Chapter 4 Setup Operations for Changing/Adding Functions (Basic Setting Mode)
4.1
Changing the Auxiliary Alarm Function
This section explains the details of setting the alarm system items listed below.
• Diagnosis output using the alarm output relay (I01)
• Energized/De-energized operation of alarm output relays when alarms occur
• Alarm hysteresis
Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select the “ALARM.”
(RANGE)
(DIAG)
Diagnosis output
Select ON to set relay I01 to diagnosis output. This setting is valid only on models with the /A1, /A2, or /A3 option.
(ON)
(RELAY)
Output relay energize/de-energize
Select the relay’s energized or de-energized operation. This setting is valid only on models with the /A1, /A2, or /A3 option.
(ENERG)
(HYS)
Hysteresis
Select the hysteresis (0.0% (OFF) to
1.0%).
(OFF)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or key to select
2. Press the or key to select
key.
or
, and press the
, and press the
4
4-1
IM 04P03B01-01E
4.1 Changing the Auxiliary Alarm Function
Explanation
Diagnosis Output
When set to ON, alarm output relay I01 becomes a dedicated diagnosis output relay, and the operation is fixed to de-energized. Diagnosis output is a function which outputs a relay signal when an error is detected in the recording section, burnout detection function, or the A/D converter.
Output Relay Energize/De-Energize Operation
Sets whether the output relay is energized or de-energized when an alarm occurs.
Energize ( ): Energizes the relay when an alarm occurs. The relay is deenergized during normal operation.
De-energize ( ): De-energizes the relay when an alarm occurs. The relay is energized during normal operation.
Hysteresis
Sets the alarm hysteresis of the measurement channels.
The hysteresis width can be set in the range of 0.0% (OFF) to 1.0% of the recording span in 0.1 steps.
The hysteresis applies to all high limit and low limit alarms of measurement channels.
<Related Topics>
Setting the alarm: Section 2.2
4-2
IM 04P03B01-01E
4.2
Changing the Integration Time of the A/D
Converter
The integration time of the A/D converter can be set. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “INTG.”
(INTG)
Select the integration time of the
A/D converter.
(AUTO)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or
2. Press the or key to select
key to select
or
key.
, and press the
, and press the
Explanation
Integration Time
Selects the integration time of the A/D converter.
Selectable Settings Integration Time Scan Interval
(Pen Model)
50 Hz (
60 Hz (
Auto (
100 ms (
)
)
) 20 ms
16.7 ms
20 ms or 16.6 ms
*2
100 ms
125 ms
125 ms
125 ms
– )
*1
*1 Selectable only on the dot model.
*2 Automatically switch by detecting the power supply frequency.
Recording Interval
(Dot Model)
1 s
1 s
1 s
2.5 s
4
4-3
IM 04P03B01-01E
4-4
4.3
Setting the Burnout Detection Function
The burnout detection function of thermocouples can be set on 1-5V or TC input channels. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “B_OUT.”
(B_OUT)
Select the channel number.
(CH1)
Select the recording operation that is carried out when a burnout is detected.
(OFF)
Channel number
The settings are activated.
(OK)
4.
Press the key to set other channels.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or
2. Press the or key to select
key to select
or
key.
, and press the
, and press the
Explanation
Burnout
Selects the action taken when a burnout is detected at the 1-5V input or the thermocouple input.
Upscale (
Downscale (
): Records off the scale on the 100% side.
): Records off the scale on the 0% side.
OFF ( ): Disables the burnout detection function.
IM 04P03B01-01E
4.4
Setting the RJC Function on TC Input
Channels
The RJC mode can be set on TC input channels. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
For the procedure on how to enter values or characters, see page 18 in the
Operation Guide
.
To change the polarity, press the or key when the leftmost digit of the value is blinking.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Selects “RJC.”
(RJC)
Select the channel number.
(CH1)
(INT)
Channel number
Select the RJC mode of the thermocouple input.
(When external (EXT) is selected)
Set the compensation voltage when using the external RJC function.
The settings are activated.
(OK)
4.
Press the
1. Press the
key.
key to set other channels.
If you are done, press the key.
5.
To return to the Operation mode,
key, use the or key to select
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
RJC
Sets the RJC mode.
Internal (
External (
): Uses the RJC function of the recorder.
): Uses an external RJC function. If external is selected, set the compensation voltage.
Compensation Voltage
Sets the compensation voltage when using an external RJC function.
The compensation voltage can be set in the range of –19999 µV to 20000 µV.
4-5
IM 04P03B01-01E
4
4-6
4.5
Changing the Channel Recording Color (Dot
Model)
The trend recording color on the dot model can be changed. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “COLOR.”
(COLOR)
Select the channel number.
(CH1)
Select the recording color.
(PRPLE)
Channel number
The settings are activated.
(OK)
4.
Press the key to set other channels.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Color
Sets the recording color of measurement channels.
By default, the recording colors are set as follows:
Channel 1: Purple ( )
Channel 2: Red (
Channel 3: Green (
)
)
) Channel 4: Blue (
Channel 5: Brown (
Channel 6: Black ( )
)
IM 04P03B01-01E
4.6
Recording by Compensating for the Pen Offset along the Time Axis (Pen Model)
The pen offset along the time axis (pen model) can be compensated. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “POC.”
(POC)
Select ON to record by compensating for the pen offset along the time axis.
(OFF)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or
2. Press the or key to select
key to select
or
key.
, and press the
, and press the
Explanation
When pen offset compensation is turned ON, an asterisk is printed by the time on the periodic printout.
Note
When pen offset compensation is enabled, all pens are aligned with the reference pen (pen that is furthest to the back: pen 2 on the 2-pen model, pen 3 on the 3-pen model, and pen 4 on the 4pen model) for recording. When recording is started, only the reference pen moves until the offset is compensated. This is not a malfunction.
4
4-7
IM 04P03B01-01E
4-8
4.7
Turning Printouts ON/OFF
Select whether to print using channel numbers or tags and set whether to print the various printout items. Basic Setting mode cannot be entered when recording is in progress.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the key, the operation is cancelled, and the display returns to a higher level menu.
Select “PRINT.”
(PRINT)
(CH.TAG)
Channel No./tag printout
Select whether to use the channel numbers (CH) or tags (TAG) for the printout.
(CH)
(CHPRN)
Channel No. printout (Dot model only)
Select whether to print the channel number or tag by the trend recording.
Select ON or OFF.
(ON)
(ALARM)
Alarm printout
Select whether to print the alarm occurrence/release (ON1, ON2 or OFF).
(ON1)
(RCD)
Recording start printout
Select whether to perform recording start printout. Select ON or OFF.
(OFF)
(SPEED)
New chart speed printout
Select whether to perform new chart speed printout. Select ON or OFF.
(ON)
To the next page
IM 04P03B01-01E
Explanation
4.7 Turning Printouts ON/OFF
From the previous page
(SCALE)
Scale printout
Select whether to print the channel scale in periodic printout. Select ON or OFF.
(ON)
(PEN)
Recording color printout
(pen model only)
Select whether to print the recording color in periodic printout. Select ON or OFF.
This is valid on channels whose scale printout is turned ON.
(ON)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Channel Number/Tag Printout
Channel ( ): Prints the channel number.
Tag ( ): Prints the tag.
Alarm Printout
ON1 (
ON2 (
OFF (
): Prints the alarm information when an alarm occurs or releases.
): Prints the alarm information only when an alarm occurs.
): Does not print alarm information.
4
IM 04P03B01-01E
4-9
4-10
4.8
Setting the Periodic Printout
Procedure
Explanation
The periodic printout settings can be specified. Basic Setting mode cannot be entered when recording is in progress
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
For the procedure on how to enter values or characters, see page 18 in the
Operation Guide
.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “PER.”
(PER.)
Select the periodic printout interval mode.
(AUTO)
Set the reference time for the printout.
(00:00)
(When the interval mode is manual)
Select the periodic printout interval.
(1H)
Select whether to enable (INST) or disable (OFF) the periodic printout.
(INST)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1 . Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Periodic Printout
Selects the periodic printout interval mode.
Auto ( ): Automatically sets the printout interval in sync with the chart speed.
Manual ( ): Set the printout interval manually.
Reference Time
Sets the reference time for determining the times for executing the periodic printout.
The reference time is set in the range of 00 to 23 in 1 hour steps. Minutes cannot be specified.
(
Interval
Select the interval from 10, 12, 15, 20, 30 minutes, 1, 2, 3, 4, 6, 8, 12, and 24 hours
to ).
Turning ON/OFF the Periodic Printout
ON (instantaneous value) ( ): Prints the measured value at that point.
OFF ( ): Disables periodic printout.
IM 04P03B01-01E
4.9
Setting the Key Lock
The keys that can be locked and the password for releasing the key lock can be set.
Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
For the procedure on how to enter values or characters, see page 18 in the
Operation Guide
.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “LOCK.”
(LOCK)
(USE)
Select "USE" to set the target keys of the key lock.
(Displays the following when the target key setting is set to USE)
Set the password.
(****)
(RCd)
RCD key
Select whether to lock the key
(LOCK or FREE).
(FREE)
(FEED)
FEED key
Select whether to lock the key
(LOCK or FREE).
(FREE)
(MENU)
MENU key
Select whether to lock the key
(LOCK or FREE).
(FREE)
(M_PRN)
Manual printout
Select whether to lock the key
(LOCK or FREE).
(FREE)
To the next page
4-11
IM 04P03B01-01E
4
4.9 Setting the Key Lock
From the previous page
(LIST)
List printout
Select whether to lock the key
(LOCK or FREE).
(FREE)
(SLIST)
Setup list printout
Select whether to lock the key
(LOCK or FREE).
(FREE)
(MSG)
Message printout
Select whether to lock the key
(LOCK or FREE).
(FREE)
(B-CLR)
Printout buffer clear
Select whether to lock the key
(LOCK or FREE).
(FREE)
(PEN)
Pen exchange (Pen model only)
Select whether to lock the key
(LOCK or FREE).
(FREE)
(RIBON)
Ribbon exchange (Dot model only)
Select whether to lock the key
(LOCK or FREE).
(FREE)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
4-12
IM 04P03B01-01E
Explanation
4.9 Setting the Key Lock
Key Lock
Select the target keys (
Not use the key lock ( )
)
Password
Sets the password for releasing the key lock. Set the password using a four-digit number.
Operation of Keys to Be Key-Locked
Sets the operation of the keys to be key-locked. Select Lock (
(
RCD:
) for each key operation.
RCD
key
) or Free
FEED:
FEED
key
MENU:
MENU
key
M_PRN:
FUNC
key + manual printout operation
LIST:
FUNC
key + list printout operation
SLIST:
FUNC
key + setup list printout operation
MSG:
FUNC
key + message printout operation
B_CLR:
FUNC
key + clear operation of the printout buffer memory
PEN:
FUNC
key + the operation of moving the pen to an easily accessible position of replacement (pen model)
RIBON:
FUNC
key + the operation carried out when replacing the ribbon cassette with the power turned ON (dot model)
<Related Topics>
Activating/Releasing the Key Lock: “Activating/Releasing the Key Lock” in the
Operation
Guide
4
IM 04P03B01-01E
4-13
4-14
4.10 Enabling the Moving Average Function (Dot
Model)
The moving average function can be enabled/disabled on the dot model. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “M_AVE.”
(M_AVE)
Select whether to use moving average function.
(NOT)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Moving Average
Enable ( ): Enables the setting of the number of samples of the moving average
Disable ( in Setting mode.
): The “M_AVE” item does not appear in Setting mode.
<Related Topics>
Setting the moving average: section 3.3
IM 04P03B01-01E
4.11 Enabling the Filter Function (Pen Model)
The input filter function on the pen model can be enabled/disabled. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “FILTR.”
(FILTR)
Select whether to use the filter function.
(NOT)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Filter
Enable (
Disable (
): Enables the setting of the filter and the time constant in Setting mode.
): The “FILTR” item does not appear in Setting mode.
<Related Topics>
Setting the filter: Section 3.2
4
4-15
IM 04P03B01-01E
4-16
4.12 Enabling the Partial Expanded Recording
Function
The partial expanded recording function can be enabled/disabled. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select the “PART.”
(PART)
Select whether to use the partial expanded recording function.
(NOT)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or
2. Press the or key to select
key to select
or
key.
, and press the
, and press the
Explanation
Partial Expanded Recording
Enable ( ): Enables the setting of the boundary position and boundary value of the partial expanded recording function in Setting mode.
Disable ( ): The “PART” item does not appear in Setting mode.
<Related Topics>
Setting the partial expanded recording: Section 3.5
IM 04P03B01-01E
4.13 Changing the Printout Font
The printout font can be changed. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “FONT.”
(FONT)
Select the printout font.
(ENG.)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Font
English (
Japanese (
): Uses the alphabet, numbers, and symbols for printout.
): Uses the alphabet, Katakana, numbers, and symbols for printout.
German (
French ( ):
): Uses the German alphabet, numbers, and symbols for printout.
Uses the French alphabet, numbers, and symbols for printout.
* Katakana (Japanese), German, and French can be used in the message printout and tag printout when the respective font is selected.
4
4-17
IM 04P03B01-01E
4-18
4.14 Changing the Print/Display Format of the Date
The format of the printout and display of the year, month, and day can be changed.
Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “DATE.”
(DATE)
Select the date format.
(YMD)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Type
Selectable
Settings
Type
Y/M/D
M/D/Y
D/M/Y
D.M.Y
M.D.Y
Printout Format
Example
2006/03/31
03/31/2006
31/03/2006
31.03.2006
Mar.31.2006
Display Format
Example
06 03 31
03 31 06
31 03 06
31 03 06
03 31 06
Notes
Default value
IM 04P03B01-01E
4.15 Enabling the Bias, Low-Cut, and Calibration
Correction Functions
The bias, low-cut, and calibration correction functions can be enabled/disabled. Basic
Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “PERS.”
(PERS.)
4
(BIAS)
Bias function
Select enable (USE) or disable (NOT).
(NOT)
(SQRT)
Low-cut function of the channel on which square root computation is assigned
Select enable (USE) or disable (NOT).
(USE)
(1-5V)
Low-cut function of the channel on which 1-5V signal is assigned
Select enable (USE) or disable (NOT).
(NOT)
(CALIB)
Calibration correction function
(Models with the /CC1 option)
Select enable (USE) or disable (NOT).
(NOT)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
4-19
IM 04P03B01-01E
4.15 Enabling the Bias, Low-Cut, and Calibration Correction Functions
Explanation
Bias
Enable (
Disable (
): Enables the setting of the bias value in Setting mode.
): The “BIAS” item does not appear in Setting mode.
SQRT Low-Cut
Sets the low-cut function for the square root computation.
Enable ( ): Enables the setting of the low-cut function when a channel is set to square root computation in Setting mode.
Disable ( ): The “SQRT” item does not appear in Setting mode.
1-5V Low-Cut
Sets the low-cut function for the 1-5V input.
Enable ( ): Enables the setting of the low-cut function when a channel is set to 1-
5V in Setting mode.
Disable ( ): The “1-5V” item does not appear in Setting mode.
Calibration Correction (/CC1 Option)
Enable ( ): Enables the setting of the calibration correction function in Basic
Disable (
Setting and Setting modes.
): The “CALIB” item does not appear in Basic Setting or Setting mode.
Note
The bias and calibration correction functions (/CC1 option) cannot be enabled simultaneously.
<Related Topics>
Setting the bias value: Section 3.10
Setting the low-cut function: Section 2.1
Setting the calibration correction function: Section 4.19
Performing calibration correction: Section 3.11
4-20
IM 04P03B01-01E
4.16 Changing the Time Printout Format
The time printout format can be changed on the alarm printout, message printout, recording start printout, and new chart speed printout. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the key, the operation is cancelled, and the display returns to a higher level menu.
Select “T_PRN.”
(T_PRN)
4
Alarm printout
Select the time printout format.
(ALARM)
(HM)
(MSG)
Message printout
Select the time printout format.
(HM)
(RCD)
(HM)
Recording start printout
Select the time printout format.
(SPEED)
New chart speed printout
Select the time printout format.
(HM)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
4-21
IM 04P03B01-01E
4.16 Changing the Time Printout Format
Explanation
Selecting the Printout Format
Select the time format of the alarm printout, message printout, recording start printout, and new chart speed printout.
• Alarm Printout, Recording Start Printout, and New Chart Speed Printout
H:M (
H:M:S (
):
):
Hour:Minute
Hour:Minute:Second
M/D H:M (
M/D H:M:S (
Y/M/D H:M:S (
): Month/Day Hour:Minute
): Month/Day Hour:Minute:Second
): Year/Month/Day Hour:Minute:Second
• Message Printout
H:M ( ):
H:M:S (
M/D H:M (
):
):
M/D H:M:S (
Y/M/D H:M:S (
NONE ( ):
Hour:Minute
Hour:Minute:Second
Month/Day Hour:Minute
): Month/Day Hour:Minute:Second
): Year/Month/Day Hour:Minute:Second
Does not print the date/time.
Note
The printout format of the year, month, and day varies depending on the print/display format of the date (see section 4.14).
4-22
IM 04P03B01-01E
4.17 Initializing the Settings
The recorder settings can be initialized to their factory default.
Be careful, because all settings except the date/time setting in the recorder will be initialized. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the key, the operation is cancelled, and the display returns to a higher level menu.
Select “INIT.”
(INIT)
Select the range to be initialized.
(SETUP)
(NO)
Select “YES” and press to execute the initialization and return to Operation mode.
Explanation
Initialization
Set (
Setup (
): Initializes the settings in Setting mode.
): Initializes the settings in Basic Setting mode and Setting mode.
Items That Are Not Initialized
The following items are not initialized.
• Adjustment value of the pen position and the adjustment value of the printer carriage position (Basic Setting mode)
• Date/Time (Setting mode)
4
4-23
IM 04P03B01-01E
4-24
4.18 Assigning Functions to the Remote Control
Input Terminals (/R1 Option)
Functions can be assigned to the remote control input terminals. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the key, the operation is cancelled, and the display returns to a higher level menu.
Select “REM.”
(REM)
Select the remote control terminal number.
(REM1)
Select the function to be assigned.
(RCD)
Remote control terminal number
The settings are activated.
(OK)
4.
Press the key to set other remote numbers.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or
2. Press the or key to select
key to select
or
key.
, and press the
, and press the
Explanation
Remote Numbers
The remote control input terminal numbers are from 1 to 5.
Functions to Be Assigned
RCD (
C_SPD (
):
):
Starts/stops recording.
Changes the chart speed.
T_ADJ (
M_PRN (
MSG1 (
MSG2 (
MSG3 (
MSG4 (
MSG5 (
NONE (
):
):
):
):
):
):
):
):
Adjusts the internal clock to the nearest hour.
Executes a manual printout.
Prints message 1.
Prints message 2.
Prints message 3.
Prints message 4.
Prints message 5.
No function is assigned.
<Related Topics>
Setting the secondary chart speed: Section 3.9
IM 04P03B01-01E
4.19 Setting the Calibration Correction Function
(/CC1 Option)
The calibration correction method and the number of correction points can be set. Basic
Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “CALIB.”
(CALIB)
Select the channel number.
(CH1)
(REVIS)
Channel number
Select whether to perform calibration correction using revise values or absolute values.
Set the number of calibration correction points.
The settings are activated.
(OK)
4.
Press the key to set other channels.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Calibration Correction Method
Revise value ( ): Specifies the difference between the correction values
Absolute value ( and input values.
): Specifies the correction values.
Number of Correction Points
Selects the number of points that make up the segments (including the start and end points) in the range of 2 to 16.
<Related Topics>
Enabling the calibration correction function: Section 4.15
Performing calibration correction: Section 3.11
4-25
IM 04P03B01-01E
4
4-26
4.20 Selecting the Menus to Be Hidden in Setting
Mode
You can select the menu items to be hidden in Setting mode. Basic Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “S.MENU.”
(S.MENU)
Select “SET.”
(SET)
(RANGE)
(ON)
Select whether to display RANGE in
Setting mode. Select ON or OFF.
(BIAS) Select whether to display BIAS in
Setting mode. Select ON or OFF.
(ON)
(ALARM)
(ON)
Select whether to display ALARM in Setting mode. Select ON or OFF.
(UNIT)
(ON)
(CHART)
(ON)
To the next page
Select whether to display UNIT in
Setting mode. Select ON or OFF.
Select whether to display CHART in Setting mode. Select ON or OFF.
IM 04P03B01-01E
Explanation
4.20 Selecting the Menus to Be Hidden in Setting Mode
From the previous page
(AUX)
Select whether to display AUX in
Setting mode. Select ON or OFF.
(ON)
(CALIB)
(Models with the /CC1 option)
Select whether to display CALIB in
Setting mode. Select ON or OFF.
(ON)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
ON (
OFF (
): Shows the menu in Setting mode.
): Hides the menu in Setting mode when customized menu is enabled.
<Related Topics>
Enabling the customized menu: Section 4.22
4
IM 04P03B01-01E
4-27
4-28
4.21 Selecting the FUNC Key Menus to Be Hidden
Procedure
You can select the FUNC key menu items to be hidden. Basic Setting mode cannot be entered when recording is in progress
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the key, the operation is cancelled, and the display returns to a higher level menu.
Select “S.MENU.”
(S.MENU)
Select “FUNC.”
(FUNC)
(M_PRN)
(ON)
Select whether to display the manual printout FUNC key. Select ON or OFF.
(SLIST) Select whether to display the setup list
FUNC key. Select ON or OFF.
(ON)
(MSG)
Select whether to display the message
FUNC key. Select ON or OFF.
(ON)
(B_CLR)
Select whether to display the buffer clear FUNC key. Select ON or OFF.
(ON)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
IM 04P03B01-01E
Explanation
4.21 Selecting the FUNC Key Menus to Be Hidden
ON(
OFF(
): Shows the FUNC key menu.
): Hides the FUNC key menu when customized menu is enabled.
<Related Topics>
Enabling the customized menu: Section 4.22
4
IM 04P03B01-01E
4-29
4-30
4.22 Enabling/Disabling the Customized Menu
The following operations are carried out when the customized menu is enabled.
• Locks Basic setting mode.
• Hides specified FUNC key menu items.
• Hides specified menu items in Setting mode.
Basic Setting mode cannot be entered when recording is in progress
Procedure
Enabling the Customized Menu
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
For the procedure on how to enter values or characters, see page 18 in the
Operation Guide
.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “CUST.M.”
(CUST.M)
(USE)
Password
(****)
Select whether to enable (USE) the customized menu.
(Displays the following when the customized menu is set to USE)
Set the password.
(P_ADJ)
Select whether to use pen/dot printing position adjustment without the password. Select ON or OFF.
(ON)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the
key.
key, use the or
2. Press the or key to select
key.
key to select
or
, and press the
, and press the
IM 04P03B01-01E
IM 04P03B01-01E
4.22 Enabling/Disabling the Customized Menu
Disabling the Customized Menu
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
For the procedure on how to enter values or characters, see page 18 in the
Operation Guide .
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “LOCK.”
(LOCK)
Enter the password.
(****)
Enter Basic Setting mode.
Select “CUST.M.”
(CUST.M)
Select NOT.
(NOT)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
4
4-31
4.22 Enabling/Disabling the Customized Menu
Explanation
Enable (
Disable (
): Locks Basic Setting mode and hides the specified menu items in
Setting mode and FUNC key menu items.
): Releases Basic Setting mode and shows the all menu items in Setting mode and all FUNC key menu items.
Password
This is the password used to release the customized menu or to enter Basic Setting mode. Set the password using a four-digit number.
Note
Changing the Settings without Releasing the Basic Setting Mode Lock
The settings in Basic Setting mode can be changed without releasing the customized menu.
Procedure
1. Enter the password in the same manner as described in “Releasing the Customized Menu,” and press the key.
2. Enter Basic Setting mode.
3. Change the settings in the same manner as the normal procedure.
4. Return to Operation mode with the customized menu enabled.
<Related Topics>
Selecting the FUNC key menus to be hidden: Section 4.21
Selecting the menus to be hidden in Setting mode: Section 4.20
Adjusting the pen/dot position: Sections 6.4 and 6.5
4-32
IM 04P03B01-01E
4.23 Changing the Temperature Unit
The unit of the temperature measured using the TC or RTD can be changed. Basic
Setting mode cannot be entered when recording is in progress
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the and keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the or key to select the value.
If you press the higher level menu.
key, the operation is cancelled, and the display returns to a
Select “TEMP.”
(TEMP)
Selects the temperature unit.
(DEG_C)
The settings are activated.
(OK)
4.
If you are done, press the key.
5.
To return to the Operation mode,
1. Press the key, use the or key to select
key.
2. Press the or key to select
key.
or
, and press the
, and press the
Explanation
Temperature Unit
°C (
°F (
): Uses Celsius.
): Uses Fahrenheit.
4
4-33
IM 04P03B01-01E