
Check defective position and parts.
NOTE :
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the remote controller and the signal line to shield cables.
–
108
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
(a) Outline of Judgment
A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.
<Judgment by flashing display on the indoor unit display part>
The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part.
Remote controller code
—
Block display
Operation lamp display flashes. (1Hz)
00 Operation lamp display flashes. (5Hz)
01
02
03
—
Operation/timer lamp displays flash. (5Hz)
Operation/defrost lamp displays flash. (5Hz)
Operation/timer/defrost lamp displays flash. (5Hz)
——
Contents of self-diagnosis
Power failure (In power ON)
Indoor P.C. board
Inter-unit cables/transmission system
Outdoor P.C. board
Cycle system, etc.
——
Check code
——
0b to 0F, 11, 12, b5, b6
04
14 to 19, 1A, 1C
1d, 1E, 1F, 21
1b, 8b
(b) Self-diagnosis by check code on the remote controller
Refer to
“
Judgment of error mode by check code on the remote controller
”
.
<Wireless remote controller type>
1. Before troubleshooting
1) Required tools/instruments
•
+ and
–
screwdrivers, spanners, radio cutting pliers, nippers, etc.
•
Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
The following operations are normal.
a) Compressor does not operate.
•
Is not 3-minutes delay (3 minutes after compressor OFF)?
•
Does not thermostat turn off?
•
Does not timer operate during fan operation?
•
Is not outside high-temperature operation controlled in heating operation?
b) Indoor fan does not rotate.
•
Does not cool air discharge preventive control work in heating operation?
c) Outdoor fan does not rotate or air volume changes.
•
Does not high-temperature release operation control work in heating operation?
•
Does not outside low-temperature operation control work in cooling operation?
•
Is not defrost operation performed?
d) ON/OFF operation cannot be performed from remote controller.
•
Is not forced operation performed?
•
Is not the control operation performed from outside/remote side?
Did you return the cabling to the initial positions?
Are connecting cables between indoor unit and receiving unit correct?
–
109
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble
→
Confirmation of check code by service mode
→
Check defective position and parts.
NOTE :
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cable of the signal line to shield cable.
(a) Outline of Judgment
A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.
<Judgment by flashing display on the indoor unit display part>
The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part
(Sensors).
Remote controller code
—
Block display
Operation lamp display flashes. (1Hz)
00
01
Operation lamp display flashes. (5Hz)
Operation/timer lamp displays flash. (5Hz)
02
03
—
Contents of self-diagnosis
Power failure (In power ON)
Indoor P.C. board
Inter-unit cables/transmission system
Operation/defrost lamp displays flash. (5Hz) Outdoor P.C. board
Operation/timer/defrost lamp displays flash. (5Hz)
——
Cycle system, etc.
——
Check code
——
0b to 0F, 11, 12, b5, b6
04
14 to 19, 1A, 1C
1d, 1E, 1F, 21
1b, 8b
(b) Self-diagnosis by check code on the remote controller
In the wireless type models, the self-diagnosis for the protective circuit operation is performed by handling the remote controller. First change the operation mode of the remote controller, and then perform the selfdiagnosis by the displayed contents of the remote controller and the existence of operation lamp flashing
(5Hz) and buzzer sound (Pi, Pi, Pi). During self-diagnosis operation, the timer lamp usually flashes (5Hz).
Selection of remote controller operation mode
1) Selection of service mode
Push the select button at lower side of the wireless remote controller with a tip of pencil, etc. for approx. 3 seconds or more. In this time, check that [00] is displayed on the room temp. display part and other displays go off.
2) Selection of normal mode
Push the reset button at lower side of the wireless remote controller with a tip of pencil, etc. In this time, check that [
“
AM
”
] display on the time display part flashes.
Cautions in service
1) After service work, be sure to push the reset button to return the mode to normal mode.
2) After service by the check codes, turn off the power switch once and then turn on the switch to return the stored memory in microcomputer to the initial status.
–
110
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
(c) Self-diagnosis with remote controller
With the indoor unit control, self-diagnosis of protective circuit action can be done by turning the remote controller operation into service mode, operating the remote controller, observing the remote controller indicators and checking whether TIMER lamp flashes (5 Hz).
NOTE :
• To perform this self-diagnosis, the remote controller with the service code of 43069666 is required.
<How to select remote control operation mode>
1. Selecting service mode
Push the switch button provided on rear bottom of the wireless remote control with a tip of pencil for more than 3 seconds. Make sure the setting temperature
“ ”
is displayed on the display and other display is turned off.
2. Selecting ordinary mode
Push the all clear button (ACL) on the rear bottom of the wireless remote controller with a tip of pencil for more than 3 seconds. Make sure the operation mode display, wind volume display, clock display and setting temperature display are turned on and
“
:
”
of the clock display is flashing.
<Cautions when doing service>
1. After completion of servicing, always push the all clear (ACL) button to return the operation mode to the normal mode.
2. After completion of servicing by the check code, turn off the power once and then turn on the power to reset memorized contents of the microcomputer to the initial status.
All clear button
Switch for selecting service mode
ACL CLOCK
ACL CLOCK
(Rear bottom of remote control)
Rear bottom cover
–
111
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
<Self-diagnosis by check codes>
1. The self-diagnosis by the check codes is conducted under the block displays.
2. Remote controller key operation under the service mode is conducted by ON/OFF or TEMP. The remote controller display by each key operation is varied as shown below. Two digit number is displayed in a hexadecimal number.
3. The self-diagnosis by the check codes is conducted with procedures shown below.
1) Enter the service mode and make sure the off timer display of the remote controller shows
“ ”
.
2) Operate the
“
ON/OFF
”
key and make sure the timer lamp on the display section is flashing (5 Hz).
3) At the same time, also make sure the operation lamp is also flashing. This shows that the protection circuit on the indoor P.C. board is working.
4) Operate the TEMP. key and make sure the remote controller display shows “ ” and flashing of the operation lamp. If the operation lamp is flashing, it shows the protection circuits for connecting cable is working or thermal fuse is blown.
5) In the same way, operate the TEMP. key so that the display is increased one by one to continue checks by the self-diagnosis as shown in the next table. From
“ ”
up to “ ” check operations of protection circuits for each block, and
“ ”
to
“ ”
check operations of the typical protection circuits.
Operating key
ON/OFF
Indication after operation
“
”
TEMP. (Up)
TEMP. (Down)
“
AUTO
”
LOUVER
“
SET
”
LOUVER
1 is added to data before operation.
(Example)
1 is subtracted from data before operation.
(Example)
10 is subtracted from data before operation.
(Example)
“
“
Data before operation is directly transferred.
(Example)
“
“ ” “
”
” “
” “
“
”
”
”
”
–
112
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14-2. Troubleshooting with CHECK Display of Remote Controller
14-2-1. In case of main remote controller/sub-remote controller A
RBC-AM1E RBC-AS1E
1. Operation for CHECK display
When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is displayed at the right side of the set up TEMP. display section, and the check data of 2 errors/faults x 16 units is displayed in the set up temp. display section.
If there is a filter display, the indoor unit No. which sends the filter signal is displayed at the right side of the set up temp. display section, and then the check code is displayed as described above.
(1 display for 3 seconds)
F A N
CHECK ADDRESS
UNIT
1 2
H E AT AU TO
CENTRAL
FILTER
PREHEA
DEFROST
L O U V E R
M A N UA L
MODE
FILTER CHECK
ON/OFF
LCD display “STANDBY” is present.
• When phase-sequence of power wiring is incorrect
• When combination of indoor units is over capacity
• Indoor unit with command excepted by operation mode select switch
• When there is an indoor unit which stopped with the indoor overflow alarm “0b”.
• Indoor unit with cooling operation command excepted by heating priority control
RESET switch
Push the switch in the hole with pin.
The remote controller resets the power supply.
(All data is cleared.)
CHECK switch
Push for 0.5 seconds to display CHECK code.
Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)
Push for 10 seconds to clear check data.
–
113
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
2. Reading of CHECK monitor display
<7 segment display>
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Hexadecimal notation
Decimal notation
<Display on CHECK monitor>
CHECK
1 2
UNIT
FILTER
FILTER sign
Indoor unit No.
CHECK code
<FILTER data>
(Example)
Case that Filter signal is sent from No.1 and No.16 units under group operation
UNIT
FILTER
UNIT
FILTER
<CHECK data>
(Example)
Room temp.sensor of No.1 is defective.
In No.16, first the heat exchanger sensor has failed.
Next, interconnection wire (serial signal line) of indoor/outdoor is defective.
CHECK
1
UNIT CHECK
1
UNIT CHECK
2
UNIT
(Example) There is no check data.
CHECK
–
114
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14-2-2. Remote controller with timer
RBC-AM1E
1. Operation for CHECK display
When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is displayed in the set up temp. display section, and check code is displayed in the TIME display section.
If FILTER display (air filter cleaning sign) is present, the indoor unit No. which sends the filter signal is displayed in the set up temp. display section, and then the check code is displayed. (1 display for 3 seconds)
LCD display STANDBY is present.
• When phase-sequence of power wiring is incorrect
• When combination of indoor units is over capacity.
• Indoor unit with command excepted by operation mode select switch
• When there is an indoor unit which stopped with the indoor overflow alarm “0b”.
• Indoor unit with cooling operation command excepted by heating priority control
MODE
FAN ONLY
COOL
HEAT
FAN
AUTO
HIGH
MED
LOW
FIX
PREHEAT
DEFROST
OPERATION
STANDBY
FILTER
TEMP
UNIT
CHECK
DEMAND
C
F
LOUVER
MANUAL
TIMER CONT.OFF ON ADDRESS
AFTER H M
REMOTE CONTROLLER
MODE
TIMER ADJUST
CHECK FILTER
ON/OFF
(This display is for remote control with timer.)
CHECK switch
Push for 0.5 seconds to display CHECK code.
Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)
Push for 10 seconds to clear check data.
RESET switch
Push the switch in the hole with pin.
The remote controller resets initialized.
(All data is cleared.)
–
115
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
2. Reading of CHECK monitor display
<7 segment display>
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Hexadecimal notation
Decimal notation
<FILTER data>
(Example)
Filter signal is sent from No.1 and No.15 units under grouping operation
UNIT
CHECK
FILTER
UNIT
CHECK
FILTER
<CHECK data>
Unit No.
UNIT
CHECK
Check code detected at first Check code detected at last
(Example)
Room temp.sensor of No.1 is defective.
In No.15, first the indoor heat exchanger sensor has failed.
Next, interconnection wire (bus communication line) of indoor/outdoor is defective.
(Example)
There is no check data.
UNIT
CHECK
UNIT
CHECK CHECK
After 3 seconds
–
116
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14-2-3. Central remote controller
1. Operation for CHECK display
When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data is displayed in the UNIT No. display section, and the check code is displayed in the set up temp. display section.
ON
MONITOR
SET
ZONE
ALL UNIT
ON
OFF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
CENTER
LOCKED
MODE
FAN ONLY
COOL
DRY
HEAT
AUTO
AUX. TYPE
TIMER No.
FAN
AUTO
HIGH
MED.
LOW
FIX
LOUVER
MANUAL
STANDBY
FILTER
TEMP.
CHECK
1 C
2
MONITOR/SET ALL/ZONE ZONE UNIT ON CENTER/LOCKED MODE TEMP.
FILTER RESET CHECK
ZONE SET/ENTER SELECT OFF TIMER ON
FAN LOUVER
CHECK switch
Push for 0.5 seconds to display CHECK code.
Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)
Push for 10 seconds to clear check data.
RESET switch
Push the switch in the hole with pin.
The remote controller resets initialized.
(All data is cleared.)
2. Reading of CHECK monitor display
<7 segment display>
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Hexadecimal notation
Decimal notation
<Display on CHECK monitor>
Unit line No. (Network address No.)
MONITOR
SET
ZONE
ALL UNIT
ON
OFF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
CENTER
LOCKED
MODE
FAN ONLY
COOL
DRY
HEAT
AUTO
AUX. TYPE
TIMER No.
FAN
AUTO
HIGH
MED.
LOW
FIX
TEMP.
1
2
LOUVER
MANUAL
STANDBY
FILTER
CHECK
C
Check code detected at first
Check code detected at last
<CHECK data>
(Example)
There is no check data.
UNIT
TEMP.
CHECK
(Example)
In No.1 unit, first the interconnection wire (bus communication line) of indoor/outdoor has failed.
Next, the room temp. sensor is defective.
For No.16 unit, the high pressure switch at the inverter unit side operates.
UNIT UNIT UNIT
TEMP.
CHECK
1
TEMP.
CHECK
2
TEMP.
CHECK
1
–
117
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14-3. Check Code Table
Error mode detected by indoor unit (1)
Block display
[MODE]
[TIMER] lamp
5Hz flash
[MODE] lamp
5Hz flash
Check code
*
Operation of diagnostic function
Cause of operation
Status of air conditioner
Error in other cycles
•
Indoor heat exchanger temp
(TC) does not vary after start of cooling/heating operation.
Coming-off, disconnection or short of indoor temp sensor
(TA)
Coming-off, disconnection or short of indoor temp sensor
(TC)
Operation continues
Operation continues
Operation continues
Condition
Judgment and measures
The serial signal is not output from outdoor unit to indoor unit.
•
Miscabling of inter-unit cables
•
Defective serial sending circuit on outdoor P.C. board
•
Defective serial receiving circuit on outdoor P.C. board
•
Compressor case thermo operation
Operation continues
Displayed when error is detected
1. Outdoor unit does not completely operate.
•
Inter-unit cable check, correction of miscabling
•
Outdoor P.C. board check, P.C. board cables check
•
Compressor case thermo check
2. In normal operation
When outdoor sending serial LED
(Green) flashes, the receiving serial
LED (Orange) also flashes. : Indoor
P.C. board (Main P.C. board) check
When the receiving serial LED
(Orange) does not flash: Outdoor P.C.
board check
BUS communication circuit error
* BUS communication was interrupted over the specified time.
Operation continues
(According to remote controller of indoor unit)
Displayed when error is detected
1. Communication line check, miscabling check
Power supply check for central controller (Central control remote controller, etc.) and indoor unit
2. Communication check (XY terminal)
3. Indoor P.C. board check
4. Central controller check
(Communication P.C. board)
Network address miss-setting
•
Addresses of central controllers (Central control remote controller, etc.) are duplicated.
Operation continues
Displayed when error is detected
1. Check central control system network address setting. (SW02)
2. Indoor P.C. board check
3. Central controller check
(Communication P.C. board)
Error in 4-way valve system
•
Indoor heat exchanger temperature rise after start of cooling operation.
•
Indoor heat exchanger temperature fall after start of heating operation.
Operation continues
Displayed when error is detected
1. Check 4-way valve.
2. Check 2-way valve and non-return valve.
3. Check indoor heat exchanger sensor
(TC).
4. Check indoor P.C. board (Main P.C.
board).
Displayed when error is detected
1. Compressor case thermo operation
2. Coming-off of detection part of indoor heat exchanger sensor
3. Check indoor heat exchanger sensor
(TC).
4. Check indoor P.C. board (Main P.C.
board).
Displayed when error is detected
1. Check indoor temp sensor (TA).
2. Check indoor P.C. board (Main P.C.
board).
Displayed when error is detected
1. Check indoor temp sensor (TC).
2. Check indoor P.C. board (Main P.C.
board).
Coming-off, disconnection or short of indoor temp sensor
(TCJ)
Operation continues
Displayed when error is detected
1. Check indoor temp sensor (TCJ).
2. Check indoor P.C. board (Main P.C.
board).
*
: No display in the setting at shipment
–
118
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Error mode detected by indoor unit (1)
Block display
[MODE] lamp
5Hz flash
Check code
Operation of diagnostic function
Cause of operation
Status of air conditioner
Error in indoor fan system
Revolutions frequency error of fan
All stop
Condition
Judgment and measures
Displayed when error is detected
1. Check indoor fan motor connector circuit (CN210).
2. Check indoor fan.
3. Check indoor P.C. board (Main P.C.
board).
Displayed when error is detected
1. Check indoor P.C. board
(EEPROM and peripheral circuits)
(Main P.C. board).
Error in indoor unit or other positions
1. EEPROM access error
Operation continues
Outside error input
Detected by input voltage level from outside devices
Operation continues
Outside interlock input
Detected by input voltage level from outside devices
All stop
Displayed when error is detected
Displayed when error is detected
1. Check outside devices.
2. Check indoor P.C. board (Main P.C.
board).
Error mode detected by indoor unit (2)
Check code
Operation of diagnostic function
Cause of operation
Status of air conditioner
Condition
Serial return signal is not sent from No. 1 indoor unit to remote controller.
•
Miscabling of inter-unit cable between remote controller and indoor unit
•
Miss-setting of indoor unit No.
(Group address)
ON/OFF
Judgment and measures
Displayed when error is detected
1. Indoor unit does not completely operate.
•
Check inter-unit cable.
•
Check indoor P.C. board. (Main/Sub P.C. boards)
•
Check remote controller.
2. In normal operation
•
Check setting of indoor unit No.
(SW01) (Sub P.C. board)
•
Check remote controller.
–
119
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Error mode detected by outdoor unit
Check code
Operation of diagnostic function
Cause of operation
Status of air conditioner
Inverter over-current protective circuit operates.
(For a short time)
All stop
Condition
Judgment and measures
Displayed when error is detected
1. Inverter immediately stops even if restarted.
•
Compressor rare short
2. Check IPDU.
•
Cabling error
Error on current detection circuit
•
Current value is high at AC side even while compressor stops.
•
Phase of power supply is missed.
Coming-off, disconnection or short of outdoor temp sensor
All stop
All stop
Displayed when error is detected
1. Compressor immediately stops even if restarted.
: Check IPDU.
2. Phase-missing operation of power supply
•
Check power voltage of R, S, T.
Coming-off, disconnection or short of outdoor temp sensor
Compressor drive output error
•
Tin thermistor temp, Tin error
(IPDU heat sink temp. is high.)
Communication error between
IPDU
•
Connector coming-off between CDB and IPDU
All stop
All stop
Compressor does not rotate.
(Over-current protective circuit works when constant time passed after activation of compressor.)
All stop
Discharge temp error
•
Discharge temp over specified value was detected.
All stop
Displayed when error is detected
1. Check outdoor temp sensor (TE, TS).
2. Check CDB.
Displayed when error is detected
1. Check outdoor temp sensor (TD).
2. Check CDB.
Displayed when error is detected
1. Abnormal overload operation of refrigerating cycle
2. Loosening of screws and contact error of IPDU and heat sink
3. Cooling error of heat sink
4. Check cabling of CDB and IPDU.
Displayed when error is detected
Displayed when error is detected
1. Compressor error (Compressor lock, etc.)
: Replace compressor.
2. Cabling trouble of compressor (Phase missing)
1. Check refrigerating cycle. (Gas leak)
2. Error of electron control valve
3. Check pipe sensor (TD).
Displayed when error is detected
1. Check power voltage. (AC200V±20V)
2. Overload operation of refrigerating cycle
3. Check current detection circuit at AC side.
Compressor breakdown
•
Operation frequency lowered and stops though operation had started.
All stop
High-voltage protection error by TE sensor
•
TE temp over specified value was detected.
All stop
DC outdoor fan motor error
•
IDC operation or lock was detected by DC outdoor fan driving.
All stop
Error on IPDU position detection circuit
Coming-off, disconnection or short of outdoor temp sensor
All stop
Operation continues
Displayed when error is detected
Displayed when error is detected
1. Overload operation of refrigerating cycle
2. Check outdoor temp sensor (TE).
1. Position detection error
2. Over-current protection circuit operation of outdoor fan drive unit
•
Check CDB.
•
Refer to Judgment of outdoor fan.
Displayed when error is detected
1. Position detection circuit operates even if driving by removing 3P connector of compressor.
•
Replace IPDU.
Displayed when error is detected
1. Check outdoor temp sensor (TO).
2. Check P.C. board.
–
120
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14-4. Troubleshooting for Each Check Code
[1A error]
Are connections of CN301 and
CN300 of CDB correct?
YES
Does the fan rotate without trouble when handling the fan with hands under condition of removing CN301 and CN300 from CDB?
YES
NO
The status that the resistance values between leads below are 50 to 80 for 40W motor (ICF-140-43) and 25 to 55 for 60W motor (ICF-140-63-1) is normal.
NO of motor winding of connector (CN301)
YES
The status that there is
5k to 20k resistance values between of motor position detection of connector
(CN300, CN302) is normal.
YES
NO
CN301
CN300
•
For RAV-SM560AT-E, CN300 changes to
CN301, and CN301 to CN300, respectively.
Normal fan motor Defective fan motor
(CDB error)
NOTE :
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.
When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.
Objective P.C. board
Fan motor winding
Motor position detection
RAV-SM560AT-E
Control P.C. board
CN300
CN301
RAV-SM800AT-E
CDB P.C. board
CN301
CN300
–
121
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[04 error]
NO
Does outdoor unit operate?
YES
Are 1, 2, 3 inter-unit cables normal?
YES
NO
Correct inter-unit cable.
Are connections of connectors normal?
YES
NO
Correct connection of connector.
Is DC310 to 340V applied between terminals of electrolytic capacitor of IPDU main circuit?
YES
* For RAV-SM560AT-E, check case thermo.
NO
Replace IPDU.
* For RAV-SM560AT-E, replace control P.C. board.
Is DC310 to 340V power supplied to CDB?
(CN03)
YES
NO
Replace IPDU.
NO
Does LED (D05) (Orange) on indoor main P.C. board flash?
YES
Is case thermo
(CN500) connected?
YES
NO
Correct connection of connector.
Does case thermo operate?
YES
NO
Check CDB.
Defect Replace
* For RAV-SM560AT-E, replace control P.C. board.
Check CDB.
Defect Replace
* For RAV-SM560AT-E, replace control P.C. board.
Check main indoor main P.C. board
(MCC-1370A).
Defect Replace
Check/Correct charged refrigerant amount.
* For RAV-SM560AT-E, replace control P.C. board.
–
122
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[08 error]
Check and replace
2-way valve, check valve, or electron expansion valve.
Is operation of
4-way valve normal?
YES
NO
NO
Is flow of refrigerant by
2-way valve, check valve, or electron expansion valve normal?
YES
Is 200V applied to
4-way valve coil terminal in heating operation?
NO
YES
Check 4-way valve.
Is circuit cable normal?
YES
NO
Check and correct circuit.
NO
Are characteristics of TC sensor resistance value normal?
* Refer to Characteristics-2.
YES
Replace TC sensor.
Check indoor main P.C. board
(MCC-1370A) and sub P.C. board (MCC-1370B).
Defect Replace
* For RAV-SM560AT-E, check control P.C. board.
Check CDB P.C. board.
YES
NO
Check CDB P.C. board.
Defect Replace
* For RAV-SM560AT-E, replace control P.C. board.
•
In cooling operation, if high pressure is abnormally raised, [08 error] may be displayed. In this case, remove cause of pressure up and then check again referring to the item [21 error].
[0C error]
Is connection of TA sensor connector
(Indoor main P.C. board CN04) normal?
YES
NO
Are characteristics of
TA sensor resistance value normal?
YES
NO
* Refer to Characteristics-1.
Check indoor P.C. board
(MCC-1370A).
Defect Replace
Correct connection of connector.
Replace TA sensor.
–
123
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[0d error]
Is connection of TC sensor connector
(Indoor P.C. board CN05) normal?
YES
NO
Are characteristics of
TC sensor resistance value normal?
YES
NO
* Refer to Characteristics-2.
Check indoor P.C. board
(MCC-1370A).
Defect Replace
Correct connection of connector.
Replace TC sensor.
[0F error]
Is connection of TCJ sensor connector
(Indoor P.C. board CN20) normal?
YES
NO
Are characteristics of
TCJ sensor resistance value normal?
YES
NO
* Refer to Characteristics-2.
Check indoor P.C. board
(MCC-1370A).
Defect Replace
Correct connection of connector.
Replace TCJ sensor.
–
124
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[99 error]
Is inter-unit cable of
A, B and C normal?
YES
NO
Is there no disconnection or contact error of connector?
NO
YES
Is individual (1 : 1) operation?
NO
YES
NO
Is unit set to No.1?
YES
NO
Are not No.1 unit duplicated?
YES
NO
Does indoor unit operate?
YES
Correct inter-unit cable of remote controller.
Correct connection of connector.
Check circuit cables.
Does LED (Green) on indoor main P.C. board flash?
(D13)
NO
YES
Set the unit to No.1.
Avoid duplication of unit No.1 setting.
Check remote controller P.C. board.
Defect Replace
Check indoor main P.C. board
(MCC-1370A).
Defect Replace
–
125
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[11 error]
Turn off the breaker once.
Turn on the breaker after approx. 10 seconds.
Does fan stop when operation stopped?
YES
NO
Is DC1V or more voltage applied between 5 + and 3
–
of the motor connector (CN210)?
YES
Start the operation with cooling mode [L (Low)].
NO
Does the fan rotate?
YES
Is DC280V or more voltage applied between 1 + and 3
–
of the motor connector (CN210)?
YES
(Connection status of motor)
Is DC15V or more voltage applied between 4 + and 3
–
of the motor connector (CN210)?
YES
Change the cooling mode to [H (High)].
NO
NO
Stop the operation and turn off the breaker.
After removing motor connector, turn on the breaker again and then stop the operation from remote controller.
NO
Is fan speed raised?
YES
Is DC15V voltage applied between 4 + and 3
–
of the motor connector (CN210)?
YES
Is DC1V or more voltage applied between 5 + and 3
–
of the motor connector (CN210) when changing the operation mode (except HEAT)?
(Check within approx. 15 seconds after operation has started.)
NO
YES
NO
Stop the operation and disconnect the receptacle. After removing motor connector, connect receptacle again and then stop the operation from remote controller.
NO
Normal fan motor
NO
Is DC1V or more voltage applied between 5 + and 3
–
of the motor connector (CN210) when changing the operation mode (except HEAT)?
(Check within approx. 15 seconds after operation has started.)
YES
NO
Does the cross flow fan rotate normally when handled with hands?
YES
Does 0 to 5V voltage
(revolutions return signal) generate between 6 + and 3
–
of the motor connector (CN210) when rotating the cross flow fan with hands under condition of operation-stop?
YES
Repair bering of the cross flow fan.
NO
–
126
– www.ilmalämpöpumput.com
Replace indoor fan motor.
Replace indoor main P.C. board
(MCC-1370A).
Replace indoor main P.C. board
(MCC-1370A).
Replace indoor fan motor.
Replace indoor main P.C. board
(MCC-1370A).
Replace indoor fan motor.
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[11 error]
Indoor fan starts rotating by inserting receptacle.
[Check output voltage (DC) of P.C. board fan motor.]
Measure the voltages of the motor connector
CN210 Pin 3 (GND (minus): Black) and Pin 5 (V line (plus): Yellow) under condition that indoor fan rotates.
DC1.0V or less DC1.0V or more
Defective indoor main P.C. board
(MCC-1370A)
Defective indoor fan motor
DC
CN210
Yellow
Black
P.C. board
6 (Blue)
5 (Yellow)
4 (White)
3 (Black)
2 –
1 (Red)
[12 error]
Is there no turbulence of power supply?
YES
Check indoor main P.C. board (MCC-1370A).
Defect Replace
NO
Check power voltage. Improve line.
Check and eliminate noise, etc.
– 127 – www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[14 error]
Is power voltage normal?
YES
NO
Improve the power supply line.
YES
Are connections of cabling/connector normal?
YES
NO
* For RAV-SM560AT-E, check RY01 on the control P.C. board.
Check and correct circuit cables.
Correct connection of connector.
Check and correct reactor connection.
Does RY01 relay of
IPDU operate?
NO
YES
Is not
“
14
”
errors output when an operation is performed by removing 3P connector of compressor?
YES
* Single-phase type is not provided to RAV-SM560AT-E.
NO
Replace IPDU.
Is not AC fuse fused?
NO
* Replace control P.C. board of RAV-SM560AT-E.
Replace IPDU.
* Replace control P.C. board of RAV-SM560AT-E.
Is compressor normal?
YES
NO
Check IPDU.
Defect Replace
Check rare short of compressor trouble.
Defect Replace
[16 error]
Are connections of cable/connector normal?
YES
NO
NO
Is compressor normal?
YES
YES
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2 ?)
NO
YES
YES
Is not winding opened?
NO
Check and correct circuit cabling such as cabling to compressor.
Compressor error Replace
Compressor error Replace
Compressor error Replace
Check IPDU P.C. board.
Defect Replace
–
128
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[18 error]
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
YES
NO
Correct connection of connector.
Are characteristics of TE/TS sensor resistance values normal?
YES
* (For RAV-SM560AT-E, CN600 TE sensor and CN603 TS sensor)
NO
Replace TE and TS sensors.
* Refer to Characteristics-3.
Check CDB.
Defect Replace
* For RAV-SM560AT-E, replace the control P.C. board
[19 error]
Is connection of TD sensor connector of CDB CN600 normal?
YES
Are characteristics of TD sensor resistance value normal?
YES
NO
Correct connection of connector.
* For RAV-SM560AT-E, CN601 on control P.C. board
NO
Replace TD sensor.
Check control P.C. board.
Defect Replace
* Refer to Characteristics-4.
[1C error] * Except RAV-SM560AT-E
Are connections of
CDB CN800 and CDB IPDU CN06 connectors normal?
YES
NO
Was the error just after power ON determined?
NO
YES
Are cabling/connector normal?
YES
NO
Correct connection of connector.
Check cabling between IPDU and CDB and connector.
IPDU P.C. board error
Defect Replace
Is there no abnormal overload?
NO
YES
NO
Is IPDU P.C. board come to closely contact with heat sink?
YES
Improve and eliminate the cause.
Correct mounting.
IPDU P.C. board error
Defect Replace
–
129
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[1d error]
NO
Is power voltage normal?
YES
Are connections of cable/connector normal?
YES
NO
NO
Is compressor normal?
YES
Improve power line.
Check and correct circuit cabling such as cabling to compressor
(phase missing) and connector.
Is there no slackened refrigerant?
YES
NO
Does electron expansion valve normally operate?
YES
NO
Compressor lock Replace
Check TE and TS sensors. Replace
Check electron expansion valve. Replace
Check IPDU and CDB.
Defect Replace
* For RAV-SM560AT-E, check control P.C. board.
Defect Replace
[1E error]
Is protective control such as discharge temprelease control normal?
YES
NO
Are connections of cable/connector normal?
YES
NO
Correct the cabling and connection of connector.
Check parts. Defect Replace
Is charged refrigerant amount normal?
YES
NO
YES
Is not abnormal overload?
NO
NO
Are characteristics of
TD sensor resistance value normal?
YES
* Refer to Characteristics-4.
Check and correct the charged refrigerant amount.
Improve and delete the cause
Replace TD sensor.
Check CDB.
Defect Replace
[1F error]
Is power voltage normal?
YES
Is not abnormal overload?
NO
Is the circuit detected by current sensor normal?
YES
* For RAV-SM560AT-E, check control P.C. board.
NO
YES
NO
Improve power line.
Improve and delete the cause.
Check and correct circuit cables.
Check IPDU.
Defect Replace
* For RAV-SM560AT-E, check control P.C. board.
–
130
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[21 error] [ ] LCD flash
Is high-voltage protective operation by
TE sensor normal?
YES
NO
Is connection of cabling connector normal?
YES
NO
Correct connection of cabling connector.
Check TE sensor.
Defect Replace
Does cooling outdoor fan normally operate?
YES
NO
Is connection of connector normal?
YES
NO
Correct connection of connector.
NO
Is fan motor normal?
YES
Replace fan motor.
NO
Check TE, TC, TS sensors.
Does electron control valve normally operate?
YES
Do not TD and TO sensors come off the detection part?
NO
YES
Replace electron expansion valve.
Correct coming-off.
Are characteristics of
TD, TO, TC sensor resistance values normal?
YES
NO
Replace TD, TO, and TC sensors.
* Refer to Characteristics-3 and 4.
Check charged refrigerant amount.
Check liquid/gas valves.
Check abnormal overload.
Check CDB.
Defect Replace
* For RAV-SM560AT-E, check control P.C. board.
–
131
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
14-5. Simple Check Method for Main Parts
14-5-1. Indoor unit
No.
Part name Check procedure
1 Temperature sensor (Ta)
Heat exchanger sensor (Tc)
Heat exchanger sensor (Tcj)
Measure the resistance value with tester by removing the connector.
(Normal temperature)
Normal value
10 k
Ω
to 20 k
Ω
Refer to Characteristics table.
2 Louver motor
MP35EA12
Measure the resistance value of each winding coil with tester.
(Under normal temperature 25
°
C)
Brown
Red
Orange
Yellow
Pink
Blue
1
2
3
4
5
6
1
2
3
4
5
6
Position
Between 1 and 2
Between 1 and 3
Between 1 and 4
Between 1 and 5
Resistance value
130 ± 40
Ω
3 Indoor fan motor
(ICF-340-30-1) lMeasure the resistance value of each winding coil with tester.
lFor P.C. board side, proceed to [11 error] of
“
Troubleshooting procedure for each check code
”
.
Position
Between
(Black) and
(Red)
Between
(Black) and
(White)
Between
(Black) and
(Yellow)
Between
(Black) and
(Blue)
Resistance value
∞
(M
Ω
)
27 to 47 k
Ω
140 to 280 k
Ω
∞
(M
Ω
)
Red 1 1
Black 3
White
Yellow
4
5
Blue 6
3
4
5
6
1
3
4
5
6
1
2
3
4
5
6
–
132
– www.ilmalämpöpumput.com
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Relational graph of temperature sensor resistance value and temperature
Resistance
(k )
10
20
0
10 20
40
TA sensor
Caracteristics-1
30
Resistance
(k )
20
30 40
Temperature [ C]
50
TC, TCJ sensor
Caracteristics-2
10
0
–
10 0 10 20 30 40 50 60 70
Temperature [ C]
20
TE, TO, TS sensor
200
Caracteristics-3
Resistance
(k )
(10 C or lower)
100
Resistance
(k )
(10 C or higher)
10
0
200
-10 0 10 20 30 40
Temperature [ C]
50 60 70
0
TD sensor
Caracteristics-4
Resistance
(k )
(50 C or lower)
100
20
Resistance
(k )
(50 C or higher)
10
0 0
50
Temperature [ C]
100
–
133
– www.ilmalämpöpumput.com
100
50
Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
Resistance
(K )
200
150
Caracteristics-5
TH sensor
Resistance
(K )
(10 C or higher)
20
15
10
5
–
30
–
20
–
10 0 10 20 30 40
Temperature [
º
C]
50 60 70 80 90 100
–
134
– www.ilmalämpöpumput.com
advertisement
Key Features
- 4-Way Air Discharge Cassette Type
- Concealed Duct Type
- High-Wall Type
- Flexible Type
- R410A Refrigerant
- Turbo Fan
- Energy Consumption Effect Ratio
- Compressor Thermo
- Pulse Motor Valve
- Wired Remote Controller
Frequently Answers and Questions
What are the different types of indoor units available?
What is the standard capacity of the units?
What is the sound level of the outdoor unit?
Related manuals
advertisement
Table of contents
- 3 SPECIFICATIONS
- 12 AIR DUCTING WORK
- 13 CONSTRUCTION VIEWS (EXTERNAL VIEWS)
- 20 SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
- 22 WIRING DIAGRAM
- 28 SPECIFICATIONS OF ELECTRICAL PARTS
- 30 REFRIGERANT R410A
- 38 CONTROL BLOCK DIAGRAM
- 48 CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
- 65 TROUBLESHOOTING
- 88 REPLACEMENT OF SERVICE INDOOR P.C. BOARD
- 92 SETUP AT LOCAL SITE AND OTHERS
- 103 ADDRESS SETUP
-
108
TROUBLESHOOTING
- 135 DETACHMENTS
- 168 EXPLODED VIEWS AND PARTS LIST