Suitable mounting position
Operating conditions: Installation
Levelflex FMP55
Applications with restricted mounting space
A0011281
• Rod probes / rope probes: must be mounted in a stilling well or bypass (® ä 23)
• Coax probes: can be mounted at an arbitrary distance from the wall of the vessel
• When mounting in the open, a weather protection cover may be installed to protect the device against extreme weather conditions.
• Minimum distance from the end of probe to the bottom of the vessel: 10 mm (0.4 in)
Mounting with remote sensor
The device version with a remote sensor is suited for applications with restricted mounting space. In this case the electronics housing is mounted at a separate position from which it is easier accessible.
A B r min
= 100 mm (4”)
6 Nm
6 Nm
6 Nm r min
= 100 mm (4”)
6 Nm
22
A Angled plug at the probe
B Angled plug at the electronics housing
A0014794
Endress+Hauser
Levelflex FMP55
• Levelflex version (see product structure):
Feature 600 "Probe Design", Option MB "Sensor remote, 3m/9ft cable, detachable+mounting bracket" (®
ä 45)
• A connecting cable is supplied with this device version
– Length: 3 m (9 ft)
– Minimum bending radius: 100 mm (4 inch)
• A mounting bracket for the electronics housing is supplied with this device version. Mounting options:
– Wall mounting
– Pipe mounting; diameter: 42 to 60 mm (1-1/4 to 2 inch)
• The connection cable has got one straight and one angled plug (90°). Depending on the local conditions the angled plug can be connected at the probe or at the electronics housing.
Notes on the mechanical load of the probe
Tensile load limit of rope probes
Sensor
FMP55
Feature 060
NA, ND
Probe
Rope 4mm (1/6") PFA>316
Tensile load limit [kN]
2
Bending strength of rod probes
Sensor
FMP55
Feature 060
CA, CB
Probe
Rod 16mm (0.63") PFA>316L
Bending strength [Nm]
30
Securing the probe
Bending strength of coax probes
Sensor Feature 060
FMP55 UA, UB
Process connection
Flange
Probe
Coax 316L, Ø 42,4 mm
Securing coax probes
For Ex-approvals: For probe lengths ³ 3 m (10 ft) a support is required.
Bending strength [Nm]
300
A0012608
Special mounting conditions
Coax probes can be supported at any point of the outer tube.
Bypasses and stilling wells
For information on bypass solutions from Endress+Hauser please contact your Endress+Hauser sales representative.
Endress+Hauser 23
24
Levelflex FMP55
1 2
A0014129
1 Mounting in a stilling well
2 Mounting in a bypass
• Pipe diameter: > 40 mm (1.6") for rod probes
• Rod probe installation can take place up to a diameter size of 100 mm. In the event of larger diameters, a coax probe is recommended.
• Side disposals, holes or slits and welded joints that protrude up to approx. 5 mm (0.2") inwards do not influence the measurement.
• The pipe may not exhibit any steps in diameter.
• The probe must be 100 mm longer than the lower disposal.
• Within the measuring range, the probe must not get into contact with the pipe wall. If necessary, use a center washer (see feature 610 of the product structure).
• Within the measuring range, the probe must not get into contact with the pipe wall. If necessary, use a PFA
center washer (see feature 610 of the product structure) (® ä 47).
• Coax probes can always be applied if there is enough mounting space.
For bypasses with condensate formation (water) and a medium with low dielectric constant (e.g.
hydrocarbons):
In the course of time the bypass is filled with condensate up to the lower disposal and for low levels the the level echo is superimposed by the condensate echo. Thus in this range the condensate level is measured instead of the correct level. Only higher levels are measured correctly. To prevent this, position the lower disposal 100 mm (4 in) below the lowest level to be measured and apply a metallic centering disk at the height of the lower edge of the lower disposal.
With heat insulated tanks the bypass should also be insulated in order to prevent condensate formation.
Underground tanks
A0014142
Endress+Hauser
Levelflex FMP55
Use a coax probe for nozzles with large diameters in order to avoid reflections at the nozzle wall.
Non-metallic vessels
When mounting Levelflex in a non-metallic vessel, use a coax probe.
Vessels with heat insulation
If process temperatures are high, the device must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection. The insulation may not exceed beyond the points labeled "MAX" in the drawings.
2 3
1
MAX MAX mm (in)
å
5 Process connection with flange - FMP55
1 Tank insulation
2 Compact device
3 Sensor remote (feature 600)
A0014654
Endress+Hauser 25