Ascon tecnologic K48

Инструкции и руководства для Ascon tecnologic K48. Мы нашли 6 инструкции доступные для бесплатного скачивания quick guide, Manual, Owner's manual

The K48 Controller and Mini-programmer is a compact and versatile device that is ideal for various control and automation applications. It offers a range of features, including PID control, ON/OFF control, autotuning, program execution, and alarm management.

Ключевые особенности

  • PID control

  • ON/OFF control

  • Autotuning

  • Program execution

  • Alarm management

Страниц: 2 Ascon tecnologic K48 quick guide

Бренд: Ascon tecnologic Категория: Measuring, testing & control Размер: 2 MB

Языки: English

Открыть мануал

Другие мануалы и документы

36 Страниц

Manual

Языки: English

40 Страниц

Owner's manual

Языки: German

36 Страниц

Owner's manual

Языки: Italian

36 Страниц

Owner's manual

Языки: Spanish

36 Страниц

Owner's manual

Языки: Spanish

Часто задаваемые вопросы

How to enter the configuration mode?

Press the button for more than 5 seconds. If the password is correct, the display will show the acronym of the first parameter group preceded by the symbol '.'.

What is the default password for configuration parameters?

The factory default password for configuration parameters is 30.

How to exit the configuration mode?

Push the button for more than 5 seconds. The instrument will come back to the “standard display”.

What are the typical values loaded in the instrument prior to shipping from factory?

The default data are the typical values loaded in the instrument prior to shipping from factory. These are the factory default parameter settings.

Вопросы и ответы

2024-12-12

H H I

How to program alarms on a K48 instrument?

Access configuration mode and modify alarm parameters. Alarm configuration is password-protected (level 3).

How to perform a reading correction on a K48 instrument?

For linear inputs, adjust parameters '[4] SSc' (Initial scale read-out) and '[5] FSc' (Full scale read-out). Temperature input calibration follows EN 60751/A2 (for RTD Pt100) and EN 60584-1 (for thermocouples). RTD Pt100 line resistance compensation is automatic (up to 20Ω/wire, with a maximum error of ±0.1% of the input range). For thermocouples, use appropriate (preferably shielded) compensation cable.