ABB DCS800 is a powerful and versatile drive designed for a wide range of industrial applications. It offers a variety of features and functions that make it ideal for controlling AC motors in demanding environments. Some of the key features of the DCS800 include precise speed and torque control, advanced diagnostics, and a rugged design. The DCS800 is also easy to install and operate, making it a great choice for both new and experienced users.
advertisement
51
Exchange of Thyristors for Size D6
Installation of "Disc Type" thyristor in converters size D6 (1900...3000 A)
All DCS800 converters sizes D5/D6/D7 are equipped with disk type thyristors. The structure of the "Disc type" semiconductor component is such that it requires a certain compression force to operate. The prevention of overheating of the component essentially depends on a good heat dissipation between the semiconductor and the conducted heat sink. It is thus important that all joints have good thermal and electrical conduction.
Required Tools
Special tools or material needed in addition to standard tools for the exchange of thyristor modules:
Torx TX10,
Torque spanner for electrical connections: 13 Nm (M8)
TX25
50
Screws are metric type; use appropriate nuts.
17 mm ring spanner for fuse and busbar connections.
24 mm ring spanner for press clamp.
Tissue paper / solvent (e.g. ethanol).
Thermal joint compound: type BECHEM-RHUS SU 2
(grease)
Manufacturer: Carl Bechem GmbH, 58089 Hagen
ABB Service: GHSN 390 001 P 0001
Disassembly tool
Note:
DCF 1066721 P1
For more detailed information about the wiring of the power part, see Hardware
Manual.
Therefore strict observance of the build in instructions given below is of utmost importance. Make sure that the new component can replace the old one in
accordance with the spare part list ( see Appendix A)
.
Semiconductors and heat sinks are to be handled carefully to avoid scratches and other damage. Avoid touching the contact surfaces. Do not lift the semiconductor with the gate wire. Do not lift the semiconductor by touching the current contact surfaces. Do not damage the welding flange or the contact surface.
Before you start work, disconnect the converter completely from the power supply then check the voltage free condition and make sure, everything is located in an electrically and mechanically safe condition!
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
52
Disk type thyristors
Some converter modules size D6 are equipped with different disc type thyristors.
For easy identification the name plate of the converter module is marked with “a” after the voltage identification:
Converter with original thyristor type T 1329Nxxx
Id code: 3ADC340081P0001
DCS800-S01-1900-08
DCS800-S02-1900-08
DCS800-S01-2050-05
DCS800-S02-2050-05
DCS800-S01-2050-06
U
1
3 ~ 800 VAC
3 ~ 800 VAC
3 ~ 525 VAC
3 ~ 525 VAC
3 ~ 600 VAC
Converter with second thyristor type T 1xxx-24
Id code: 3ADC340098P0001
DCS800-S01-1900-08
DCS800-S02-1900-08
DCS800-S01-2050-06
a a
DCS800-S01-2050-05
a
DCS800-S02-2050-05
a a
DCS800-S02-2050-06
DCS800-S01-2050-07
3 ~ 600 VAC
3 ~ 690 VAC
DCS800-S02-2050-06
DCS800-S01-2050-07
a a
DCS800-S02-2050-07 3 ~ 690 VAC
DCS800-S02-2050-07
a
Parts list
The current and voltage ratings of original and second thyristor type are the same, but the sizes of gate and cathode terminals are different. Thus it is not possible to interchange both thyristor types as spares.
Attention: Use always the correct spare thyristor!
Original thyristor type
Thyristor T 1329Nxxx with Id code 3ADC340081P0001
Original thyristor type
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
Gate (4):
Cathode (5):
Faston 2.8 x 0.8 mm
Faston 4.8 x 0.8 mm
Conductive plate: Diameter 48 mm
Second thyristor type
Thyristor T 1xxx-24 with Id code 3ADC340098P0001
53
Second thyristor type
Gate (y): Round terminal D = 1.5 mm
Cathode (K
1
): Faston 4.8 x 0.5 mm
Conductive plate: Diameter 50 mm
BCT thyristors
In some converter modules size D6 so called BCT’s (Bidirectional-Controlled-
Thyristors) are used. BCT’s are a pair of anti-parallel thyristors in one disk type
housing. They can easily identified by the second pair of gate leads. The second gate is marked with Gate B on the thyristor.
Faston 4.8 x 0.5
Gate A
Faston 6.3 x 0.8
Gate B
Gate B
BCT.dsf
Gate A
Gates of BCT
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
54
Note:
The Faston connectors of the gates are of different size.
Gate A should always be in front of the clamped heat sinks due to cooling reasons.
Location of BCT’s gate A when built in
Find faulty thyristor
1.
Find the defective branches by performing an OHM test (both polarities)
between U1, V1, W1 and C1, D1 (see picture
Anti-parallel B6-bridges with branching fuses
2.
Disconnect the branching fuses of the defective branches.
3.
Find the defective thyristors by performing an OHM test (both polarities) over their heat sinks.
4.
In a 4 - quadrant converter with BCT’s change the BCT.
5.
In a 4 - quadrant converter with 2 single thyristors change both thyristors clamped between the same heatsinks at once.
Note:
Because “Disc Type” semiconductors need a certain compression force to operate properly, a measurement outside the clamped heat sinks might be wrong. To be sure which thyristor is broken change only one thyristor, clamp the heat sinks again and repeat step three.
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
55
Remove faulty thyristor
1.
Replace all blown fuses and reconnect all fuses taken out during search for the faulty thyristor.
2.
Remove the screws of the DC - busbar plates adjacent to the defective thyristors
DCbusbar plates
Location of the DC - busbar plates
Note:
It depends on the location of the defective thyristor which DC-busbar plates have to be disconnected.
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
56
3.
Write down the direction and location of the thyristors to be removed and mark their gate leads. In case of BCT’s add the position of the gates.
4.
Remove the gate leads if possible.
5.
Loosen the mounting clamp at the top of the thyristor stack. mounting clamp indicating spring
Handling of indicating spring and mounting clamp
Attention: While loosen the mounting clamp the indicating spring must be pulled
out a little, otherwise the spring will be damaged!
Do not remove the nuts totally, otherwise the treaded rods will fall down!
6.
Pull out both DC-busbar plates.
DCbusbar plates
DC-busbar plates
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
7.
Attach the disassembly tool at the faulty thyristor and prize open the upper and lower heat sinks.
57
push down push down
Use of disassembly tool
8.
Remove the thyristors with e.g. a pair of pliers.
Attention: To centre the thyristors spring pins are used. The pins are inlayed into
all lower heat sinks. Open the gap wide enough that the thyristor and the pins are not damaged while removing the thyristor!
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
58
Install new thyristor
1.
Ensure that the new thyristor is of the correct type ( see appendix A) . Keep the
semiconductor and its surroundings clean. If necessary clean them with a piece of tissue paper moistened with solvent.
Note:
Do not touch the polished surfaces of the thyristor.
2.
Clean the polished surfaces of the semiconductor with a piece of tissue paper moistened with solvent. Dry all surfaces. Spread a thin layer of heat conducting paste on both sides of the thyristor, if necessary use a rubber spatula.
Prepare disk type thyristor
3.
Clean all parts with tissue paper moistened with solvent, which have had or will have contact with the thyristor or each other (lower / upper heat sink). Do not clean the surfaces of grease too thoroughly, because the aluminum surfaces will oxidize in a few seconds. Dry all surfaces.
4.
Centre the thyristors by means of the spring pins.
Note:
Be sure that the thyristor is installed in the right direction. Do not pinch or cut the gate leads or any other cable.
5.
Turn the thyristor so that the gate leads point in the right direction. When changing BCT’s make sure, that gate A is in front (see fig.
on
6.
Connect the gate leads if possible.
7.
Insert first the top DC-busbar plate and then the bottom one.
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
DC-busbar plates and heatsinks
DC-busbar plates and adjacent heat sinks
Note:
The DC - busbar plates should line up with the adjacent heat sinks.
8.
Reconnect the DC-busbars.
9.
Tighten the nuts of the mounting clamp by hand so that the clamp is in parallel with the contact surface of the heat sinks.
59
Torque indicating spring loose condition
Mounting clamp; loose condition
Note:
The indicating spring is a very sensitive instrument and must be handled with care.
10.
Tighten each nut in turn, half a turn at a time with the help of a ring spanner until the indicating spring clicks into position “correct torque”. Do not tighten the screws any further.
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
60
Torque indicating spring correct torque
Mounting clamp, correct torque
Note:
The correct torque is indicated by means of the welded indicating spring.
11.
Perform an OHM test to make sure the thyristor is ok.
12.
Reconnect all other dismantled parts.
13.
Perform an OHM test between U1, V1, W1 and C1, D1 to make sure the power part is ok.
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
61
front
Stack
rear
C1(+)
V11
V24
U1
V21
V14
D1(-)
V16
V23
V1
V26
V13
C1(+)
V15
V22
W1
D1(-)
V25
V12
View from the right
A6_thyr_locat.dsf
Location of thyristors in frame D6 (4-Q bridge with single thyristors)
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
62
front
stack
rear
C1(+)
V11 / V24
U1
V14 / V21
D1(-)
V16 / V23
V1
V13 / V26
C1(+)
V15 / V22
W1
D1(-)
V12 / V25
View from the right
A6_thyr_locat.dsf
Location of thyristors in frame D6 (4-Q bridge with BCT’s)
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
63
front
stack
rear
C1(+)
V11
U1
V14
D1(-)
V16
V1
V13
C1(+)
V15
W1
D1(-)
V12
View from the right
A6_thyr_locat.dsf
Location of thyristors in frame D6 (2-Q bridge with single thyristors)
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
64
C1(+)
D1(-)
U1
V1
W1
F11
F14
F16
F13
F15
F12
C1(+)
F11
U1
F14
D1(-)
F16
V1
F13
C1(+)
F15
W1
F12
D1(-)
A6_branch_fuse_locat.dsf
Location of parallel branch fuses frame D6
Exchange of Thyristors for Size D6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
3ADW000195R0501 DCS800 Service Manual e e
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Key Features
- Precise speed and torque control
- Advanced diagnostics
- Rugged design
- Easy to install and operate
- Wide range of applications
Related manuals
Frequently Answers and Questions
What are the main benefits of using the DCS800 drive?
What are some of the applications that the DCS800 drive is suitable for?
How do I install and operate the DCS800 drive?
advertisement
Table of contents
- 1 DCS800
- 5 Safety instructions
- 5 What this chapter contains
- 5 To which products this chapter applies
- 5 Usage of warnings and notes
- 6 Installation and maintenance work
- 7 Grounding
- 9 Mechanical installation
- 10 Operation
- 13 Table of contents
- 16 Introduction
- 16 How to use this manual
- 16 Contents of this manual
- 16 Target group
- 16 Associated publications
- 17 Storage and transport
- 17 Name plate and type code
- 18 Type code
- 19 Current and voltage ratings
- 21 Fault Tracing Thyristors
- 21 Tools
- 21 For commissioning and fault tracing
- 22 Additionally for service and preventive maintenance
- 22 How to detect a faulty thyristor
- 22 A fuse is blown
- 23 DC-current pulses measured by an oscilloscope
- 23 Thyristor diagnosis
- 23 Ripple monitor
- 24 How to find a faulty thyristor
- 24 Converters size D1 to D4 (20...1000 A)
- 24 Blown fuses
- 25 Converters size D5, D6, and D7 (900...5200 A)
- 25 Blown fuses
- 25 Ripple monitor
- 27 Handling the Semiconductors
- 27 General Instruction how to handle the Semiconductors
- 29 Exchange of Thyristors for Size D1 to D4
- 29 Installation of OnBoard bridge and thyristor modules in converters size D1 to D4 (20...1000 A)
- 29 Required Tools
- 29 Find faulty thyristor modules
- 30 Remove faulty thyristor modules
- 34 Install new thyristor modules
- 36 Remove faulty OnBoard bridge (V1)
- 36 Install new OnBoard bridge (V1)
- 37 OnBoard bridge (V1) and thyristor module location in DCS800-S01 (2-Q) units
- 38 OnBoard bridge (V1) and thyristor module location in DCS800-S02 (4-Q) units
- 39 OnBoard bridge and thyristor module terminals
- 41 Exchange of Thyristors for Size D5
- 41 Installation of "Disc Type" thyristor in converters size D5 (900...2000 A)
- 41 Required Tools
- 42 Disk type thyristors
- 42 Original thyristor type (900 A)
- 43 Second thyristor type (900 A)
- 43 Original thyristor type (1200 A)
- 44 Second thyristor type (1200 A)
- 45 Find faulty thyristor
- 46 Remove faulty thyristor
- 47 Install new thyristor
- 51 Exchange of Thyristors for Size D6
- 51 Installation of "Disc Type" thyristor in converters size D6 (1900...3000 A)
- 51 Required Tools
- 52 Disk type thyristors
- 52 Original thyristor type
- 53 Second thyristor type
- 53 BCT thyristors
- 54 Find faulty thyristor
- 55 Remove faulty thyristor
- 58 Install new thyristor
- 65 Exchange of Thyristors for Size D7
- 65 Installation of "Disc Type" thyristor in converters size D7 (2050...5200 A)
- 65 Required Tools
- 66 Find faulty thyristor
- 69 Install new thyristor
- 75 Exchange of SDCS-CON-4
- 75 General
- 75 Required Tools
- 75 Overview SDCS-CON-4 exchange
- 75 1. Save parameters
- 77 2. Write down type code of the drive
- 77 3. Set jumpers on the new SDCS-CON-4 according to the old SDCS-CON-4
- 77 4. Exchange the SDCS-CON-4
- 80 5. Set type code of the drive
- 80 6. Enable application program
- 80 7. Download and compare parameters
- 83 Service
- 83 How to remove the converter fans in frames D1 to D3 (two fans)
- 83 230 VAC:
- 83 115 VAC:
- 84 Removing the converter fans
- 87 How to remove the converter fans in a frame D3 (four fans)
- 87 230 VAC:
- 87 115 VAC:
- 88 Removing the converter fans
- 92 How to remove the converter fan in a frame D6
- 93 How to remove the converter fan in a frame D7
- 94 DCS800 firmware download
- 94 General
- 94 Download SDCS-CON-4 firmware
- 94 Requirements:
- 94 Workspaces
- 94 Firmware / text file
- 97 Start download tool:
- 97 Choose workspace:
- 98 Activate firmware download:
- 99 Choose COM Port and communication speed:
- 100 Download firmware file to device:
- 101 Disconnect tool:
- 102 Activate text download:
- 103 Choose COM Port and communication speed:
- 104 Download text file to device:
- 105 Disconnect tool:
- 106 Close download tool
- 107 Add firmware or text files
- 107 Start download tool:
- 107 Choose workspace:
- 113 Close download tool:
- 114 Create a workspace
- 114 Start download tool:
- 114 Create new workspace:
- 115 Name new workspace:
- 117 Choose Device And Kernel:
- 118 Communication Port:
- 119 Device Settings:
- 120 Connection Type:
- 121 Programming Options:
- 121 Now the project for the firmware file is finished:
- 123 Choose Device And Kernel:
- 124 Communication Port:
- 125 Device Settings:
- 126 Connection Type:
- 127 Programming Options:
- 127 Now the project for the text file is finished:
- 128 Close download tool:
- 129 Download SDCS-COM-8 firmware
- 131 Set type code
- 133 Type code table
- 134 DC-Motor neutral zone adjustment
- 134 Types concerned
- 134 Summary
- 134 General
- 135 Preventive Maintenance
- 136 Recommended regular maintenance
- 136 Maintenance schedule
- 137 Annual preventive maintenance
- 140 3 years preventive maintenance
- 141 6 years preventive maintenance
- 143 9 years preventive maintenance
- 145 Appendix A - Spare Parts List