FX
3U
Series Programmable Controllers
User’s Manual - MODBUS Serial Communication Edition
9 Slave Specification
9.2 MODBUS device address allocation
1
Command Code
0x0B
0x0C
0x0F
0x10
Subcommand
Code
Command Name Details
Get Communication Event
Counter
Get Communication Event
Log
Write Multiple Coils
Write Multiple Registers
Read communication event counter
Read communication event log
Write multiple binary (R/W) devices
Write multiple 16 bit (R/W) registers
Slave ID details:
- PLC run/stop state
0x11 Report Slave ID
RUN Status: RUN = FFH
STOP = 00H
0x16
0x17
Mask Write Register
Read/Write Multiple
Registers
- Slave ID F3H (FX
3U
- same as computer link)
Note: No additional data is supported
Manipulate slave register with AND Mask / OR
Mask
Read/Write multiple 16 bit (R/W) registers
9.2
MODBUS device address allocation
The following information details device allocation when using default values and how to create user defined device address allocation values.
9.3
MODBUS device address allocation (Default Values)
The following table provides the default values for MODBUS address allocation for Bit devices and word devices.
Bit device:
MODBUS Binary Device Address
Discrete Inputs (Read Only) Coils (Read / Write)
0x0000-0x1DFF
0x1E00-0x1FFF
0x0000-0x1DFF
0x1E00-0x1FFF
0x2000-0x2FFF
0x3000-0x31FF
0x3200-0x32FF
0x3300-0x33FF
0x3400-0x34FF
0x2000-0x2FFF
0x3000-0x31FF
0x3200-0x32FF
0x3300-0x33FF
-
FX
3U
Device
M0-M7679
M8000-M8511
S0-S4095
TS0-TS511
CS0-CS255
Y0-Y377
X0-X377
2
3
4
5
6
7
8
9
10
85
FX
3U
Series Programmable Controllers
User’s Manual - MODBUS Serial Communication Edition
9 Slave Specification
9.3 MODBUS device address allocation (Default Values)
Word device:
MODBUS Word Device Address
Input-Register (Read Only) Holding-Register (Read / Write)
0x0000-0x1F3F
0x1F40-0x213F
0x2140-0xA13F
0x0000-0x1F3F
0x1F40-0x213F
0x2140-0xA13F
0xA140-0xA33F
0xA340-0xA407
0xA408-0xA477
0xA140-0xA33F
0xA340-0xA407
0xA408-0xA477
0xA478-0xA657
0xA658-0xA677
0xA678-0xA777
0xA778-0xA797
0xA798-0xA7A7
0xA7A8-0xA7B7
0xA7B8-0xA7C7
0xA478-0xA657
0xA658-0xA677
0xA678-0xA777
0xA778-0xA797
0xA798-0xA7A7
0xA7A8-0xA7B7
-
*1.
CN200-255 are 32-bit counters.
FX
3U
Device
D0-D7999
D8000-D8511
R0-R32767
TN0-TN511
CN0-CN199
CN200-CN255
*1
M0-M7679
M8000-M8511
S0-S4095
TS0-TS511
CS0-CS255
Y0-Y377
X0-X377
86