Manuals and User Guides for Allen-Bradley ASEM 6300M DC Powered Panel Monitors. We found 1 manuals for free downloads Installation instructions

Allen-Bradley ASEM 6300M DC Powered Panel Monitors offer a range of display sizes and resolutions, with IP65 environmental protection making them suitable for demanding applications like food processing and life sciences. They can be used in both non-hazardous and hazardous locations with long-distance capabilities for connecting to a computer up to 100 meters away.

Key Features

  • IP65 Protection
  • Various display sizes
  • Non-hazardous & hazardous locations
  • Long-distance capabilities
  • DC power input
  • Touch screen calibration
  • UL/cUL certified
  • CE marked
  • RVL (remote video link)

Pages: 6 Allen-Bradley ASEM 6300M DC Powered Panel Monitors Installation instructions

Brand: Allen-Bradley Size: 542 KB

Languages: English

Open manual

Frequently Answers and Questions

What are the environmental requirements for using the ASEM 6300M DC Powered Panel Monitor?
The monitor can operate in a temperature range of -5°C to 60°C and a relative humidity of 20% to 90% non-condensing. It is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications, at altitudes up to 2000 meters. The monitor should be installed indoors unless rated for hazardous locations.
What are the power requirements for the ASEM 6300M DC Powered Panel Monitor?
The monitor requires a 24V DC power supply (18-32V DC SELV input voltage range). The nominal output power of the power supply should be 25% larger than the rated power of the monitor. Allen-Bradley recommends using a single grounded connection for the DC powered model to minimize noise.
What are the mounting requirements for the ASEM 6300M DC Powered Panel Monitor?
The monitor should be mounted horizontally in a 0° vertical position with the I/O ports facing downward. The mounting surface material must be 2-6 mm thick, and the roughness of the panel surface must not exceed 120 microns.
Can the ASEM 6300M DC Powered Panel Monitor be used in hazardous locations?
Yes, certain models are rated for use in Class I, Division 2 Groups A, B, C, D hazardous locations with a temperature code of T5. However, the front USB port is not for use in hazardous locations. Only use the front USB port for installation and maintenance purposes.
How do I calibrate the touch screen on the ASEM 6300M DC Powered Panel Monitor?
ASEM 6300M models with analog resistive touch screens use an eGalax Touch driver and can be field calibrated. Models with PCAP touch screens use the native Microsoft Windows HID driver and cannot be field calibrated. Refer to the 6300M Panel Monitor User Manual for more information on field calibration.