Horizontal Mounting Guidelines – Single Drive Unit Only. Allen-Bradley PowerFlex 755 IP00, NEMA/UL Open Type

Add to My manuals
76 Pages

PowerFlex 755 IP00, NEMA/UL Open Type Drive is a powerful drive designed for use in user-supplied enclosures. It's suitable for a range of applications, including industrial automation, process control, and material handling. The drive provides a variety of features that make it easy to install and operate, including a user-friendly interface and a range of mounting options.

advertisement

Horizontal Mounting Guidelines – Single Drive Unit Only. Allen-Bradley PowerFlex 755 IP00, NEMA/UL Open Type | Manualzz

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Horizontal Mounting

Guidelines – Single Drive

Unit Only

To guard against sub-panel flexing, support pieces should be added to the underside of the panel along each long edge.

Figure 8 - Open Style Drive - Horizontal Installation

26

Converter (AC Input) Field

Termination Kit

Optional Inverter (DC Bus)

Field Termination Kit

Inverter (AC Output) Field

Termination Kit

Figure 9 - Bottom Inlet Ducting Kit Dimensions

325.00 (12.795)

312.00 (12.283)

287.00 (11.299)

207.00 (8.150)

127.00 (5.000)

47.00 (1.850)

0.00 (0.000)

16.00 (0.630)

15.00 (0.591) 0.00 (0.000)

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

Bottom Inlet Duct Kit

M6 x 1 - 18 places

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Derating Guidelines for Horizontal Mounting - Three-Phase Input/Output, Frame 8 Only

Light Duty Normal Duty Heavy Duty

Catalog

Code

50/60 Hz Input Output 50/60 Hz Input Output 50/60 Hz Input Output

Volts Amps Volts Amps Power Volts Amps Volts Amps Power Volts Amps Volts Amps Power

380…400V AC Three-Phase Input, 2 kHZ Carrier Frequency

C460 400 450 0-400 439 200 KW 400 450 0-400 439 200 KW 400 321 0-400 313 160 KW

C540 400 488 0-400 475 224 KW 400 488 0-400 475 224 KW 400 381 0-400 371 200 KW

C567 400 511 0-400 497 250 KW 400 511 0-400 497 250 KW 400 394 0-400 384 200 KW

C650 400 625 0-400 609 315 KW 400 625 0-400 609 315 KW 400 450 0-400 439 224 KW

C750 400 665 0-400 647 355 KW 400 665 0-400 647 355 KW 400 488 0-400 475 250 KW

C770 400 694 0-400 676 355 KW 400 694 0-400 676 355 KW 400 536 0-400 522 300 KW

480V AC Three-Phase Input, 2 kHZ Carrier Frequency

D430 480 387 0-460 394 300 HP 480 387 0-460 394 300 HP 480 295 0-460 301 200 HP

D485 480 435 0-460 443 350 HP 480 435 0-460 443 350 HP 480 330 0-460 336 250 HP

D545 480 470 0-460 479 400 HP 480 470 0-460 479 400 HP 480 362 0-460 369 250 HP

D617 480 567 0-460 577 450 HP 480 567 0-460 577 450 HP 480 387 0-460 394 300 HP

D710 480 610 0-460 622 500 HP 480 610 0-460 622 500 HP 480 435 0-460 443 350 HP

D740 480 639 0-460 650 550 HP 480 639 0-460 650 550 HP 480 492 0-460 501 400 HP

600V AC Three-Phase Input, 2 kHZ Carrier Frequency

E295 600 272 0-600 288 250 HP 600 272 0-600 288 250 HP 600 208 0-600 220 200 HP

E355 600 302 0-600 320 300 HP 600 302 0-600 320 300 HP 600 226 0-600 239 200 HP

E395 600 332 0-600 352 350 HP 600 332 0-600 352 350 HP 600 251 0-600 266 250 HP

E435 600 352 0-600 373 350 HP 600 352 0-600 373 350 HP 600 272 0-600 288 250 HP

E460 600 390 0-600 413 400 HP 600 390 0-600 413 400 HP 600 302 0-600 320 300 HP

E510 600 416 0-600 441 450 HP 600 416 0-600 441 450 HP 600 325 0-600 344 350 HP

690V AC Three-Phase Input, 2 kHZ Carrier Frequency

F265 690 252 0-690 267 250 KW 690 252 0-690 267 250 KW 690 164 0-690 174 186 KW

F330 690 283 0-690 300 300 KW 690 283 0-690 300 300 KW 690 203 0-690 215 200 KW

F370 690 313 0-690 332 335 KW 690 313 0-690 332 335 KW 690 235 0-690 249 250 KW

F415 690 351 0-690 373 375 KW 690 351 0-690 373 375 KW 690 283 0-690 300 300 KW

F460 690 382 0-690 405 400 KW 690 382 0-690 405 400 KW 690 286 0-690 304 315 KW

F500 690 404 0-690 429 425 KW 690 404 0-690 429 425 KW 690 316 0-690 335 350 KW

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

27

advertisement

Key Features

  • IP00, NEMA/UL Open Type
  • Frames 8-10
  • 200 - 1500 kW (250 - 2000 Hp)
  • User-supplied enclosure
  • AC and DC input options
  • Control pod mounting
  • Roll-out cart support
  • Detailed installation instructions
  • Safety guidelines

Related manuals

Frequently Answers and Questions

What are the available frame sizes for the PowerFlex 755 drive?
The PowerFlex 755 drive is available in frames 8, 9, and 10.
What is the power range of the PowerFlex 755 drive?
The PowerFlex 755 drive has a power range of 200 - 1500 kW (250 - 2000 Hp).
What type of enclosure is required for the PowerFlex 755 drive?
The PowerFlex 755 drive requires a user-supplied enclosure. The enclosure must meet certain requirements, such as ingress protection and ventilation.
What type of input options are available for the PowerFlex 755 drive?
The PowerFlex 755 drive is available with both AC and DC input options.
What are the control pod mounting options for the PowerFlex 755 drive?
The control pod can be mounted within the drive or remotely. Refer to publication 750-IN015 for remote mounting information.