advertisement
TB7220U
CommercialPRO™
Programmable Thermostat
INSTALLATION INSTRUCTIONS
APPLICATION
The TB7220U Programmable Thermostat provides electronic control of 24 Vac heating and cooling systems.
See Table 1 for a description.
Feature
Powering Methods
System Types
Changeover
System Setting
Fan Setting
Table 1. TB7220U Thermostat Description.
Description
• Battery only
• Direct connection to a 24 Vac transformer only
• Direct connection to a 24 Vac transformer with battery backup
• Conventional (up to 2 Heat, 2 Cool stages)
• Heat Pump (up to 3 Heat, 2 Cool stages)
Manual or automatic changeover (selectable)
Heat-Off-Cool-Auto
Auto-On
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
INSTALLATION
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
Select Thermostat Location
Select a location for the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
62-0221-05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
YES
NO
6. Insert the mounting screws into the wall anchors and tighten.
DRILLED
HOLES (2)
WALL
ANCHORS (2)
NO
NO 5 FEET
[1.5 METERS]
WALLPLATE
M22258
Fig. 1. Select thermostat location.
Do not install the thermostat where it can be affected by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall behind the thermostat.
Separate Wallplate from
Thermostat
1. Separate the wallplate from the thermostat. See
Fig. 2.
WALLPLATE
WIRE HOLE
THERMOSTAT
M22267
Fig. 2. Separate wallplate from thermostat.
Install Wallplate (See Fig. 3)
Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow pointing up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two
3/16 in. holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Tap the wall anchors (provided) into the drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the wallplate and position the wallplate over the wall anchors.
M22268
MOUNTING
SCREWS (2)
Fig. 3. Install wallplate.
WIRING
IMPORTANT
— All wiring must agree with applicable codes, ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is not required.
NOTES:
— Sensor wires must have a cable separate from the thermostat control cable.
— Refer to Table 2 for terminal designation descriptions.
— See Fig. 6 through 16 for wiring diagrams for specific equipment applications.
1. Select set of terminal identifications that correspond to your system type (conventional or heat pump).
(See Fig. 4).
C
G
Y
O/B
RC
R
SCREW
TERMINALS
C
G
Y
W
RC
R
W2
Y2
A
S1
S2
W1
Y2
A
S1
S2
CONVENTIONAL
HEAT PUMP
M23010
Fig. 4. Terminal identifications for system type.
2. Loosen screw terminals used for the application.
3. Insert the wires into the terminal block and tighten each screw terminal.
4. Push excess wire back into the wall opening and restrict wires to the shaded area. See Fig. 5.
5. Plug the wall opening with nonflammable insulation to prevent drafts from affecting the thermostat.
62-0221—05 2
WIRE WALLPLATE
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
WALL OPENING
SHADED AREA
M22266
Fig. 5. Restrict wires to shaded area of wire hole.
Terminal Designation
RC (see Note 1)
R (see Note 1)
Y
C (see Note 2)
W
G
W2
Y2
O/B (see Note 3)
A (see Note 4)
S1 (See Note 5)
S2 (See Note 5)
W1
Table 2. Terminal Designation Descriptions.
Description
Power for cooling—connect to secondary side of cooling system transformer.
Power for heating—connect to secondary side of heating system transformer.
Compressor output.
Common wire from secondary side of cooling system transformer.
Heat relay.
Fan relay.
Second stage heat relay.
Second stage cooling.
Changeover valve for heat pumps.
Economizer/Time-Of-Day (TOD) output—powered via RC terminal.
Optional outdoor or indoor remote sensor.
Optional outdoor or indoor remote sensor.
Auxiliary Heat Relay Output (Head Pump Mode 2H/1C, 3H/2C)
NOTES:
1.
2.
3.
4.
5.
When used in a single-transformer system, leave metal jumper wire in place between RC and R. If used on a two-transformer system, remove metal jumper wire between RC and R.
Common wire is optional when thermostat is used with batteries. When using separate transformers for heating and cooling, the common must come from the cooling transformer.
If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).
Reference economizer literature for wiring details. When set for economizer operation, the A terminal provides the occupancy signal.
(Power indicates occupied.)
Sensor wires must have a cable separate from the thermostat control cable.
Terminal “A” Wiring Details for
Economizers
— Wire the A terminal to the W7212 “N” terminal, or the
W7459 “TR” terminal.
— When using dual transformers at the thermostat, the cooling transformer must power the economizer.
— The A signal is powered from the RC terminal and energizes the economizer to signal occupied status and drive the damper to the set minimum position.
Table 3. Wiring Diagrams.
System Type
Standard Heat/Cool
Heat Only
Heat Only with Fan
Cool only
Standard Multistage up to 2 Heat/2 Cool
Heat Pump
(No Auxiliary Heat)
Wallplate
Terminal
Identifications
Conventional
Conventional
Conventional
Conventional
Conventional
Heat Pump
Heat Pump
(with Auxiliary Heat)
Heat Pump
Multiple TR21 Sensors
Multiple C7189U Sensors —
3
—
Wiring
Diagram
Figure
6, 7
8
9
10
11, 12
13, 14
15, 16
17, 18, 19
20
62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Conventional System Wiring
1
L1
1
(HOT)
L2
24 VAC
2
HEAT RELAY
COMPRESSOR CONTACTOR
FAN RELAY
C
G
Y
W
RC
R
3
W2
Y2
A
S1
S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
2
3
ECONOMIZER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
M23011
Fig. 6. Typical wiring of single transformer
1H/1C system.
L2 24 VAC
2
C
G
Y
W
RC
R
3
W2
Y2
A
S1
S2
HEAT RELAY
ECONOMIZER
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
OPTIONAL.
M23013
Fig. 8. Typical hookup of heat-only system.
1
L1
(HOT)
L2
24 VAC
2
C
G
Y
W
RC
R
3
W2
Y2
A
S1
S2
L1
1
(HOT)
24 VAC
L2
COOLING
TRANSFORMER
2
C
G
Y
W
RC
R
3 W2
Y2
A
S1
S2
1
L1
(HOT)
24 VAC
L2
HEATING
TRANSFORMER
FAN RELAY
COMPRESSOR CONTACTOR
HEAT RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
ECONOMIZER
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT
TO THE COOLING TRANSFORMER SECONDARY.
M23012
Fig. 7. Typical hookup of dual transformer
1H/1C system.
HEAT RELAY
FAN RELAY
ECONOMIZER
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2 FACTORY INSTALLED JUMPER.
3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
M23014
Fig. 9. Typical hookup of heat-only system with fan.
1
L1
(HOT)
L2
24 VAC
2
C
G
Y
W
RC
R
3
W2
Y2
A
S1
S2
COMPRESSOR CONTACTOR
FAN RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
2
3
ECONOMIZER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
M23015
Fig. 10. Typical hookup of cool-only system.
62-0221—05 4
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
L2
1
24 VAC
2
C
G
Y
W
RC
R
3 W2
Y2
A
S1
S2
COOL RELAY 1 COOL RELAY 2
FAN RELAY
HEAT RELAY 1
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY 2
ECONOMIZER
1
2
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
M23016
Fig. 11. Typical hookup of single transformer multistage system (up to 2H/2C).
1
L1
(HOT)
L2
24 VAC
2
C
G
Y
W
RC
R
3
W2
Y2
A
S1
S2
1
FAN RELAY
COOL RELAY 1 COOL RELAY 2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
2
3
HEAT RELAY 1
HEAT RELAY 2
ECONOMIZER
24 VAC
L2
HEATING
TRANSFORMER
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT
TO THE COOLING TRANSFORMER SECONDARY.
M23017
Fig. 12. Typical hookup of dual transformer multistage system (up to 2H/2C).
5 62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Heat Pump System Wiring
L1
(HOT)
L2
1
24 VAC
3
W1
Y2
A
S1
S2
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
FAN RELAY
2 FACTORY INSTALLED JUMPER.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
ECONOMIZER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
5
3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
5 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
M23018
Fig. 13. Typical hookup of single-stage heat pump with no auxiliary heat (1H/1C).
L1
(HOT)
4 O/B
RC
R
C
G
Y
2
3
L2
1
24 VAC
4
C
G
Y
O/B
RC
R
2
W1
Y2
A
S1
S2
FAN RELAY
CHANGEOVER VALVE
COMPRESSOR 1 COMPRESSOR 2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
5
ECONOMIZER
2
3
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
5 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
M23019
Fig. 14. Typical hookup of multistage heat pump with no auxiliary heat (2H/2C).
L1
(HOT)
L2
1
24 VAC
4
C
G
Y
O/B
RC
R
2
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
FAN RELAY
ECONOMIZER
3
W1
Y2
A
S1
S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
5
AUXILIARY HEAT RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
3
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
5 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
M23020
Fig. 15. Typical hookup of single-stage heat pump with auxiliary heat (2H/1C).
L2
1
24 VAC
4
C
G
Y
O/B
RC
R
2
3
W1
Y2
A
S1
S2
CHANGEOVER VALVE
COMPRESSOR 1
FAN RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
5
AUXILIARY HEAT RELAY
COMPRESSOR 2
ECONOMIZER
2
3
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
4
5
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
M23021
Fig. 16. Typical hookup of multistage heat pump with auxiliary heat (3H/2C).
62-0221—05 6
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Sensor Wiring for Temperature
Averaging
S1
SUBBASE
S2
TR21
SUBBASE
S1 S2
TR21
T T T T
TR21
T T T4
1
TR21-A
T3
TR21
T T
TR21 TR21
T T T T
M27481
Fig. 17. Wiring four T7770A1006 (20K ohm) Sensors.
S1
SUBBASE
S2
1 THE TR21-A IS A 10K OHM SENSOR.
M27483
Fig. 19. Wiring two TR21 (20K ohm) Sensors and one
TR21-A (10K ohm) sensor to provide a temperature averaging network
S1
SUBBASE
S2
1
C7189 C7189
T4 T3 T4 T3
C7189 C7189
1
TR21-A
1
TR21-A
1 THE TR21-A IS A 10K OHM SENSOR.
M27482
Fig. 18. Wiring two TR21-A (10K ohm) Sensors to provide a temperature averaging network.
1 WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M23027
Fig. 20. Wiring four C7189U (10K ohm) Sensors to provide a temperature averaging network.
7 62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
POWER THE THERMOSTAT
You can choose from three methods to power the thermostat:
• Batteries only (AA alkaline).
• 24 Vac direct connection only.
• 24 Vac direct connection with battery backup (AA alkaline).
REMOVE
TAB
Wiring 24 Vac Common
• Single-Transformer System—Connect the common side of the transformer to the C screw terminal of the thermostat wallplate. Leave the metal jumper wire in place between RC and R.
• Two-Transformer System—Connect the common side of the cooling transformer to the C screw terminal of the thermostat wallplate. Remove the metal jumper wire between RC and R.
Installing Batteries
1. Install two AA alkaline batteries on the back of the thermostat as marked. See Fig. 21.
BATTERIES (2) BATTERY HOLDER
M22260
Fig. 22. Remove tab labeled REMOVE from thermostat back.
Mount Thermostat to Wallplate
1. Align the terminal screw blocks with the pins on the back of the thermostat.
2. Push the thermostat straight onto the wallplate until it snaps into place. See Fig. 23.
WALL
M22259
BACK OF THERMOSTAT
Fig. 21. Installing batteries.
2. Locate and remove the tab labeled Remove. See
Fig. 22.
IMPORTANT
This tab must be removed in order to set the real-time clock.
Fig. 23. Mount thermostat to wallplate.
M23024
62-0221—05 8
SETTING CALENDAR AND TIME
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
This thermostat is designed to, under normal use, automatically keep current time and day in memory for up to ten years once the calendar is set. There are two ways to set the calendar and time for this thermostat:
SETTING DATE/TIME WHEN THERMOSTAT IS FIRST
POWERED
When the thermostat is first powered, the display is ready to set the calendar and time. The thermostat proceeds through a sequence of setup screens. See Fig. 24.
SETTING DATE/TIME AFTER THERMOSTAT IS
ALREADY FUNCTIONING
Use the installer setup to set year, month and day. See the Installer Setup Numbers, Settings, and Tests section.
YEAR
MONTH
DAY
UP AND DOWN BUTTONS
CHANGES MONTH, DAY,
YEAR AND TIME
Tue
PM
Done
GO BACK BUTTON
GOES BACK TO
LAST SETTING
DONE BUTTON
ADVANCES TO TIME SETTING
SCREEN AND HOME SCREEN
NEXT BUTTON
ADVANCE TO NEXT SETTING
Fig. 24. Setting calendar and time after initial powerup.
ADVANCED SETTINGS
The thermostat has advanced settings to match the HVAC system. These settings can be adjusted to match specific needs. See the following section (Installer Setup
Numbers, Settings, and Tests) for details.
M23023
9 62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)
Configure Installer Setup
1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until the screen changes.
4. When the display changes, release the System and
Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers and settings.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
Installer System Tests
Use the Installer System Test section to test the heating, cooling and fan. Refer to the latter portion of Table 4.
Table 4. Installer Setup Menu.
Installer
Setup
Number
0120
0130
0140
0150
0160
Installer Setup
Name
Default
Setting
Date (Year Upper) 20
All Settings
20—20xx
21—21xx
Date (Year Lower) 04 00-99
Date (Month)
Date (Day)
Schedule Options
6
15
4
1-12
1-31 (Month Dependent)
0170
0175
0180
System Selection
TOD/Economizer output (terminal A)
8
0
Heat Fan Operation 0
0—Non-Programmable
4—Programmable
1—1H/1C Conv
2—1H/1C HP
3—1H w/o fan
4—1H with fan
6—1C
7—2H/1C HP (Aux. Heat)
8—2H/2C Conv
9—2H/1C Conv
10—1H/2C Conv
11—2H/2C HP
12—3H/2C HP (Aux.
Heat)
0—Unused
1—TOD
2—Economizer
0—System controls fan
1—Thermostat controls fan (ON during call for heat)
0185
0190
0220
0230
Pre-occupancy
Purge Duration
Reversing Valve
O/B
Cycles Per Hour
(CPH) for first stage compressor
CPH for second stage compressor
0
0
3
3
0—no duration
1—one hour
2—two hours
3—three hours
0—O (O/B On Cool)
1—B (O/B On Heat)
1-6
1-6
Notes
Available year range: 2001 - 2178
Available year range: 2001 - 2178
To use the Emergency Heat button, select setting
#7 or #12. See Fig. 16 or 17 for auxiliary heat wiring.
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period, and deenergizes A during Unoccupied.
Only shown for conventional system with heat stages (ISU 0170) and fan capability selected.
If heat pump is selected, fan always operates with
Thermostat control.
The only thing that allows the fan to turn off during occupied periods is a manual override of the fan from On to Auto.
Only shown if thermostat is programmable (ISU
0160).
Pre-occupancy purge enabled by nonzero duration
(and sends economizer to minimum position).
Only shown with heat pump system selected.
Only shown for system with cool stages (ISU
0170). Selection in this stage changes second stage cool default CPH.
Only shown for system with two stages of cool
(ISU 0170).
62-0221—05 10
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
0240
Installer Setup
Name
CPH for first stage conventional heat
Default
Setting
5 1-12
All Settings
0250
0260
0270
0280
0300
0310
CPH for second stage conventional heat
CPH for Auxiliary
Heat
Continuous
Backlight
Changeover
Deadband
9
CPH for third Stage
Heat
9
9
0
1
3°F
(2°C)
1-12
1-12
1-12
0—No
1—Yes
Notes
Only shown for conventional system with heat stages (ISU 0170).
Selection in this stage changes default CPH of second stage heat.
Only shown for conventional system with at least two stages conventional heat or 2H/1C heat pump
(ISU 0170).
Only shown for 3H/2C heat pump system (ISU
0170).
Only shown for multi-stage heat pump system with more heat than cool stages (ISU 0170).
Always shown. If AC power not present the option is overridden and normal backlight operation occurs.
Only shown for system with both heat and cool stages (ISU 0170).
Only shown for Auto Changeover system (ISU
0300).
0320
0330
0340
0350
0360
0535
0540
0580
Temperature
Indication Scale
Daylight Saving
Remote
Temperature
Sensor
Heat Pump
Compressor
Lockout
Heat Pump
Auxiliary Lockout
Temporary
Occupied Duration
Limit
3
Number of Periods 4
Minimum
Compressor Off
Time
0
2
0
0
0
5
0—Manual
1—Auto
2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
0—°F
1—°C
0—Disabled
1—Enabled (US 1987)
2—Enable (US 2007)
3—Enabled (Europe)
0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35(1.5)—35°F (1.5°C)
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
0—None
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)
0—no duration
1—one hour
2—two hours
3—three hours
4—four hours
2—2 Periods
4—4 Periods
0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
Averaging would not include on-board sensor. It is accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing compressor lockout while displaying temperature).
Only shown for heat pump systems with more heat stages than cool (ISU 0170) and remote outdoor control sensor (ISU 0340 is 2).
Must enforce a dead band between this and
Auxiliary Lockout.
Only shown for heat pump systems with more heat stages than cool (ISU 0170) and remote outdoor control sensor (ISU 0340 at 2).
Must enforce a dead band between this and Heat
Pump Compressor Lockout.
0 means no limit.
Does not appear if Non-programmable is chosen
(ISU 0160).
Applies to all days of the week.
Only shown if system has cool stages (ISU 0170).
11 62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
0600
0610
0640
Installer Setup
Name
Heat Temperature
Range Stops
Cool Temperature
Range Stops
Clock Format
Default
Setting
90
All Settings
40 to 90°F (4 to 32°C)
50
12
50 to 99°F (10 to 37°C)
Notes
Only shown if system has heat stages (ISU 0170).
Only shown if system has cool stages (ISU 0170).
0650
0660
0670
0680
0685
0690
0695
0700
0710
Extended Fan-on time Heat
Extended Fan-on time Cool
Keypad Lockout
Temperature
Control Heat
Recovery Heat
Ramp Rate
Temperature
Control Cool
Recovery Cool
Ramp Rate
Temperature
Display Offset
Restore Factory
Defaults
0
0
0
2
5
2
3
0
0
12—12 Hour
24—24 Hour
0—Off
90—90 seconds
0—Off
40—40 seconds
0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
1—Less Aggressive
2—Standard
3—More Aggressive
0-20°F/hour
1—Less Aggressive
2—Standard
3—More Aggressive
0-20°F/hour
-3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
0—No
1—Yes
Not displayed with cool-only systems (ISU 0170) or with fan set to system control (ISU 0180 at 0).
Only shown for systems with cool stages (see ISU
0170).
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.
Only shown if system has heat stages (ISU 0170).
Only integral gains affected. Affects control operation in all control regimes (not just recovery or setpoint change).
More Aggressive stops signal prior to reaching the setpoint. (For use with oversized equipment.)
Only shown if system has heat stages (ISU 0170).
0 disables ramped recovery (step setpoint change at period start time).
Only shown if system has cool stages (ISU 0170).
Only integral gains affected. Affects control operation in all control regimes (not just recovery or setpoint change).
More Aggressive stops signal prior to reaching the setpoint. (For use with oversized equipment.)
Only shown if system has cool stages (ISU 0170).
0 disables ramped recovery (step setpoint change at period start time).
This offset applies to both the control temperature and to the display temperature for indoor sensor
(and remote indoor sensor).
Resets all ISU parameters to default values and resets the schedule to default (see Table 5).
Retains only calendar settings and time.
INSTALLER TESTS
Test 1 Installer Test
Cool
0
Test 2
Test 3
Test 4
Test 8
Installer Test
Fan
Installer Test
Heat
Installer Test
Auxiliary Heat
Installer Test
TOD/Economizer
0
0
0
0
0—Off
1—Cool Stage 1
2—Cool Stage 2
0—Off
1—Fan On
0—Off
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3
0—Auxiliary Heat Off
1—Auxiliary Heat On
0—TOD/Economizer Off
1—TOD/Economizer On
NOTE: Press the Done key to exit the Installer System Test.
62-0221—05 12
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
OPERATION
System Settings
Heat—Thermostat controls the heating system.
Off—Both heating and cooling systems are off.
Cool—Thermostat controls the cooling system.
Auto—Thermostat automatically changes between heat and cool operation, depending on indoor temperature.
Fan Settings
Auto —Fan runs only when heating/cooling system is on.
On—Fan runs continuously.
Table 5 shows default program settings. See Owner’s
Guide for complete instructions to change the program.
Table 5. Default Program Settings.
Schedule
Period
Occ1
Unocc1
Occ2
Unocc2
Setpoints
Time
8:00am
Heat
70°F
(21°C)
10:00pm 55°F
(10°C)
1:00pm 70°F
(21°C)
12:00pm
(Noon)
55°F
(10°C)
Cool
75°F
(25.5°C)
85°F
(24°C)
75°F
(25.5°C)
85°F
(24°C)
Fan
Setting
On
Auto
On
Auto
Minimum-Off Timer
(Compressor Protection)
The thermostat has an adjustable Minimum-Off Timer that can be set from zero to five minutes (Factory Setting—five minutes). The Minimum-Off Timer can be bypassed through the Installer System Test or it can be bypassed permanently by setting the Minimum-Off Timer to 0 minutes in the Installer Setup. The Minimum-Off Timer is activated after the compressor turns off:
— If the thermostat is system powered (common wire), the Minimum-Off Timer is also activated upon initial startup and after power interruptions.
— If there is a call for cooling or heating during the
Minimum-Off Time, the thermostat displays “Wait.”
— When the Minimum Off Timer expires, “Cool On” or
“Heat On” (heat pumps only)” appears solidly in the display and the compressor and fan turn on.
Outdoor or Indoor Temperature
Sensor
Allow outdoor or indoor temperature sensor to absorb the air for a minimum of five minutes before taking a reading.
See the Sensor instructions for more information.
Economizer/TOD Logic (Table 6)
Table 6. Operation of Terminal A.
Effective
Occupancy
Occupied
Call for
Cool
—
Unoccupied Yes
No
Override —
Terminal A
Economizer TOD
Energized Energized
Energized De-energized
De-energized De-energized
Energized Energized
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor
Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) installed; the thermostat controls this function:
1. Choose correct heat pump application in Installer
Setup Number 0170.
2. Choose Outdoor Temperature Sensor for Heat
Pump Temperature Lockouts Option in Installer
Setup Number 0340.
3. Choose appropriate Balance Point Temperature in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE
POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected
Balance Point Temperature (ISU 0350), only the compressor operates and the fan (G terminal) energizes when the thermostat calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE
POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected
Balance Point Temperature (ISU 0350), only the Fossil
Fuel (auxiliary heat) operates and the fan (G terminal) does not energize when the thermostat calls for heat.
Heat Pump with Auxiliary (Backup) Heat and Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer
Setup Number 0170.
2. Choose Outdoor Temperature Sensor for
Control Option in Installer Setup Number 0340.
3. Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
4. Choose Auxiliary Lockout Temperature in
Installer Setup Number 0360.
NOTE: There is a 5°F deadband between Compressor and Auxiliary Heat lockout temperatures.
Operation in Heat Mode
When the outdoor temperature is:
— Below the Compressor Lockout Temperature, only the
Auxiliary Heat operates.
— Above the Auxiliary Lockout Temperature, only the
Compressor operates. See Fig. 31.
— Between the two temperatures, both the Compressor and Auxiliary Heat operate.
50
COMPRESSOR ONLY
AUXILIARY
LOCKOUT
TEMPERATURE
BOTH COMPRESSOR AND
AUXILIARY HEAT
35
AUXILIARY ONLY
COMPRESSOR
LOCKOUT
TEMPERATURE
M19950
Fig. 25. Heat Pump Operation with Lockout
Temperatures Set.
13 62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
TROUBLESHOOTING (TABLE 7)
Symptom
Display does not come on.
Temperature settings do not change.
Heating or cooling does not come on.
Thermostat is calling for Heat
(Heat on) or Cool (Cool on) but no heating or cooling is running.
Heat does not turn on (Heat
On is solid in the display).
Table 7. Troubleshooting.
Possible Cause
Thermostat is not being powered.
The upper or lower temperature limits were reached.
The keypad is fully locked.
Thermostat minimum off-time is activated.
System selection not set to Heat or
Cool.
System type Selection is incorrect.
Action
Check for 24 Vac between C and RC.
Check that AA batteries are installed correctly and are good.
Check temperature setpoints.
Check Installer Setup Numbers 0600 and
0610; modify as needed.
Check Installer Setup Number 0670 to change keypad locked options.
Wait up to five minutes for the system to respond.
Set system Selection to correct position.
Heating or cooling equipment is not operating.
Heating equipment failure.
Check Installer Setup Number 0170 and make sure correct System type is chosen.
Check wiring.
Check Installer Setup Number 0170 and make sure correct system type is chosen.
Verify operation of equipment in System Test mode.
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem.
Loose or broken wire connection between thermostat and heating equipment.
Heat pump puts out cool air in the heat mode and warm air in the cool mode.
Changeover Valve (Installer Setup
Number 0190) is not configured to match the changeover required by the installed heat pump.
Both the heating and cooling equipment are running at the same time.
The heating equipment is not a heat pump but the System Type (Installer
Setup Number 0170) is set to Heat
Pump.
Heating and cooling wires are shorted together.
Cooling does not turn on (Cool
On is solid in the display).
Cooling equipment failure.
Check for 24 Vac between the heat terminal
(W) and transformer common. If 24 Vac is present, the thermostat is functional. Check the heating equipment to find the cause of the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment.
Set Changeover Valve (Installer Setup
Number 0190) to match the changeover required by the installed heat pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or cooling equipment.
Separate the shorted heating and cooling wires.
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem.
Loose or broken wire connection between thermostat and cooling equipment.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If 24 Vac is present, the thermostat is functional. Check the cooling equipment to find the cause of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If voltage is not present, check the wire connection (loose or broken) between the thermostat and the cooling equipment.
62-0221—05 14
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Table 7. Troubleshooting. (Continued)
Symptom
Fan does not turn on in a call for heat (electric furnace).
Heating equipment is running in the cool mode.
Possible Cause
Fan Control in Heating is set to Gas or
Oil Furnace (Setting 0180).
Heating equipment is not a heat pump but System Type (Installer Setup
Number 0170) is set to Heat Pump.
Heating equipment does not turn off and heat temperature setting is set below room temperature (Heat On is not in the display).
Cannot set the system setting to Heat.
Heating equipment is not a heat pump but System Type (Installer Setup
Number 0170) is set to Heat Pump.
System Type (Installer Setup Number
0170) is set to Cool Only.
Action
Set Fan Control in Heating to Electric
Furnace (Setting 0180).
Set System Type (Installer Setup Number
0170) to match the installed heating and/or cooling equipment.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or cooling equipment.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or cooling equipment.
Cannot set the system setting to Cool.
System Type (Installer Setup Number
0170) is set to Heat Only or Heat Only with Fan.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or cooling equipment.
Heat On is not in the display.
System setting is not set to Heat and/or temperature setting is not set above room temperature.
Set the system setting to Heat and set the temperature setting above the room temperature.
Cool On is not in the display.
System setting is not set to Cool and/or the temperature setting is not set below room temperature.
Set the system setting to Cool and set the temperature setting below the room temperature.
Wait is in the display.
Compressor minimum off timer is active.
Wait up to five minutes for the cooling or heating (heat pump) equipment to turn on.
15 62-0221—05
TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
SPECIFICATIONS
Electrical Ratings:
Terminal
W (Heating)
Y (Cooling)
Voltage
(50/60 Hz)
20 - 30 Vac
20 - 30 Vac
G (Fan) 20 - 30 Vac
A (Economizer/TOD) 20 - 30 Vac
Running
Current
0.02 - 1.0A
0.02 - 1.0A
0.02 - 0.60A
0.02 - 1.0A
Thermostat Dimensions: 3-3/4 in. (95 mm) high x 6 in.
(152 mm) wide x 1-3/8 in. (35 mm) deep.
Accessories:
C7089U Outdoor Sensor: 10K ohm NTC.
C7189U Remote Indoor Sensor: 10K ohm NTC.
C7772 Flush-Mount Remote Indoor Sensor:
20K ohm NTC.
TR21 Wall-Mount Remote Indoor Sensor:
20K ohm NTC.
TR21-A Wall-Mount Remote Indoor Sensor:
10K ohm NTC.
Temperature Setting Range:
Heating: 40°F to 90°F (4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient Temperature:
0°F to 120°F (-18°C to 49°C).
Shipping Temperature:
-30°F to 150°F (-34.4°C to 65.6°C).
Operating Relative Humidity (Non-condensing):
5% to 90%.
Perchlorate Material
This thermostat contains a Lithium battery which may contain Perchlorate material.
The following statement is required:
Perchlorate Material—special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9 customer.honeywell.com
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
62-0221—05 E.K. Rev. 04-10
Printed in U.S.A.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 Application
- 1 Installation
- 1 When Installing this Product...
- 1 Select Thermostat Location
- 2 Separate Wallplate from Thermostat
- 2 Install Wallplate (See Fig. 3)
- 2 Wiring
- 4 Conventional System Wiring
- 6 Heat Pump System Wiring
- 7 Sensor Wiring for Temperature Averaging
- 8 Power the Thermostat
- 8 Wiring 24 Vac Common
- 8 Installing Batteries
- 8 Mount Thermostat to Wallplate
- 9 Setting Calendar and Time
- 9 Advanced Settings
- 10 Installer Setup Numbers, Settings, and Tests (Table 4)
- 10 Configure Installer Setup
- 10 Installer System Tests
- 13 Operation
- 13 System Settings
- 13 Fan Settings
- 13 Minimum-Off Timer (Compressor Protection)
- 13 Outdoor or Indoor Temperature Sensor
- 13 Economizer/TOD Logic (Table 6)
- 13 Heat Pump Temperature Lockouts
- 14 Troubleshooting (Table 7)
- 16 Specifications