9 Parameters
9.1
Standard parameters
Parameter Description
P-01 Max. speed limit
(Hz or rpm)
P-02
P-03
P-04
P-05
P-06
P-07
P-08
P-09
P-10
P-11
Min. speed limit
(Hz or rpm)
Acceleration ramp time (s)
Deceleration ramp time (s)
Voltage boost
Range
P-02 to 5
×
P-09
(max. 500 Hz)
0 – P-01 (max. 500 Hz)
0.0 – 600 s
0.0 – 600 s
Default
50.0 Hz
1)
0.0 Hz
5.0 s
Explanation
Maximum speed limit in Hz or rpm (see P-10)
Minimum speed limit in Hz or rpm (see P-10)
Stop mode select
Energy optimizer 0 Disabled
Motor rated voltage
Motor rated current
Motor rated frequency
Motor rated speed
0
1
2
Ramp to stop
Coast to stop
Ramp to stop (fast stop)
1 Enabled
0, 20 – 250 V
0, 20 – 500 V
5.0 s
0
0
230 V
400 V
2)
Acceleration ramp time from 0 to 50 Hz (fixed) in seconds.
Deceleration ramp time from 50 Hz (fixed) to standstill in seconds. If set to 0, then the fastest possible ramp time without trip is activated.
If the supply is lost and P-05 = 0, then the drive will try to continue running by reducing the speed of the load using the load as a generator.
If P-05 = 2, then the drive will ramp to stop using the P-24 deceleration ramp when mains supply is lost. Also activates constant power braking mode for normal braking.
When enabled, automatically reduces applied motor voltage on light load.
Rated (nameplate) voltage of the motor in volts.
The value is limited to 250 V for low voltage drives. Setting to 0 disables voltage compensation.
Rated (nameplate) current of the motor in amps. 25 – 100 % of drive current rating DR-Motor rating
25 – 500 Hz 50 Hz
1)
Rated (nameplate) frequency of the motor.
0 – 30000 rpm
0 – 20 % of max output voltage.
Resolution 0.1 %
• Size 1 = 20 %
• Size 2 = 15 %
• Size 3 = 10 %
0
Motor power dependent
When not set to 0 all speed-related parameters are displayed in rpm. Activates slip compensation when motor nameplate speed is set.
Applies an adjustable boost to the MOVITRAC
® voltage output at low speed to assist with starting
’sticky’ loads. For continuous applications at low speed use a force ventilated motor.
U
P-07
9
P-07
2
20 %
10 %
0 %
P-09 f
P-09
2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Operating Instructions – MOVITRAC® LTE-B
39
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 1 Important Notes
- 4 Structure of the safety notes
- 6 Application environment
- 6 Waste disposal
- 7 2 Safety Notes
- 7 Installation and startup
- 8 Operation and servicing
- 9 3 General specifications
- 9 Input voltage ranges
- 9 Product designation
- 10 Overload capability
- 10 Protection features
- 11 4 Mechanical Installation
- 11 Dimensions
- 16 IP20 housing: mounting and dimensions of switch cabinet
- 18 5 Electrical Installation
- 18 Prior to installation
- 20 Installation
- 24 Signal terminals overview
- 25 RJ45 Communication Socket
- 26 UL-compliant installation
- 27 Electromagnetic compatibility
- 29 6 Startup
- 29 User interface
- 30 Easy startup
- 35 7 Operation
- 35 Drive status
- 36 8 Service and fault codes
- 36 Troubleshooting
- 36 Fault history
- 37 Fault codes
- 38 SEW electronics service
- 39 9 Parameters
- 39 Standard parameters
- 40 Extended parameters
- 44 P-15 Digital inputs function select
- 46 Real-time monitoring parameters (read-only)
- 48 10 Technical Data
- 48 10.1 Conformance
- 48 10.2 Environmental
- 49 10.3 Output power and current ratings
- 58 11 Index