Potter VSR-CR

Manuals and User Guides for Potter VSR-CR. We found 1 manuals for free downloads Owner's manual

Potter VSR-CR is a vane type waterflow switch for use on wet sprinkler systems where external corrosion is a concern. It is UL Listed and CUL Listed for use on a steel pipe; schedules 5 through 40, sizes 2" - 6" and is UL and CUL Listed for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). The VSR-CR may also be used as a sectional waterflow detector on large systems. The VSR-CR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.

Key Features

  • Corrosion resistant hardware of 316 stainless steel
  • Corrosion resistant powder coated base and saddle
  • NEMA 4X/IP66 Rated Enclosure suitable for indoor or outdoor use
  • Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL
  • Two sets of SPDT (Form C) Contacts
  • Adjustable retard delay from 0 to 60-90 seconds
  • Cover Tamper Switch Kit available as an option

Pages: 4 Potter VSR-CR Owner's manual

Brand: Potter Category: Industrial & lab equipment Size: 1 MB

Languages: English

Open manual

Frequently Answers and Questions

What is the maximum surge for the VSR-CR?
18 FPS (5.5 m/s)
What is the temperature range for the VSR-CR?
40°F - 120°F, (4.5°C - 49°C) - UL
Can the VSR-CR be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems?
No, it should not be used as the sole initiating device for these systems.