Commissioning
Program sequence test
Adjusting burner output
Testing the burner program sequence before initial gas release
• Close the manual shut-off valve upstream of the compact gas unit.
• Bridge the gas pressure switch
(terminal 2 and 3) if necessary if there is insufficient gas pressure upstream of the compact gas train. Disconnect the burner from the power supply first.
• Start the burner by switching on the heat generator and test the program sequence.
• The blower starts after a delay, depending on the automatic combustion control unit setting.
• Pre-ventilation period (54 s)
• Pre-ignition period (3 s)
• Solenoid valves open
• Safety time (3 s)
• Safety shutdown at the end of the safety time with locking of automatic combustion control unit (malfunction lamp lit).
• Disconnect the burner from the power supply by disconnecting the electrical connection and remove the wire jumper for the gas pressure switch if necessary.
• Reconnect the electrical connection.
• Unlock the automatic combustion control unit.
• Start the burner.
Rapid stroke
Initial gas flow adjustment
Main flow adjustment
Pressure switch
Coil
Access to filter
Connecting flange
Initial load flow adjustment - rapid stroke adjustment
• Twist off protective cap B and turn it through 180° to use it as an adjustment tool.
• Turn the adjustment spindle to the minimum position, then turn it back towards the plus symbol to the middle position (approximately 3 half turns).
The initial gas flow is now set to around half open.
• To achieve smooth starting characteristics, the initial gas flow should be adapted to the pressure characteristics of the heat generator.
Full load flow adjustment
• Loosen the locking screw until rotary knob C becomes adjustable. Do not loosen the sealed screw on the opposite side.
• Reduce the main flow by turning knob
C clockwise or reduce it by turning it anti-clockwise. The total path to adjust from minimum to maximum flow is approximately 4.5 turns.
• Retighten the locking screw following the adjustment.
pBr (4-20 mbar)
Adjusting screw of the gas pressure regulator
Pressure regulator adjustment
The adjusting screw has a path of 60 turns for adjusting the output pressure.
Three turns clockwise or anti-clockwise increases or reduces pressure by
1 mbar respectively.
At commissioning:
• fine tune the adjustment (more or less pressure)
• Check the gas pressure either at the multiblock pBr (M4) or the gas collector measurement nipple Ø9.
Optimising combustion values
Optimum combustion values can be achieved by adjusting the position of the baffle plate (dimension Y) if necessary.
Doing this can have an effect on starting characteristics, pulsation and combustion values. Any reduction in scale value Y increases the CO
2
value.
However, starting characteristics become harsher. Compensate for the change in airflow if necessary by adjusting the air flap position.
N.B.: Observe the minimum required flue gas temperature specified by the boiler manufacturer and the requirements demanded of flue gas ducts for avoiding condensation.
Locking screw
Sealed screw
40 02/2007 - Art. Nr. 13 021 281A
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Description du brûleur
- 5 Sélection des rampes gaz
- 5 Rampe gaz
- 8 Coffret de commande et de sécurité SG
- 10 Options de raccordement
- 12 Montage du brûleur
- 13 Contrôle / Réglage / Montage
- 16 Données de réglage du brûleur
- 17 Réglage de l'air
- 18 Contrôle du déroulement du programme
- 18 Réglage du brûleur
- 19 Réglage manostat gaz / manostat d'air
- 19 Contrôle du fonctionnement
- 19 02/2007 - Art. Nr
- 25 Burner description
- 27 Gas train selection
- 27 Gas train
- 30 SG113 automatic combustion control unit
- 32 Connection options
- 34 Burner assembly
- 35 Checking/adjusting/assembly
- 35 Burner head for natural gas/propane gas
- 37 Checks before commissioning
- 38 Burner adjustment data
- 39 Air regulation
- 40 Program sequence test
- 40 Adjusting burner output
- 41 Gas/air pressure switch adjustment
- 41 Function check
- 41 02/2007 - Art. Nr