YASKAWA PC3 GPD333 Drive

Manuals and User Guides for YASKAWA PC3 GPD333 Drive. We found 3 manuals for free downloads Manual, instruction manual

Below you will find brief information for Varispeed-606PC3 CIMR-PCU2, Varispeed-606PC3 CIMR-PCUB, Varispeed-606PC3 CIMR-PCU4. These ultra-compact, all-digital inverters provide low-noise operation. Several models are available rated for 230V, 240V and 460V power input. They feature a digital operator for accessing program constants and operation variables or a drive status indicating plate. Enclosure types include enclosed wall-mounted or water and dust tight options.

Key Features

  • Ultra-compact design

  • All-digital control for precise operation

  • Low-noise operation

  • Available with digital operator or indicating cover

  • Multiple enclosure options (NEMA 1, NEMA 4)

  • Adjustable frequency and voltage output

Pages: 81 YASKAWA PC3 GPD333 Drive Manual

Brand: YASKAWA Category: Power adapters & inverters Size: 1 MB

Languages: English

Open manual

Other manuals and documents

157 Pages

instruction manual

Languages: English

210 Pages

Manual

Frequently Answers and Questions

Where should the Varispeed-606PC3 inverter be installed?

The VS-606PC3 should be installed vertically in areas with an ambient temperature between +14 to 104 °F (-10 to +40 °C), protected from rain, moisture, oil sprays, direct sunlight, corrosive gases or liquids, airborne dust or metallic particles, salt spray, vibration, magnetic noise, high humidity, and combustibles.

What kind of branch circuit protection should be used?

Connect MCCBs or Fuses between the AC main circuit power supply and the VS-606PC3 input terminals to protect the wiring. Use Listed Class RK5 fuses.

What should I do if the wiring distance between the inverter and motor is long?

If the wiring distance is long, reduce the inverter carrier frequency. The carrier frequency can be set by constant No. 43.

What is a function of grounding terminal?

Ground the casing of the VS-606PC3 using ground terminal G. Ground resistance should be 100 ohms or less.