Amana AVPTC is an air handler with a built-in thermal expansion valve for cooling and heat pump applications. It features a variable-speed ECM blower motor and integrated communicating ComfortBridge™ Technology. Commissioning and diagnostics are possible via on-board Bluetooth with the CoolCloud phone and tablet application.
advertisement
Nomenclature
Brand
A Single-Piece Air Handler
A
1
Unit Application
R Multi Position PSC Motor
S Multi Position EEM Motor
V Multi Position Variable-Speed
Motor - Communicating
Cabinet Finish
U Unpainted
P Painted
Expansion Device
F Flowrater
T Expansion Device
V Inverter Tuned Expansion Valve
V
2
P
3
T
4
C
5
25
6,7
Communications
C = ComfortBridge
TM
Compatible
B
8
1
9
4
10
BA
11,12
Engineering*
Major/Minor Revisions
( *Not used for inventory management)
Refrigerant Charge
4 = R-410A
Electrical
1 208/230V, 1 Phase, 60 Hz
25 = 2 Tons
29 = 2½ Tons
31 = 2½ Tons
33 = 2 Tons
Cabinet Width
B = 17½"
C = 21"
D = 24½"
Nominal Capacity @ 13 SEER
35 = 3 Tons 49 = 4 Tons
37 = 2½ - 3½ Tons 59 = 4-5 Tons
39 = 3 Tons 61 = 5 Tons
2
HKS X
1 2
03
3
X
4
A
5
AA
6,7
Unit Type
HKS Heat Kit for
Air Handlers
Circuit Breaker
X No circuit breaker
C Circuit Breaker
Heating Capacity @ 240 Volts
03 3.0 kW 15 14.4 kW
05
06
08
4.5 kW
6.0 kW
8.0 kW
10 9.6 kW
19 19.2 kW wth 150F limit
20 19.2 kW with 170F limit
25 25.0 kW
A Single Phase 208 V
B Single Phase 240 V
C Single Phase 208/240 V
D Three Phase 208 V
H Special case 208 V *
Revisions
Engineering Revisions
E Three Phase 240 V
Phase
F Three Phase 208/240 V
G Three Phase 460 V
Cabinet Size (MAX)
C C Cabinet
D D Cabinet
X All Cabinet Sizes www.amana-hac.com
*Refer S&R Plate
SS-AAVPTC
Product Specifications
AVPTC
25B14B*
AVPTC
29B14B*
AVPTC
31C14B*
AVPTC
33C14B*
AVPTC
35B14B*
AVPTC
37B14B*
AVPTC
37C14B*
AVPTC
37D14B*
Nominal Ratings
Cooling (BTU/h)
CFM (High range)
Blower
Diameter
Width
Coil Drain Connection FPT
24,000 30,000 30,000 24,000 28,000 36,000 36,000 36,000
1085/650 1085/610 1315/870 1090/685 1020/685 1085/610 1315/870 1375/865
9½"
6"
¾"
9½"
6"
¾"
10⅝"
8"
¾"
10⅝"
8"
¾"
9½"
6"
¾"
9½"
6"
¾"
10⅝"
8"
¾"
10⅝"
10⅝"
¾"
Service Valve
Liquid
Suction
Electrical Data
⅜"
¾"
⅜"
⅞"
⅜"
⅞"
⅜"
⅞"
⅜"
¾"
⅜"
⅞"
⅜"
⅞"
Voltage
Min Circuit Ampacity
208/240
4.9/4.9
Max. Overcurrent Device (amps) 15/15
208/240
6.5/6.5
15/15
208/240
6.5/6.5
15/15
208/240
4.9/4.9
15/15
208/240
4.9/4.9
15/15
208/240
6.5/6.5
15/15
208/240
6.5/6.5
15/15
208/240
6.5/6.5
15/15
Minimum VAC
Maximum VAC
Blower Motor
FLA
HP
Ship Weight (lbs)
197
253
3.9
½
116
197
253
5.2
¾
129
197
253
5.2
¾
144
197
253
3.9
½
118
197
253
3.9
½
116
197
253
5.2
¾
129 144
Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed.
Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed
197
253
5.2
¾
⅜"
⅞"
197
253
5.2
¾
155
AVPTC
39C14B*
AVPTC
49C14B*
AVPTC
49D14B*
AVPTC
59C14B*
AVPTC
59D14B*
AVPTC
61D14B*
Nominal Ratings
Cooling (BTU/h)
CFM (High range)
Blower
Diameter
Width
Coil Drain Connection FPT
36,000
1315/965
10⅝"
8"
¾"
48,000 42,000 48,000 48,000 60,000
1420/1040 1530/1195 1595/875 1990/1445 2025/1630
10⅝"
8"
¾"
10⅝"
10⅝"
¾"
10⅝"
8"
¾"
11¹⁵⁄₁₆"
10⅝"
¾"
11¹⁵⁄₁₆"
10⅝"
¾"
Service Valve
Liquid
Suction
Electrical Data
Voltage
Min Circuit Ampacity
208/240
6.5/6.5
Max. Overcurrent Device (amps) 15/15
Minimum VAC
Maximum VAC
Blower Motor
FLA
HP
⅜"
⅞"
197
253
5.2
¾
⅜"
⅞"
208/240
6.5/6.5
15/15
197
253
5.2
¾
⅜"
⅞"
208/240
6.5/6.5
15/15
197
253
5.2
¾
⅜"
⅞"
208/240
8.6/8.6
15/15
197
253
6.9
1
⅜"
⅞"
208/240
8.6/8.6
15/15
197
253
6.9
1
⅜"
⅞"
208/240
8.6/8.6
15/15
197
253
6.9
1
Ship Weight (lbs)
118 125 167 144 155 167
Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed.
Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed
SS-AAVPTC www.amana-hac.com
3