Allen-Bradley AC (120V) ISO Output

Manuals and User Guides for Allen-Bradley AC (120V) ISO Output. We found 1 manuals for free downloads Installation instructions

Allen-Bradley AC (120V) ISO Output is a versatile and reliable output module designed for industrial automation applications. This module features 16 isolated outputs, capable of driving various motor starters and other compatible devices. The module provides surge suppression circuitry to protect the output triacs from high-voltage transients. It also employs zero voltage turn-on technology to minimize electromagnetic interference and inrush currents. With its compact size and robust design, the Allen-Bradley AC (120V) ISO Output module is an ideal choice for a wide range of applications.

Key Features

  • 16 isolated outputs
  • Surge suppression circuitry
  • Zero voltage turn-on
  • Compatible with various I/O chassis
  • Drives motor starters
  • Field wiring arm for easy connection
  • Individual fuses for each output
  • CSA certified

Pages: 12 Allen-Bradley AC (120V) ISO Output Installation instructions

Brand: Allen-Bradley Size: 192 KB

Languages: English

Open manual

Frequently Answers and Questions

What is the maximum load current per output?
The maximum load current per output is 2A continuous, with a peak surge of 20A for 100ms. However, the total continuous current per module is limited to 8A.
Is the Allen-Bradley AC (120V) ISO Output module compatible with all 1771 I/O chassis?
No, this module is compatible with all 1771 I/O chassis except for the 1771-A1, -A2, or -A4 chassis. It is also compatible with the 1771-AM1 and 1771-AM2 chassis.
How do I replace a blown fuse on the module?
You can replace a blown fuse by first turning off power to the I/O chassis backplane. Remove the module and access the fuse through the holes on the side cover. Remove the blown fuse and replace it with a 3A 2AG slo-blow fuse.