Levelflex FMP55
Reference operating conditions
Maximum measured error
Performance characteristics
• Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
• Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflection factor ≥ 0,8 (surface of the water for coax probe, metal plate for rod and rope probe with min.
1 mm (0.04 in) diameter)
• Flange for rod or rope probe ³ 300 mm (12 in) diameter
• Distance to obstacles ³ 1 m (40 in)
• For interface measurement:
– Coax probe
– DC of the lower medium = 80 (water)
– DC of the upper medium = 2 (oil)
Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the span.
Output: digital
Sum of non-linearity, nonrepeatability and hysteresis
Level measurement:
Measuring range up to 10 m (33 ft): ±2 mm (0.08 in)
Offset / Zero
Interface measurement:
• Measuring range up to 500 mm (19.7 in): ±20 mm (0.79 in)
• Measuring range >500 mm (19.7 in): ±10 mm (0.39 in)
• If the thickness of the interface is <100 mm (3.94 in):
±40 mm (1.57 in)
±4 mm (0.16 in)
1) Add error of the analogous value to the digital value.
analog
1)
±0.02 %
±0.03 %
If the reference conditions are not met, the offset/zero point arising from the mounting situation may be up to
±12 mm (0.47 in) for rope and rod probes. This additional offset/zero point can be compensated for by entering a correction (parameter "level correction") during commissioning.
Differing from this, the following measuring error is present in the vicinity of the lower probe end:
rod probe and coax probe
80
60
40
20
0
-20
-40
-60
-80
0
DC = 2
DC > 7
50 100 150 200 250
distance from probe end [mm]
300
rope probe
80
60
40
DC > 7
20
0
-20
-40
-60
-80
0 50 100 150 200 250 300
distance from probe end [mm]
A0014154-EN
If for rope probes the DC value is less than 7, then measurement is not possible in the area of the straining weight (0 to 250 mm from end of probe; lower blocking distance).
20 Endress+Hauser
Levelflex FMP55
Differing from this, the following measuring error is present in the vicinity of the upper probe end
(rod/rope only):
Resolution
Reaction time
Influence of ambient temperature
R
40 mm
30 mm
20 mm
10 mm
D
2 mm
0 mm
- 2 mm
- 10 mm
- 20 mm
- 30 mm
- 40 mm
DC = 2
DC > 7
100 mm 200 mm
A0015091
D Sum of non-linearity, non-repeatability and hysteresis
R Reference point of measurement
DC Dielectric constant
• digital: 1 mm
• analog: 1 mA
The reaction time can be parametrized. The following step response times (as per DIN EN 61298-2)
3)
if the damping is switched off:
are valid
Probe length
< 10 m (33 ft)
Level measurement
Sampling rate
3.6 measurements/second
Step response time
< 0.8 s
Probe length
< 10 m (33 ft)
Interface measurement
Sampling rate
³ 1.1 measurements/second
The measurements are carried out in accordance with EN 61298-3
• digital (HART, PROFIBUS PA): average T
K
= 0.6 mm/10 K
• analog (current output):
– zero point (4 mA): average T
– span (20 mA): average T
K
K
= 0.02 %/10 K
= 0.05 %/10 K
Step response time
< 2.2 s
3) According to DIN EN 61209-2 the response time is the time which passes after a sudden change of the input signal until the output signal for the first time assumes 90% of the steady-state value.
Endress+Hauser 21