Manning EC-F2 NH3

Manuals and User Guides for Manning EC-F2 NH3. We found 1 manuals for free downloads Manual

Below you will find brief information for Ammonia Sensor EC-F2-NH3. This manual provides instructions for installing and operating the EC-F2-NH3 ammonia sensor. It covers aspects like location selection, wiring, startup procedures, calibration, troubleshooting, and maintenance.

Key Features

  • Electrochemical ammonia sensor
  • 4/20 mA output
  • Ranges from 0-100 ppm to 0-1,000 ppm
  • Diffusion method for gas sampling
  • Operates in temperatures from -50°F to +120°F
  • NEMA 1 enclosure

Pages: 9 Manning EC-F2 NH3 Manual

Brand: Manning Category: Measuring, testing & control Size: 159 KB

Languages: English

Open manual

Frequently Answers and Questions

How do I properly locate the EC-F2-NH3 sensor?
The sensor should be easily accessible for calibration and maintenance. Consider personnel protection and leak detection needs when choosing the location. Mount the sensor vertically and ensure proper ventilation.
What kind of wiring is recommended for the EC-F2-NH3 sensor?
Use three conductor, insulated, stranded, shielded copper cable. The cable length should be no greater than 1,500 feet. Ensure the shield wire is properly grounded at the control panel.
What are the startup procedures for the EC-F2-NH3 sensor?
After ensuring proper wiring, power up the sensor and allow 24 hours for stabilization. Then, perform a response test using a small amount of ammonia to verify functionality.
How do I calibrate the EC-F2-NH3 sensor?
The sensor comes factory calibrated, but you can adjust zero and span settings using the zero and span pots. Use certified calibration gas for accurate results.
What is the typical sensor life for the EC-F2-NH3?
Sensor life varies depending on the environment. In a refrigerated area, expect 3-4 years. In a non-refrigerated area, expect 1.5-2 years. High ammonia levels can shorten this life.