Original instructions
SIRe Advanced
Modbus communication
GB .... 2
SIRe Modbus
This manual describes how to connect SIRe
Advanced with Modbus/RTU via RS485, the
technical specification of the protocol in SIRe,
the parameters and their use.
For more information about other functions
in SIRe, please see the main manual.
For more information about Modbus please
contact your BMS supplier or
www.modbus.org
Connection
Modbus/RTU via RS485, connects on a 3
pole contact on terminal [BUS] on the SIReA1N.
What information is presented
Please see list of parameters.
What information is not presented
Information regarding run times for each
individual unit is stored on the B1-pcb and
can only be viewed locally.
Modbus Information
Supported functions
Function codes 01, 02, 03, 04, 05, 06,
08, 15, and 16 are supported. Diagnostics (08)
supports sub-codes 0, 2, 10, 11, 12, 13, and
14.
PDU length
Maximum PDU length is 256 bytes.
Supported network topology
General 2-wire topology described in
Modbus specifications is supported. Multiple
slaves are supported.
Software supports only RTU mode; ASCII
mode serial transmission is not supported.
Ground level
Internal and external bus shares the
same common ground, the RS-485 signals are
not isolated.
Start and stop bits
One start bit, one stop bit.
Parity
Current software uses only
'None' parity mode.
Broadcast
Broadcast not supported because A1
fails to not to respond broadcast.
Setting values outside valid range
If written values are outside their
allowed range, they will be set to the nearest
value which is in the range.
Bus termination
Bus is not terminated but it has 4.7
kohm pull-up and pull-down resistors.
Registers used
Coils, discrete inputs, and input
registers are supported, but there are no
registers. So the responce is always "Illegal
data address".
Holding register
16 bit integer register R/W
Terminal
Modbus/RTU
RS-485
(EIA/TIA-485)
Function
23
D0
A/A’
Non-inverting
Pull-down [-]
24
D1
B/B’
Inverting
Pull-up [+]
25
Com
C/C’
Signal ground
SIReUA1 Menu structure - Gateway functions
> Installer menu
Mixing cabinet
External control
General settings
> Installer menu > External
control
0-10V fan control
0-10V heat control
Gateway functions
> Installer menu > External
control > Gateway functions
> Installer menu > External
control > Gateway functions
System on/off enable
Room temp. enable
Outdoor temp. enable
Fan speed enable
Heating step enable
Door position enable
=4x00051
=4x00049
> Installer menu > External
control > Gateway functions
> Installer menu > External
control > Gateway functions
Baud rate and Modbus ID is set
locally, using the control panel,
SIReUA1, see menu structure.
System on/off enable
Room temp. enable
Outdoor temp. enable
Heating step enable
Door position enable
Week program enable
=4x00046
=4x00050
Explanation:
Room temp. enable
Outdoor temp. enable
Water temp. enable
Door position enable
Week program enable
Modbus ID
=4x00047
=4x00052
Ambient
Electrically heated
Water heated
AC
FH
All
Air Curtains
Fan Heaters
All type
> Installer menu > External
control > Gateway functions
> Installer menu > External
control > Gateway functions
> Installer menu > External
control > Gateway functions
> Installer menu > External
control > Gateway functions
Outdoor temp. enable
Water temp. enable
Fan speed enable
Week program enable
Modbus ID
Baud rate
=4x00086
Set using UA1
> Installer menu > External
control > Gateway functions
> Installer menu > External
control > Gateway functions
Water temp. enable
Fan speed enable
Heating step enable
Week program enable
Modbus ID
Baud rate
=4x00048
Set using UA1
Register
Room temperature
Outdoor temperature
Fan speed
Heating step
Door position
System on/off
Week program
Room temp. day SET
Room temp. night SBT
High speed limit
Speed closed door Low
Summer/Winter Season
Door mode
Fan mode FanMode
Stepless fan control
T max speed winter TmaxH
T min speed winter TminH
T min speed summer TminC
T max speed summer TmaxC
Over run mode Auto/fix
High speed over run Hdelay
Low speed over run Ldelay
Outdoor temp. limit TLIMH
Eco / Comfort TcomfortMode
Open door setp. diff. DiffS
Heating step diff. DiffH
Room temp. sensor Calib
Outdoor temp. sensor Calib
Return temp. sensor
Return temp. limit
Heating step limit
Modbus
4x00001
4x00002
4x00003
4x00004
4x00005
4x00006
4x00007
4x00008
4x00009
4x00010
4x00011
4x00012
4x00013
4x00014
4x00015
4x00016
4x00017
4x00018
4x00019
4x00020
4x00021
4x00022
4x00023
4x00024
4x00025
4x00026
4x00027
4x00028
4x00029
4x00030
4x00031
0
0
0
-10,0
-10,0
0
0
0
5
0
0
0
-30
-30
-30
-30
0
0
0
0
0
0
5
5
0
0
0
0
0
-1500
-1500
Min
3
90
1
10,0
10,0
10,0
10,0
1
35
500
180
1
30
30
30
30
1
3
2
1
100
100
35
35
2
1
1
100
100
1500
1500
Max
Step
°C
K
K
0,1°C
0,1°C
°C
s
s
°C
°C
°C
°C
%
%
°C
°C
%
%
0.1°C
0.1°C
Unit
All
All
All
All
AC
All
All
AC
AC
AC
AC
AC
AC
AC
All
FH
AC
All
AC
All
All
All
All
All
AC
All
All
All
All
Type
Limit the heat, when using stepless heat, 0-100%
Maximum temperature of return water when WTA is used (temp. > [set value] reduces the waterflow)
0 = Room, 1 = Return water. If WTA is used, set 4x00029=1
Offset of the outdoor temperature value
Offset of the room temperature value
The temperature difference between activation of electrical heating steps or
increase of fan speed for water heated FH.
Increase of temperature set value when the door opens.
0 = Eco, 1 = Comfort. See main manual for function description.
Blocks the heat when value on outdoorsensor is above set value.
Set overruntime for low speed when parameter 4x00020=1
Reads currently used overrun time when 4x00020=0 and not the manually set value.
Rounds to nearest multiple of 10. Manually set overruntime for High speed when parameter 4x00020=1
0 = Auto, 1 = User See main manual for function description.
At what outside temperature the AC should run at high speed during summer conditions
At what outside temperature the AC should run at low speed during summer conditions
At what outside temperature the AC should run at low speed during winter conditions
At what outside temperature the AC should run at high speed during winter conditions
0 = Off, 1 = On Used for controlling a unit with frequency inverter, EC-motors or
other 0-10VDC controlled fan.
0 = Auto, 1 = Thermostat, Manual fan, 2 = Thermostat, Auto fan, 3 = Manual
0 = Auto, 1 = Fix Open/Close, 2 = Fix open
Set depending on use of door (Always open, open/closed or a mix.)
0 = Summer (no heat), 1 = Winter (Heat available) Parameter not active in Advanced.
Speed limit at closed door
Limits the fans maximum speed (For AC, at open door)
Temperature setpoint when Night is active
Temperature setpoint during Day time (deafault value)
0 = Off, 1 = Day, 2 = Night. To write: set parameter 4x00052=1
0 = Off, 1 = On. To write: set parameter 4x00051=1
0 = Closed door, 1 = Open door. To write: set parameter 4x00050=1
Read or write heat step. To write: set parameter 4x00049=1
Read or write fan speed. To write: set parameter 4x00048=1
Read or write outdoor temperature. To write: set parameter 4x00047=1
Read or write room temperature. To write: set parameter 4x00046=1
Notes
Register
Stepless heat control
Control range limit
Filter timer on/off
Filter timer setting
External filter guard
Last filter change HCFL
Mixing cabinet ctrl ON/OFF
Min outlet temp.
Day damper pos. DPD
Night damper pos. DPN
External on/off ON/OFF
0-10V fan control ON/OFF
0-10V heat control ON/OFF
Set point correction
Enable ext. room temp.
Enable ext. outd. temp.
Enable ext. fan speed
Enable ext. heating step
Enable ext. door contact
Enable ext. on/off
Enable ext. week prgm.
Clock, year
Clock, month
Clock, day of month
Clock, hours
Clock, minutes
Clock, seconds
Max over run time Delay/
DelayF
It over run stop T
Time interval stages ET
Modbus
4x00032
4x00033
4x00034
4x00035
4x00036
4x00037
4x00038
4x00039
4x00040
4x00041
4x00042
4x00043
4x00044
4x00045
4x00046
4x00047
4x00048
4x00049
4x00050
4x00051
4x00052
4x00053
4x00054
4x00055
4x00056
4x00057
4x00058
4x00059
4x00060
4x00061
1
10
10
0
0
0
1
1
2010
0
0
0
0
0
0
0
-10
0
0
0
0
0
5
0
0
0
0
5
0
Min
10
40
300
59
59
23
31
12
2099
1
1
1
1
1
1
1
10
1
1
1
100
100
35
1
1
9950
1
35
1
Max
min
°C
s
s
m
h
°C
%
%
°C
h
h
°C
Unit
AC
All
All
All
All
All
All
All
All
All
All
AC
All
All
All
All
All
All
All
All
FH
FH
FH
FH
All
All
All
All
All
All
Type
During the function Stages (see main manual) the roomtemp is measured every [set value] minute
If internal temp. Drops below set value during overrun countdown, the fan stops.
Fan overrun countdown after heat has been on. Rounds to nearest multiple of 10.
Reading year copies system clock to internal buffer. All reads and writes are from/to internal buffer.
Writing seconds copies time from internal buffer to system clock.
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
0 = Off, 1 = On Set =1 if BMS should write value to SIRe
If central sensor is used and offset is required
0 = Off, 1 = On (ExternalHeatControlEnable) A1X T13-14
Activate if external heat signal is connected to terminals 13 and 14
0 = Off, 1 = On (ExternalFanControlEnable) A1X T11-12
Activate if external fan rpm signal is connected to terminals 11 and 12
0 = Off, 1 = On (ExternalOnOffEnable) A1X T15-16
Activate if external On/Off signal is connected to terminals 15 and 16
sets damper position during night time
sets damper position during day time or if no week program is used
Set minimum air outlet temperature.
0 = Off, 1 = On. Activate when fan heater is used together with mixing cabinet.
Time since last filter change. Read only
0 = Off, 1 = On. Activate if external filter guard is connected to terminals 9 and 10.
Set countdown time for the filter alarm. Rounds to nearest multiple of 50.
0 = Off, 1 = On. Activates the filter timer
Limits a Users maximum set value
0 = Off, 1 = On. For water heated units 4x00032=1.
For electrical units additional external components must be used for stepless heat.
Notes
Min. water flow 0-3 V, 0,1V step
Door contact func. NC/NO
It_react
It_alarm
RTG_react
RTG_alarm
Min. return temp.
Device ID Read only:
Motor alarm TK
Over heating alarm ON/OFF
Outlet temp. Limit
Outlet temp. limit Eco
Outlet temp. limit Diff
Outlet temp. limit Alarm
Installation year
Installation month
Installation day
Reserved for future use, no access.
4x00063
4x00064
4x00065
4x00066
4x00067
4x00068
4x00069
4x00070
4x00071
4x00072
4x00073
4x00074
4x00075
4x00076
4x00077
4x00078
4x00079
4x00080
E2 two or more B1 have same ID
4x00102
Reserved for future use, no access.
4x00089
E1 Communication error
Reserved for future use, no access.
4x00088
4x00101
Reserved for future use, no access.
4x00087
Reserved for future use, no access.
Enable ext. return water temp.
4x00086
Reset alarm
Baud rate
4x00085
4x00100
Modbus ID
4x00084
4x00090
Reserved for future use, no access.
4x00083
4x00082 Mixing Cab. Outdoor temp. limit
4x00081 Return water temperature. (WTA)
0
Functionality mode Comp/Adv
4x00062
0
0
0
0
-50
30
0
20
20
0
0
5
5
5
5
5
0
0
Min
Modbus Register
1
1
1
1
50
100
100
100
100
1
1
30
20
20
15
15
1
30
1
Max
°C
0,1°C
°C
°C
°C
°C
°C
°C
°C
0,1V
Unit
All
All
All
All
All
FH
All
All
All
All
All
All
All
All
All
All
AC
All
Type
Please see QG/main manual for information regarding alarm and errors.
Communication error may sometimes not be presented via Modbus.
Reads 1 if at least one alarm is active. Write 1 to reset all alarms.
1 = Off, 1 = On. Set =1 if BMS should write value to SIRe
0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200, 4 = 38400, 5 = 57600
Read only.
SIRe to receive water temp. from BMS. Write/Read to/from BMS. To write: set parameter 4x00086=1
Read only. For information only.
Read only. For information only.
Read only. For information only.
[Set value] = overheat alarm
[Set value] above outlet temp. Limit, Heat=0
[Set value] limits the air outlet temperature in Eco mode (32°C) Heat decreases
[Set value] limits the air outlet temperature in Comfort mode, overides set
0 = Normal, 1 = Disabled. Activate/Deactivate internal over heat alarm
0 = Normal, 1 = Disabled. Activate/Deactivate motorprotection alarm
1=AC1, 2=AC2…, 129=FH1, 130=FH2… 254/255=Unknown or error. Unit program, Reads from B1.
Depends on unit. Should not be changed.
Frost protection: At stationary fan, [Set value] is the minimum return water temperature.
Frost protection: Return water sensor (WTA) Set value opens valve , stops fan and closes damper
Frost protection: Return water sensor (WTA) Set value opens valve
Frost protection: Internal temp sensor Set value opens valve , stops fan and closes damper
Frost protection: Internal temp sensor Set value opens valve
0 = NC, 1 = NO. (Only physical contact). Invert door contact function
Set minimum waterflow when valve is closed. 0,1V=1%
0 = Advanced, 1 = Competent. Set functionlevel. If competent is set, the system ignore outdoor sensor value or errors
Notes
Register
E3 B1 without program
E4 Missing/faulty RTX sensor on B1
Always zero, writes ignored
E6 Faulty RTG sensor on B1
E7 Missing RTG (when mandatory)
E8 It sensor error
Always zero, writes ignored
E10 two B1 with different program
Always zero, writes ignored
E12 Missing/faulty RTX on A1X
Always zero, writes ignored
E14 Outdoor sensor error
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
E21 Sensor error in UA1
Always zero, writes ignored
E23 Incompatible B1
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
Always zero, writes ignored
A1 Motor alarm
A2 Overheat alarm
A3 Freeze alarm
A4 Filter alarm
A5 External alarm
Reserved for future use, no access.
Reserved for future use, no access.
Empty
Modbus
4x00103
4x00104
4x00105
4x00106
4x00107
4x00108
4x00109
4x00110
4x00111
4x00112
4x00113
4x00114
4x00115
4x00116
4x00117
4x00118
4x00119
4x00120
4x00121
4x00122
4x00123
4x00124
4x00125
4x00126
4x00127
4x00128
4x00129
4x00130
4x00131
4x00132
4x00133
4x00134
4x00135
Empty
0
0
0
0
0
0
0
0
0
0
0
Min
1
1
1
1
1
1
1
1
1
1
1
Max
Unit Type
Empty
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Units with software from different generations. Require excahange of components, contact Frico
E22 not available through Modbus. Please see QG/main manual for more information.
E20 not available through Modbus. Please see QG/main manual for more information.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Please see QG/main manual for information regarding alarm and errors.
Notes
Notes