- No category
advertisement
Section V - Servicing
Safety
Safety procedures while servicing the compressor are important to both the service personnel and to those who may be around the compressor and the system it serves. Listed below are some, but not all, procedures that should be followed:
• Wait for the unit to cool before starting service. Temperatures may exceed 180°F when the compressor is operating.
• Clean up fluid spills immediately to prevent slipping.
• Loosen, but do not remove, flange or component bolts. Carefully pry apart to be sure there is no residual pressure before removing bolts.
• Never use a flammable solvent such as gasoline or kerosene for cleaning air filters or compressor parts.
• Safety solvents are available and should be used in accordance with their instructions.
NOTICE!
Maintenance or service should be performed by trained and qualified service technicians only.
CAUTION!
Unusual noise or vibration indicates a problem. Do not operate the compressor until the source has been identified and corrected.
Water Removal
Water vapor may condense in the reservoir and must be removed. Water is heavier than the compressor fluid and will collect at the bottom of the reservoir.
The frequency with which the water must be removed is determined by the ambient air conditions. During hot and humid conditions, water should be drained off the bottom of the reservoir daily. In cold and dry conditions, water may only need to be drained weekly.
WARNING!
Water content in the compressor fluid in excess of 200 PPM could cause bearing damage and/or airend failure.
To drain water from the reservoir:
• Turn the compressor off by the main switch and perform proper lockout/ tagout procedure.
• Completely depressurize the compressor circuits (reference
‘Preparing for Maintenance or Service’ on page 70 and ‘Safety’ instructions on page 72).
• Allow compressor to sit idle for at least
5 minutes.
• Open the drain valve.
• Close the valve when the water flow changes to compressor fluid.
(When the drain is first opened some compressor fluid may come out before the water starts to flow.)
• Since this water will contain some compressor fluid, dispose of the water in accordance with Local, State, and
Federal environmental regulations.
72
Quincy Compressor-QGV Series
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Safety Alert Symbols
- 8 Spare Parts Ordering Information
- 8 Serial/Model Identification Plate
- 9 Royal Blue Warranty
- 12 General Description
- 13 The Compression Cycle
- 13 Air Flow
- 13 Capacity Control System
- 14 Cooling System
- 14 Air-cooled Fluid Coolers
- 14 Water-cooled Fluid Coolers
- 15 Electrical System
- 16 Control Panel
- 18 Receiving
- 18 Moving the Unit to the Installation Site
- 19 Location
- 20 Piping Connections
- 20 Relief Valves
- 21 Electrical
- 21 Pneumatic Circuit Breakers or Velocity Fuses
- 21 Guards
- 21 Manual Vent and Shutoff Valve
- 22 Water and Sewer Facilities at the Installation Site (water-cooled models)
- 23 Compressor Rotation
- 23 Fan Rotation (air-cooled only)
- 23 Shipping Supports
- 24 Prior to Starting
- 25 Starting the Compressor
- 26 Control Panel Operation
- 26 Main Screen
- 32 Menu Screen
- 58 Upgrading Touch Screen (HMI) Code
- 63 QGV Network Setup
- 75 Stopping the Compressor - Normal Operation
- 75 Stopping the Compressor - Emergency
- 76 Preparing for Maintenance or Service
- 77 Maintenance Schedule
- 78 Safety
- 78 Water Removal
- 79 Service Adjustments
- 80 Changing Compressor Fluid
- 81 Fluid Level
- 81 Fluid Filter
- 82 Fluid Scavenging System
- 82 Fluid Cooler/Aftercooler (air-cooled)
- 82 Air/Fluid Tubing
- 84 Air Filter
- 85 Air/Fluid Separator Element
- 86 Control Panel Fault or Service Messages
- 87 Electronic Control
- 88 Shaft Seal
- 90 Fluid Specifications
- 91 Lubrication
- 91 Fluid Sample Valve
- 92 Factors Affecting Fluid Life
- 92 Fluid Analysis Program - General
- 94 Understanding the Analysis Report
- 96 QuinSyn-Plus
- 97 QuinSyn-XP
- 98 QuinSyn-PG
- 99 QuinSyn-F
- 99 QuinSyn Flush
- 100 Cleaning and Flushing with QuinSyn Flush
- 102 Converting to QuinSyn-Plus
- 102 Converting to QuinSyn-XP
- 103 Converting to QuinSyn-PG
- 103 Converting to QuinSyn-F
- 104 Fluid Parameters
- 106 Failure to Start
- 107 Unscheduled Shutdown
- 107 Thermal Overload Relays Tripping
- 108 Low Air Delivery
- 108 Low Receiver Pressure
- 108 High Receiver Pressure
- 109 High Discharge Air Temperature and/or High Fluid Injection Temperature
- 110 Frequent Air/Fluid Separator Clogging
- 111 Fluid Discharge Out Blowdown Valve
- 111 Frequent Fluid Filter Clogging
- 111 Excessive Water Content In Fluid
- 112 Excessive Fluid Consumption
- 112 Frequent Air Cleaner Clogging
- 112 Inlet Valve Not Opening Or Closing In Relation To Air Demand
- 113 Compressor Does Not Unload When There Is No Air Demand
- 113 To Reset Pressure
- 113 Compressor Will Not Time-out Or Shut Down When Unloaded (Auto/Dual Only)
- 113 Excessive Water in Plant Air Distribution System
- 113 Pressure Relief Valve Exhausting
- 118 QGV-75/100/125 (air-cooled)
- 119 QGV-75/100/125 (water-cooled)
- 120 QGV-150 (air-cooled)
- 121 QGV-200 (air-cooled)
- 122 QGV-150/200 (water-cooled)