7. Commissioning

7.1 General

After filling the installation with water in the previous section please follow the following steps to complete the installation of the unit.

WARNING

DO NOT operate the immersion heaters or primary circuit until the cylinder has been filled with water.

`

WARNING: If the unit is to be left unused following installation and commissioning, e.g. unoccupied properties, the water heater should be drained or regularly flushed through with fresh mains water once a week.

`

When placing the unit into service, the procedure for filling the unit and the system checks above should be observed.

7.2 Checklist before commissioning

`

Check all water connections for leaks and rectify as necessary.

`

Turn off mains water supply.

`

Remove the pressure reducing valve head work to access the strainer mesh, clean and re-fit.

`

Turn the water supply back on.

`

Manually open, for a few seconds, each relief valve in turn, checking that water is discharged and runs freely through the tundish and out at the discharge point.

`

Ensure that the valve(s) reseat satisfactorily.

7.3 Commissioning procedure

Direct units

`

Switch on electrical supply to the immersion heater(s) and allow the cylinder to heat up to normal working temperature (65°C recommended).

`

If necessary the temperature can be adjusted by inserting a flat bladed screwdriver in the adjustment spindle on front of the immersion heater thermostat and rotating. The adjustment represents a temperature range of 15°C to 74°C.

`

Check the operation of thermostat(s) and that no water has issued from the expansion relief valve or temperature/pressure relief valve during the heating cycle.

Indirect units

`

Fill the indirect (primary) circuit following the boiler manufacturer’s commissioning instructions.

`

To ensure the cylinder primary heat exchanger is filled, the 2 port motorised valve (supplied) should be manually opened by moving the lever on the motor housing to the MANUAL setting. When the primary circuit is full return the lever to the

AUTOMATIC position.

`

Switch on the boiler, ensure the programmer is set to Hot Water and allow the cylinder to heat up to a normal working temperature 65 o

C (recommended).

Thermal cut-out reset under cap

Figure 17: Indirect controls

Temperature control clockwise to increase, counter-clockwise to decrease

30

40

0

°C

50

60

Unvented Hot Water Cylinder

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • High capacity: 800L - 1000L storage capacity ensures ample hot water for multiple bathrooms and appliances.
  • Energy-efficient: Advanced insulation minimizes heat loss, reducing energy consumption and lowering running costs.
  • Fast heat-up time: Powerful immersion heater provides rapid heating, ensuring hot water is always available when you need it.
  • Easy installation and maintenance: Compact design and accessible components simplify installation and ongoing servicing.
  • Safety features: Built-in safety systems, including over-temperature protection and thermal cut-out, ensure safe operation.
  • Durable construction: High-quality materials and robust construction guarantee longevity and reliability.
  • Quiet operation: Advanced design minimizes noise levels, providing a peaceful living environment.

Related manuals

Frequently Answers and Questions

What type of installation is required for this cylinder?
The installation must be carried out by a competent plumbing and electrical installer in accordance with relevant building regulations and water regulations.
How do I fill the cylinder with water?
Filling instructions are provided in the installation manual. Ensure that the system is filled slowly to avoid water hammer.
What are the dimensions of the cylinder?
Dimensions can be found in the technical specifications section of the installation manual.
What is the warranty period for this product?
Warranty information is provided in the guarantee section of the installation manual.