DVPEN01-SL

Ethernet Communication Module

Application Manual

Ethernet Communication Module DVPEN01-SL

Warning

3 Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages on the device or injuries to staff.

3

Switch off the power before wiring.

3

RTU-DNET is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur.

3

RTU-DNET is to be used for controlling the operating machine and equipment. In order not to damage it, only qualified professional staff familiar with the structure and operation of RTU-DNET can install, operate, wire and maintain it.

3

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wirings again before switching on the power and DO NOT touch any terminal when the power is switched on. Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference.

Table of Contents

1 INTRODUCTION...................................................................................................................................3

1.1

Functions.....................................................................................................................................3

1.2

Specifications ..............................................................................................................................3

2 PRODUCT PROFILE & OUTLINE .......................................................................................................4

2.1

Dimension ...................................................................................................................................4

2.2

Product Profiles...........................................................................................................................4

2.3

LED Indicators.............................................................................................................................5

2.4

RJ-45 PIN Definition....................................................................................................................5

3 INSTALLATION & WIRING ..................................................................................................................5

3.1

Installation ...................................................................................................................................5

4 CONTROL REGISTER (CR) ................................................................................................................6

4.1

Control Registers in DVPEN01-SL..............................................................................................6

4.2

Explanations on CR ....................................................................................................................8

4.3

Numbering of Left-Side Extension Modules ..............................................................................12

5 SETTING UP SOFTWARE .................................................................................................................13

5.1

Setting up Communication & Searching for Modules................................................................13

5.2

Basic Settings ...........................................................................................................................16

5.3

Network Settings .......................................................................................................................18

5.4

Setting up E-Mails .....................................................................................................................20

5.5

Data Exchange..........................................................................................................................22

DVP-PLC Application Manual

1

Ethernet Communication Module DVPEN01-SL

5.6

IP Filter ..................................................................................................................................... 23

5.7

Static ARP Table ....................................................................................................................... 24

5.8

Setting up Password................................................................................................................. 25

5.9

Returning to Default Setting ..................................................................................................... 26

5.10

Export & Import of DVPEN01-SL Files ..................................................................................... 27

5.11

Recording IP Address ............................................................................................................... 28

6 APPLICATION EXAMPLES............................................................................................................... 29

6.1

Setting up IP and Communicating through WPLSoft................................................................ 29

6.2

Connecting the PC with DVPEN01-SL through LAN ................................................................ 32

6.3

Setting up IP and Communicating through WPLSoft................................................................ 36

6.4

Setting up Password and Clearing Password .......................................................................... 37

6.5

When the Password is Lost (Returning to Default Setting by RS-232)..................................... 39

6.6

IP Filter Protection .................................................................................................................... 40

6.7

Setting up Static ARP Table ...................................................................................................... 42

6.8

Application of E-Mail................................................................................................................. 43

6.9

Application of Data Exchange (1) ............................................................................................. 45

6.10

Application of Data Exchange (2) ............................................................................................. 47

6.11

Application of Data Exchange (3) ............................................................................................. 48

6.12

Application of Modbus TCP Master (1)..................................................................................... 49

2 DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

1 Introduction

Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read the manual carefully before using the module.

DVPEN01-SL is an Ethernet communication module for remote setting and communication through

WPLSoft. DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and exchange data. It supports Modbus TCP communication protocol and can conduct remote monitoring by using

SCADA (Supervisor Control And Data Acqusition) software or HMI (Human Machine Interfaces). DVPEN01-SL can be the master of Modbus TCP, sending out Modbus TCP instrcutions and controlling the peripheral equipment. In addition, under MDI/MDI-X auto-detection, it does not need to use a crossing cable. See the contents below for more detailed instructions on DVPEN01-SL module.

1.1 Functions z Auto-detects 10/100Mbps transmission speed z MDI/MDI-X z Supports Modbus TCP protocol (at the same time supports Master and Slave mode) z Able to send out E-mails z Auto-corrects the RTC in PLC through the Internet time correction function z Supports point-to-point data exchange (Max. data exchange length: 200 bytes)

1.2 Specifications

ƒ Internet interface

Item Specification

Number of ports

Transmission method

Transmission cable

Transmission speed

Network protocol

ƒ Serial communication interface

1 Port

IEEE802.3, IEEE802.3u

Category 5e

10/100 Mbps Auto-Detect

ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, Modbus TCP

Item Specification

Interface RS-232

Number of ports 1 Port

Transmission cable DVPACAB230, DVPACAB215, DVPACAB2A30, DVPACAB2B10

ƒ Environment

Item

Noise immunity

Environment

Specification

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV

Analog & Communication I/O: 1KV

Damped-Oscillatory Wave: Power Line: 1KV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;

Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

DVP-PLC Application Manual

3

Ethernet Communication Module DVPEN01-SL

Item Specification

Vibration/ Shock Resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

ƒ Electrical specifications

Item

Power supply voltage

Power consumption

Insulation voltage

Weight (g)

Specification

24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU.)

1.5W

500V

92 (g)

2 Product Profile & Outline

2.1 Dimension

3 [0.118]

DVPEN01

POWER

RS-232

100M

LINK

RS-232

60 [2.362]

LAN

Unit:mm [inches]

4

4

1

3

DVPEN01

POWER

RS-232

100M

LINK

RS-232

2

8

7

LAN

9

6

5

1. Model name

2. Extension port to connect device

6. Fixing tenon for extension unit/module

7. Fixing clip for extension unit/module

3. Extension port to connect extension module 8. RS-232 connection port

4. POWER, LINK, RS-232, 100M indicators 9. Ethernet RJ-485 connection port

5. DIN rail clip

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

Indicator Color

POWER Green

RS-232 Red

100M Orange

LINK Green

Indication

Communication status of the series port

Network status

Network communication speed

2.4 RJ-45 PIN Definition

RJ-45 sketch Terminal No.

3

6

1

2

4, 5, 7, 8

Definition

Tx+

Tx-

Rx+

Rx-

-

Explanation

Positive pole for data transmission

Negative pole for data transmission

Positive pole for data receiving

Negative pole for data receiving

N/C

3 Installation & Wiring

This section gives instructions on how to connect DVPEN01-SL with PLC MPU and how to connect

DVPEN01-SL to the network.

3.1 Installation

Connect PLC MPU to DVPEN01-SL z Adjust the extension clip on the left side of the MPU. z Meet the extension port of the MPU with DVPEN01-SL as shown in the figure below. z Fasten the extension clip.

DVP28SV DVPEN01

POWER

RS-232

100M

LINK

RS-232

LAN

Connect DVPEN01-SL to other extension modules z To connect DVPEN01-SL with the other extension module, lift the extension clip of the extension module by a screwdriver and open the side cover.

DVP-PLC Application Manual

5

Ethernet Communication Module DVPEN01-SL

Connect DVPEN01-SL to the Network

Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL.

Network connection between the PC and DVPEN01-SL:

PC Master

DVPEN01

POWER

RS-232

100M

LINK

DVPEN01

DVP28SV

DVP28SV

RS-232

Ethernet

DVPEN01

POWER

RS-232

100M

LINK

DVPEN01 DVP28SV

DVP28SV

RS-232

6

LAN LAN

4 Control Register (CR)

4.1 Control Registers in DVPEN01-SL

CR#

HW LW

Attribute

#1

#2

Content Explanation

R Firmware version

Set up by the system; read only. Model code of DVPEN01-SL

= H’4050

Displaying the current firmware version in hex.

R Communication mode b0: Modbus TCP mode; b1: data exchange mode

#3

#4

#5

#6

W

W

W

W

E-Mail Event 1 trigger

E-Mail Event 2 trigger

E-Mail Event 3 trigger

E-Mail Event 4 trigger

Set up whether to send E-Mail 1

Set up whether to send E-Mail 2

Set up whether to send E-Mail 3

Set up whether to send E-Mail 4

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

CR#

HW LW

#8

Attribute

R

Content

Status of E-Mail 3, 4

Explanation b0 ~ b7: Current status of E-Mail 2 b8 ~ b15: Current status of E-Mail 1 b0 ~ b7: Current status of E-Mail 4 b8 ~ b15: Current status of E-Mail 3

Filled in by the user, and it will be send by E-mail.

Filled in by the user, and it will be send by E-mail.

Filled in by the user, and it will be send by E-mail.

Filled in by the user, and it will be send by E-mail.

#13 R/W Data exchange trigger Set up whether to send out data in data exchange mode

#14 R Status of data exchange Displaying current status of data exchange.

#24 ~ #15 - Reserved

Destination IP address for data exchange

#27 - Reserved

#28 R/W Destination Slave ID Destination Slave ID for data exchange

#48 ~ #29 R/W Data transmission buffer Buffer for transmitted data in data exchange

#68 ~ #49 R Data receiving buffer Buffer for received data in data exchange

Selecting DHCP or Static IP

#71 #70 R/W IP address

#73 #72 R/W Subnet mask

#75 #74 R/W Gateway

#76 R IP status

#80 ~ #77 - Reserved

Setting up IP address

Setting up subnet mask of DVPEN01-SL

Setting up default gateway IP address

Displaying current IP status

Slave transmission buffer address for data exchange

Number of registers for read data

Buffer address for the receiving Master in data exchange

Buffer address for the receiving Slave in data exchange

Number of registers for data transmission

Master transmission buffer address for data exchange

#110 ~ #87 - Reserved

#111 R/W 8-bit processing mode Setting up Modbus TCP Master control as 8-bit mode

#113 ~ #112 - Reserved

#114 R/W Modbus TCP time-out Setting up Modbus TCP time-out (in ms)

#115 R/W Modbus TCP trigger Setting up whether to send out data in Modbus TCP mode

#118 #117 R/W

Modbus TCP destination IP

Setting up destination IP address for Modbus TCP transaction

DVP-PLC Application Manual

7

Ethernet Communication Module DVPEN01-SL

8

CR#

HW LW

Attribute Content Explanation

#119 R/W Modbus TCP data length Setting up the data length for Modbus TCP transaction

#219 ~ #120 R/W Modbus TCP data buffer Data buffer of Modbus TCP for storing sending/receiving data

#248 ~ #220 - Reserved

Displaying the errors. See table of error codes in the following section for more information.

#255 ~ #252 - Reserved

Symbols “R” refers to “able to read data by FROM instrcution”; “W” refers to “able to write data by TO instrcution”.

4.2 Explanations on CR

C R # 0 : Model Name

Explanations:

1. Model code of DVPEN01-SL = H’4050.

2. You can read the model code in the program to see if the extension module exists.

C R # 1 : Firmware Version

Explanations:

The firmware version of DVPEN01-SL is displayed in hex, e.g. H’0100 indicates version V1.00.

C R # 2 : Communication Mode

Explanations:

Bit No. Mode “0”

Disable

Disable

“1”

Enable

Enable

„ E-mail Functions

CR#3 ~ 6: E-Mail Event 1 ~ 4 Trigger

Explanations:

When the CR is set as “1”, E-mail sending will be enabled. After the sending is completed, the

CR will automatically be reset as “0”. Note: Please trigger by differential instrcutions.

C R # 7 ~ 8 : Status of E-Mail 1 ~ 4

Explanations:

1. CR#7_b0 ~ b7: current status of E-Mail 2; CR#7_b8 ~ b15: current status of E-Mail 1.

2. CR#8_b0 ~ b7: current status of E-Mail 4; CR#8_b8 ~ b15: current status of E-Mail 3.

3. Table of E-Mail status

CR value

0

E-Mail status

Not been sent

2 E-Mail sending is successful

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

CR value

10

11

12

13

E-Mail status

Fail to connect to SMTP-Server

Incorrect recipient E-Mail address

SMTP-Server communication error

Exceeding the max. number of TCP connection

3 ~ 9, 14 ~ 255 Reserved

C R # 9 ~ 1 2 : E-Mail 1 ~ 4 Additional Message

Explanations:

The user fills in the code, and the code will be stored in the title of the E-Mail and sent out with the

E-Mail.

„ Data Exchange

C R # 1 3 : Data Exchange Trigger

Explanations:

When the CR is set as “0”, the data in data exchange area will not be transmitted. When the CR is set as “1”, the data in data exchange area will be transmitted.

C R # 1 4 : Data Exchange Status

Explanations:

When the CR is set as “0”, the data have not yet been received. When the CR is set as “1”, the data exchange is in progress. When the CR is set as “2”, the data exchange is successful. When the CR is set as “3”, the data exchange fails.

CR value

0

1

2

3

Status

Data have not yet been received.

Data exchange is in progress.

Data exchange is successful.

Data exchange fails.

C R # 2 5 , 2 6 : Destination IP

Explanations:

To set up the Slave IP address for data exchange manually, write “0” into CR#28 first before setting up the destination IP. See explanations on CR#70 and #71 for how to set.

C R # 2 8 : Destination Slave ID

Explanations:

When you set up the Salve ID (i.e. K1 ~ K255) for data exchange, DVPEN01-SL will automatically search for the corresponding IP address from the Slave IP list. For example, if the

ID is set as “0”, the value in CR#25 and #26 will be regarded as the destination IP.

C R # 2 9 ~ 4 8 : Data Transmission Buffer

Explanations:

DVP-PLC Application Manual

9

Ethernet Communication Module DVPEN01-SL

Storing the data to be transmitted to the remote MPU.

C R # 4 9 ~ 6 8 : Data Receiving Buffer

Explanations:

Storing the data received from the remote MPU.

C R # 8 1 : Read Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange. Only register address is allowed (e.g. D0 = H’1000).

C R # 8 2 : Read Length for Data Exchange

Explanations:

The number of receiving registers (K1 ~ K128) in data exchange.

C R # 8 3 : Read Length for Data Exchange

Explanations:

Setting up the Modbus address of the register for Master data exchange.

C R # 8 4 : Written-in Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange.

C R # 8 5 : Written-in Address for Data Exchange

Explanations:

The number of transmission registers (K1 ~ K128) in data exchange.

C R # 8 6 : Transmission Address for Data Exchange

Explanations:

1. Setting up the Modbus address of the register for Master data exchange.

2. Example: Write H’1000 (D0) into CR#81, K1 into CR#82, and H’1064 (D100) into CR#83. If the data exchange is successful, the value in D0 of the Slave will be written into D100 of the

MPU. Or write H’1002 (D2) into CR#84, K4 into CR#85, and H’1008 (D8) into CR#86. If the data exchange is successful, the value in D8 ~ D11 of the Master will be written into D2 ~ D5 of the Slave. Both sending and receiving can be executed at the same time. When the values in CR#82 and #85 are both “0”, DVPEN01-SL will use the default registers (CR#29 ~ CR#68) and number of registers (K20).

10

„ Network Settings

C R # 6 9 : DHCP/Static IP

Explanations:

You can select either DHCP or Static IP. When the CR value is set as “0” Æ Static IP; When the

CR value is set as “1” Æ DHCP (dynamic IP).

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

C R # 7 0 , 7 1 : IP Address

Explanations:

1. Setting up the IP address of our equipment in hex. When in DHCP mode, you can only read and cannot write.

2. Example: Assume you’d like to set the IP address as 192.168.0.2, you have to write H’0002 into CR#70 and H’C0A8 into CR#71 to complete the setting. (K192 = H’C0, K168 = H’A8, K0

= H’00, K2 = H’02)

C R # 7 2 , 7 3 : Subnet Mask

Explanations:

1. Setting up the subnet mask of our equipment in hex. When in DHCP mode, you can only read and cannot write.

2. Example: Assume you’d like to set the subnet mask as 255.255.255.0, you have to write

H’FF00 into CR#72 and H’FFFF into CR#73 to complete the setting.

C R # 7 4 , 7 5 : Gateway

Explanations:

Setting up the gateway of our equipment in hex. When in DHCP mode, you can only read and cannot write. See the explanations on CR#70 and #71 for how to set.

C R # 7 6 : IP Status

Explanations:

Displaying the current IP status. When the CR value is “0” Æ normal status; when the CR value is “1” Æ DHCP setting has not completed; when the CR value is “2” Æ IP setting in progress.

„ Sending Modbus TCP Instruction

C R # 111 : 8-bit Processing Mode

Explanations:

Setting up the Modbus TCP transmission mode. When the CR value is set as “0” Æ 16-bit mode; when the CR value is set as “1” Æ 8-bit mode.

C R # 11 4 : Modbus TCP Time-Out

Explanations:

Setting up the communication time-out (in ms) for Modbus TCP mode.

C R # 11 5 : Modbus TCP Trigger

Explanations:

When the CR value is set as “1”, Modbus TCP will be triggered. After the data transmission is completed in Modbus TCP mode, the CR value will automatically be reset to “0”. Please trigger by differential instructions.

DVP-PLC Application Manual

11

Ethernet Communication Module DVPEN01-SL

C R # 11 6 : Modbus TCP Status

Explanations:

Displaying the current communication status of Modbus TCP mode. When the CR value is set as”0” Æ the data have not yet been received; when the CR value is set as “1” Æ the data exchange is in progress; when the CR value is set as “2” Æ the data exchange is successful; when the CR value is set as “3” Æ the data exchange fails.

CR value

0

1

2

3

Data exchange status

The data have not been received.

The data exchange is in progress.

The data exchange is successful.

The data exchange fails.

C R # 11 7 , 11 8 : Modbus TCP Destination IP

Explanations:

Setting up the destination IP address in Modbus TCP mode. See explanations on CR#70 and

#71 for how to set.

C R # 11 9 : Modbus TCP Data Length

Explanations:

Setting up the length of communication data in Modbus TCP mode. Length for 8-bit mode: K1

~K100; length for 16-bit mode: K1 ~ K200.

C R # 1 2 0 ~ 2 1 9 : Modbus TCP Data Buffer

Explanations:

Buffer for transmitted/received data in Modbus TCP mode.

C R # 2 5 1 : Error Code

Explanations:

Table of error code:

Bit No. b0 b1 b2 b3

Error

The network is not yet connected.

Incorrect IP setting

CR#13 is set as “transmitting data”, but the data exchange is forbidden.

CR#13 is set as “transmitting data”, but the data exchange mode has not yet been enabled. b7 b8

SMTP-Server connection fails.

DHCP has not obtained the correct network parameter.

12

4.3 Numbering of Left-Side Extension Modules

After DVPEN01-SL is installed properly, you need to compile the PLC program to control the extension modules. PLC offers FROM instrcution (for reading) and TO instrcution (for writing) to control the control

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL registers (CR) in the extension module.

Numbering of the modules: Every extension module connected to PLC MPU has a No. to allow you to know which module is which when compiling the PLC program. The first extension module attached at the left hand side of the PLC MPU is numbered as K100, the second as K101, the third K102, and so on.

5 Setting up Software

This section gives instructions on how to set up DVPEN01-SL by WPLSoft and explanations on each setup page. Before you start a setup page, you have to select “Ethernet” in the communication setting. Next, you can search by IP address or use Auto-Search. You also can open the setup page for DVPEN01-SL by RS-232.

DVPEN01-SL is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall.

5.1 Setting up Communication & Searching for Modules

1. Communication settings

• Open WPLSoft in your PC and click on “Communication Setting”.

• Select “Ethernet” as the transmission type.

DVP-PLC Application Manual

13

Ethernet Communication Module DVPEN01-SL

2. Auto-search

• Press “Auto-Search” (circled) to search for every DVPEN01-SL in the network and display them in the left column.

• Move the cursor to the module you would like to set up. Double click it to enter the setup page.

• You will see the basic setup page as follow.

14 DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

3. Searching by IP address

• Set the transmission type as “Ethernet” first. Next click on the “Static IP Search” icon (circled) to search for the designated IP.

• Press the “search” icon and you will open the window for entering the IP address. Enter the IP of

DVPEN01-SL you would like to search in the IP address column, or click on the IP address in the

IP list. Press “OK" to start the searching.

• The DVPEN01-SL searched is displayed in the left column. Move the cursor to the module you would like to set up. Double click it to enter the setup page.

DVP-PLC Application Manual

15

Ethernet Communication Module DVPEN01-SL

4. Opening DVPEN01-SL setup page by RS-232`

• Select “RS232" as the transmission type in communication setting. You will have to designate a communication port. When DVPEN01-SL is searched by RS-232, you do not need to set up the parameters (i.e. data length, parity, stop bits and baud rate).

• After setting up the communication port, press “RS-232 search” icon (circled). If the searching is successful, the setup page for DVPEN01-SL will open automatically.

The basic settings include parameters as module name, language, enabling Modbus TCP and time correction.

„ Setting up DVPEN01-SL basics

16 DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

• Module Name:

There can be many DVPEN01-SL modules in the network. Thus, you can set up a module name for each module to identify the module when you need to use them.

• Module Language:

You can select a language for each module name, and the windows will be displayed in the selected language.

• Enable Modbus TCP:

To enable or disable Modbus TCP. When Modbus TCP is disabled, WPLSoft will not be able to upload or download.

• Enable time correction:

DVPEN01-SL adopts NTP (Network Time protocol), which means it can acquire correct time automatically from the time server in the network and correct the RTC in the MPU every fixed period of time to ensure correct time in the MPU. The default setting of this function is “disable”.

• Start Daylight Saving Time:

Daylight Saving Time; also known as summer time, is a conventional local time adopted by many countries in the world on a seasonal basis. Most commonly DST is obtained by adjusting the official local time forward, by one hour, for the spring, summer, and early autumn periods. Daylight

Saving Time is not implemented in Taiwan; therefore, you do not need to check this item.

• Time Server:

IP address of the time server. You can acquire correct time from the time server to correct the time in the MPU.

• Time Zone:

A time zone is a region of the Earth that has adopted the same standard time, usually referred to as the local time. Most adjacent time zones are exactly one hour apart, and by convention compute their local time as an offset from Greenwich Mean Time (see also UTC). Standard time zones can be defined by geometrically subdividing the Earth's spheroid into 24 lunes (wedge-shaped

DVP-PLC Application Manual

17

Ethernet Communication Module DVPEN01-SL sections), bordered by meridians each 15° of longitude apart. The local time in neighboring zones is then exactly one hour different. However, political and geographical practicalities can result in irregularly shaped zones that follow political boundaries or that change their time seasonally (as with daylight saving time), as well as being subject to occasional redefinition as political conditions change. You should choice the Time zone that you are.

The first step for all the network equipment to connect to the network is to have its own IP address (Internet

Protocol). The IP address is like a number for every network equipment to be identified in the network.

1. Setting up static IP of the PC

• Enter Control Panel → Network Connection → click on “Local Area Connection”

• You will see the “Local Area Connection Status” window. Click on “Properties”.

18

• Click on “Internet Protocol (TCP/IP).

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

• Enter 192.168.0.1 into IP address. Click on “OK” to complete the IP address setting of the PC.

2. Setting up DVPEN01-SL Network

• IP configuration:

There are two types of IP, static IP and DHCP.

Static IP: Preset or manually modified by the user.

DHCP: Automatically updated by the server. There has to be a server in the LAN.

DVP-PLC Application Manual

19

Ethernet Communication Module DVPEN01-SL

IP Explanation

Static The user enters the IP address, subnet mask and gateway.

DHCP DHCP server offers the IP address, subnet mask and gateway.

• IP address:

IP address is the location of the equipment in the network. Every equipment connected to the network has to have an IP address. Incorrect IP address will result in connection failure on the equipment or even other equipment. Ask your ISP for questions about IP address setup. The default

IP for DVPEN01-SL is 192.168.1.5.

• Subnet mask:

Subnet mask is an important parameter for setting up the subnet, used for seeing if the destination

IP and the local equipment are in the same subnet. If not, the equipment will send the packet to the gateway, and the gateway will send the packet to another subnet. Incorrect setting may cause the destination equipment unable to communicate with DVPEN01-SL. To see if your setting is correct, conduct bitwise AND operations between your IP and subnet mask and destination IP and subnet mask. If the two values obtained are the same, the two IPs are in the same subnet. The default subnet mask of DVPEN01-SL is 255.255.255.0.

• Gateway:

Gateway is the gate for two different subnets, allowing the two ends in different subnets to communicate. For example, if the LAN has to be connected to WAN, it will need a gateway to bridge the communication. The IP of the gateway has to be in the same subnet as DVPEN01-SL. The default gateway IP address of DVPEN01-SL is 192.168.1.1.

5.4 Setting up E-Mails

E-mail is the abbreviation of electronic mail, which transmits mails through the network. DVPEN01-SL has

E-Mail functions for the user to pre-save a segment of text messages, which can be a descriptive message or error message, into the subject of the E-Mail. When the E-Mail is triggered, DVPEN01-SL will send the messages to the user by E-Mail. There are two sub-pages in the E-Mail setup page.

„ Setting up DVPEN01-SL mail

20 DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

The E-Mail will first be sent to SMTP server, and SMTP server will send it to the designated address. For example, assume there is an E-Mail to be sent to [email protected], and the SMTP server is 172.16.144.121. The E-Mail will be sent to SMTP server first, and the server will further send it to the recipient [email protected].

2. Subject of E-Mail:

You can enter text message in the column, and the message will be placed in the subject of the

E-Mail and sent to the recipient. DVPEN01-SL is able to contain 1 ~ 4 E-Mail subjects (max. 63

English characters are allowed).

3. E-Mail of Sender:

Maximum 63 English characters are allowed.

4. E-mail of Recipient:

You can enter 4 E-Mail addresses. One mail can be sent to 4 addresses (max. 63 English characters are allowed).

DVP-PLC Application Manual

21

Ethernet Communication Module DVPEN01-SL

22

After you have set up all the parameters for the E-Mail, you will need to select recipients. The

E-Mail will be sent to the designated recipients when the E-Mail is triggered. To trigger E-Mail, set the value is CR#3 ~ CR#6 as “1”.

6. See “Application Examples Section 6.8” for more details.

Notes:

To correctly send out E-Mails, there has to be a SMTP server in the network. When we send out an E-Mail, the mail will be sent to SMTP server first, and the server will further send the mail to the designated address.

DVPEN01-SL is able to designate a data exchange area for PLC MPUs to exchange and synchronize their data.

„ Setting up DVPEN01-SL data exchange

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

Check the box to enable or disable data exchange. Start data exchange after enable it.

2. Communication Address & Data exchange host IP:

You have to enter the IP address of DVPEN01-SL at the other end. For example, if you would like

DVPEN01-SL to exchange data with 192.168.0.1, set No. 1 as 192.168.0.1. When the data are being exchanged, if the value in CR#28 is H’0001, the data will be exchanged with 192.168.0.1.

3. See “Application Examples Section 6.11” for more details.

IP filter is used for restricting the connection of the network in case some uncertain IP will cause errors. Only the IP set within a certain range can establish a connection. Other IPs will be rejected.

„ Setting up IP filter

DVP-PLC Application Manual

23

Ethernet Communication Module DVPEN01-SL

24

1. Enable IP Filter Function:

Check the box to enable IP filter.

2. IP:

IP addresses that are allowed to establish connections. Maximum 8 IPs are allowed.

3. Netmask:

The subnet of the IP is allowed to establish a connection. To see whether the destination IP is allowed, conduct bitwise AND operations between the allowed IP and subnet mask and destination IP and subnet mask. If the two values obtained are the same, the destination IP is allowed by the IP filter. For example, assume the IP is 192.168.0.1 and subnet mask

255.255.255.255, the only one IP allowed to establish a connection is 192.168.0.1. If the subnet mask is 255.255.255.0, the IPs allowed to establish connections will become 192.168.0.0 ~

192.168.0.255.

ARP (Address Resolution Protocol) is used for obtaining the MAC address corresponding to the IP address in data transmission. For example, there is a datum to be sent to 172.16.155.250, but you do not know the corresponding MAC address. You can use ARP to look up the MAC address by IP address, and the corresponding MAC address will be saved, so you do not need to look it up again when sending the next datum.

Therefore, if you do not know the MAC address, you will have to spend some time looking up the MAC address.

If you want to enhance the transmission efficiency, use static ARP table to save time. For example, assume IP:

192.168.0.1 and MAC: 00:14:22:56:0F:7F. As long as there are data sent to 192.168.0.1, you will get the MAC address from the table.

„ Setting up static ARP table

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

Destination IP address in data transmission.

2. MAC:

The MAC address corresponding to the IP address.

Note:

Incorrect settings may result in connection failure. Therefore, DO NOT set the MAC address of the equipment without the network into the table.

5.8 Setting up Password

To prevent the set values in DVPEN01-SL from being modified, you can set up password to lock the settings in DVPEN01-SL.

„ Setting up DVPEN01-SL password

DVP-PLC Application Manual

25

Ethernet Communication Module DVPEN01-SL

26

Check the box to modify the password.

Maximum 4 characters are allowed. Leave the column “blank” to disable the password protection function.

Enter the new password again.

4. See “Application Examples Section 6.4” for more details.

Note:

After the password is locked, all the pages cannot be set up unless you unlock the password.

However, if you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. For example, if you have locked DVPEN01-SL but forget the password, you have to return DVPEN01-SL to factory default setting by RS-232, and all the settings will return to default ones.

5.9 Returning to Default Setting

If you need to clear all the settings after many modifications on the settings and return the settings to default ones, check the “default setting” box.

„ Setting up DVPEN01-SL returning to default setting

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

Check “Default Setting” box and click on “Yes”.

Note:

If you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. It takes approximately 10 seconds to return to default setting, so

DO NOT switch off the power within the 10 seconds.

5.10 Export & Import of DVPEN01-SL Files

After you set up all the settings in DVPEN01-SL, you can export you settings and save them into files. You can also read out the files, which is a handy approach for you to manage all the settings in DVPEN01-SL.

„ Export and import of files

DVP-PLC Application Manual

27

Ethernet Communication Module DVPEN01-SL

28

Save all the settings of DVPEN01-SL into *.eni files. The exported files do not include the password.

2. Import:

Select a file and the file will be imported to all the settings.

When DVPEN01-SL is searching for a designated IP, there is a list for you to directly select and designate a module to be searched. “Recording IP address” function is to add a DVPEN01-SL module into the list for you to see the module in the searching.

„ Recording IP address

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

Input IP Address:

Press “Add” to record the IP address of the module into the list.

6.1 Setting up IP and Communicating through WPLSoft

Application Setting up network parameters of DVPEN01-SL directly on the PC.

Network requirement

(1) IP of PC executing WPLSoft: 192.168.0.3

(2) Subnet mask: 255.255.255.0; Gateway: 192.168.0.1

(3) IP of DVPEN01-SL: 192.168.0.4

(4) Connect the PC and DVPEN01-SL by RJ-45 cable.

Note: Both PC and DVPEN01-SL have to adopt static IP.

1. The connection

DVPEN01 DVP-PLC

PC

2. Open "Communication Setting” in WPLSoft.

3. Select “Ethernet” and press "OK”.

DVP-PLC Application Manual

29

Ethernet Communication Module DVPEN01-SL

30

4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network.

5. Designate a DVPEN01-SL and double click it to open the setup page.

DVP-PLC Application Manual

6. Open “Basic” setup page.

Ethernet Communication Module DVPEN01-SL

7. Switch to “Network” setup page

DVP-PLC Application Manual

31

Ethernet Communication Module DVPEN01-SL

8. Enter IP address: 192.168.0.4; Netmask: 255.255.255.0; Gateway: 192.168.0.1. Press “OK” to complete the setup, and WPLSoft will automatically search for DVPEN01-SL.

9. The IP of DVPEN01-SL has been modified into the new setting (DELTA DVPEN01-SL:

192.168.0.4).

10. Click on DELTA DVPEN01-SL, and WPLSoft will be able to communicate with the MPU.

6.2 Connecting the PC with DVPEN01-SL through LAN

Application Setting up network parameters of DVPEN01-SL by WPLSoft through LAN.

Network requirement

(1) Connect the PC and DVPEN01-SL by using DHCP server through LAN.

(2) IP of DVPEN01-SL: 172.16.157.148

Note: DVPEN01-SL can use RJ-45 cable with/without jump wire.

1. The connection

32 DVP-PLC Application Manual

PC

Ethernet Communication Module DVPEN01-SL

DHCP Server

DVPEN01 DVP-PLC

PC

Hub

2. Open “Communication Setting” in WPLSoft.

3. Select “Ethernet” and press “OK”.

DVP-PLC Application Manual

33

Ethernet Communication Module DVPEN01-SL

4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network. Follow “View Æ

Workspace Æ Communication” or “View Æ Workspace Æ Project” to find the detected

DVPEN01-SL module (default module name: DELTA DVPEN01-SL, IP: 192.168.1.5) in the window.

5. Designate a DVPEN01-SL and double click it to open the setup page.

34 DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

6. Open the setup page. You can modify the module name for easier identification.

7. Next, set up the new IP of DVPEN01-SL. First switch to “Network” setup page. If there is a DHCP server in the LAN, select DHCP in “IP Configuration”. If there is no DHCP server in the LAN, you can set a static IP. Please be noted that the settings of subnet mask and gateway have to be the same as the settings in the same LAN. Press “OK” to complete the setting, and WPLSoft will automatically search for DVPEN01-SL.

8. The module name and IP of DVPEN01-SL have been modified into new settings (TEST:

172.16.157.148).

9. Click on DVPEN01-SL, and WPLSoft will be able to communicate with the MPU (e.g. uploading/downloading program or monitoring devices).

DVP-PLC Application Manual

35

Ethernet Communication Module DVPEN01-SL

6.3 Setting up IP and Communicating through WPLSoft

Application Setting up network parameters of DVPEN01-SL by ladder diagram

Network requirement

(1) IP of DVPEN01-SL: 192.168.0.4

(2) Subnet mask: 255.255.255.0; Gateway: 192.168.0.1

(3) If DVPEN01-SL is damaged, change to a new DVPEN01-SL and execute

STOP→RUN. The IP of the new DVPEN01-SL will be modified into 192.168.0.4.

(4) DVPEN01-SL is the first extension module attached in the left hand side of PLC.

1. The connection

DVPEN01 DVP-PLC

PC

36

2. See 6.1 for how to set up the communication. Download the program to PLC.

M1002

MOV K0 D0

MOV H4 D1

MOV HC0A8

MOV HFF00

MOV HFFF

D2

D3

D4

MOV H1 D5

MOV HC0A8

T0 K100

D6

K69 D0 K7

END

Explanations:

• Use M1002 to trigger all the settings. When DVPEN01-SL goes from STOP to RUN, D0 = 4 refers to using static IP address. Write the IP address into D1 and D2, subnet mask into D3 and

D4, and gateway into D5 and D6.

• The IP address is to be set as 192.168.0.4. Therefore, write H’0004 into D1 and H’C0A8 into D2.

(K192 = H’C0, K168 = H’A8, K0 = H’00, K2 = H’02)

• The subnet mask is to be set as 255.255.255.0. Therefore, write H’FF00 into D3 and H’FFFF into D4. (K255 = H’FF)

• The gateway is to be set as 192.168.0.1. Therefore, write H’0001 into D5 and H’C0A8 into D6.

(K1 = H’1)

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

• Use TO instruction to write the network setting parameters D0 ~ D7 into CR#69 ~ #75 in

DVPEN01-SL. DVPEN01-SL is the first extension module numbered K100 attached at the left hand side of PLC. (See 4.3 for more details.)

• After the program is being executed, all the previous network settings in DVPEN01-SL will be modified into new settings.

3. If DVPEN01-SL is damaged, please change to a new DVPEN01-SL. The default IP for

DVPEN01-SL is 192.168.1.5.

4. Execute STOP → RUN in the new DVPEN01-SL and search for it again. We can see the IP has been modified into 192.168.0.4.

6.4 Setting up Password and Clearing Password

Application Setting up and clearing password by WPLSoft

Network requirement

(1) Set password in DVPEN01-SL

(2) Unlock DVPEN01-SL

(3) Clear the password in DVPEN01-SL

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to “Password” page.

3. Check “Modify” box and enter “aabb” in “New Password” and “Confirm Password" columns. Click on

“OK” to save the password.

DVP-PLC Application Manual

37

Ethernet Communication Module DVPEN01-SL

38

4. Open the setup page again, and DVPEN01-SL is now locked by the password. You cannot open any of the settings now. Click on “Unlock” to leave the entering password window.

5. Enter the password to temporarily unlock the protection and modify the parameters. If you close the setup page, the locking will automatically be recovered.

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

6. To clear the password, simply leave the password columns blank. Click on “OK” to clear the password.

7. After the password is cleared, you can modify the parameters.

6.5 When the Password is Lost (Returning to Default Setting by RS-232)

Application Returning to default setting by RS-232

Network requirement

(1) DVPEN01-SL is set with a password.

(2) The password is forgotten.

1. Use DVPACAB2A30 cable to connect the PC and DVPEN01-SL and open the setup page. Open the “reset to default setting”” pages. Click on “Unlock”.

DVP-PLC Application Manual

39

Ethernet Communication Module DVPEN01-SL

2. Check the “Default Setting” box and the “Warning” dialog box will appear. Click on “Yes” to return to default setting (in approx. 5 ~ 10 seconds), and the password will be cleared as well.

3. After the searching, all the parameters have already returned to their default settings.

6.6 IP Filter Protection

Application Setting up IP filter protection

Network requirement

(1) IP of DVPEN01-SL: 192.168.0.4

(2) Only connections to 192.168.0.7 and 172.16.0.1~172.16.0.255 are allowed.

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to “IP Filter” page.

40 DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

3. Check “Enable IP Filter Function” box. Enter “192.168.0.7” in No. 1 IP and “255.255.255.255” in all

“Netmask” columns.

4. Enter “192.168.0.1” in No. 2 IP and “255.255.255.0” in No.2 “Netmask” column. Click on "OK” to complete the setting. Only the equipment within the IP range can be connected.

DVP-PLC Application Manual

41

Ethernet Communication Module DVPEN01-SL

6.7 Setting up Static ARP Table

Application Setting up static ARP table

Network requirement

(1) MAC address of equipment 192.168.1.6 is 00:18:23:10:00:35

(2) MAC address of equipment 192.168.1.1 is 00:18:23:10:00:04

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to “Static ARP Table” page.

3. Check “Enable ARP Table” box. Enter “192.168.1.6” in No. 1 IP, and its corresponding MAC address is “00:18:23:10:00:35”.

42

4. Enter “192.168.1.1” in No.2 IP, and its MAC address is “00:18:23:10:00:04”. Click on “OK” to complete the setting. Only the equipment within the IP range can be connected.

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

Note:

The MAC address of DVPEN01-SL can be obtained from WPLSoft or the MAC address sticker on the equipment. The MAC address of PC can be found in the “Network Connection Details” (see below).

Application

Network application

Sending an E-Mail to notify the administrator when the current status of X0 and Y0 is changed.

(1) SMTP Server IP: 172.16.144.121。

(2) E-mail address of administrator: [email protected]

(3) An E-mail message will be generated when the status of X0 and Y0 is changed.

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to "Mail” page.

DVP-PLC Application Manual

43

Ethernet Communication Module DVPEN01-SL

44

3. In “Subject and Mail” page, enter the address of SMTP server, subject of E-Mail, and E-mail address of the recipient.

4. Switch to “Select Recipients” page. Check all the boxes of “Recipient 1”. Click on “OK” to complete the setting.

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

5. After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and download it to the MPU. See below for the program design:

X0

T0 K100 K3 K1 K1

X0

T0 K100 K4 K1 K1

Y0

T0 K100 K5 K1 K1

Y0

T0 K100 K6 K1 K1

END

Explanations:

• If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of

DVPEN01-SL, and the first E-Mail will be sent out.

• If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of

DVPEN01-SL, and the second E-Mail will be sent out.

• If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of

DVPEN01-SL, and the third E-Mail will be sent out.

• If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of

DVPEN01-SL, and the fourth E-Mail will be sent out.

6.9 Application of Data Exchange (1)

Application Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A

Network requirement

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5”

(4) Update from PLC_B to PLC_A

1. See 6.1 for how to set up the communication.

2. Open the setup page of PLC_B and switch to “Data Exchange” page.

DVP-PLC Application Manual

45

Ethernet Communication Module DVPEN01-SL

3. Check “Enable Data Exchange” box. Enter IP address of PLC_A “192.168.0.4” in No. 1 Data

Exchange Host IP column. Click on “OK” to complete the setting.

46

4. After all the settings in PLC_B are completed, compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design:

M1000

D100

M1013 M2 M1

SET M1

M1

TOP K100 K28 K1 K1

TOP K100 K29 D100 K7

TOP K100

TOP K100

K14

K13

K0

K1

K1

K1

SET M2

RST M1

M2

FROM K100 K14 D14 K1

= D14 K2 RST

RST

M2

M2 = D14 K3

END

Explanations:

• The data exchange will be executed every one second.

• Write the communication address of the destination PLC in CR#28, and DVPEN01-SL will automatically detect by the previous setting that No. 1 IP is “192.168.0.4".

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

• Write the data in RTC into CR#29 ~ CR#35.

• Write “1” into CR#13 to start the data exchange.

• CR#14 = 2 refers to successful exchange. CR#14 = 3 refers to failed exchange.

5. Compile the ladder diagram for PLC_A and download it to PLC_A.

M1013

FROM K100 K49 D0 K7

END

Explanations:

• The received data are stored in CR#49 ~ CR#55.

• The data received every one second are written into D0 ~ D6.

6.10 Application of Data Exchange (2)

Application

Network requirement

Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A by designating IP by ladder diagram.

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5

(4) Update from PLC_B to PLC_A

1. See 6.1 for how to set up the communication. Compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design:

M1000

D100

M1013 M2 M1

SET M1

M1

TOP K100 K28 K0 K1

M2

= D14 K2

= D14 K3

TOP

TOP

K100

K100

TOP K100

TOP K100

TOP K100

K26 HC0A8

K25

K29

H4

D100

K14

K13

K0

K1

K1

K1

K7

K1

K1

SET

RST

M2

M1

FROM K100

RST

RST

M2

M2

END

K14 D14 K1

DVP-PLC Application Manual

47

Ethernet Communication Module DVPEN01-SL

48

Explanations:

• The data exchange will be executed every one second.

• Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination

PLC.

• Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 =

H’C0A8) should be written into CR#26, and the last two IP codes (0.4 = H’0004) into CR#25.

• Write the data in RTC into CR#29 ~ CR#35.

• Write “1” into CR#13 to start the data exchange.

• CR#14 = 2 refers to successful execution. CR#14 = 3 refers to failed execution.

2. Compile the ladder diagram for PLC_A and download it to PLC_A.

M1013

FROM K100 K49 D0 K7

END

Explanations:

• The received data are stored in CR#49 ~ CR#55.

• The data received every one second are written into D0 ~ D6.

6.11 Application of Data Exchange (3)

Application

Network requirement

Writing the time in RTC in PLC_B directly into D0 ~ D6 of PLC_A without writing in ladder diagram into PLC_A.

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5

(4) Update from PLC_B to PLC_A.

1. See 6.1 for how to set up communication.

2. Compile the ladder diagram in the MPU and download it to PLC_B. We do not need to write any corresponding ladder diagram into PLC_A.

M1000

D100

M1013 M2 M1

SET M1

M1

TOP K100 K28 K0 K1

TOP K100 K26 HC0A8 K1

TOP K100

TOP K100

TOP K100

TOP K100

K25 H4

K81 H1000

K84 H1000

K85 K7

K1

K1

K1

K1

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

TOP K100 K86 H1064 K1

TOP

TOP

K100

K100

K14

K13

K0

K1

K1

K1

SET M2

RST M1

M2

FROM K100 K14 D14 K1

= D14 K2 RST

RST

M2

M2 = D14 K3

END

Explanations:

• The data exchange will be executed every one second.

• Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination

PLC.

• Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 =

H’C0A8) should be written into CR#26, and the last two IP codes (0.4 = H’0004) into CR#25.

• Write the Modbus address of D0 (H’1000) in PLC_A into CR#81 and CR#84.

• Write the Modbus address of D100 (register of RTC) (H’1064) into CR#86.

• Write the number of registers K7 into CR#85.

• Write “1” into CR#13 to start the data exchange.

• CR#14 = 2 refers to successful execution. CR#14 = 3 refers to failed execution.

• Once the data exchange is successful, the values in D1313 ~ D1318 in PLC_B will be written into

D0 ~ D6 of PLC_A.

6.12 Application of Modbus TCP Master (1)

Application Compiling Modbus instrcution by PLC_B, making Y0 of PLC_A flashing

Network requirement

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5

(4) Update from PLC_B to PLC_A

(5) Use Modbus instrcution 050500FF00 to set “On” Y0.

(6) Use Modbus instrcution 0505000000 to set “Off” Y0.

(7) Y0 goes between On/Off once every one second.

1. See 6.1 for how to set up the communication.

2. Compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design.

We do not need to write any corresponding ladder diagram into PLC_A.

DVP-PLC Application Manual

49

Ethernet Communication Module DVPEN01-SL

50

M1013 M2

M1

M1

= D0 K0

= D0 K1

SET

TOP

TOP

M1

K100 K118 HC0A8

K100 K117 H4

TOP

TOP

K100 K111

K100 K120

TOP K100 K121

K100 K122 TOP

TOP K100 K123

K1

H0

H5

H5

H0

HFF TOP K100 K124

TOP

TOP

K100 K124

TOP

K100 K125

K100 K119

H0

H0

K6

TOP K100 K116

TOP

INC

K100 K115

D0

K0

K1

K1

K1

K1

K1

K1

K1

K1

K1

K1

K1

K1

K1

K1

M2

= D0 K2 MOV

SET

RST

K0

M2

M1

D0

FROM K100 K116

RST

RST

M2

M2

D14 K1

= D14 K2

= D14 K3

END

Explanations:

• The data exchange will be executed every one second.

• Write the IP address of PLC_A into CR#117 and CR#118. The first two IP codes (192.168 =

H’C0A8) should be written into CR#118, and the last two IP codes (0.4 = H’0004) into CR#117.

• Set CR#111 as “1” to enable the 8-bit mode. The Modbus instrcution is stored in the low byte of

CR#120 ~ CR#247.

• Write Modbus instrcution into CR#120 ~ CR#125. CR#120 is the Modbus address.

DVP-PLC Application Manual

Ethernet Communication Module DVPEN01-SL

• Write the length of the instrcution into CR#119.

• Write “1” into CR#115 to start the execution of Modbus TCP instrcution.

• CR#116 = 2 refers to successful execution. CR#116 = 3 refers to failed execution.

• If the execution is successful, Y0 on PLC_A will go between On and Off every one second.

DVP-PLC Application Manual

51

Ethernet Communication Module DVPEN01-SL

MEMO

52 DVP-PLC Application Manual

advertisement