Manuals and User Guides for YASKAWA iQpump Micro. We found 3 manuals for free downloads installation Guide, User manual, Quick start Guide

Below you will find brief information for CIMR-PW BV0006, CIMR-PW BV0010, CIMR-PW BV0012, CIMR-PW BV0018, CIMR-PW 2V0006, CIMR-PW 2V0010, CIMR-PW 2V0012, CIMR-PW 2V0020, CIMR-PW 2V0030, CIMR-PW 2V0040. This guide outlines the proper wiring of the iQpump Micro AC Drive and motor, along with configuration steps for a simplex pump application. It includes essential safety messages, installation practices, environmental considerations, and an overview of fault diagnostics and parameter settings to prepare the drive for basic operation.

Key Features

  • Compact Intelligent Pump Controller

  • Supports 200 V and 400 V classes

  • Single-phase (1-5 HP) and three-phase (1-25 HP) input models

  • Step-by-step Quick Start Procedure for installation and basic setup

  • Comprehensive safety messages and warnings

  • Detailed electrical and mechanical installation guidelines

  • Basic fault diagnostics and troubleshooting information

  • Parameter settings for initial operation

Pages: 118 YASKAWA iQpump Micro installation Guide

Brand: YASKAWA Category: Industrial & lab equipment Size: 17 MB

Languages: English

Table of contents

Open manual

Other manuals and documents

444 Pages

User manual

Languages: English

32 Pages

Quick start Guide

Languages: English

Frequently Answers and Questions

What safety precautions should I observe before servicing the drive?

Before servicing, disconnect all power to the equipment. Wait at least 5 minutes for capacitor discharge after disconnecting the power supply. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. Measure for unsafe voltages to confirm the drive is safe prior to servicing.

What are the recommended environmental conditions for installing the iQpump Micro AC Drive?

The drive should be installed indoors in an area free from oil mist, dust, metal shavings, water, harmful gases, excessive vibration, and direct sunlight. The ambient temperature should be between -10 °C and +40 °C (14 °F to 104 °F) with 95% RH or less, free of condensation.

Can I install multiple iQpump Micro drives side-by-side?

Yes, multiple drives can be mounted side-by-side with a minimum clearance of 2 mm between them. However, derating must be considered, and parameter L8-35 must be set. For IP20/NEMA 1, UL Type 1 enclosures, the top covers of all drives must be removed when mounted side-by-side.

What is the recommended method for wiring the drive's main circuit terminals?

Yaskawa recommends using ring terminals on all drive models. UL/cUL approval requires the use of UL Listed closed-loop crimp terminals. Ensure to use the tools recommended by the terminal manufacturer for crimping.

What should I do if the motor operates at low speeds and I need full torque?

The cooling fan of a standard motor reduces its efficiency at low speeds, potentially leading to overheat if full torque is applied. To prevent damage, reduce the load torque as the motor slows. For 100% continuous torque at low speeds, a motor specifically designed for drive operation should be used.

Questions & Answers

2025-12-20

C C D

What should be checked if there is no power at the 24V supply for the digital input terminals?

Check the setting of DIP switch S3. If S3 is set to SINK (default), the drive uses its internal 24V power supply. If S3 is set to SOURCE, an external 24V power supply is required, which must be connected and verified for function.

What is the expected voltage range for the A2 terminal when configured as a voltage input?

If the A2 terminal is configured as a voltage input (DIP switch S1 set to "V" and Parameter H3-09 set to 0 or 1), the voltage range should be 0 to +10 Vdc.

What voltage should be measured on the transducer signal wire?

This depends on the transducer connection type:

  • For a 3-Wire transducer connection (voltage output), the signal wire typically shows a voltage range of 0 to 10 Vdc.
  • For a 2-Wire transducer connection, the signal is typically a current signal (4 to 20 mA), and current measurement would be appropriate for the signal wire itself.