PowerXplorer
TM
PX5
USER’S GUIDE
DRANETZ - BMI
1000 New Durham Road
Edison, New Jersey 08818-4019
WARNING
Death, serious injury, or fire hazard could result from improper connection of this instrument. Read and understand this manual before connecting this instrument. Follow all installation and operating instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National Electrical Code (ANSI/
NFPA 70-2002) of USA and any additional safety requirements applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by qualified personnel only. The National Electrical Code defines a qualified person as “one who has the skills and knowledge related to the construction and operation of the electrical equipment and installations, and who has received safety training on the hazards involved.”
Qualified personnel who work on or near exposed energized electrical conductors must follow applicable safety related work practices and procedures including appropriate personal protective equipment in compliance with the Standard for Electrical Safety Requirements for Employee Workplaces (ANSI/NFPA
70E-2004) of USA and any additional workplace safety requirements applicable to your installation.
Published by Dranetz-BMI
1000 New Durham Road
Edison, NJ 08818-4019 USA
Telephone: 1-800-372-6832 or 732-287-3680
Fax: 732-248-1834
Web site: www.dranetz-bmi.com
Copyright© 2003, 2004 Dranetz-BMI
All rights reserved.
No part of this book may be reproduced, stored in a retrieval system, or transcribed in any form or by any means—electronic, mechanical, photocopying, recording, or otherwise—without prior written permission from the publisher, Dranetz-BMI, Edison, NJ 08818-4019.
Printed in the United States of America.
P/N UG-PX5 Rev. F ii
ADVERTENCIA
Una conexión incorrecta de este instrumento puede producir la muerte, lesiones graves y riesgo de incendio. Lea y entienda este manual antes de conectar. Observe todas las instrucciones de instalación y operación durante el uso de este instrumento.
La conexión de este instrumento debe ser hecha de acuerdo con las normas del Código Eléctrico Nacional
(ANSI/NFPA 70-2002) de EE. UU., además de cualquier otra norma de seguridad correspondiente a su establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada por personal calificado solamente. El Código Eléctrico Nacional define a una persona calificada como "una que esté familiarizada con la construcción y operación del equipo y con los riesgos involucrados."
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code (ANSI/NFPA 70-2002) des
Etats-Unis et à toutes les exigences de sécurité applicables à votre installation.
Cet instrument doit être installé, utilisé et entretenu uniquement par un personnel qualifié. Selon le
National Electrical Code, une personne est qualifiée si "elle connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers que cela implique".
WARNUNG
Der falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer verursachen. Bevor Sie dieses Instrument anschließen, müssen Sie die Anleitung lesen und verstanden haben. Bei der
Verwendung dieses Instruments müssen alle Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen Bestimmungen für
Elektrizität (ANSI/NFPA 70-2002) der Vereinigten Staaten, sowie allen weiteren, in Ihrem Fall anwendbaren Sicherheitsbestimmungen, vorgenommen werden.
Installation, Betrieb und Wartung dieses Instruments dürfen nur von Fachpersonal durchgeführt werden.
In dem nationalen Bestimmungen für Elektrizität wird ein Fachmann als eine Person bezeichnet, welche
"mit der Bauweise und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren vertraut ist." iii
Safety Summary
Definitions
Symbols
WARNING statements inform the user that certain conditions or practices could result in loss of life or physical harm.
CAUTION statements identify conditions or practices that could harm the Power
Xplorer, its data, other equipment, or property.
NOTE statements call attention to specific information.
The following International Electrotechnical Commission (IEC) symbols are marked on the top and rear panel in the immediate vicinity of the referenced terminal or device:
!
Caution, refer to accompanying documents (this manual).
Direct current (DC) operation of the terminal or device.
Power Switch
Definiciones
Las ADVERTENCIAS informan al usuario de ciertas condiciones o prácticas que podrían producir lesiones mortales o daño físico.
Las PRECAUCIONES identifican condiciones o prácticas que podrían dañar la Power
Xplorer, sus datos, otros equipos o propiedad.
Las NOTAS llaman la atención hacia la información específica.
Símbolos
Los siguientes símbolos de la Comisión Internacional Electrotécnica (IEC) aparecen marcados en el panel superior y el posterior inmediatos al terminal o dispositivo en referencia:
!
Precaución, consulte los documentos adjuntos (este manual).
Operación de corriente continua (CC) del terminal o dispositivo.
Interruptor de encendido
Continued on next page
iv
Safety Summary,
Continued
Définitions
Symboles
Les messages d’AVERTISSEMENT préviennent l’utilisateur que certaines conditions ou pratiques pourraient entraîner la mort ou des lésions corporelles.
Les messages de MISE EN GARDE signalent des conditions ou pratiques susceptibles d’endommager “PowerXplorer”, ses données, d’autres équipements ou biens matériels.
Les messages NOTA attirent l’attention sur certains renseignements spécifiques.
Les symboles suivants de la Commission électrotechnique internationale (CEI) figurent sur le panneau arrière supérieur situé à proximité du terminal ou de l’unité cité:
!
Mise en garde, consultez les documents d’accompagnement (ce manual).
Fonctionnement du terminal ou de l’unité en courant continu (CC).
Interrupteur de tension
Definitionen
WARNUNGEN informieren den Benutzer darüber, daß bestimmte Bedingungen oder
Vorgehensweisen körperliche oder tödliche Verletzungen zur Folge haben können.
VORSICHTSHINWEISE kennzeichnen Bedingungen oder Vorgehensweisen, die zu einer Beschädigung von PowerXplorer, seiner Daten oder anderer Geräte bzw. von
Eigentum führen können.
Symbole
HINWEISE machen auf bestimmte Informationen aufmerksam.
Die folgenden Symbole der Internationalen Elektrotechnischen Kommission
(International Electrotechnical Commission; IEC) befinden sich auf der Abdeck- und
Seitenplatte unmittelbar am betreffenden Terminal oder Gerät.
!
Vorsichtshinweis, siehe Begleitdokumente (dieses Handbuch).
Gleichstrombetrieb im Terminal oder Gerät.
Netzschalter
Continued on next page
v
Safety Summary,
Continued
Safety precautions
The following safety precautions must be followed whenever any type of voltage or current connection is being made to the PX5.
• Wear proper Personal Protective Equipment, including safety glasses and insulated gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
• Set the PX5 power switch to Off.
• Before connecting to electric circuits to be monitored, open their related circuit breakers or disconnects. DO NOT install any connection of the PX5 to live power lines.
• Connections must be made to the PX5 first, then connect to the circuit to be monitored.
These safety precautions are repeated where appropriate throughout this manual.
vi
Statements and Notices
Statement of warranty
All products of Dranetz-BMI are warranted to the original purchaser against defective material and workmanship for a period of one year from the date of delivery. Dranetz-
BMI will repair or replace, at its option, all defective equipment that is returned, freight prepaid, during the warranty period. There will be no charge for repair provided there is no evidence that the equipment has been mishandled or abused. This warranty shall not apply to any defects resulting from improper or inadequate maintenance, buyersupplied hardware/software interfacing, unauthorized modification or misuse of the equipment, operation outside of environmental specifications, or improper site preparation or maintenance.
Statement of reliability
The information in this manual has been reviewed and is believed to be entirely reliable, however, no responsibility is assumed for any inaccuracies. All material is for informational purposes only and is subject to change without prior notice.
Notice regarding
FCC compliance
This device has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his/her own expense.
Notice regarding proprietary rights
This publication contains information proprietary to Dranetz-BMI. By accepting and using this manual, you agree that the information contained herein will be used solely for the purpose of operating equipment of Dranetz-BMI.
Continued on next page
vii
Statements and Notices,
Continued
Copyright
This publication is protected under the Copyright laws of the United States, Title 17 et seq. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form, by any means, electronic, mechanical, magnetic, optical, chemical, manual, or otherwise, without the prior written consent of Dranetz-BMI, 1000 New Durham Road, Edison,
New Jersey 08818.
Copyright © 2003, 2004 Dranetz-BMI
All Rights Reserved. Printed in the United States of America.
Trademarks
PowerXplorer, Scope Mode, NodeLink and DranView are registered trademarks of
Dranetz-BMI.
viii
Table of Contents
Safety Summary ....................................................................................................................
Statements and Notices..........................................................................................................
iv vii
CHAPTER 1 - Getting Started
Overview ...............................................................................................................................
1-1
Unpacking the PX5................................................................................................................
1-3
Standard Accessories .............................................................................................................
1-4
PX5 Controls, Indicators, and Connectors ............................................................................
1-5
Top and Side Views ........................................................................................................
1-6
Front View ......................................................................................................................
1-7
Bottom View ...................................................................................................................
1-8
Rear View .......................................................................................................................
1-9
Upgrading Firmware from a Data Card.................................................................................
1-10
PX5 Features..........................................................................................................................
1-12
Basic Operation .....................................................................................................................
1-14
Power-on Sequence.........................................................................................................
1-15
Home Screen Icons .........................................................................................................
1-15
CHAPTER 2 - Voltage Measurement Cable and Current Probe Connections
Overview ...............................................................................................................................
2-1
Connecting Voltage Measurement Cables ............................................................................
2-4
Connecting Current Probes....................................................................................................
2-9
CHAPTER 3 - View Real Time Data
Overview ...............................................................................................................................
3-1
Section A -Scope Mode ...............................................................................................................
3-2
Overview ...............................................................................................................................
3-2
Turning Channels On/Off ......................................................................................................
3-3
Checking Input Range ...........................................................................................................
3-4
Section B -Meter Mode ................................................................................................................
3-5
Overview ...............................................................................................................................
3-5
Standard Meter Tab ...............................................................................................................
3-6
Distortion Meter Tab .............................................................................................................
3-8
User Specified Frequency Meter Tab ....................................................................................
3-10
Imbalance Meter Tab.............................................................................................................
3-11
Advanced Power Meter Tab ..................................................................................................
3-12
Section C -Harmonics ..................................................................................................................
3-15
Overview ...............................................................................................................................
3-15
Harmonic Graph ....................................................................................................................
3-16
Harmonic Detail ....................................................................................................................
3-17
Harmonic Options..................................................................................................................
3-18
Harmonic List ........................................................................................................................
3-20 ix
Table of Contents,
Continued
Section D -Voltage and Current Phasor .......................................................................................
3-19
Overview ...............................................................................................................................
3-19
Phasor Screen ........................................................................................................................
3-20
Phasor Rotation......................................................................................................................
3-21
Phasor Parameter/Channel Selection.....................................................................................
3-23
CHAPTER 4 - Instrument Settings
Overview ...............................................................................................................................
4-1
Access Instrument Settings Menu .........................................................................................
4-2
Time and Date Settings..........................................................................................................
4-3
Select Language.....................................................................................................................
4-5
Set Display Preferences .........................................................................................................
4-6
Touch Screen Calibration ......................................................................................................
4-7
Turn Threshold Beeper On/Off .............................................................................................
4-9
Communications....................................................................................................................
4-10
Memory Card.........................................................................................................................
4-12
Reset to Factory Configurations ............................................................................................
4-14
CHAPTER 5 - Start Menu
Overview ...............................................................................................................................
5-1
Section A -Automatic Setup.........................................................................................................
5-3
Section B -Wizard Setup..................................................................................................
5-6
Overview ...............................................................................................................................
5-6
Current Probe Selection.........................................................................................................
5-8
Scale Factor Setup .................................................................................................................
5-10
Circuit Type Selection ...........................................................................................................
5-12
Nominal Values .....................................................................................................................
5-14
Mode of Operation.................................................................................................................
5-17
Monitoring Mode...................................................................................................................
5-18
Advanced Options .................................................................................................................
5-19
Site Name/Memory Card.......................................................................................................
5-20
Section C -Monitor Same Circuit.................................................................................................
5-24
Overview ...............................................................................................................................
5-24
Turning Monitoring On/Off...................................................................................................
5-25
Monitoring at a Specified Time and Date .............................................................................
5-28
Modify Trigger Parameters and Intervals..............................................................................
5-33
Section D -Load Setup Template from Card................................................................................
5-34
Section E -Load Data from Card..................................................................................................
5-35
Overview ...............................................................................................................................
5-35
Loading Data from Card........................................................................................................
5-35
Card Error Messages .............................................................................................................
5-36 x
Table of Contents,
Continued
CHAPTER 6 - Advanced Setup Options
Overview ...............................................................................................................................
Advanced Options Menu .......................................................................................................
Transient Limit ......................................................................................................................
6-1
6-2
6-3
High Frequency Transients .............................................................................................
Recording Transients ......................................................................................................
6-4
6-5
RMS Variation Limit.............................................................................................................
6-9
Waveform Capture ................................................................................................................
6-14
Characterizer Options ............................................................................................................
6-15
Journal Limit..........................................................................................................................
6-16
Journal Interval for Timed Readings .....................................................................................
6-21
EN50160 Power Quality (for strict EN50160 monitoring only) ...........................................
6-23
CHAPTER 7 - View Event Data
Overview ...............................................................................................................................
7-1
Section A -Events.........................................................................................................................
7-4
Overview ...............................................................................................................................
7-4
Event Data Display ................................................................................................................
7-5
Event Activity Graph.............................................................................................................
7-6
Event List...............................................................................................................................
7-7
Event Detail ...........................................................................................................................
7-9
Event Options ........................................................................................................................
7-12
Section B -Trend ..........................................................................................................................
7-15
Overview ...............................................................................................................................
7-15
Trend Display ........................................................................................................................
7-16
Trend Setup............................................................................................................................
7-17
Section C -Reports .......................................................................................................................
7-20
Overview ...............................................................................................................................
7-20
EN50160 ................................................................................................................................
7-22
EN50160 Compliance Limits ................................................................................................
7-24
Compliance Statistical Bar Chart ..........................................................................................
7-27
Compliance History ...............................................................................................................
7-30
Event Satistics........................................................................................................................
7-32
Min/Max Table for Power Frequency and RMS Voltage .....................................................
7-34
PQ Status ...............................................................................................................................
7-35
PQ Status Trend Display .......................................................................................................
7-36
Section D -Downloading Events from PX5 to a Computer .........................................................
7-38
Overview ...............................................................................................................................
7-38
External Communication Interface........................................................................................
7-39
Downloading Events via NodeLink ......................................................................................
7-47
Viewing Events via DranView ..............................................................................................
7-48
DranView with HASP ...........................................................................................................
7-49 xi
Table of Contents,
Continued
APPENDIX A - Optional Accessories
Overview ...............................................................................................................................
A-1
Hardware Accessories List & Descriptions...........................................................................
A-2
Software Accessories List .....................................................................................................
A-8
APPENDIX B - Technical Specifications
Overview ...............................................................................................................................
B-1
General...................................................................................................................................
B-2
Interfaces ...............................................................................................................................
B-3
Measured Parameters.............................................................................................................
B-4
Computed Parameters............................................................................................................
B-6
Parameter Settings in Monitoring Mode ...............................................................................
B-10
TR2500 Current Probe...........................................................................................................
B-12
TR2510 Current Probe...........................................................................................................
B-13
APPENDIX C - Battery Specifications and Replacement Procedure
Overview ...............................................................................................................................
C-1
Battery Specifications............................................................................................................
C-2
Battery Pack Safety Precautions............................................................................................
C-3
Battery Pack Replacement.....................................................................................................
C-4
APPENDIX D - User Replaceable Parts List
APPENDIX E - Common Circuit Connections
Overview ...............................................................................................................................
E-1
Verifying Voltage and Current Connections .........................................................................
E-5
Single Phase...........................................................................................................................
E-7
Split Phase .............................................................................................................................
E-8
3 Phase, Four Wire Wye........................................................................................................
E-9
3 Phase (Floating or Grounded) Delta ...................................................................................
E-10
3 Phase 2-Watt Delta .............................................................................................................
E-11
Generic Circuit ......................................................................................................................
E-12
2 1/2 Element Without Voltage Channel B ...........................................................................
E-13
2 1/2 Element Without Voltage Channel C ...........................................................................
E-14
Connecting to a Potential Transformer (PT) .........................................................................
E-15
Connecting to a Current Transformer (CT) ...........................................................................
E-17
Connecting to an Isolated Current Transformer (ISO) ..........................................................
E-18
APPENDIX F - Event Classification
APPENDIX G - PX5 Menu Structure xii
Dranetz-BMI PowerXplorer
TM
PX5
xiii
C H A P T E R 1
Getting Started
Overview
PowerXplorer description
The Dranetz-BMI PowerXplorer
TM
PX5 is a portable, hand-held, eight-channel power quality meter/monitor. This cutting-edge power quality instrument is designed with a color liquid crystal display (LCD) 1/4 VGA, using touch screen technology. It can monitor, record and display data on four voltage channels and four current channels simultaneously.
PX5 is designed to meet both the IEEE 1159 and IEC 61000-4-30 Class A standards for accuracy and measurement requirements. It can do PQ-optimized acquisition of power quality related disturbances and events. It is designed with a statistical package called
Quality of Supply (QOS), with monitoring and setup protocols set to determine voltage measurement compliance required for EN50160 monitoring. European standard
EN50160 requires that measurement parameters must be within a specified percentage for 95% of the time.
PowerXplorer PX5 is available in two models:
• Model PX5-XFAST is equipped with the high speed sampling analog board for microsecond transient detection digitization and analysis. The PX5-XFAST performs measurements for 50/60 Hz power frequency systems.
• Model PX5-400 performs measurements for 400 Hz power frequency systems. The
PX5-400 will also monitor at 50/60 Hz. The user needs to set the default frequency to either 400 Hz, 60 Hz or 50 Hz, depending on the application. When operating at 400
Hz, rms calculations are made on a cycle-by-cycle basis with 1 cycle step; whereas at
50/60 Hz mode, it steps at 1/2 Hz. Also, the PX5-400 does not calculate the IEEE
1459 power parameters as well as flicker, which are not defined at 400 Hz.
PX5 Firmware
The firmware for the PX5 is contained on internal FLASH memory. It has an operating system capable of performing multiple applications. When an updated version of the firmware is released, the user can upgrade the internal program by putting the latest
PX5 firmware program card in the appropriate slot of the mainframe. See page 1-10
for instructions on how to upgrade PX5 firmware from a data card.
The PX5 firmware can monitor power quality phenomena for troubleshooting and/or compliance purposes. It can record inrush conditions, carry out long-term statistical studies to establish performance baselines, and perform field-based equipment testing and evaluation for commissioning and maintenance. The firmware integrates an intuitive instrument setup procedure to ensure the capture of all relevant data for additional post process analysis, report writing, and data archiving using other compatible Dranetz-BMI software applications such as NodeLink
®
and DranView
®
.
1-1
Overview, continued
This manual
This manual contains instructions for operating both PX5 models - PX5-XFAST and
PX5-400.
In this chapter
The following topics are covered in this chapter.
Topic
Unpacking the PX5
Standard Accessories
PX5 Controls, Indicators, and Connectors
Upgrading Firmware from a Data Card
PX5 Features
Basic Operation
See Page
1-3
1-4
1-5
1-10
1-12
1-14
1-2
CH 1/ Getting Started
Unpacking the PX5
Introduction
For maximum protection against possible shipping damage, PX5 has been sealed in a two-piece, plastic suspension pack, enclosed within a durable shipping carton. After opening the carton, inspect the contents for possible shipping damage and check the carton inventory.
Unpacking
Unpack the PX5 from the carton as follows:
Step
1
2
3
Action
Remove any remaining literature inside the top of the carton.
Carefully remove the PX5 from its shipping carton.
Remove all accessories inside the carton. Check that all of the standard accessories (see page 1-4) are included.
Shipping damage inspection
Visually inspect the PX5 for possible shipping damage. If any damage exists, first notify and file an insurance claim with your carrier or underwriter or both. Then notify
Dranetz-BMI Customer Service Department of your intentions to return the unit. DO
NOT return the PX5 without prior instructions from Dranetz-BMI Customer Service
Department. Dranetz-BMI Customer Service Department can be reached at (732) 287-
3680 or 1-800-372-6832.
Repacking for return shipment
If the unit must be returned to Dranetz-BMI for service or repair, wrap the unit securely in heavy packaging material and place in a well padded box or crate to prevent damage.
Do not return the PX5 in an unpacked box. Dranetz-BMI will not be responsible for damage incurred during transit due to inadequate packing on your part.
Return notice
Notify Dranetz-BMI Customer Service of your intention of returning the unit. Do not return the unit without prior instructions from Dranetz-BMI. Dranetz-BMI Customer
Service Department can be reached at (732) 287-3680 or 1-800-372-6832.
1-3
Standard Accessories
Standard Accessories
Standard accessories
The following table lists the PX5's standard accessories.
Cable Set
Easel
AC Adapter
Description
*US Power Cord
*European Power Cord
*United Kingdom Power Cord
*Australian Power Cord
Notice: Charge Battery
PowerXplorer User’s Guide
*User specified, one standard only.
116042-G3
Part Number
116038-G1
117029-G1
USSTDCORD (900744)
EUROSTDCORD (115369-G2)
UKSTDCORD (115368-G2)
AUSTDCORD (901347)
899117
UG-PX5
Optional accessories
Batteries
Refer to Appendix A for the list of hardware and software optional accessories available for use with PX5.
Refer to Appendix C for the description and replacement of the batteries contained in
PX5.
Replaceable parts
Calibration
Refer to Appendix D for the user replaceable parts.
The recommended calibration interval for this unit is once every 12 months.
We recommend that you return the unit to the factory for calibration. If you decide to do so, first contact the Dranetz-BMI Customer Service Department to obtain an
Authorization Number.
Telephone: (732) 287-3680 or 1-800-372-6832
FAX: (732) 248-9240
Fill out the Repair/Service Order form enclosed in the shipping carton and ship it along with the unit to the Dranetz-BMI Repair Department. (If this form is missing, ask the
Dranetz-BMI Customer Service Department for a replacement.)
1-4
CH 1/ Getting Started
PX5 Controls, Indicators, and Connectors
Dimensions
PX5 is a self-contained, portable instrument weighing less than 5 pounds and measuring 8" (20.3 cm) deep by 12" (30.5 cm) wide by 2.5" (6.4 cm) high. This section identifies and describes the controls, indicators, and connectors on all sides of the PX5, shown with rubber boot installed.
Top View
Front View
Rear View
Bottom View
S L O T 1
S L O T 2
1-5
PX5 Controls, Indicators, and Connectors, continued
Top and Side views
The top (circuit connection) view features the input voltage and current connectors.
The left side contains the optical interface port. The right side contains the AC adapter input connector. Both sides have rings for attaching the supplied carrying strap. See below for descriptions of the top and side connectors.
1 2 3 4 5 6 7 8 9 10 11 12
13 14
Parts table
Part Function
1
CH A, + Differential Voltage Input Connector; color red.
2
CH A, - Differential Voltage Input Connector; color white.
3
CH A, PROBE, Current Input Connector.
4
CH B, + Differential Voltage Input Connector; color yellow.
5
CH B, - Differential Voltage Input Connector; color white.
6
CH B, PROBE, Current Input Connector.
7
CH C, + Differential Voltage Input Connector; color blue.
8
CH C, - Differential Voltage Input Connector; color white.
9
CH C, PROBE, Current Input Connector.
10
CH D, + Differential Voltage Input Connector; color grey.
11
CH D, - Differential Voltage Input Connector; color white.
12
CH D, PROBE, Current Input Connector.
13
Optical Serial Data Port
14
AC Adapter/Battery Charger Input Connector.
1-6
CH 1/ Getting Started
Front view
The front view primarily shows the color touch screen LCD. See below for descriptions of the PX5 front display.
1 2
Parts table
Part Function
1
Mainframe Protective Rubber Boot Enclosure
2
Liquid Crystal Display (LCD). Provides 3.75 x 4.75 inches display consisting of 1/4 VGA size screen of text and graphic information. The color LCD is equipped with touch screen technology, operable using the finger and/or PDA stylus. Touch screen display permits menu selection, alphanumeric data entry, and has a compact fluorescent (CCFL) backlighting that is always on for low light level viewing.
The following are some basic care instructions for the LCD monitor:
• Use and store the unit within the specified temperature and humidity range. The LCD screen may be adversely affected by exposure to high temperature or humidity. Condensation or moisture produced by sudden temperature changes may also damage the LCD screen. Clean any moisture from surface immediately.
• Be careful when cleaning or removing stains on the LCD surface.
Gently wipe the surface with a soft cloth or cotton pad. Isopropyl alcohol may be used, but make sure that all solvent residue is removed.
• Do not apply excessive force to the LCD surface. The LCD screen contains sensitive electronic components that may be damaged due to strong impact.
1-7
PX5 Controls, Indicators, and Connectors, continued
Bottom view
The bottom view features two slots. Either slot can be used to hold the data card.
NOTE: Use only one card slot (one data card) at a time. The additional slot will be used for future communications options.
The bottom also features LED indicators and the On/Off power button. See below for descriptions of the slots, indicators, and button.
1
S L O T 1
S L O T 2
Parts table
2 3 4 5 6
Part Function
1
Slot 1. Holds and connects data card to internal circuitry. Data card works in either Slot 1 or Slot 2. Eject card by pushing data card release.
2
Slot 2. Holds and connects data card to internal circuitry. Data card works in either Slot 1 or Slot 2. Eject card by pushing data card release.
NOTE: This additional slot will be used for future options.
3
Battery Charge Indicator. LED will light steadily while battery is fast charging and blink when fully charged.
4
Status Indicator. LED will light steadily when abnormal condition is detected.
The unit is operating normally when light is off.
5
Power Indicator. LED will blink in a heartbeat fashion (once per second) when the unit is operating normally.
6
On/Off Power Button. Push for on, push for off.
1-8
Rear view
CH 1/ Getting Started
The rear view shows the battery compartment and the easel studs to mount the unit to desired angular position for use on a flat surface or to hang from a panel.
1-9
Upgrading Firmware from a Data Card
Upgrading Firmware from a Data Card
PX5 firmware web upgrade
Users can upgrade the PX5 internal program by downloading the latest firmware update release from the web and installing it into the PX5 internal memory. Refer to the instructions below on how to upgrade PX5 firmware.
PX5 firmware upgrades can be downloaded from the Dranetz-BMI website. Log on to www.dranetz-bmi.com for the latest information on firmware update releases.
Copy PX5 firmware program in data card
The procedure below specifies how to download the latest PX5 firmware from the web and copy it into a data card.
Step Action
1
2
Locate the latest version of the firmware upgrade (in data file format
“hostcode.bin”) from the Dranetz-BMI website www.dranetz-bmi.com.
Dranetz-BMI regularly posts the latest information and instructions regarding PX5 firmware upgrade releases.
Format the Compact Flash data card using the Memory Card options in
PX5. The card must be formatted before it can be written to. Refer to
Chapter 5 Start Menu - Site Name/Memory Card on page 5-20 for instructions on how to format data card.
3
4
NOTE: All data and setups stored in card will be lost when you format the data card. Copy any files that you want to save to a computer first before formatting card.
Insert the Compact Flash data card into the appropriate slot in the computer. If the computer does not accommodate a Compact Flash card in its native format, use a compatible PC card adapter to be able to read/ write data into the card.
Download and copy the latest version of the PX5 firmware upgrade program (data file “hostcode.bin”) from the Dranetz-BMI website to the data card.
Refer to page 1-11 for instructions on how to install the data card containing the latest firmware upgrade to PX5.
1-10
CH 1/ Getting Started
Install data card to PX5
The procedure below specifies how to install the data card containing the latest firmware upgrade to PX5.
Step
1
2
3
4
5
6
7
Action
Make sure that the unit is off. If not, press the PX5 On/Off power button to turn unit off.
Remove the data card from its protective holder and check that the plug end of card is clean and free of any obstruction.
NOTE: If plug end of card is dirty, clean with static-free, dry, low pressure air to remove any foreign material causing obstruction of the plug holes.
At the bottom of the unit, position the data card with the label facing up and the plug end facing the top slot (Data Card Slot 1). Make sure that there are no other cards in the unit except for the data card.
Insert the card fully into the top slot (Data Card Slot 1) until resistance is felt, then press firmly until the card engagement is felt.
NOTE: Do not force the card further into the slot if no card engagement is felt. Remove card and check if there is foreign object on or in the plug end of the card. Remove any obstruction. Reinsert data card and repeat card engagement. If card cannot be engaged, STOP all further action and call
Dranetz-BMI Technical Support at 1-800-372-6832 for assistance.
Turn the unit on by pushing the on/off button. The loader should display
“Booting from program card”. If not, call Dranetz-BMI Technical Support for assistance.
The instrument will prompt the user to verify whether or not to upgrade the firmware. Press Yes and the upgrade procedure will commence. Do not turn the power off nor remove the data card while firmware upgrade is in progress.
If no errors were detected, a window displaying “Installation Complete” will pop up. Remove the data card from the unit.
1-11
PX5 Features
PX5 Features
Touch screen function
All PX5 functions described below are operable using a color LCD touch screen technology. Users may use a finger and/or a PDA stylus to apply pressure to the LCD screen to result in touch screen recognition. The touch screen display is also workable with lineman gloves on. Touch screen buttons will appear in reverse-video to show visual feedback of contact along with audible feedback. In order to reduce power consumption, the backlight of the LCD screen times-out after a specified programmable time of no user activity. The backlight reactivates by touching any part of the screen.
Scope mode
Meter mode
Harmonics
Scope mode functions as an oscilloscope, displaying real-time waveforms of voltage and current for up to eight channels simultaneously, with one second update rate. The colors of waveform display are user programmable. Scope mode also provides a textual display of rms values, division for axis values, and frequency.
Meter mode functions as a true rms voltmeter and a true rms clamp-on ammeter.
Voltage and current measurements, along with other calculated and advanced power parameters, are displayed on the Meter mode screens in both textual and graphical format.
Harmonics display the amplitude and phase of each harmonic to the 63rd harmonic in both graphical and textual format.
Phasor diagram The phasor screen displays a graph that indicates phase relations between voltage and current based upon the angles at the fundamental frequency, as determined by Fourier analysis. Phasor diagram displays voltage and current phasors for all channels.
Functioning as a phase angle meter, the unit can display system imbalance conditions and provides such information in textual form also. The phase angle display can also verify if monitoring connections have been made correctly. Animated phasor demo rotations demonstrating resistive, inductive and capacitive loads can be displayed.
Flicker
Flicker is a phenomenon due primarily to rapid small fluctuations of the voltage. Loads that exhibit continuous, rapid variations in the load current, particularly the reactive component, can cause voltage variations often referred to as flicker. Flicker is characterized by modulation at a frequency typically less than 25 Hz. Modulating signal magnitudes as low as 0.5% of the fundamental for frequencies between 5-10 Hz can result in perceptible light flicker.
Event
An event occurs when a programmed threshold limit is crossed. An event consists of the pre-trigger cycle(s), trigger cycle(s), and post-trigger cycle(s).
Continued on next page
1-12
CH 1/ Getting Started
Monitoring capacity
PX5 can monitor the following power configurations:
• Single Phase • 3 Phase 2-Watt Meter Delta
• Split Phase • Generic
• 3 Phase Delta
• 3 Phase Wye
• 2 1/2 Element without V
B
• 2 1/2 Element without V
C
While monitoring any of the above configurations, the PX5 can also be connected to monitor neutral to ground voltage and neutral or ground current.
Automatic setup, Wizard setup, or
Advanced setup
Setup is a configuration of parameter thresholds that control the data recorded by PX5.
Users may perform instrument setup in three ways: via Automatic Setup which utilizes auto-configured settings and allows users to proceed directly with data monitoring; via
Wizard Setup which follows a step-by-step sequence where users go through a series of circuit setup screens; or via Advanced Options setup which allows users to modify trigger parameters and intervals or tweak threshold settings.
Trend
Users can generate plots for all journalled data combined with min/max recordings of that parameter. Most journal parameters have multiple channels to plot.
Reports
Data Card
Users have two options on how to view QOS compliance reports.
EN50160 displays statistical reports on QOS compliance based on an analysis of the voltage as per requirements of the EN50160 standard. Compliance data is presented in bar charts, statistical tables, and graphs. Statistical data is calculated on the required parameters specified in EN50160 over one week interval to produce a PASS/FAIL decision of QOS compliance.
PQ Status presents a status summary for QOS via the annunciator panel. The panel is color coded such that green indicates the parameter is within limits and/or no events have occurred since the last time the panel was cleared. Red indicates the parameter is out of limits and/or events of that type have occurred since last cleared. Unlike the
EN50160 which reports on QOS compliance on a weekly basis, PQ Status monitors compliance continuously. The user may choose to clear or reset existing data on the panel and restart monitoring at a new time and date. PQ Status automatically displays the time and date since the panel was last cleared.
PX5 supports the use of Compact Flash data cards with AT LEAST 32MB storage capacity. The user replaceable data card serves as primary storage for data. Data monitoring CANNOT proceed without the data card. PX5 is designed to accommodate the Compact Flash card in its native format, and does not require the use of a PC card adapter. However, a PC card adapter can be used to read the data into a laptop or other computer with a PC card slot.
1-13
Basic Operation
Basic Operation
Introduction
The normal power source for the PX5 is its internal battery pack. The AC Adapter/
Battery Charger is used to charge the battery. Always charge the battery fully before use. PX5 will always operate on the charger and is designed to do so, regardless of the state of charge of the battery.
Battery pack
Type: Sealed, rechargeable NiMH (Nickel Metal Hydride) cells.
Length of operation: PX5 can operate on a fully charged battery pack for more than two
(2) hours with the backlight on. When the backlight is turned off, the unit can operate for more than three (3) hours. For information on how to turn backlight on or off, see
Chapter 4 Instrument Settings - Set Display Preferences on page 4-6.
Charging: The battery pack can be charged by connecting the AC Adapter/Battery
Charger to the PX5. A screen warning will appear during operation when battery charge is low. A depleted battery pack can be recharged in six (6) hours whether the unit is on or off. The Battery Charge Indicator glows steadily while charging, and flashes when fully charged.
NOTE: The Battery Charge Indicator functions whenever the AC Adapter/Battery
Charger is properly connected.
AC power source
PX5 can be operated from a 50/60 Hz 120/230V AC power source with or without the battery pack installed.
Connect the AC Adapter output cable to the Input Connector on the right side of the
PX5. Connect the AC Adapter power cord to an appropriate outlet.
Refer to Appendix C for the specifications and replacement of the batteries contained in PX5.
1-14
Power on sequence
CH 1/ Getting Started
Follow these steps to turn on the PX5 and display the Home screen.
Step Action
1 Connect ac adapter/battery charger plug into the right side of PX5.
2 Plug the ac adapter into an ac power source.
3 Press the PX5 On/Off power button to turn the unit on.
Result: The Home screen will be displayed.
MARK001b
Home screen features
Home screen is frequently referenced as the starting point for all major functionalities of PX5.
The date and time appear on the top right corner of the Home screen. Both can be configured to appear in a different format. See page 4-3 for the procedure on how to set and reformat time and date.
The unit name and model, PX5 program revision level, and status messages appear on the top portion of the Home screen. Pertinent information that appear in the status message area are the monitoring status, circuit configuration, percentage of data card used while monitoring, site/file name, number of event cycles saved, and number of timed intervals saved.
MONITORING STATUS: OFF indicates that the instrument is not actively monitoring data. The monitoring status message will change to ON, DONE or
ARMED, depending upon the state of data monitoring. See page 5-25 for the procedure on how to turn monitoring on/off.
Home screen contains the icons used to access the various PX5 functions. See page
1-16 for the description of each icon found in Home screen.
1-15
Basic Operation, continued
Home screen icons
Home screen contains the following icons used to access various PX5 functions:
Scope - Scope mode shows real-time voltage and current waveforms of the signals on the measuring inputs. See Chapter 3 View Real Time Data - Section A Scope Mode.
Meter - Meter mode displays voltage and current measurements, along with other calculated parameters. See Chapter 3 View Real Time Data - Section B Meter Mode.
Harmonics - Harmonic screen displays a spectral graph and textual matrix featuring the amplitude and phase of each voltage and current harmonic to the 63rd harmonic. See
Chapter 3 View Real Time Data - Section C Harmonics.
Phasor - Phasor diagrams indicate phase relations between voltage and current based upon the angles of the fundamental. See Chapter 3 View Real Time Data - Section D
Voltage and Current Phasor.
Preferences - Users can set instrument preferences like time and date, threshold alarm feedback, language selection, communications, LCD display, and data card operation.
See Chapter 4 Instrument Settings.
Events - Events result in a contiguous collection of cycles that is recorded into memory.
Events are classified according to IEEE 1159, IEC 61000-4-30 Class A, and EN50160 standards. Events are displayed only after monitoring has been turned on or upon reading a stored file from the data card. See Chapter 7 View Event Data - Section A
Events.
Trend - Trend allows users to view plots of journalled data along with min/max measurements over the interval. See Chapter 7 View Event Data - Section B Trend.
Reports - PX5 allows users to view two types of reports on QOS compliance. EN50160 reports show graphs and statistical tables reflecting the compliance of parameters specified according to EN50160 standard. PQ Status shows a quick status summary of the parameters using the annunciator panel. The color coded panel indicates whether or not the parameter is within limits and/or events have occurred since the last time the panel was cleared. See Chapter 7 View Event Data - Section C Reports.
Start/Setup - Users have the option to use Automatic Setup and proceed directly with data monitoring or they can configure the instrument step-by-step using the Wizard
Setup. Users can also do Advanced setups to modify trigger parameters and intervals or tweak threshold settings under the Advanced Setup Options. See Chapter 5 Start Menu and Chapter 6 Advanced Setup Options.
1-16
C H A P T E R 2
Voltage M easurem ent Cable and Current Probe C onnections
Overview
Introduction
This section describes how to connect the PX5 to make basic single phase voltage measurements. For multi-phase connection diagrams, refer to Appendix E.
In this chapter
The following topics are covered in this c
hapter.
Topic
Connecting Voltage Measurement Cables
Connecting Current Probes
See Page
2-4
2-9
WARNING Death, serious injury, or fire hazard could result from improper connection of this instrument. Read and understand this manual before connecting this instrument.
Follow all installation and operating instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National
Electrical Code (ANSI/NFPA 70-2002) and any additional safety requirements applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by qualified personnel only. The National Electrical Code defines a qualified person as “one who has the skills and knowledge related to the construction and operation of the electrical equipment and installations, and who has received safety training on the hazards involved.”
Qualified personnel who work on or near exposed energized electrical conductors must follow applicable safety related work practices and procedures including appropriate personal protective equipment in compliance with the Standard for
Electrical Safety Requirements for Employee Workplaces (ANSI/NFPA 70E-2004) of USA and any additional workplace safety requirements applicable to your installation.
Continued on next page
2-1
Overview, continued
ADVERTENCIA Una conexión incorrecta de este instrumento puede producir la muerte, lesiones graves y riesgo de incendio. Lea y entienda este manual antes de conectar. Observe todas las instrucciones de instalación y operación durante el uso de este instrumento.
La conexión de este instrumento debe ser hecha de acuerdo con las normas del
Código Eléctrico Nacional (ANSI/NFPA 70-2002) de EE. UU., además de cualquier otra norma de seguridad correspondiente a su establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada por personal calificado solamente. El Código Eléctrico Nacional define a una persona calificada como "una que esté familiarizada con la construcción y operación del equipo y con los riesgos involucrados."
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code
(ANSI/NFPA 70-2002) des Etats-Unis et à toutes les exigences de sécurité applicables à votre installation.
Cet instrument doit être installé, utilisé et entretenu uniquement par un personnel qualifié. Selon le National Electrical Code, une personne est qualifiée si "elle connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers que cela implique".
WARNUNG Der falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer verursachen. Bevor Sie dieses Instrument anschließen, müssen Sie die Anleitung lesen und verstanden haben. Bei der Verwendung dieses Instruments müssen alle
Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen
Bestimmungen für Elektrizität (ANSI/NFPA 70-2002) der Vereinigten Staaten, sowie allen weiteren, in Ihrem Fall anwendbaren Sicherheitsbestimmungen, vorgenommen werden.
Installation, Betrieb und Wartung dieses Instruments dürfen nur von
Fachpersonal durchgeführt werden. In dem nationalen Bestimmungen für
Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der
Bauweise und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren vertraut ist."
2-2
CH 2/ Voltage Measurement Cable and Current Probe Connections
Safety precautions
The following safety precautions must be followed whenever any type of voltage or current connection is being made to the PX5.
• Wear proper Personal Protective Equipment, including safety glasses and insulated gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
• Press the PX5 On/Off power button to Off.
• Before connecting to electric circuits to be monitored, open their related circuit breakers or disconnects. DO NOT install any connection of the PX5 to live power lines.
• Connections must be made to the PX5 first, then connect to the circuit to be monitored.
Continued on next page
2-3
Connecting Voltage Measurement Cables
Connecting Voltage Measurement Cables
Measurement cable set
Description: Voltage measurement cables are provided as standard accessories and are stored in a cable pouch as part of the measurement cable set, P/N 116042-G3. Each cable set consists of a cable and alligator clip.
Voltage Rating: Direct connection of all voltage measurement cables are rated at 600
Vrms max. For measuring voltages greater than 600 Vrms, potential transformers (PTs) must be used.
Contents: The voltage measurement cables are shown on page 2-5 (positioned relative to their actual use). A cable set consists of eight, 6-foot channel measurement cable assemblies (probes), each with a detachable, alligator jaw, safety clip assembly
(maximum jaw opening, 3/4 in (20 mm)). The safety clip assemblies are red (+) and black (-) for each of the four channels. One cable each of red (channel A), yellow
(channel B), blue (channel C), and grey (channel D), and four each of white are provided.
A pouch for storage of the cables and the AC adapter/battery charger is included in the contents of the measurement cable set, but is not shown in the figure.
Optional fused voltage adapter
There are two optional fuse accessory kits available for use with the measurement cables for PX5. One kit (P/N FVA-1) contains one fused voltage adapter and one measurement connecting Red cable 50 cm in length. The other kit (P/N FVA-4) contains four voltage adapters and four measurement connecting cables 50 cm in length
(one Red, one Yellow, one Blue, and one Grey).
The single fuse voltage adapter kit is used for one single voltage measurement input.
While the four fuse voltage adapter kit is used for a three phase and neutral voltage measurement inputs.
Continued on next page
2-4
Measurement cable set with optional fuse diagram
CH 2/ Voltage Measurement Cable and Current Probe Connections
N O TE : 2 FT C A B LE
IN C L U D E D W IT H
FU S E V O LT A G E
A D A P TE R
O PT IO N AL
FU S E
V O LT A G E
A D A P TE R
O PT IO N AL
FU S E
V O LT A G E
A D A P TE R
O PT IO N AL
FU S E
V O LT A G E
A D A P TE R
O PT IO N AL
FU S E
V O LT A G E
A D A P TE R
WARNING
WARNING
WARNING
WARNING
PX5-11.vsd
To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
For continued protection against risk of fire or shock hazard replace only with same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is
Littelfuse, part number KLKD0.30 rated 600V AC/DC, 0.3A fast blow.
Do not replace fuse again if failure is repeated. Repeated failure indicates a defective condition that will not clear with replacement of the fuse. Refer condition to a qualified technician.
Contact Dranetz-BMI Customer Service for more information on the fused voltage adapter. Refer to Dranetz-BMI Information Sheet titled Model FVA - Fuse Voltage
Adapter, P/N 899107.
2-5
Connecting Voltage Measurement Cables, continued
Connection guidelines
Follow these guidelines when making voltage connections.
• Refer to the measurement cable set figure for color coding of probes that connect to input channel connectors A, B, C, and D.
• Each channel input has plus (+) and minus (-) differential inputs of 1 to 600 Vrms max.
Example: Single phase connection
The following figure shows a voltage connection to a single phase circuit for channel A.
PX5-12.vsd
Continued on next page
2-6
CH 2/ Voltage Measurement Cable and Current Probe Connections
Example:
Neutral to ground connection
The following figure shows a voltage connection using channel D as a differential input for measuring neutral to ground voltage. Connections are identical for split phase and wye configurations. One probe connects the source neutral line to the D+ input.
Another probe connects the ground to the D- input.
PX5-13.vsd
2-7
Connecting Voltage Measurement Cables, continued
Safety precautions
WARNING
The following safety precautions apply to current probe connections in addition to those safety precautions stated on page 2-3.
• DO NOT attempt to measure current in any circuit in which the circuit to ground voltage exceeds the insulation rating of the current probe (600 Vrms max).
• Make sure the jaws of the current probe are tightly closed. Keep mating surfaces clean and free from foreign matter.
DO NOT USE non-insulated current probe cores around a non-insulated wire.
Probes of this type are designed for use around insulated wires only. Use only completely insulated probe cores with no exposed conductive areas of the core around non-insulated wires.
ADVERTENCIA NO UTILIZAR transformadores de corriente sin material aislante al rededor de conductores sin material aislante. Los Transformadores de corriente de este tipo están diseñados para ser utilizados solamente con conductores con aislamiento eléctrico. Utilizar transformadores de corriente completamente aislados alrededor de conductores sin aislamiento.
AVERTISSEMENT
N'EMPLOYEZ PAS les noyaux courants non-isolés de sonde autour d'un fil nonisolé. Des sondes de ce type sont concues pour l'usage autour des fils isolés seulement. L'utilisation seulement a complétement isolé des noyaux de sonde sans des secteurs conducteurs exposés du noyau autour des fils non-isolés.
WARNUNG
VERWENDEN Sie keine Stromzangen mit nicht isolierten Ferritkernen bei
Messungen an nicht isolierten Leitungen. Stromzangen dieses Typs sind nur für
Messungen an isolierten Leitern geeignet. Bitte verwenden Sie zur Messung an nicht isolierten Leitungen Stromzangen mit vollständig isoliertem Kernmaterial.
Continued on next page
2-8
Connecting Current Probes
CH 2/ Voltage Measurement Cable and Current Probe Connections
Current probes
Several Dranetz-BMI current probes can be used with the PX5. Typical current probes are illustrated on page 2-10. Refer to Appendix A for descriptions and part numbers of probes and adapter cables. Refer to Appendix B for specifications of current probe models TR2500 and TR2510.
NOTE: The TR2500 can perform all current measurements except high frequency transient detection.
Probe positioning: An arrow marking on the handle is a guide to ensure that you position the probe with the arrow pointing towards the load when monitoring the line conductor. Correct position of the probe is necessary for correct power measurements, where in-phase voltage and current measurements are necessary. A positive watts reading indicates that the probe is pointed towards the load, and a negative reading indicates that the probe is pointed towards the source.
Continued on next page
2-9
Connecting Current Probes, continued
Typical current probes
2-10
4300 TO LEMFLEX
CURRENT PROBE
A DA PTER CA BLE
116310-G1
PX5-14.vsd
NOTE: Current probes TR2500 can be used interchangeably with TR2500A, TR2510 with TR2510A, and TR2520 with TR2520A.
Continued on next page
CH 2/ Voltage Measurement Cable and Current Probe Connections
Typical current probes
(continued)
Actual photos of TR series probes and part numbers are shown below to aid users in probe identification. Contact Dranetz-BMI Customer Service Department for more information on current probes, pricing and availability.
P/N TR-2500 P/N TR-2510 P/N TR-2520
P/N TR-2500A P/N TR-2510A P/N TR-2520A
Continued on next page
2-11
Connecting Current Probes, continued
Single phase current probe connection example
The following figure shows how to connect a current probe to channel A for current monitoring of a single phase line.
The current probe may be connected to the return line if desired to measure the return current when checking for load current leakage, loop current relationships, etc. If measuring power, position the probe with the arrow pointing towards the load.
PX5-15.vsd
NOTE: The connection shown above is not recommended without a voltage connection to ensure frequency synchronization. If this configuration is used, then an internal frequency reference must be entered. Refer to pages 5-14 to 5-16.
2-12
C H A P T E R 3
View Real Time Data
Overview
Introduction
PX5 allows users to view power quality phenomena as it happens, when it happens.
The instrument is able to capture and process data in real time, and allows users to view it in Scope mode, Meter mode, Harmonics, and Phasor display.
Access to real time data
Icons for Scope mode, Meter mode, Harmonics and Phasor display are available in the
Home screen. Follow these steps to display the Home screen.
Action...
STEP 1: Press the PX5 On/Off power button to turn the unit on.
The Home screen will be displayed.
Result...
In this chapter
This chapter is divided into four sections.
Section
A
B
C
D
Scope Mode
Meter Mode
Harmonics
Title
Voltage and Current Phasor
MARK001
See Page
3-2
3-5
3-15
3-20
3-1
Overview
Section A
Scope Mode
Overview
Introduction
Scope mode allows you to view real-time voltage and current waveforms for up to eight channels simultaneously.
Scope mode screen
The Scope mode screen can be displayed by pressing the Scope key on the Home screen.
Volts/Amps channel labels and RMS values for displayed waveforms
Display one cycle of selected waveforms which are scaled relative to the largest peak value. V & I are scaled separately.
Frequency
Voltage scale
Turn channels on/off
(p. 3-3)
Current scale
MARK201
Show channels input range (p. 3-4)
Return to Home screen
In this section
The following topics are covered in this section.
Topic
Turning Channels On/Off
Checking Input Range
See Page
3-3
3-4
3-2
CH 3/ View Real Time Data
Turning Channels On/Off
Select channels to display
From the Scope mode screen, press Chan to turn Volts/Amps channel selection on/off.
MARK202
Any of the following will turn channels on/off:
• Press the desired Volts/Amps channel to turn it on/off.
• Press Volts or Amps button to turn on/off all channels of that parameter.
• Press A, B, C, D to turn on/off both the Volts and Amps for that channel.
Press OK to accept channel selection.
3-3
Checking Input Range
Checking Input Range
Input range
The Input Range screen is displayed by pressing the CkRng key on the Scope mode screen. Input Range shows the detected range for all channels. The number after the status shows the percentage of the input of the instrument’s full range.
MARK205
The input range can only be viewed, not changed. Press OK when done viewing the input range.
Input range description
The following table describes the messages that may register on the Input Range screen. The instrument is able to detect the input range for voltage and current channels
A, B, C, and D.
Input Range
OK
OVER
UNDER
N/A
CLIP
Description
Within Range
Over Range
Under Range
Channel Disabled
Clipping
If input range is OVER, UNDER, or CLIP, then the rms readings will not be accurate.
Using CTs below 10% of Full Scale may also cause inaccuracies in amplitude, phase and harmonic distortion readings.
3-4
CH 3/ View Real Time Data
Section B
Meter Mode
Overview
Introduction
Meter mode allows you to view real-time meter data. The metered parameters available are logically separated into the following tabs: Standard, Distortion, User Specified
Frequency, Imbalance, and Advanced Power. Meter screens are displayed in tabular form.
NOTE: Meter mode operation does not interfere with any of PX5’s other monitoring or recording functions. The individual voltage and current channel meter readings are not affected by the monitoring setup. Turning monitoring of individual channels off does not affect meter readings. Meter and Scope data is NOT available if you are viewing a stored file from the data card.
Metered parameters display
PX5 is designed to provide setup as well as data display. Metered parameters are available for display regardless if they are being journalled under Setup New Circuit >
Advanced Options > Journal Limit Setup. Users can trend journal entries by limits
(Very High, High, Low, Very Low) or by time (users can set the time interval of how often rms and waveform snapshots will be recorded even when no disturbances occur).
For the procedure on how to set entries under journal parameters, go to Chapter 6
Advanced Setup Options - Journal Limit on page 6-17.
In this section
The following topics are covered in this section.
Topic
Standard Meter Tab
Distortion Meter Tab
User Specified Frequency Meter Tab
Imbalance Meter Tab
Advanced Power Meter Tab
See Page
3-6
3-8
3-10
3-11
3-12
3-5
Standard Meter Tab
Standard Meter Tab
Standard meter list
Meter mode can be displayed by pressing the Meter icon on the Home screen. At startup, meter mode defaults in the Standard tab featuring the basic power quality parameters available. The standard metering properties include Voltage, Computed
Basic, Power, Demand, Energy, Harmonics and Flicker as shown below.
3-6
MARK301
Standard Tab
Basic
(for A, B, C, D)
Computed
Basic
Power
(for A, B, C, D,
Total)
Parameter Name
Volts
NOTE: Some voltage channel meter values are derived based on the circuit type selection. The values will change depending on the wiring configuration setup.
Volts
Label
Ampere Amps
Vector Displacement Power Factor Vector Displacement PF
Arithmetic Displacement Power
Factor
Arithmetic Displacement
PF
Residual Current
Net Current
Watts
Volts Ampere
Volts Ampere Reactive
True Power Factor
Displacement Power Factor
Residual Current
Net Current
W
VA
VAR
TPF
DPF
NOTE: See Appendix B Technical Specifications - Computed Parameters on page B-6 for definition of parameters.
Continued on next page
CH 3/ View Real Time Data
Standard meter list (continued)
Standard Tab
Demand
Energy
(for A, B, C, D,
Total)
Harmonics
(for A, B, C, D)
Flicker
(for A, B, C)
Parameter Name
Active Power Demand
Apparent Power Demand
Reactive Power Demand
RMS Current Demand Phase A
RMS Current Demand Phase B
RMS Current Demand Phase C
RMS Current Demand Average
Label
Active Power Demand
Apparent Power Demand
Reactive Power Demand
RMS Current Demand Ph A
RMS Current Demand Ph B
RMS Current Demand Ph C
RMS Current Demand Avg
Watt Hours
Volts Ampere Hours
Watt Hrs
VA Hrs
Volts Ampere Reactive Hours VAR Hrs
Voltage Total Harmonic Distortion V THD
Current Total Harmonic Distortion I THD
RMS Harmonic Current RMS I Harm
Harmonic Power Unsigned
Short Term Flicker
Harm Pwr Unsigned
Pst
Long Term Flicker (Sliding)
Long Term Flicker
Plt (Slide)
Plt
3-7
Distortion Meter Tab
Distortion Meter Tab
Distortion meter list
PX5 is able to meter distortions or uncharacteristic changes in the waveform of original signals. Distortion calculations measure the deviation of complex waveshapes from pure sine waves. Harmonics are measured in accordance with IEC 61000-4-7 Class I.
3-8
MARK311
Distortion Tab
THD
(for A, B, C, D)
TID
(for A, B, C, D)
Parameter Name
Voltage Total Harmonic Distortion
Fundamental
Current Total Harmonic Distortion
Fundamental
Voltage Total Harmonic Distortion Root
Sum of Square
Current Total Harmonic Distortion Root
Sum of Square
Voltage Total Interharmonic Distortion
Fundamental
Current Total Interharmonic Distortion
Fundamental
Voltage Total Interharmonic Distortion
Root Sum of Square
Current Total Interharmonic Distortion
Root Sum of Square
Label
V THD fund
I THD fund
V THD RSS
I THD RSS
V TID fund
I TID fund
V TID RSS
I TID RSS
Continued on next page
CH 3/ View Real Time Data
Distortion meter list (continued)
Distortion Tab
TIF
(for A, B, C, D)
Parameter Name
Voltage Telephone Influence Factor
Fundamental
Current Telephone Influence Factor
Fundamental
Voltage Telephone Influence Factor
RMS
Current Telephone Influence Factor
RMS
Telephone Influence Factor Product
Crest Factor
(for A, B, C, D)
Power
(for A, B, C, D)
Voltage Crest Factor
Current Crest Factor
Signed Phase Harmonic Power
Unsigned Phase Harmonic Power
Transformer
(for A, B, C, D)
Transformer Derating Factor
K Factor
Label
V TIF fund
I TIF fund
V TIF RMS
I TIF RMS
TIF Prod
Volts Crest Factor
Amps Crest Factor
Signed
Unsigned
Derating Factor
K Factor
3-9
User Specified Frequency Meter Tab
User Specified Frequency Meter Tab
User frequency meter list
Voltage and current harmonics for each phase and neutral channel can be metered under the User Specified Frequency tab. The value fields are initially not specified to allow users to choose the numbers or the range of harmonic frequencies to meter. The system simultaneously measures voltage and current so that harmonic power can be obtained.
Whereas harmonic summary values include harmonics up to the 127th in Standard
Power Quality mode, individual harmonics displayed on the instrument are only available up to the 60th.
User Frequency Tab
Voltage
(for A, B, C, D)
Parameter Name
User Selected Voltage Harmonic 1
User Selected Voltage Harmonic 2
User Selected Voltage Harmonic 3
Current
(for A, B, C, D)
User Selected Voltage Harmonic 4
User Selected Current Harmonic 1
User Selected Current Harmonic 2
User Selected Current Harmonic 3
User Selected Current Harmonic 4
MARK321
User 1
Label
User 2
User 3
User 4
User 1
User 2
User 3
User 4
3-10
CH 3/ View Real Time Data
Imbalance Meter Tab
Imbalance meter list
The Imbalance metering tab shows positive, negative and zero sequence components for voltage and current.
Imbalance Tab Parameter Name
V/I Sequence Positive Sequence Voltage
Negative Sequence Voltage
Zero Sequence Voltage
Positive Sequence Current
Negative Sequence Current
Zero Sequence Current
V/I Imbalance Voltage Imbalance (RMS/RMS
Average)
Voltage Imbalance (S2/S1)
Voltage Imbalance (S0/S1)
Current Imbalance (RMS/RMS
Average)
Current Imbalance (S2/S1)
Current Imbalance (S0/S1)
MARK331
Label
Positive Sequence Voltage
Negative Sequence Voltage
Zero Sequence Voltage
Positive Sequence Current
Negative Sequence Current
Zero Sequence Current
V Imbalance (RMS/RMS
Avg)
V Imbalance (S2/S1)
V Imbalance (S0/S1)
I Imbalance (RMS/RMS
Avg)
I Imbalance (S2/S1)
I Imbalance (S0/S1)
3-11
Advanced Power Meter Tab
Advanced Power Meter Tab
Advanced power meter list
Advanced power metering tab meters multiple total apparent power and power factor parameters, calculated using arithmetic and vector sums of the individual phases. These methods may produce different values with distorted and/or imbalance phases.
Demand/Advanced Energy include various energy parameters on per phase and total basis as well as in forward and reverse mode. Some parameters such as displacement power factor are only valid for the fundamental frequency. The Advanced tab also allows trending of rapid voltage changes that result in light flicker. Flicker parameters under the Advanced tab are used primarily for specialized testing. Flicker measurements are calculated as per IEC 61000-4-15.
3-12
MARK341
Advanced Tab Parameter Name Label
Arithmetic Sum Arithmetic Sum Power Factor Arithmetic Sum PF
Arithmetic Sum Displacement
Power Factor
Arithmetic Sum DPF
Arithmetic Sum Volts Ampere Arithmetic Sum VA
Fund Arithmetic Sum VA
Vector Sum
Fundamental Arithmetic Sum
Volts Ampere
Vector Sum Power Factor
Vector Sum Displacement
Power Factor
Vector Sum Volts Ampere
Fundamental Vector Sum Volts
Ampere
Vector Sum PF
Vector Sum DPF
Vector Sum VA
Fundamental Vector Sum VA
Continued on next page
CH 3/ View Real Time Data
Advanced power meter list
(continued)
Advanced Tab
Peak Power
Parameter Name
Peak Watt Demand
Label
Peak Watt Demand
Peak Volts Ampere Demand
Peak Volts Ampere Reactive
Demand
Peak VA Demand
Peak VAR Demand
Peak Current Demand Phase A Peak Current Dmd Ph A
Peak Current Demand Phase B Peak Current Dmd Ph B
Peak Current Demand Phase C Peak Current Dmd Ph C
Peak Current Demand Average Peak Current Demand Avg
Predicted Power Predicted Watt Demand Predicted W Demand
Predicted Volts Ampere Demand Predicted VA Demand
Predicted Volts Ampere
Reactive Demand
Predicted VAR Demand
Coincident Power Volts Ampere Demand at Peak
Watt Demand
Volts Ampere Reactive Demand at Peak Watt Demand
VA Demand at Peak Watt
Demand
VAR Demand at Peak Watt
Demand
Coincident Power
Factor
Watt Demand at Peak Volts
Ampere Reactive Demand
Volts Ampere Demand at Peak
Volts Ampere Reactive Demand
Volts Ampere Reactive Demand at Peak Volts Ampere Demand
Watt Demand at Peak Volts
Ampere Demand
Watt Demand at Peak VAR
Demand
VA Demand at Peak VAR
Demand
VAR Demand at Peak VA
Demand
Watt Demand at Peak VA
Demand
Avg PF at Peak W Demand Average Power Factor at Peak
Watt Demand
Average Power Factor at Peak
Volts Ampere Reactive Demand
Average Power Factor at Peak
Volts Ampere Demand
Avg PF at Peak VAR
Demand
Avg PF at Peak VA Demand
Continued on next page
3-13
Advanced Power Meter Tab, continued
Advanced power meter list
(continued)
Advanced Tab
Advanced Energy
(for A, B, C, D,
Total)
Instantaneous
Flicker
(for A, B, C)
Parameter Name
Forward Fundamental Frequency
Watt Hours
Forward Fundamental Frequency
Volts Ampere Reactive Hours
Reverse Fundamental Frequency
Watt Hours
Reverse Fundamental Frequency
Volts Ampere Reactive Hours
Instantaneous Flicker
Instantaneous Flicker LPF
Square Root of Instantaneous
Flicker
Square Root of LPF
Fwd Whr
Label
Fwd VAR Hr
Rev Whr
Rev VAR Hr
Pinst
Pinst LPF
Pinst Sq Root
Sq Root LPF
3-14
CH 3/ View Real Time Data
Section C
Harmonics
Overview
Harmonics display
PX5 allows users to view voltage and current harmonics/interharmonics in graphical or in list form. Harmonics are waveform distortion, a steady-state deviation from an ideal power frequency sinusoid and is characterized by the spectral content of the waveform.
Interharmonics are frequency components between the harmonic frequencies. The IEC
61000-4-7 Standard dictates that harmonic analysis is done using a synchronous window of 10 cycles for 50 Hz, or 12 cycles for 60 Hz. This results in bins which are nominally 5 Hz wide. The actual width of the bins is equal to the actual frequency divided by 10 if the nominal frequency is 50 Hz, and 12 if 60 Hz. For example, if actually operating at 49.9 Hz, the bin is 4.99 Hz, but is labelled “5 Hz” as specified by the standard.
Use the respective touch screen buttons to display the next Channel (Channels A, B, C,
D) and the next Parameter (V, I, W) of harmonic data. The number of harmonics/ interharmonics displayed is up to the 60th. Summary values of odd, even and total distortion are displayed. A summary of harmonic distortion as well as interharmonic distortion values per phase/parameter are also available on display.
Users can determine the number or range of harmonic frequencies to trend and view in detail. There is also the option to select how to plot harmonic/interharmonic data and specify the units of measure by which harmonic data is calculated.
Harmonic Graph: Harmonics are measured in accordance with IEC 61000-4-7 Class 1.
Users can choose the unit of measure by which harmonic data is calculated and graphed, based on a Percentage of the fundamental value or in Engineering units (volts and amps). Frequency components of harmonic graphs can be displayed either in Hertz or in Harmonic Number. The graphs can be zoomed and rescaled.
Harmonic List: The list gives a textual display of the following for each of the measured values: frequency and harmonic number; magnitude in Engineering units and percent of fundamental; phase in degrees (for harmonics only). This list is displayed in order of ascending frequency, and can also be sorted in order of descending magnitude.
In this section
The following topics are covered in this section.
Topic
Harmonic Graph
Harmonic Detail
Harmonic Options
Harmonic List
See Page
3-16
3-17
3-18
3-20
3-15
Harmonic Graph
Harmonic Graph
Harmonic graph display
The harmonic graph can be displayed by pressing Harmonics on the Home screen. The screen defaults to a graphical spectrum display, although users have the option to choose between the graph and list form. The screen will show a spectral graph featuring the amplitude of the harmonics relative to the fundamental frequency.
Use the properties under the Options button to select the vertical and horizontal measurement scale. The percent magnitude of the first 60 harmonics are graphed relative to the fundamental.
Total harmonic distortion
(THD) on Odd contribution and Even contribution based on 127 harmonics*
Display is updated approximately once per second
MARK221
Switch channel display
Switch to
V, I, or W
Zoom in to desired range of frequencies
(p. 3-17)
Show harmonics text
(p. 3-20)
Set harmonic options
(p. 3-18)
*The odd contribution is the square root of the sum of the squares of the relative
amplitudes of harmonics 3, 5, and 7 through N-1, where N is a function of sampling frequency. The even contribution is similar for harmonics 2, 4, and 6 through N. Total value is the square root of the sum of the squares of the odd and even distortions.
3-16
CH 3/ View Real Time Data
Harmonic Detail
Harmonic graph details
PX5 allows users to determine the numbers or the range of harmonic frequencies to trend. A blue box showing the default zoomed area appears once the Detail button is pressed. Touch any side of the zoom box to activate the drag function. Touch and drag the sides of the zoom box to expand or narrow in on a select number of harmonic/ interharmonic graphs. The zoom box moves horizontally only. The vertical scale will autoscale when zoomed.
NOTE: To select whether the vertical is scaled to the fundamental or the greatest harmonic, use the Options key (see page 3-18).
Fundamental exceeds square so bar extends past top touch and drag zoom box to desired magnification scope
MARK235
MARK235b harmonic data plot
(shown in channel color) interharmonic data plot
(shown in gray)
MARK235c
The magnify buttons serve as zoom function keys, each of which feature a plus sign or a minus sign within. Press Zoom+ to display the zoomed area and view harmonic graphs in greater detail. Users may repeatedly zoom in on a plot for up to seven (7) levels. Press Zoom-(n) to unzoom graph display one increment at a time, where n is the counter of how many times the harmonic graphs have been magnified.
3-17
Harmonic Options
Harmonic Options
Harmonic/
Interharmonic data plots
The voltage and current harmonics and/or interharmonics for each phase channel can be trended using the Options button. The properties specified under Harmonic Options apply when harmonic/interharmonic data is viewed in either graph or list form.
Properties under Show Harmonics... pertain to both the graph and the list, and determine how the harmonics and interharmonics are used.
If Show Harmonics... only is enabled, then only the actual harmonics are shown.
If Show Harmonics... and Interharmonics is enabled, the spectrum will include all the (nominal) 5 Hz bins, which includes the actual interharmonics as well. On the graph, the harmonics are shown in the channel color, while interharmonics are shown in gray color. On the text, the harmonics are shown in boldface.
If Show Harmonics... calculated including adjacent interharmonics is enabled, the interharmonics are not explicitly shown but the harmonic values include the adjacent interharmonic values in their calculation, as specified by IEC 61000-4-7.
The IEC 61000-4-7 Standard specifies that the interharmonic bins adjacent to the harmonic be included in the computation of that harmonic. For example, if there was a
3rd harmonic (150 Hz) of 10%, and the value of the 145 Hz bin was 1%, and the value of the 155 Hz bin was 2%, then the value reported in the bin labelled “150 Hz” would also include contributions from the 145 Hz and 155 Hz bins. This would give
10
2
+
1
2
+
2
2
=
10.2%, not 10%.
The following graphs illustrate harmonic computation as per IEC 61000-4-7 Standard.
Harmonic Computation for 50 Hz
3.0%
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
… 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220 …
3rd harmonic
+
2 adjacent interharmonics
4th harmonic
+
2 adjacent interharmonics
Continued on next page
3-18
CH 3/ View Real Time Data
Harmonic/
Interharmonic data plots
(continued)
Harmonic Computation for 60 Hz
3.0%
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
… 160 165 170 175 180 185 190 195 200 205 210 215 220 225 230 235 240 245 250 …
3rd harmonic
+
2 adjacent interharmonics
4th harmonic
+
2 adjacent interharmonics
Properties under Graph Units pertain to the way the graph (not the list) is labelled. The vertical scale can be in Percent or Engineering units, and Scale to Fund (full scale) can be chosen to be the fundamental at 100% or the largest component. The engineering unit for voltage is volts and for current is amperes. The horizontal axis can be in Hz or Harmonic Number. harmonic data display measurement scale for frequency (x axis) and amplitude (y axis) of harmonics full scale graph relative to fundamental frequency
MARK236
3-19
Harmonic List
Harmonic List
Harmonic text display
To view the harmonics magnitude text display, press List from the Harmonic graph screen on page 3-16. The harmonic parameters displayed on list include: (from leftmost column) the harmonic/interharmonic frequency in Hz, frequency in number, voltage rms or maximum load of current (depending on parameter selected), percent amplitude of harmonics, and harmonic phase angle value.
By default, harmonic and interharmonic frequency values are arranged in order of increasing frequency. Use the Sort button to organize harmonic text display in order of decreasing magnitude. The harmonic values are shown in boldface.
Harmonic phase degree values from 1 to 60 are displayed for voltage and current; while phase degree values from 1 to 50 are displayed for harmonic watts. Harmonic phase angle values can be normalized to the phase of the fundamental of the displayed channel. Use the Norm button to show the normalized phase angle values.
MARK237
Toggle between Normalized and
UnNormalized phase values
MARK237b
3-20
CH 3/ View Real Time Data
Section D
Voltage and Current Phasor
Overview
Phasor display
The phasor screen displays a graph that indicates the phase relations between the voltage and current based upon the angles of the fundamentals, as determined by
Fourier analysis.
Phasor screen shows eight phasors autoscaled with zero degrees to the right (normally channel A voltage) for clockwise rotation and with synchronized channels. Users are allowed to display up to four channels at any one time for either volts or amps, or a single channel for both volts and amps, depending on the phases being monitored.
A touch screen Demo button presents an animated phasor demo rotation for resistive, capacitive and inductive loads.
In this section
The following topics are covered in this section.
Topic
Phasor Screen
Phasor Rotation
Phasor Parameter/Channel Selection
See Page
3-22
3-23
3-25
3-21
Phasor Screen
Phasor Screen
Phasor screen display
The Phasor screen is displayed by pressing Phasor on the Home screen.
The Phasor screen shows eight phasors autoscaled with zero degree to the right for clockwise rotation and with synchronized channels. The left sidebar shows rms values for Volts/Amps for channels A, B, C and D; zero, positive and negative values for
Volts/Amps; zero, positive and negative sequence component values for Volts/Amps.
Depending on the phases being monitored, up to four channels may be displayed at any one time for either Volts or Amps, or a single channel for both Volts and Amps. An arrow head and channel label are displayed on the vector.
Correct rotation is clockwise from 0
º
If a channel is less than
20% of the maximum voltage (or current), the phasor is not displayed
Sync channel is displayed at 0
º -
normally channel
A voltage
MARK241
Show animated phasor demo rotation for Resistive,
Inductive and Capacitive loads (p. 3-23)
3-22
CH 3/ View Real Time Data
Phasor Rotation
Animated phasor rotation
Graphic illustration in the form of rotating phasors relative to the sine wave graph of a four wire wye circuit is available by pressing the Demo button on the Phasor screen
(see page 3-22). The Demo key will be replaced by Start/Stop once phasor rotation has been viewed. Press Start to replay animated phasor rotation. Users can choose to Stop the phasor demo rotation at any time.
Phasor vectors are displayed using a clockwise rotation from the zero degrees reference. Animated phasor demo for Resistive, Inductive and Capacitive loads is available for viewing.
Sample 3-Phase, three wire delta rotation
The following diagrams describe the positive phase rotation of voltage and current phasors (for Resistive, Inductive and Capacitive loads) for a three phase, three wire delta connection. An arrow head on the line indicates direction pointing toward the load.
Three phase vectors are displayed as three lines, 120 degrees apart in a Resistive load
Display parameter/channel selection (p. 3-25)
MARK242
Return to
Phasor screen
Start/Stop demo plot waveforms as rotate phasors; press any time
Switch phasor demo rotation between
Resistive, Inductive and Capacitive load effects; press any time (p. 3-24)
Continued on next page
3-23
Phasor Rotation, continued
Sample 3-Phase, three wire delta rotation
(continued)
The following diagrams describe the positive phase rotation of voltage and current phasors (for Resistive, Inductive and Capacitive loads) for a three phase, three wire delta connection. An arrow head on the line indicates direction pointing toward the load.
Three phase vectors are displayed as three lines, 120 degrees apart in an Inductive load
MARK243
Three phase vectors are displayed as three lines, 120 degrees apart in a Capacitive load
Phasor diagrams
MARK244
Refer to Appendix E for the diagrams that describe the voltage and current phasors for the standard type of power connections.
3-24
CH 3/ View Real Time Data
Phasor Parameter/Channel Selection
Parameter/
Channel display
The Parameter/Channel selection screen is displayed by pressing Chan on the phasor
Demo screen. Depending on the phases being monitored, up to four channels may be displayed at any one time for either Volts or Amps, or a single channel for both Volts and Amps.
MARK245
Press to enable/disable the parameter/channel for display in the animated phasor rotation. Any of the following will turn channels on/off:
• Press the desired Volts/Amps channel to turn it on/off.
• Press Volts or Amps button to turn on/off all channels of that parameter.
• Press A, B, C, D to turn on/off both the Volts and Amps for that channel.
Press OK to accept channel selection. The phasor Demo rotations will display the parameters/channels enabled.
3-25
3-26
C H A P T E R 4
Instrument Settings
Overview
Introduction
This chapter describes the miscellaneous tasks that users can perform to keep the PX5 running efficiently. These are tasks that users might perform only occasionally.
In this chapter
The following topics are covered in this chapter.
Topic
Access Instrument Settings Menu
Time and Date Settings
Select Language
Set Display Preferences
Touch Screen Calibration
Turn Threshold Beeper On/Off
Communications
Data Card
Reset to Factory Configurations
See Page
4-2
4-3
4-5
4-6
4-7
4-9
4-10
4-12
4-14
4-1
Access Instrument Settings Menu
Access Instrument Settings Menu
Preferences menu screen
All functions in this chapter are found under the Instrument Settings menu. Follow these steps to display the Instrument Settings menu screen.
Action...
STEP 1: Press the PX5 On/Off power button to turn the unit on.
The Home screen will be displayed.
Result...
MARK001b
STEP 2: Press Preferences. The
Instrument Settings Setup Menu will be displayed.
MARK151
4-2
CH 4/ Instrument Settings
Time and Date Settings
Time and Date display
Users have the option not only to set the exact time and date, but also to select the format of how time and date will appear on screen.
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Time and Date.
Result...
• Press Time if you want to change the time settings.
Proceed to Step 2 on page 4-4.
• Press Date if you want to change the date settings.
Proceed to Step 3 on page 4-4.
• Press Date Style to select the format in which you want date displayed on screen. View the three different date format selections each time you press
Date Style.
• mm/dd/yy format
• dd/mm/yy format
• yy/mm/dd format
• Press Clock Style to select the format in which you want time displayed on screen. View the three different time format selections each time you press
Clock Style.
• analog
• digital using 1 to 12 hr format (AM/PM)
• digital using 1 to 24 hr format
• Press OK to accept new time/ date settings and return to
Instrument Settings menu.
• Press Cancel to discard changes in time/date settings and return to Instrument
Settings menu.
MARK152
Continued on next page
4-3
Time and Date Settings, continued
Time and Date
Display
(continued)
Action...
STEP 2: Press the field representing hours, minutes, and seconds to change time settings.
Use the numeric keypad to enter new time settings. Time should be entered in a 24-hour format
(example: 14:00:00 for 2:00 PM).
Result...
• Press OK to accept changes in time settings.
• Press Cancel to discard changes in time settings.
NOTE: Clock time and format can be changed anytime following this same procedure.
STEP 3: Press to select the month, day, and year. Enter the year using numbers from the keypad.
• Press OK to accept changes in date settings.
• Press Cancel to discard changes in date settings.
NOTE: Date settings and format can be changed anytime following this same procedure.
MARK153
MARK154
4-4
CH 4/ Instrument Settings
Select Language
Select Language PX5 menu screens appear in the English language by default. Users have the option to set screen display to any of the following languages: English, Swedish, Spanish,
German, French, Italian, Simplified Chinese, Traditional Chinese, or Finnish.
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Language.
Result...
• Check to select the desired language in which you want display screens to appear.
• Press OK to accept new language selection. The screen will return to Instrument
Settings menu. All screens will automatically change to the selected language.
• Press Cancel to retain present language.
MARK155
4-5
Set Display Preferences
Set Display Preferences
LCD settings
User programmable settings for the LCD screen include the backlight timer, contrast, password protect, parameter/channel colors, and touch screen calibration.
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Display Preferences.
• Automatic backlight shutoff timer is provided for the LCD display. Press Backlight Timer to automatically turn off backlight after 1, 2, 5, 10 or 15 minutes of no user activity. Set the Backlight Timer to Always
On if you do not want the backlight to shut off.
NOTE: The auto-shutoff feature extends the life of the battery and should be duly considered.
• Press Contrast to brighten/dim screen display to preferred percentage.
• Press Password Protect to enable/disable password log in code to PX5. When password protect is enabled and the user reactivates PX5 from autoshutoff (see Backlight Timer setting), the keypad screen used to enter password will appear.
The user will have to enter the correct password to continue using PX5. The message Invalid
Password! will appear when an incorrect password is entered.
• Press Channel Colors to change the color of the parameter/ channel display. Select desired color from a 28 color selection grid.
• Press Calibrate Touch Screen to calibrate the unit’s touch screen functionalities. Proceed to page 4-7.
• Press Exit to return to
Instrument Settings menu.
Result...
MARK156
4-6
CH 4/ Instrument Settings
Touch Screen Calibration
Calibration procedure
PX5 is able to perform calibration to ensure the proper operation of the unit’s touch screen functionalities. The calibration procedure will correct the problem of out of tolerance touch screen malfunction. Note that errors corrected by this calibration procedure are specific only to touch screen operation.
Action...
STEP 1: From the Display Setup
Menu (see page 4-6) screen, press
Calibrate Touch Screen.Test if touch screen recognition operates properly by applying pressure on the LCD screen.
Result...
• Press Clear to reset LCD screen and delete display markings.
• Press Calib to begin touch screen calibration procedure.
Proceed to Step 2.
• Press Cancel to end calibration test and return to Display
Setup.
STEP 2: Follow the instruction
Tap Center of Target to begin calibration. Target object X is initially located in the lower middle section of the screen.
• A series of screens will flash showing movement of the target object: from the lower middle section to mid-right and finally to upper left section of the screen.
MARK164
• To end touch screen calibration, tap the center of the target object X now located in the upper left section of the screen. Proceed to Step 3 on page 4-8.
MARK164b
MARK165
MARK166
Continued on next page
4-7
Touch Screen Calibration, continued
Calibration procedure
(continued)
Action...
STEP 3: Once touch screen calibration is done, a message will appear to indicate Touch screen
was successfully calibrated.
Result...
• Press OK to continue on with calibration test verification.
Proceed to Step 3.
STEP 3: Test if touch screen recognition operates properly by applying pressure on the LCD screen.
• Press Clear to reset LCD screen and delete display markings.
• Press Accept to complete the touch screen calibration procedure. Accepting will save and store new touch screen calibration data in memory.
Once the new data is stored, the old touch screen calibration data is lost. The screen will return to the Display Setup
Menu.
• Press Cancel to discontinue the touch screen calibration procedure. Pressing Cancel will retain the previous touch screen calibration constants, no new calibration data will be stored in memory. The screen will return to the Display Setup menu.
4-8
MARK167
MARK168
CH 4/ Instrument Settings
Turn Threshold Beeper On/Off
Audible alarm
When set to ON, the unit will beep when threshold limits are crossed and other event triggers occur. The beep that provides audible feedback to pressing touch screen key is not affected by this setting.
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Turn Beeper On/Off.
Result...
• The unit can provide audible alarm signals when triggered.
Press Threshold Beeper to turn the alarm On or Off.
• Press Exit to return to
Instrument Settings menu.
MARK157
4-9
Communications
Communications
Communication interface setup
Communications Settings is where instrument-specific information is entered to allow the PX5 to communicate to external devices using the optional Isolated Communications
Module assemblies or modem (see related information on Chapter 7 View Event Data -
Section D Downloading Events from PX5 to a Computer).
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Communications.
• Press Enable Communications to activate/deactivate the communications port. External communication devices connect to the PX5 mainframe via the optical serial data port. The optical serial data port connector is located on the left side of the instrument.
• Press to enter the communications
Device Address from 01 to 32 for use with the optional Fiber Optic to Ethernet adapter.
Result...
MARK159
• Select the corresponding Baud
Rate to set connection speed.
Default baud rate is 115200.
• Press External Modem
Connected if you want to activate communications via an external modem. Press Change to modify the modem initialization string.
The string must begin with “AT”.
Dranetz-BMI recommends using the same brand and model of modem at both ends of the communications link. See Chapter
7 View Event Data - Section D on page 7-43 for instructions on modem connections.
• Press IP to configure your
Ethernet settings and allow the
PX5 to operate on the network.
Proceed to Step 2 on page 4-11.
• Press OK to accept changes in communications settings.
NOTE: For instructions on how to physically connect to NodeLink using the external communications devices, see Chapter 7 View
Event Data - Section D Downloading Events from PX5 to a Computer on page 7-38.
• Press Cancel to discard changes in communications settings and return to Instrument Settings menu.
4-10
Continued on next page
Communication interface setup
(continued)
Action...
STEP 2: Entering the correct IP address settings will enable the
PX5 to communicate with the network.
Prior to entering the IP setttings, make sure that the PX5 is connected to the computer network via the Fiber optic to
Ethernet Adapter (P/N COMM-
OEA).
After you have determined the proper IP address and settings, proceed as follows:
• Type in your Ethernet IP
Address in the appropriate fields. Use the numeric keypad to enter the IP setting.
• Type in your Ethernet Subnet
Mask in the appropriate fields.
Use the numeric keypad to enter the Subnet Mask setting.
• Type in your Gateway in the appropriate fields. Use the numeric keypad to enter the
Gateway setting.
Result...
When done entering IP settings, press OK. Pressing OK will store the values in the instrument.
Press Send to configure the
Ethernet adapter using the new IP address settings. Follow the instructions that appear on screen to complete the IP setting configuration procedure.
Press Cancel to ignore changes and retain the previous IP settings, no new values will be stored in the instrument.
CH 4/ Instrument Settings
MARK159b
4-11
Data Card
Data Card
Format/View data card
The Memory Card screen displays information on the card inserted in the data card slot, including the amount of total space, available space, and used space in card. The
Memory Card screen also prompts users to set filename and format card in preparation for monitoring and writing of data.
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Memory Card.
Result...
• Card Status indicates status condition of the card inserted in the data card slot. The following messages may appear under Card Status (refer to pages 5-20 to 5-21 for a detailed description of each card status message):
• Not Inserted
• Contains File
• Empty
• Fragmented
• Unformatted
• Invalid Card
MARK160
• Card size indicates the full storage capacity of the data card. The amount of remaining space and used space in data card are also displayed on screen.
• Press Format to format the data card. Proceed to Step 2 on page 4-13.
NOTE 1: PX5 does not support file fragmentation. When creating a file, it will take the largest continuous block and use that size block for data storage. Deleting files from data card is not recommended. Whenever possible, transfer the files to a computer and then reformat the card using the PX5 when there is no more space available to begin new data storage.
NOTE 2: Refer to Chapter 5 Start Menu - Site
Name/Memory Card on pages 5-20 to 5-23 for more information on data card operation.
• Press View to display files stored in data card. Proceed to Step 3 on page 4-13.
• Press Exit to discard changes and return to Instrument Settings menu.
Continued on next page
4-12
Format/View data card
(continued)
Action...
STEP 2: All data and setups stored in data card will be lost when you format the card.
• A confirmation message verifies whether you want to continue with data card format or not.
Press Yes to continue data card format. Press No to cancel data card format.
• The message Format
Successful! indicates that data card format has been completed. Press OK to exit card format procedure and return to the Memory Card screen.
Result...
STEP 3: PX5 lists data file names stored in data card, along with file size, time and date when data was recorded. The text color indicates the type of file: black is for data file (.ddb), green is for setup file
(.set), and red is for an unknown file.
• Press Up/Down arrow keys to scroll the page up or down by one line.
• Press and drag the scroll bar to move the page up or down.
• Press Exit to quit and return to
Memory Card screen.
CH 4/ Instrument Settings
MARK161
MARK162
MARK163
4-13
Reset to Factory Configuration
Reset to Factory Configurations
Definition
Procedure
Factory configurations are the default settings of all programmable features of the PX5 as it left the factory.
Follow these steps to reset the PX5 to its factory configuration.
Action...
STEP 1: From the Instrument
Settings Setup Menu screen, press
Reset to Factory Defaults.
Result...
A confirmation message verifies if you want to reset the instrument to factory configuration and lose all new data and settings.
• Press Yes to erase existing settings and reset the instrument to factoryconfigured setups. The screen will return to the Instrument
Settings menu.
• Press No to cancel.
MARK158
4-14
CH 4/ Instrument Settings
Factory default settings
Dranetz-BMI has set the default values for the various parameters of the PX5.
Current Probes: TR2500/TR2500A for A, B, C; TR2510/TR2510A for D
Scale Factors: 1:1 for V and I, channels A, B, C, D
Circuit Type: three phase wye
Mode of Operation: monitor
Nominal Value: measured V, I, frequency
Monitoring Mode: Standard Power Quality
Advanced Operations: individual limit setups
Transient Limits: intantaneous peak = 3X nominal V, waveshape = 10% ,
rms dev = 10% , fast transient = 3X nominal V, none for I
RMS Variation Limits: 10% Very Low, 90% Low, 110% High for voltage; none for
current
Journal Limit: journalling By Time for the various parameters
Triggers: all V trigger; all V and I channels
Journal Interval
Power Values:
Power Values Interval: 15 minutes
Waveform Snapshot: OFF
Demand and Energy:
Demand Sub-Interval: 5 minutes
Sub-Intervals per Interval: 3
Harmonics Journal Interval: 15 minutes
Flicker:
Pst (Short Term) Interval: 10 minutes
Plt (Long Term) Interval: 2 hours
Site Name: Power Xplorer Site
Clock Type: Analog
Date: mm/dd/yy
Language: English
Display
Backlight Timer: 1 minute
Contrast: 70%
Password Protect: OFF
4-15
4-16
C H A P T E R 5
Start Menu
Overview
Start menu options
The Start Menu allows users to perform the following: set up the PX5 for monitoring of an electrical system, load previously saved setups from card, and load data from card.
There are three ways to set up the instrument for monitoring. The length of time to monitor a circuit can vary from a few hours to a few weeks depending on the user application.
• Automatic Setup automatically configures the instrument’s circuit type, voltage and current channels, and parameter thresholds. The auto-configured setup enables users to proceed directly with data monitoring.
• Wizard Setup takes the user through a series of screens prompting for information about the circuit to be monitored. The unit automatically turns on the correct voltage and current channels when user selects a circuit type. Parameter thresholds are automatically set based on the line voltage and current values that the user enters.
Threshold limits for capturing events are also set according to the monitoring mode selected.
• Advanced setup options (see Chapter 6) allow the user to modify trigger parameters and intervals that were previously set up through Automatic or Wizard setups. Under advanced setup, each channel must be turned on individually, but any combination can be used. Threshold limits can be set to any value within the acceptable range.
The user can turn on any available parameter. Users have wider control over all setup functions when using advanced setup options.
Selection of setup method typically depend on user application and extent of familiarity with the operation of the intrument.
Monitor same circuit makes use of the existing setup for monitoring. If a template of setups has been previously saved to the card, you may load it using the menu below.
Load setup template from card enables you to use previously saved setups. If you wish to load a previously saved data file from the card, use the menu below.
Load data from card allows you to transfer saved events from data card to PX5.
5-1
Overview, continued
Displaying Start
Menu
Follow these steps to display the Start Menu.
Action...
Result...
STEP 1: Press the PX5 On/Off power button to turn the unit on.
The Home screen will be displayed.
STEP 2: Press Start/Setup. The
Start Menu will be displayed.
MARK001b
MARK100
In this chapter
This chapter is divided into five sections:
Section
A
B
C
Automatic Setup
Wizard Setup
Monitor Same Circuit
Title See Page
5-3
5-6
5-24
D Load Setup Template from Card 5-34
E Load Data from Card 5-35
5-2
CH 5/ Start Menu
Section A
Automatic Setup
Overview
Automatic Setup procedure
Automatic Setup is a one-stop process using pre-defined values to set the unit automatically. Users have the option to view the summary list of parameter settings, change probe types if current will be monitored, and/or proceed directly with data monitoring. Follow these steps to perform Automatic Setup.
Action...
STEP 1: From the Start Menu, press Automatic Setup. The autoconfigured circuit type, nominal voltage, current and frequency values appear on screen. Data card status and available space in card are also displayed.
• To continue Automatic Setup and begin data monitoring, press OK. Proceed to Step 2.
• To view the list of parameter settings for Automatic Setup, press Summary. Proceed to
Step 3 on page 5-4.
• To display/change probe types for current monitoring, press
Probe. Proceed to Step 4 on page 5-4.
• Press Cancel to quit and return to Start Menu.
STEP 2: The Monitoring Menu screen allows users to begin monitoring immediately or at a specified time and date.
Result...
• To start monitoring, press Start
Now!
Proceed to Section C Monitor
Same Circuit - Turning
Monitoring On/Off on page 5-24.
MARK101a
MARK123b
Continued on next page
5-3
Overview, continued
Automatic Setup procedure
(continued)
Action...
STEP 3: Summary displays the list of parameter settings for
Automatic Setup. The setup summary is available for review before, during and after monitoring.
• Press Up/Down arrow keys to scroll the page up or down by one line.
Result...
• Press and drag the scroll bar to move the page up or down.
• When done reviewing the
Setup Summary, press Exit.
The screen will return to Auto-
Config.
STEP 4: Various probe types are available for each channel for current monitoring.
• Press Change to display the probe types available for each channel. Proceed to Step 5 on page 5-5.
• If using identical probe type for all Channels, press to enable
Set Identical. The display will change to show only one probe selection for all channels. Press
Change to display the probe types available. Proceed to Step
5 on page 5-5.
• Press OK to accept probe selection and return to Autoconfig screen.
• Press Cancel to disregard probe selection and return to
Auto-config screen.
5-4
MARK123c
MARK101b
MARK103b
Continued on next page
Automatic Setup procedure
(continued)
Action...
STEP 5: Select your desired probe type.
NOTE: Use the same probes for the following: TR2500 for
TR2500A, TR2510 for TR2510A,
TR2520 for TR2520A.
• If the current probe that you are using is not on the list, select
Other. Then press Scale to define the CT scale factor on the current probe. Proceed to
Step 6.
• Press OK to accept probe selection and monitor current.
• Press Cancel to retain previous probe settings and return to previous screen.
STEP 6: You need to set the CT scale factor when using a current probe that is not on the list.
Pressing Scale will show the numeric window to enter the CT scale factor on the current probe.
Use the keypad to set the CT scale factor. See sample scale factor calculation on page 5-10.
• Press OK to accept the CT scale factor value. The Current
Probe Selection screen will be displayed.
• Press ...
....
if you want to clear and retype numeric values.
• Press x1000 to multiply the value by 1000.
• Press Cancel to discard changes and return to the previous screen (screen shown on Step 5).
Result...
CH 5/ Start Menu
MARK104
MARK104b
5-5
Overview
Section B
Wizard Setup
Overview
Introduction
Wizard Setup guides the user through the circuit setup step-by-step, via a series of screens prompting for information about the circuit to be monitored. The unit automatically turns on the correct channels, sets the parameter thresholds and waveform capture settings depending on the detected circuit type, nominal voltage and current values, and monitoring mode specified by the user.
Monitoring modes
PX5 allows users to monitor events in the following setup categories: Standard Power
Quality, Current Inrush, Fault Recorder, Long-term Timed Recording, Continuous Data
Logging, and EN50160 Power Quality mode. Selecting any setup category automatically sets trigger and capture conditions. Advanced users are free to mix and match settings (see Chapter 6 Advanced Setup Options).
Standard Power Quality, Demand, Energy: PX5 algorithms automatically evaluate existing rms and waveform conditions to optimize setups to reliably capture data. This feature ensures that the first-time user gets the expected results, while providing the experienced user with the ability to tweak settings for specific applications. Either way, the necessary data used to identify critical events and optimize mitigation solutions is recorded into the data card as it occurs.
Current Inrush: Determining system characteristics during current inrush conditions such as impedance changes during motor energization or the I
2 t curve of a breaker trip is key to preventative maintenance and enhanced power system performance. Inrushtype events such as motor start-up typically requires extended duration cycle-by-cycle recording. With PX5, users can capture and store detailed data to evaluate system performance against specifications and previous benchmark data. Under the current inrush mode, triggers are current-based. By operating in the inrush mode, the instrument will capture and store highly detailed data to a Compact Flash data card in real time, then rearm and be ready to capture data during the next test run.
Fault Recorder: A fault in a wire circuit is usually due to unintentional grounding, a break in the line, a crossing or shorting of the wires, etc. A digital fault recorder logs extended duration cycle-by-cycle recording. Under the fault recorder mode, triggers are voltage-based. PX5 can help locate failures detected in various components of assorted equipment by recording an extended period of cycle-by-cycle data to capture the entire duration of the fault and the associated system response.
Continued on next page
5-6
CH 5/ Start Menu
Monitoring modes
(continued)
Long-term Timed Recording, Demand, Energy: Performing a statistically valid power quality energy survey requires the capture of a set of basic data over an extended period of time. PX5 is designed to facilitate long-term monitoring by collecting min/max/avg data at each predetermined interval in order to perform post-process harmonic and other events analysis. PX5 is also designed to be left unattended in the field, recording statistically representative data for long-term analysis. Using the Dranetz-BMI lockable portable case option or other available enclosures, power quality studies can be carried out in harsh weather environments.
Continuous Data Logging, Demand, Energy: This logs the rms and power values once per second for totally gapless logging. Cyclic triggers are disabled. No waveforms are recorded under this monitoring mode.
EN50160 Power Quality: EN50160 monitors and reports Quality of Supply (QOS) compliance as specified by the EN standard. The seven parameters required by
EN50160 to determine QOS compliance are: Power Frequency, Supply Voltage
Variations, Rapid Voltage Changes, Supply Voltage Unbalance, Harmonic Voltage,
Interharmonic Voltage, and Mains Signalling. A full discussion on EN50160 is found on Chapter 7 View Event Data - Section C Reports.
In this section
The following topics are covered in this section.
Topic
Current Probe Selection
Scale Factor Setup
Circuit Type Selection
Nominal Values
Mode of Operation
Monitoring Mode
Advanced Options
Site Name/Memory Card
See Page
5-8
5-10
5-12
5-14
5-17
5-18
5-19
5-20
5-7
Current Probe Selection
Current Probe Selection
Selecting current probe
Follow these steps to monitor current and select probe type.
Action...
STEP 1: From the Start Menu, press Setup new circuit.
• If current will not be monitored, press Next. Go to page 5-10.
• If current will be monitored, press Change to display the probe types available for each channel. Proceed to Step 2.
• If using identical probe type for all Channels, press to enable
Set Identical. The display will change to show only one probe selection. Press Change to display the probe types available. Proceed to Step 2.
• If you want to enable/disable current channels, press to select/deselect Enable
Currents.
• Press Cancel to quit and return to Start menu.
Result...
STEP 2: Select your desired probe type.
NOTE: Use the same probes for the following: TR2500 for
TR2500A, TR2510 for TR2510A,
TR2520 for TR2520A.
• If the current probe that you are using is not on the list, select
Other. Then press Scale to define the CT scale factor on the current probe. Proceed to
Step 3 on page 5-9.
MARK101
MARK103
MARK104
Continued on next page
5-8
CH 5/ Start Menu
Selecting current probe
(continued)
Action...
STEP 2: (continued)
• Press OK to accept probe selection and monitor current.
• Press Cancel to retain previous probe settings and return to previous screen.
Result...
STEP 3: You need to set the CT scale factor when using a current probe that is not on the list.
Pressing Scale will show the numeric window to enter the CT scale factor on the current probe.
Use the keypad to set the CT scale factor. See sample scale factor calculation on page 5-10.
• Press OK to accept the CT scale factor value. The screen shown in Step 2 will be displayed.
• Press ...
....
if you want to clear and retype numeric values.
• Press x1000 to multiply the value by 1000.
• Press Cancel to discard changes and return to the previous screen (screen shown on Step 2).
MARK104b
Other relevant information on current probes
Refer to Chapter 2 Voltage Measurement Cable and Current Probe Connections for illustrations of typical current probes and for guidelines on how to connect current probes.
Refer to Appendix A for descriptions and part numbers of probes and adapter cables.
Refer to Appendix B for Dranetz-BMI current probes technical specifications.
5-9
Scale Factor Setup
Scale Factor Setup
What is a scale factor?
A scale factor is the ratio of the input to output for a particular current transformer (CT) or potential transformer (PT). A scale factor is entered in PX5 and then multiplied automatically by the measured voltage or current so the unit displays the correct values, as referenced to the primary side, rather than the secondary side of the PT or CT.
NOTE: If voltage and current connections are made without using any of the above named devices, the scale factor should be set to 1.
When to use
Scale factors must be entered for the following conditions:
• A Dranetz-BMI current probe is connected to a permanently installed CT.
• The current connections are made using a Dranetz-BMI ISO box.
• The voltage connections are made using a PT.
Non-Dranetz equipment
Refer to the CT name plate or to the manufacturer’s literature to determine the scale factor.
Sample calculation
The scale factor for a single CT or PT is calculated from its step-up or step-down ratio.
Example of step-down ratio
If a current transformer has a step-down ratio of 1000A:5A, therefore:
Scale Factor = 1000/5 = 200
Example of step-up ratio
If a potential transformer has a step-up ratio of 1V:10V, therefore:
Scale Factor = 1/10 = 0.1
5-10
CH 5/ Start Menu
Scale factor setup screen
After setting up current probe configurations, the Scale Factor screen is displayed.
Action...
STEP 1: From the Current Probe
Selection screen, press Next to display the Scale Factor Setup.
Result...
• If voltage and current connections are made without using any current or potential transformer devices, the scale factor is set to the default value of 1. Press Next and go to page
5-11.
• To enter new scale factors, press the numeric field of the
Volts/Amps channel where you want to enter new scale factors.
Proceed to Step 2.
• Press Cancel to quit and return to Start menu.
STEP 2: Enter a new scale factor value using the numeric keypad.
Press OK to accept the new scale factor.
• Press .. .
. .. to clear and retype numeric values.
• Press x1000 to multiply the value by 1000.
• Press Cancel to discard changes and retain previous scale factor value, and return to
Scale Factor Setup screen.
MARK105
MARK105b
5-11
Circuit Type Selection
Circuit Type Selection
Circuit setup
PX5 is able to display wiring diagrams from which users can select the circuit type appropriate to their application. The instrument will display the detected circuit configuration and compare the detected voltages, currents, and phase sequence (if applicable) to the selected circuit type. Refer to Appendix E for the descriptions of common circuit connections.
Action...
STEP 1: From the Scale Factor
Setup screen, press Next to display Circuit Type Selection.
Read the Warning advisory, then press Accept to display the menus for circuit selection.
Result...
• To select a circuit configuration, press the Ckt arrow keys until the desired configuration is displayed.
An auto circuit detection window is displayed to show if selected circuit tpe and the detected voltages, currents, and phase sequence match (text in green) or do not match (text in red).
When done with Circuit setup, press Next. Go to page 5-14.
• Real-time Scope and Phasor screens are available. These functions help verify if the wiring configuration matches the circuit being monitored.
Press Scope to check if the waveforms look correct for the specified wiring setup. Proceed to Step 2 on page 5-13.
Press Phasor to view if phasor display match those expected from the specified wiring diagram. Proceed to Step 3 on page 5-13.
• Press Cancel to discard changes and return to Start menu.
MARK107
MARK108
Continued on next page
5-12
Circuit Setup
(continued)
Action...
STEP 2: Scope mode allows users to verify if waveforms look correct for the specified wiring setup.
Result...
• To check input range, press
CkRng. The Input Range screen displays the detected range for voltage and current channels A, B, C, and D.
• The instrument registers a message on the Input Range screen that corresponds to the detected input range for each channel:
Input Range
OK
OVER
UNDER
N/A
CLIP
Description
Within Range
Over Range
Under Range
Channel Disabled
Clipping
• When done checking the input range, press OK to return to the
Scope mode screen. Once in
Scope mode screen, press Exit to return to Circuit Type
Selection screen.
STEP 3: Phasor display shows a graph that indicates phase relations between voltage and current.
For more information on phasors, refer to Chapter 3 View Real
Time Data - Section D Voltage and Current Phasor.
• Press Demo to show animated phasor rotations.
• Press Exit to return to Circuit
Type Selection screen.
CH 5/ Start Menu
MARK201
MARK205
MARK241
5-13
Nominal Values
Nominal Values
Frequency, voltage and current settings
The Nominal Values screen allows users to enter values for frequency nominal line voltage and current, or use the computed nominal values displayed on screen.
Action...
STEP 1: Nominal Values screen appears as users prepare the instrument to record data. From the Circuit Type Selection screen, press Next to display Nominal
Values.
Result...
• If the computed nominal values are acceptable without change, press Next. Go to page 5-17.
• To enter a new nominal
Frequency, Voltage and/or
Current value, press the corresponding field and proceed to Step 2.
MARK110
• To set the properties to track frequency of a monitored system, press Tracking.
Proceed to Step 3 on page 5-15.
NOTE: Make sure that the nominal values computed by PX5 are correct. Nominal values are used as basis for setting default thresholds and other parameters for circuit monitoring.
• Press Cancel to quit and return to Start menu.
STEP 2: Enter a new nominal
Frequency/Voltage/Current value using the numeric keypad. Press
OK to accept the new value.
• Press ...
.. .
to clear and retype numeric values.
• Press x1000 to multiply the value by 1000.
• Press Cancel to retain previous nominal values and return to
Nominal Values screen.
MARK110b
Continued on next page
5-14
Frequency, voltage and current settings
(continued)
Action...
STEP 3: Tracking allows users to set parameters to monitor changes in frequency.
Result...
Voltage Class:
Check to select the power system that define the voltage range of distribution of the monitored system.
• Standard voltage range is 16-
440 Hz.
• Fast voltage range is 16-65 Hz.
• Internal uses the nominal frequency when making measurements where no reference signal is available.
NOTE: Always enter a nominal frequency that matches your line frequency. This ensures that if the PX5 loses external sync, it will have a corresponding internal sync.
Sync Channel:
Check to specify the external sync mode to show which channel the signal is connected to. See page 5-
16 for more details on frequency synchronization.
• Ch A Volts: When set to Ch A,
PX5 attempts to sync to an incoming voltage signal.
• Ch D Volts: When set to Ch D,
PX5 only attempts to sync to voltage Ch D.
Tracking Range:
The Min and Max refer to the range of frequencies that the phase locked loop will “hunt” if sync is lost. See page 5-16 for more details on frequency tracking.
• Press OK to accept new frequency tracking settings.
• Press Cancel to quit and return to Nominal Values screen.
CH 5/ Start Menu
MARK110c
5-15
Nominal Values, continued
Frequency synchronization
Normal frequency synchronization (sync) of PX5 analog signal processing circuits is controlled by analyzing the external AC voltage signal input on channel A. Loss of external sync causes the PX5 to poll other valid voltage channels (A, B, or C) for an alternate external sync. If none exists, then internal sync is automatically selected. The frequency used for internal is entered under Frequency on the Nominal Values screen
(see page 5-14).
Depending on the type of circuit configuration, the instrument will attempt to autosearch to sync to any valid voltage channel. The autosearch function will be disabled when users specify sync mode Ch D Volts. Typically, external sync on Ch D is specified if it is known that signals on A, B or C are inappropriate for use as a sync source (i.e. the frequency is unstable or DC). A low distortion 50, 60 or 400 Hz signal can be input to Ch D and used as a sync signal.
NOTE: Failure to connect an external sync or to select an internal sync during current monitoring will result in erroneous data being collected and displayed.
Frequency tracking
Tracking determines how the phase locked loop circuitry responds to sudden changes in frequency.
Standard mode: On a normal power quality application [Standard], the system is designed to “ride through” voltage changes to keep tracking the fundamental frequency even in the absence of voltage.
Fast mode: When operating on a local generator [Fast], the frequency will vary more as loading changes occur. The Fast mode allows the instrument to follow these changes more closely.
Internal mode: In cases where no reference signal is available (such as DC monitoring), the Internal setting is used to set the sample rate.
5-16
CH 5/ Start Menu
Mode of Operation
Basic meter setup
After entering the correct nominal values for circuit monitoring, users have the option to set the instrument to record data or to use the instrument as a meter.
Action...
STEP 1: From the Nominal
Values screen, press Next to display the Mode of Operation.
• To set up the instrument to record data, press to enable
Continue and set limits to record events and statistical
data. Press Next and go to page 5-18.
• To use the instrument as a meter, press to enable Use as a
meter. Proceed to Step 2.
• Press Cancel to discard changes and return to Start menu.
STEP 2: The instrument is now configured for your specified wiring setup and is ready to use as a meter.
• Press Finish to begin using instrument as a meter and return to Home screen.
• Press Cancel to discard meter mode operation and return to
Start menu.
Result...
MARK109
MARK109b
5-17
Monitoring Mode
Monitoring Mode
Choose a monitoring mode
PX5 provides six monitoring modes of operation from which to monitor and capture data relevant to user application.
Action...
STEP 1: From the Basic Meter screen, press Next to display the different Monitoring Mode setups.
Result...
• Check to select your desired monitoring mode setup. Press
Next and go to page 5-19.
• Press Cancel to quit and return to Start menu.
MARK111
Monitoring mode descriptions
NOTE
Standard Power Quality, Demand, Energy optimizes the instrument to collect data for troubleshooting using standard power quality parameters, with numerous trigger conditions set.
Current Inrush is ideal for recording motor start-up and inrush conditions. This setting is used when recording is triggered on change in current with longer cycle-bycycle waveform capture than Standard Power Quality.
Fault Recorder is similar to Inrush but with a voltage trigger.
Long-term Timed Recording, Demand, Energy sets the instrument to use periodic measurements only. This setting is used for long-term statistical studies and benchmarking field-based equipment testing and evaluation. No triggers are set so only trended values are available.
Continuous Data Logging, Demand, Energy sets the instrument to log rms and power values once per second until memory is filled or for specified time period.
EN50160 Power Quality monitors and reports Quality of Supply (QOS) compliance as specified by the EN50160 standard. A full discussion on EN50160 is found on
Chapter 7 View Event Data - Section C Reports.
Users can override the default settings to customize the instrument to their application.
For the default settings of parameters in each monitoring mode, see Appendix B
Technical Specifications - Parameter Settings in Each Monitoring Mode on page B-10.
5-18
CH 5/ Start Menu
Advanced Options
Advanced setup options
After selecting a monitoring mode, the system is now ready to begin monitoring and to record data in card. Prior to actual monitoring, users have the option to accept the default threshold settings and proceed with monitoring, or to review and/or modify monitoring settings.
Action...
STEP 1: From the Choose
Monitoring Mode screen, select monitoring mode, then press Next to display Advanced Options.
Result...
The following screen will appear if the selected monitoring mode is non-EN50160:
• If the default settings for the specified monitoring mode are acceptable without change, press Next. Go to page 5-20.
• To review and/or modify default threshold settings, press the desired parameter on screen. Go to Chapter 6
Advanced Setup Options.
MARK112
• Press Cancel to quit and return to Start menu.
The following screen will appear if the selected monitoring mode is EN50160 Power Quality:
MARK112b
See Chapter 6 Advanced Setup Options for a detailed discussion of each threshold parameter displayed in the Advanced Options screen.
5-19
Site Name/Memory Card
Site Name/Memory Card
Where you can save data
PX5 uses the Compact Flash data card as primary storage for event, journal, and setup data. It automatically saves data in the card when monitoring is on. The Compact Flash card must be installed in either data card Slot 1 or Slot 2 in order to record data.
NOTE: Although PX5 is able to detect availability of data card in either slot, Dranetz-
BMI strongly recommends the use of only one card slot (one data card) at a time.
Data card size
PX5 requires a Compact Flash data card with minimum storage capacity of 32MB, maximum of 128MB. See Appendix A Optional Accessories for the part numbers of
Compact Flash cards supplied by Dranetz-BMI.
NOTE: Dranetz-BMI Compact Flash data cards have been tested to work properly with the PX5. Non-Dranetz-BMI Compact Flash cards may not be compatible with the instrument and cannot be supported by Dranetz-BMI Customer Service in case problems arise. Users are advised to use only Dranetz-BMI parts and accessories.
Filename
The following files are created on the data card: filename.set for setups template and
filename.ddb for saved events. The maximum allowable length for a site/file name is 32 characters.
Data card screen Before monitoring begins, the Site Name/Memory Card screen is displayed. The screen reports the current operational status of the data card.
MARK113
Data card status messages
The following messages may appear in the data card status line.
Status Message Description
Not Inserted
Empty
Contains File
Data card not inserted or not detected. Insert a valid data card to proceed.
Data card is empty.
Data card presently contains files.
5-20
Continued on next page
CH 5/ Start Menu
Data card status messages
(continued)
Status Message
Fragmented
Unformatted
Invalid Card
Description
A fragmented FAT was detected. Monitoring cannot proceed with a fragmented data card. Either change the data card or format to continue.
Data card is not formatted. Format the data card or replace with a different card to continue.
Data card is not valid for monitoring. Change the data card to proceed.
Data card operation
The data card screen prompts users to set filename and format card in preparation for monitoring and writing of data.
Action...
STEP 1: From the Advanced
Options screen, press Next to display data card status.
• If the default filename is acceptable without change, and if the card is formatted to save data, press Finish. The sytem is ready to begin monitoring. Go to Section C Monitor Same
Circuit - Turning Monitoring
On/Off on page 5-24.
• Press Change to enter a new site/file name. Proceed to Step
2 on page 5-22.
• Press Format card to format the data card.
NOTE: All data and setups stored in data card will be lost when you format the card.
Copy any files that you want to save to a computer first before formatting card.
• Press Memory Card Contents to view list of data files stored in card.
• Press Cancel to discard changes and return to Start
Menu.
Result...
MARK113
Continued on next page
5-21
Site Name/Memory Card, continued
Data card operation
(continued)
Action...
STEP 2: Enter a new site/file name using the onscreen keyboard. Press OK to accept the new site/file name.
Result...
• Press Shift to enter a character in uppercase.
• Press CAPS to enter all characters in uppercase.
• Press Space to enter a space in between characters.
• Press Clear All to delete the entire name on the space provided.
• Press .. .
.. .
to erase a character.
• Press Cancel to retain the default site/file name and return to Site Name/Memory Card screen.
MARK114
Writing setup template to data card
Saving setups template means writing current configurations and threshold setups to the data card. Configurations and setups include the following:
• Present circuit type
• Present scale factors
• Thresholds
• Waveform capture settings
• Interval for timed readings
• Site name
NOTE: The filename extension for the setup template is SET, i.e. filename.set.
5-22
CH 5/ Start Menu
Guidelines on file data transfer
PX5 treats the Compact Flash data card like a hard disk storing files in DOS format.
For successful card data transfer, keep the following points in mind:
• PX5 supports a maximum DOS directory size of 128MB. Minimum required
Compact Flash data card size is 32MB.
• Compact Flash cards allow users to store multiple files in one card. The Site name will be used as the filename for record files (i.e. if the site name is Power Xplorer
Site, the filename will be Power Xplorer Site00.DDB). A number is automatically appended to the name such that filenames are automatically incremented every time the user starts monitoring with that same filename.
• PX5 does not support file fragmentation. When creating a file, it will take the largest contiguous block and use that size block for data storage. Deleting files from the data card is NOT RECOMMENDED. When there is no more space available to begin new data storage, reformat the card using the PX5, after transferring data files to a computer.
5-23
Overview
Section C
Monitor Same Circuit
Overview
Introduction
Menu options for monitoring become available only after setting up the instrument or from reading a setup template from data card. Users can monitor the same circuit, and configure combinations of setups unique to their task applications.
Monitoring options
Users have the option to begin monitoring immediately or at a specified time and date.
The Monitoring Menu also allows users to do Advanced setups via the Modify Trigger
Parameters and Intervals option. Unlike the Automatic and Wizard setup procedures,
Advanced setup allows users to change parameters and enter new limits to capture events. A full discussion on modifying threshold settings is found in Chapter 6
Advanced Setup Options.
In this section
The following topics are covered in this section.
Topic
Turning Monitoring On/Off
Monitoring at a Specified Time and Date
See Page
5-25
5-28
Modify Trigger Parameters and Intervals 5-33
5-24
CH 5/ Start Menu
Turning Monitoring On/Off
Start/Stop monitoring
Follow these steps to start and end monitoring.
Action...
STEP 1: From the Automatic
Setup screen, press OK to start monitoring (see page 5-3). The
Monitoring Menu screen will be displayed.
OR
STEP 1: From the Start Menu screen (see page 5-2), press
Monitor Same Circuit.
NOTE: Monitoring Menu screen will only be available after setting up the instrument or from reading a setup template from card.
OR
STEP 1: At the end of the Wizard
Setup, the Site Name/Memory
Card screen prompts users to press Finish so as to start monitoring (see page 5-21). The
Monitoring Menu screen will be displayed.
• To start monitoring, press Start
Now! Proceed to Step 2 on page 5-26.
• To set monitoring at a specified date and time, press Monitor
using Start and End times. Go to page 5-28.
• To modify parameter settings, press Modify Trigger
Parameters and Intervals.
Proceed to page 5-33.
• To review the present setups, press View Setup Summary.
Proceed to Step 5 on page 5-27.
• Press Save Setup Template to
Card to write setups to card as template for future use.
• Press Exit to cancel and return to Home screen.
Result...
MARK121
Continued on next page
5-25
Turning Monitoring On/Off, continued
Start/Stop monitoring
(continued)
5-26
Action...
STEP 2: While the instrument is actively monitoring data, the message MONITORING
STATUS: ON appears on the top section of the Home screen (see
NOTE).
Result...
Users cannot change the time and date nor perform memory card operations while the instrument is actively monitoring data.
However, the rest of the function keys, including date style and clock style, are operable even while monitoring status is ON.
• To end monitoring, press Stop.
Proceed to Step 3.
MARK122
NOTE: The following status messages are displayed after monitoring is turned on.
MONITORING STATUS: ON (monitoring will continue until Stop is pressed or when specified end time is reached; START TIME and date are displayed while monitoring is on)
CIRCUIT TYPE: xxxxxx (default or user specified)
MEMORY CARD: x% (remaining space in the data card in percent)
FILENAME: User specified or Power Xplorer Site xx.ddb (where xx increments every time data is saved using the same file name)
EVENTS SAVED: xx (counter on the number of events saved to the data card; CYCLES SAVED appears instead of Events Saved if characterizer is set to None (Raw
Data) - see page 6-15)
JOURNALS LOGGED: xx (counter on the number of timed readings recorded)
STEP 3: Stop Monitoring Menu confirms whether users want to end monitoring, cancel monitoring, or view present setups.
• To turn monitoring off, press Stop
Now! This will save any pending data and close the file. Proceed to
Step 4 on page 5-27.
• To cancel monitoring, press
Abort. All data collected will be lost when monitoring is aborted.
• To view setups, press View
present setup. This does not change any monitoring parameters. Proceed to Step 5 on page 5-27.
• To continue monitoring, press
Exit.
MARK123
Continued on next page
CH 5/ Start Menu
Start/Stop monitoring
(continued)
Action...
STEP 4: When monitoring ends, the message MONITORING
STATUS: DONE appears on screen (see NOTES).
• To capture a new set of data or to edit threshold settings, press
Start/Setup. The Start Menu screen will be displayed. Go to page 5-2.
Result...
• To view recorded data, press
Trend, Events, or Reports. Go to Chapter 7 View Event Data.
MARK124b
NOTE 1: The message MONITORING
STATUS: DONE appears to indicate that monitoring is completed and active recording is disabled.
NOTE 2: The Events button will display data if periodic measurements at regular intervals are available or if thresholds have been crossed. See
Chapter 7 View Event Data.
STEP 5: Press View present setup to dislay the parameter settings in effect. Setup summary is available for review before, during, and after monitoring.
• Press Up/Down arrow keys to scroll the page up or down by one line.
• Press and drag the scroll bar to move the page up or down.
• When done reviewing the
Setup Summary, press Exit.
The screen will return to the
Stop Monitoring Menu options on page 5-26.
MARK123c
5-27
Monitoring at a Specified Time and Date
Monitoring at a Specified Time and Date
Schedule monitoring
Follow these steps to set monitoring at a specified time and date.
Action...
STEP 1: From the Automatic Setup screen, press OK to start monitoring (see page 5-3). The
Monitoring Menu screen will be displayed.
OR
STEP 1: From the Start Menu screen (see page 5-2), press
Monitor Same Circuit.
NOTE: The Monitoring Menu screen will only be available after setting up the instrument or from reading a setup template from the memory card.
OR
STEP 1: At the end of the Wizard
Setup, the Site Name/Memory Card screen prompts users to press
Finish so as to start monitoring (see page 5-21). The Monitoring Menu screen will be displayed.
• To set monitoring at a specified date and time, press Monitor
using Start and End times.
Proceed to Step 2.
Result...
For descriptions of the other buttons, refer to Section C Monitor
Same Circuit - Turning Monitoring
On/Off on page 5-25.
STEP 2: PX5 will monitor and collect data using either of the following monitoring schedules:
• Press Start & End time to specify the date/time when the unit will begin and end monitoring. See page 5-29.
• Press Time Interval to specify the length of the recording interval for each file, and the time/date to start monitoring interval. See page 5-32.
• Press
Cancel to quit and return to the monitoring menu.
5-28
MARK121
MARK125a
CH 5/ Start Menu
Monitoring using start & end time
You can specify the date and time when the unit will begin and end monitoring.
Action...
STEP 1: When monitoring using the Start & End time schedule, the current date and time (set to the next full hour) are displayed on screen.
• Start at: indicates the date and time when the unit will begin data monitoring.
• End at: indicates the date and time when the unit will stop data monitoring.
By default, the system will automatically end monitoring one week from the time/date monitoring starts. However, users are allowed to specify their own time/date when they want to stop monitoring.
For example: Set monitoring to -
Start at: Sept. 9, 2003; 12:00:00
End at: Sept. 9, 2003; 12:30:00
Press the End at: Date and Time keys and proceed to Step 2.
Result...
• Press OK to accept the settings and return to Home screen.
• Press Cancel to retain previous monitoring settings and return to Home screen.
STEP 2: Use the Date and Time function keys to set when monitoring will start and end.
• Press Date to enter desired month-day-year to start/end monitoring. Use the numeric keypad to enter the year.
• Press OK to accept changes in date settings. Continue with Step
2 on page 5-30.
• Press Cancel to discard changes in date and return to Monitoring
Control Menu.
MARK125b
MARK126
Continued on next page
5-29
Monitoring at a Specified Time and Date, continued
Monitoring using start & end time
(continued)
Action...
STEP 2 (continued):
• Press Time to enter desired hour-minute-second to start/ end monitoring. Press to select the hour/minute/second field to display the numeric keypad.
Use the keypad to enter time settings.
Result...
• Press OK to accept changes in time settings. Proceed to Step 3 on page 5-31.
• Press Cancel to discard changes in time and return to
Monitoring Control Menu.
MARK127
MARK129
MARK130
Continued on next page
5-30
Monitoring using start & end time
(continued)
Action...
STEP 3: The screen will display the new settings once the monitoring Start time/date and
End time/date have been set.
• Press the time and date function keys when you want to change time/date monitoring settings. Refer back to Step 2 on page 5-29.
Result...
• Press OK when done setting the Start and End monitoring time/date. Proceed to Step 4.
• Press Cancel to discard the changes in time/date monitoring settings and return to Monitoring Menu.
STEP 4: After specifying the Start and End time/date of monitoring, the message MONITORING
STATUS: ARMED appears on screen.
Armed means that the system will automatically begin monitoring at the specified Start time and date.
Once monitoring status is ON, follow the Start/Stop monitoring procedure found on page 5-26.
CH 5/ Start Menu
MARK131b
MARK132
5-31
Monitoring at a Specified Time and Date, continued
Monitoring at scheduled intervals
You can specify the date and time when the unit will begin monitoring, and choose from the following interval cycles when the unit will end recording and start a new file: daily, weekly, bi-weekly, or a customized number of days. Data monitoring will end when memory is full or when monitoring is stopped manually.
Action...
STEP 1: When monitoring using
Time Interval, the current date and time (set to the next full hour) are displayed on screen. Select the interval schedule on how often you want the unit to automatically end and start a new data file.
• Start at: Indicates the date and time when the unit will begin monitoring.
• Interval: Indicates the time period when the unit will automatically collect and download event data.
Result...
• Daily: Monitors data in 24-hour cycle and then starts a new file.
The unit will append the filename for data collected every 24 hours.
• Weekly: Monitors data in 7-day cycle and then starts a new file.
The unit will append the filename for data collected every 7 days.
• Bi-Weekly: Monitors data in
14-day cycle and then starts a new file. The unit will append the filename for data collected every 14 days.
• Custom: The user specifies the time period (in days) when the unit will end recording interval.
Press Change to set new time interval.
• Press OK to accept the settings and return to Home screen. The message MONITORING
STATUS: ARMED appears on screen.
Armed means that the system will automatically begin monitoring at the specified Start time and date.
• Press Cancel to retain previous monitoring settings and return to
Home screen.
MARK125c
MARK125d
5-32
CH 5/ Start Menu
Modify Trigger Parameters and Intervals
Advanced setups The Modify Trigger Parameters and Intervals screen allows users to turn on any available parameters and enter new threshold limits. Advanced Setup provides users wider control over all setup functions.
Action...
STEP 1: From the Monitoring
Menu screen, press Modify
Trigger Parameters and Intervals.
Result...
The following screen will appear if the selected monitoring mode is non-EN50160 (see page
5-17):
• Press a parameter if you want to review and/or modify its default threshold settings. Go to Chapter 6 Advanced Setup
Options for a detailed discussion of the various trigger parameters and intervals.
• Press Site Name to set new filename prior to data monitoring. The onscreen keyboard will appear (see page
5-22 for instructions on how to use the keyboard).
MARK136
The following screen will appear if the selected monitoring mode is EN50160 Power Quality (see page 5-18):
• Press Scale Factors to enter new scale factor values for
Volts/Amps channels. The
Scale Factor Setup screen will appear (see page 5-11 for instructions on how to enter a new scale factor value).
• Press Exit to quit and return to
Monitoring Menu.
MARK137
Refer to Chapter 6 Advanced Setup Options for a detailed discussion on modifying trigger parameters and intervals.
5-33
Overview
Section D
Load Setup Template from Card
Overview
Introduction
PX5 enables users to load saved setup template files (.set) from the data card.
NOTE: Loading a setup template from the card will overwrite your existing setup.
Loading saved setups
Action...
STEP 1: From the Start Menu, press Load setup template from card. PX5 lists the setup template files (.set) stored in data card, along with file size, time and date when the setup files were recorded. Setup files are arranged in the order of date and time they were recorded.
Result...
• Press Up/Down arrow keys to scroll the page up or down by one line.
• Press to select (highlight) the desired setup template file.
• Press OK to load setup template from card to PX5.
Proceed to Step 2.
• Press Cancel to quit and return to Start Menu.
STEP 2: The message Setup
Template Loaded appears once the setup is successfully loaded from the data card to the PX5.
• Press OK to exit. The
Monitoring Menu screen will appear and users can begin monitoring.
MARK138
MARK139
5-34
CH 5/ Start Menu
Section E
Load Data from Card
Overview
Introduction
Data files (.ddb) consist of events that are saved to the data card while monitoring is on.
PX5 allows users to load stored data files directly from the card.
In this section
The following topics are covered in this section.
Topic
Loading Data from Card
Card Error Messages
See Page
5-35
5-36
Loading data from card
Follow these steps to load data from card.
Action...
STEP 1: From the Start Menu, press Load data from card. PX5 lists the data files (.ddb) stored in memory card, along with file size, time and date when the data files were recorded. Data files are arranged in the order of date and time they were recorded.
Result...
• Press Up/Down arrow keys to scroll the page up or down by one line.
• Press to select (highlight) the desired data file.
• Press OK to load data from card to PX5 and return to Home screen.
• Press Cancel to quit and return to Start Menu.
MARK140
NOTE
If an error message is displayed, refer to Card Error Messages on page 5-36.
5-35
Card Error Messages
Card Error Messages
Error messages
The following error messages may be displayed.
Error Message
Card not inserted
Card not ready
Card read error
No files on card
Description
No data card inserted or inserted improperly.
The Compact Flash card controller is not ready. Try reinserting the data card.
The data contains errors or the file has an invalid version.
No valid data file on card.
5-36
C H A P T E R 6
Advanced Setup Options
Overview
Introduction
This chapter describes the options available to users with applications that require advanced setups. Although PX5 is designed to capture data no matter what the setup is, users are able to configure combinations of setups unique to their task applications.
Definitions
Setup: A pre-set condition of parameter thresholds and waveform capture settings for each channel that determines what will constitute an event and what waveform data will be saved when this event occurs.
Event: An event occurs when a pre-set or programmed threshold is crossed. Events result in a contiguous collection of cycles that is saved into memory. An event consists of pre-trigger cycle(s), trigger cycle(s), and post-trigger cycle(s).
Parameter threshold: A value that the PX5 compares to a measurement to decide if an event occurs. Also called a limit. For example, if the input voltage is measured as 135
Vrms, and the parameter threshold for voltage is 132 Vrms, PX5 saves this limit crossing to memory as an event.
In this chapter
This chapter covers the following topics:
Topic
Advanced Options Menu
Transient Limit
High Frequency Transients
Recording Transients
RMS Variation Limit
Waveform Capture
Characterizer Options
Journal Limit
Journal Interval for Timed Readings
EN50160 Power Quality (for strict EN50160 monitoring only)
See Page
6-2
6-3
6-4
6-5
6-9
6-14
6-15
6-16
6-21
6-23
6-1
Advanced Options Menu
Advanced Options Menu
Advanced menu settings
Advanced Options lists the threshold parameters available for review or modification.
PX5 allows users to customize threshold settings according to their task applications.
Action...
STEP 1: From the Choose
Monitoring Mode screen (see page 5-18), select monitoring mode, then press Next to display
Advanced Options.
• To review/modify limits for transient events, press
Transient Limit. Go to page
6-3.
• To review/modify limits for rms variations, press RMS
Variation Limit. Go to page
6-9.
Result...
The following screen will appear if the selected monitoring mode is non-EN50160:
• To review/modify trigger channels, press Waveform
Capture. Go to page 6-14.
• To select event characterizer, press Characterizer Options.
Go to page 6-15.
• To review/modify journal limit setups, press Journal Limit.
Go to page 6-16.
• To review/modify journal interval settings, press Journal
Interval. Go to page 6-21.
MARK112
The following screen will appear if the selected monitoring mode is EN50160 Power Quality:
• To review/modify threshold settings for EN50160 monitoring, press EN50160
Options. Go to page 6-23.
• Press Next to accept threshold settings for advanced setups and to display memory card screen. Go to page 5-20.
• Press Prev to return to the
Monitoring Mode screen. Go to page 5-18.
• Press Cancel to quit and return to Start Menu.
MARK112b
6-2
CH 6/ Advanced Setup Options
Transient Limit
Transient detection
Dranetz-BMI instruments label rms voltage or current variations as either sags (voltage or current decreases below low limit) or swells (voltage or current increases above high limit) as per IEEE 1159. Voltage disturbances which are shorter in duration than typical sags and swells are classified as transients. Two basic types of transients are:
1) impulsive transients characterized by very rapid changes in the magnitude of measured quantities and commonly caused by capacitors or inductors switching on line, loose wires, lightning, static, and power failures; and 2) oscillatory transients defined as a temporary, rapid discontinuity of the waveform. PX5 has extensive recording capabilities for low and medium frequency transients using the following trigger mechanisms:
• RMS difference cycle-to-cycle
• Crest or Absolute peak (Instantaneous)
• Waveshape cycle-to-cycle magnitude/duration variation
RMS variations
RMS stands for root mean square, a mathematical formula used to measure the average voltage and current behaviors. RMS variations result whenever voltage or current behaviors rise above or fall below the programmed thresholds. See RMS Variation
Limit on page 6-9 for more information on rms variations.
Absolute peak settings
The crest factor or instantaneous peak is the absolute peak sample value within one cycle. The instantaneous peak triggers on the absolute peak value of the entire waveform.
Waveform capture settings
Oscillatory transients are types of disturbances usually captured as waveshape faults.
PX5 captures pre-trigger and post-trigger waveform cycles. The waveshape fault triggering algorithm essentially compares the samples for each cycle to the corresponding samples from the previous cycle. If the samples differ by more than the threshold tolerance for a length of time exceeding window percent of the power frequency cycle, a waveshape fault is registered. A trigger occurs when either waveshape or rms deviation rise above the programmed thresholds. Waveshape trigger values include the magnitude and duration of the difference between the present and previous cycle.
Once a record trigger is detected, instantaneous waveform information is recorded for the prescribed voltage and current channel(s). Disturbance monitoring requires that voltage be continuously sampled, and recorded only if the signals exceed specified values. Waveshape changes are only triggerable for voltage transients as the current waveshapes are usually continually changing on a normally operating distribution system. However most types of disturbances require that current be recorded as well to help determine the source of the disturbance.
6-3
High Frequency Transients
High Frequency Transients
High frequency impulsive transient
High frequency detected transients uses special circuitry to detect and capture transients as small as 1 microsecond in duration. These transients can be positive and/or negative values above or below the low frequency waveshape.
PX5 is designed with the high speed sampling analog board that can capture voltage and current transients. Because these types of disturbances usually exhibit very narrow widths and fast rise and fall times, they are quickly damped by the system. They tend to be unidirectional when close to their source.
6-4
CH 6/ Advanced Setup Options
Recording Transients
Procedure to record transient disturbance
PX5 uses four different algorithms to detect and record transients:
• Peak or Instantaneous trigger magnitude
• High frequency negative/positive peak detectors magnitude
• Waveshape threshold duration or window
• Waveshape threshold magnitude or tolerance
Action...
STEP 1: From the Advanced
Options screen, press Transient
Limit.
• Press the limit field to change limit. Use the keypad to enter the instantaneous limit. This value is compared against the absolute value of each A/D sample of the V and I channel waveforms.
NOTE: Do not set this value to less than or equal to the peak of the normal waveform. For a sinusoidal waveform, the peak is 1.414 x the rms value.
Failure to do this will result in continuous triggering.
• Enable toggles whether this limit is enabled or disabled.
• Amps toggles between Volts and Amps.
• Press Group A B C to set identical limit value for
Channels A, B and C.
• Press Next to set the high frequency transient detectors.
Proceed to Step 2 on page 6-6.
• Press Cancel to discard changes and return to
Advanced Options menu.
Result...
MARK112_101
MARK112_102
Continued on next page
6-5
Recording Transients, continued
Procedure to record transient disturbance
(continued)
Action...
STEP 2: The high speed sampling analog board installed in PX5 enables it to detect high frequency transients.
Result...
• Press the limit field to change limit. Use the keypad to enter the high frequency limit.
• Enable toggles whether this limit is enabled or disabled.
• Amps toggles between Volts and Amps.
• Press Group A B C to set identical threshold value for
Channels A, B and C.
• Press Next to set the waveshape threshold duration.
Proceed to Step 3.
• Press Prev to return to the instantaneous peak transient screen.
• Press Cancel to retain previous high frequency limit and return to Advanced Options menu.
STEP 3: PX5 shows the “floating window” algorithm used for waveshape fault detection.
• Press limit field under
Threshold to change limit. Use the keypad to enter the threshold limit or tolerance. If the wave samples differ by more than the threshold tolerance for a time exceeding the duration or window percent of power frequency cycle, a waveshape fault is registered.
• Press limit field under
Duration to change limit. Use the keypad to enter the threshold duration or window.
6-6
MARK112_103
MARK112_104
Continued on next page
CH 6/ Advanced Setup Options
Procedure to record transient disturbance
(continued)
Action...
STEP 3 (continued):
Result...
• Enable toggles whether this limit is enabled or disabled.
• Amps toggles between Volts and Amps.
Previous Cycle with Floating W indow
• Press Group A B C to set identical waveform threshold duration values for Channels A,
B and C.
• Press Next to set the rms distortion waveshape limit.
Proceed to Step 4.
• Press Prev to return to the high frequency transient screen.
• Press Cancel to retain previous threshold duration and return to
Advanced Options menu.
Trigger
Present
Cycle
NOTE: The figure above helps illustrate the
“floating window” algorithm used for waveshape fault detection. This window is visualized on screen as sliding along a waveform, precisely one cycle behind the previous sample point, v i
. The height of the window defines a maximum allowable voltage deviation in magnitude. The width of the duration corresponds to a number of sample points, N. For each sample v i
, when compared to v i-1 cycle where the deviation in magnitude is outside the maximum allowable deviation, a counter is incremented. For each sample v i
that is within the maximum allowable deviation, the counter, if greater than 0, is decremented. If the count reaches N, a trigger occurs.
STEP 4: PX5 allows users to set rms distortion waveshape limit.
• Press the limit field to change limit. Use the keypad to enter the treshold limit beyond which rms voltage variations occur.
• Enable toggles whether this limit is enabled or disabled.
• Amps toggles between Volts and Amps.
• Press Group A B C to set identical rms threshold value for Channels A, B and C.
MARK112_105
• Press Next to set the transient waveform capture pre- and post-cycles setup. Proceed to
Step 5 on page 6-8.
Continued on next page
6-7
Recording Transients, continued
Procedure to record transient disturbance
(continued)
Action...
STEP 4 (continued):
• Press Prev to return to the cycle-to-cycle waveshape screen.
• Press Cancel to retain previous rms limit and return to
Advanced Options menu.
STEP 5: Select how you want to specify the number of waveform cycles to record before (Pre-) and after (Post-) the trigger cycle.
• Enable Use Default if you want to use the default waveform trigger cycle counts for transient events (Pre-trigger cycles = 1, Post-trigger cycles
= 2).
• Enable Set the same as RMS
Variation Wave Snapshot
Pre/Post Setting if you want to use the same waveform trigger cycle counts to capture transient events and rms events
(Pre-trigger cycles = 2, Posttrigger cycles = 2). See Step 3 of the Procedure to record rms variation on page 6-12.
• Press Finish to accept the new waveform capture cycle settings. The screen will return to Advanced Options menu.
• Press Prev to return to the rms distortion waveshape screen.
• Press Cancel to retain previous cycle counts and return to
Advanced Options menu.
Result...
MARK112_106
MARK112_107
Note on phase settings
Phase settings depend upon the wiring configuration or circuit type selected under
Setup New Circuit. For example, for wye circuits, Line-Neutral (L-N), Neutral-Ground
(N-G), and Line-Line (L-L) voltage limits can be set. For delta circuits, only L-L limits can be set.
6-8
CH 6/ Advanced Setup Options
RMS Variation Limit
RMS variation setup properties
RMS stands for root mean square, a mathematical formula used to compute the equivalent value of the voltage and current. Voltage and current changes are measured and checked against the programmed limits. Thresholds are set as high limits (threshold above the programmed limit) and low limits (threshold below the programmed limit).
RMS variations result whenever voltage or current rms value rise above or fall below the programmed threshold limits. The limits determine how sensitive the instrument should be (note that statistical and trending information is always captured regardless of the limit settings, so the user will never be without a data even if he/she did not set the limits to the ideal values).
PX5 allows users to set the limits for each of the triggers, as well as the amount of rms sample (cycles) to record before and after trigger cycle.
RMS trigger parameters
In order for the instrument to trigger on rms variation, any one of the measured quantities for which a trigger is enabled must go above the High Limit or below the
Low Limit for a period of at least one rms sample point (which are taken twice per cycle with a one cycle sliding integration window).
The disturbance end point is defined as the cycle when all channels for which triggers are enabled have come back within limits (plus hysteresis) for a minimum duration of
Cycles specified in range to end event. Until this criteria is met, any subsequent excursions beyond the thresholds are considered part of the original disturbance. To minimize the number of triggers recorded for a sequence of closely spaced disturbances, hysteresis is employed in both voltage and time for the begin-event and end-event thresholds.
NOTE: Hysteresis values assigned to limits are set by the system and not programmable by the user.
6-9
RMS Variation Limit
Procedure to record rms variation
The following parameters are required to define how an rms variation is triggered:
• Low Limit
• High Limit
• Cycles in range to end event
Action...
STEP 1: From the Advanced
Options screen, press RMS
Variation Limit.
• Press the threshold parameter
(High, Low, Very Low) to change/enable or disable threshold values. See Appendix
F Event Classification for definition of limit values.
Proceed to Step 2 on page 6-11.
Result...
• Press % of Nominal to display the base unit for entering thresholds. To enter limits in percent of nominal, check the
% of nominal checkbox. If unchecked, limits are entered in absolute values.
• Press Group A B C to set identical threshold values for
Channels A, B and C.
• Press Next to define the number of rms summary and rms waveform cycles to be saved. Proceed to Step 3 on page 6-12.
• Press Cancel to discard changes and return to
Advanced Options menu.
MARK112_201
MARK112_202
MARK112_206
Continued on next page
6-10
CH 6/ Advanced Setup Options
Procedure to record rms variation
(continued)
Action...
STEP 2: Press the High limit,
Low Limit, and/or Very Low
Limit field to display the numeric keypad used to set threshold values. Use the keypad to enter limits for the corresponding phase in the High limit, Low Limit, and Very Low Limit fields. RMS variation event occurs at the time one or more phases of voltage or current goes outside of the programmed limits. The event ends when all channels for which triggers are enabled have come back within the limits for the duration of the cycles specified to end event.
• Press Disabl to deactivate the limit field.
Result...
MARK112_211
NOTE 1: Parameter thresholds are best left disabled unless you have an application that specifically calls for them.
• Press OK to accept the new threshold limits for rms variation.
NOTE 2: The High limit must be set at least .1 higher than the Low limit for each active channel or the entered value will not be accepted.
• Press Cancel to discard changes and return to the rms
Variations Setup screen.
• When done entering limit values, close the keypad (press
OK or Cancel).
NOTE 3: Hysteresis values assigned to limits are set by the system and not programmable by the user.
Continued on next page
6-11
RMS Variation Limit, continued
Procedure to record rms variation
(continued)
Action...
STEP 3: Users can define the number of rms summary and waveform cycles to be saved before the start (pre-), after the start (post-start), and after the end
(post-end) of the event.
Result...
The Pre- and Post- trigger settings under Waveform Capture
(Cycles) specify the number of waveform cycles to record before, during, and after the event.
Although waveform cycle recording is enabled by default, users have the option not to record waveform cycles.
• Press Enable to turn waveform cycle recording on/off.
Press any Pre- or Post- trigger cycle field. Use the numeric keypad to enter the cycle counts for corresponding rms sample/ waveform cycle capture.
RMS Summary (Cycles):
• Press Pre-Trigger to set the number of cycles for Pre-event start rms samples. This setting is also used for Pre-event end cycles. Use the keypad to enter the number of cycles of rms samples to record before the event start trigger cycle.
• Press In-Out Post to set the number of cycles for Post-event start cycles. Use the keypad to enter the number of cycles to record after the event start cycle.
• Press Out-In Post to set the number of cycles for Post-event end cycles. Use the keypad to enter the number of cycles to record after the event end point.
6-12
MARK112_209
MARK112_212
Continued on next page
CH 6/ Advanced Setup Options
Procedure to record rms variation
(continued)
Action...
STEP 3 (continued):
Result...
Waveform Capture (Cycles):
These values can also be used for transient waveform capture.
Screen below shows sample changes in cycle settings:
• Press Pre-Trigger to set the number of cycles for Pre-event start waveform cycles. Use the keypad to enter the number of waveform cycles to be saved before the event start and event end cycles.
• Press Post-Trigger to set the number of cycles for Post-event end waveform cycles. Use the keypad to enter the number of waveform cycles to be saved after the event start and event end cycles.
MARK112_213
When done entering values, close the keypad by pressing OK to accept the new cycle count settings or Cancel to ignore changes and return to previous cycle settings.
• Press Finish to accept the new cycle count settings for rms variation.
• Press Prev to return to the
RMS Variation Limit screen.
• Press Cancel to retain previous cycle count settings and return to Advanced Options menu.
NOTE
The number of pre-trigger cycles for waveform capture should be less than or equal to the number of pre-trigger cycles for rms summary. The same applies to the post-trigger cycles.
6-13
Waveform Capture
Waveform Capture
Trigger channel setup
PX5 allows users to set the trigger channels/parameters for waveform capture.
Action...
STEP 1: The checked fields show the channels that will have waveforms recorded should a trigger occur. This cross-trigger function prevents recording of meaningless data from unused
(disabled) channels.
Result...
• Press to select the Volts or
Amps channel matrix. The channels selected for the matrix will be displayed. Each matrix assigns a different group to trigger and save. See NOTE describing the characteristics of each channel matrix.
MARK112_207
Check/Uncheck a channel field to enable/disable channel for waveform capture. Proceed to
Step 2.
NOTE:
First row channel selection: When individual
Volts (V
A
, V
B
, V
C
, V
D
) trigger, save waveform data for the checked channels under “Saved
Waveforms”.
• Press OK to accept new trigger channel settings and return to
Advanced Options menu.
I
Second row channel selection: When Amps (I
B
, I
C
, I
D
) trigger, save waveform data for the
A
, checked channels under “Saved Waveforms”.
• Press Cancel to retain previous trigger channel settings and return to Advanced Options menu.
Third row channel selection: When Volts phaseto-phase settings (V
A-B
, V
B-C
, V
C-A
) trigger, save waveform data for the checked channels under “Saved Waveforms”.
• Press Group A B C to set identical matrix for Channels
A, B and C.
STEP 2: Depending on the matrix selected, press to check/uncheck the trigger channel for waveform capture.
• Press Clear to reset channel matrix. The previous channel settings will be cleared.
MARK112_208
6-14
CH 6/ Advanced Setup Options
Characterizer Options
Event characterizer setup
Events will be characterized according to the measurement standard selected under the characterizer mode.
Action...
STEP 1: From the Advanced
Options screen, press
Characterizer Options.
PX5 measures event data in compliance with the criteria set by IEEE 1159 or IEC 61000-4-30
Class A.
• Check IEEE 1159 Standard or
IEC 61000-4-30 Standard to characterize event data. Check
None (Raw Data) if you do not want to characterize event data according to any measurement standard.
• Press OK to accept changes in characterizer setting and return to Advanced Options menu.
• Press Cancel to retain previous characterizer setting and return to Advanced Options menu.
Result...
MARK112_214
Refer to Appendix F Event Classification for information on the range of variations as per IEEE and IEC Standards.
6-15
Journal Limit
Journal Limit
Journal entry settings
PX5 allows power parameters to be trended using periodic readings that are stored in a journal. Statistical information is always captured regardless of the limit settings, so users will never be without a trend even if he/she did not set the limits correctly. The system collects data even when no disturbances occur by recording periodical statistical data (By Time).
Page 6-17 shows one example of how to set entries under the Standard - Basic parameter. The same procedure applies when setting entries under other journal parameters.
Page 6-18 features the list of journal parameters that can be trended.
Logging data by limits
Limit methods allow users to set the threshold units by which high and low limits of voltage trigger and current trigger are calculated. Thresholds are set in ranges with high limit (threshold above the normal range) and low limit (threshold below the normal range). The following threshold limits are used to trend journal parameters:
Very High: specifies an absolute limit for comparison that is higher than the high limit
High: specifies an absolute limit for comparison that is higher than the low limit
Low: specifies an absolute limit for comparison that is lower than the high limit
Very Low: specifies an absolute limit for comparison that is lower than the low limit
Deadband: specifies how much a value can change before another event is recorded
The Very high must be greater than High, Very low less than Low. Deadbands or sensitivity is used to record incremental changes in the parameter besides when limits are crossed. The hysteresis values assigned to limits are fixed and not programmable by the user. All limit values are used to determine if corresponding reporting or logging action should take place.
Logging data by time
PX5 is able to measure periodic samples as well as take snapshots of the voltage and/or current waveform. The Journal Interval menu (see page 6-22) allows users to set the time of how often the instrument will record power parameter values, demand and energy, harmonics, and flicker.
NOTE
Users can record data simultaneously by limits and by time. Make sure to enable the parameters to trend under Journal Categories and Journal Interval.
6-16
CH 6/ Advanced Setup Options
Sample journal parameter setup
Action...
STEP 1: From the Advanced
Options screen, press Journal
Limit. The Journal Categories screen will be displayed.
Press a category to display journal parameters and the limit setup menu. For example, press
Standard List to display the parameters under it. Proceed to
Step 2.
Result...
NOTE
MARK112_301
STEP 2: Press to select the journal parameter you want to set up.
• Press to select the applicable phase (A, B, C, D) or phase-tophase setting (A-B, B-C, C-A) where you want to set threshold limits.
• If you want to set threshold limits to capture data, press to check Enable. The limit fields will be activated to allow you to enter threshold values.
Press the limit field (Very
High, High, Low, Very Low,
Dead Band) to display the numeric keypad. Use the keypad to enter the limits for the corresponding phase.
• Press Exit to accept the new threshold limits for the journal entry.
• If you want to record periodical statistical data by time interval, select Journal Interval under
Advanced Options screen.
Refer to pages 6-21 to 6-22.
Repeat the same procedure to set entries for other journal parameters.
MARK112_301b
MARK112_302
6-17
Journal Limit, continued
Journal
Parameter List
The following parameters are available for trending under the Journal Limit Setup.
Refer to Appendix B Technical Specifications - Computed Parameters for the definition of parameters.
Basic
RMS
Voltage
RMS
Current
Frequency
Computed
Basic
Vector
Displacement PF
Arithmetic
Displacement PF
Residual
Current
Power
Active
Power
Apparent
Power
Standard List
Demand Energy Harmonics Flicker
Total Fund
Frequency
VAR
Net Current True Power
Factor
Displacement Power
Factor
Active
Power
Demand
Apparent
Power
Demand
Reactive
Power
Demand
RMS
Current
Demand
Watt
Hrs
VAR
Hrs
VA Hrs
Voltage
THD
Current
THD
RMS
Harmonic
Current
Harmonic
Power
Unsigned
Short
Term
Flicker
Slide
Long
Term
Flicker
Long
Term
Flicker
Total
Harmonic
Distortion
Voltage
THD (Fund)
Current
THD (Fund)
Voltage
THD (RSS)
Curernt
THD (RSS)
Total
Interharmonic
Distortion
Voltage TID
(Fund)
Current TID
(Fund)
Distortion
Telephone
Influence
Factor
Crest
Factor
Voltage TIF
(Fund)
Current TIF
(Fund)
Volts
Crest
Factor
Amps
Crest
Factor
Voltage TID -
(RSS)
Current TID -
(RSS)
Voltage TIF
(RMS)
Current TIF
(RMS)
TIF Current
Product
Power
Harmonic
Power
(Signed)
Harmonic
Power
(Unsigned)
Transformer
Transformer
Derating
Factor
Transformer
K Factor
Continued on next page
6-18
CH 6/ Advanced Setup Options
Journal
Parameter List
(continued)
User Specified Frequency
User Specified Volts
User Selected Voltage Harmonic 1
User Specified Amps
User Selected Current Harmonic 1
User Selected Voltage Harmonic 2
User Selected Voltage Harmonic 3
User Selected Voltage Harmonic 4
User Selected Current Harmonic 2
User Selected Current Harmonic 3
User Selected Current Harmonic 4
Sequence
Positive Sequence Voltage
Negative Sequence Voltage
Zero Sequence Voltage
Positive Sequence Current
Negative Sequence Current
Zero Sequence Current
Imbalance
Imbalance
V Imbalance (RMS/RMS Avg)
V Imbalance (S2/S1)
V Imbalance (S0/S1)
I Imbalance (RMS/RMS Avg)
I Imbalance (S2/S1)
I Imbalance (S0/S1)
Arithmetic Power
Arithmetic Sum PF
Arithmetic Sum DPF
Arithmetic Sum VA
Fund. Arithmetic Sum VA
Advanced Power
Vector Power
Vector Sum PF
Vector Sum DF
Vector Sum VA
Fund. Vector Sum VA
Continued on next page
6-19
Journal Limit, continued
Journal
Parameter List
(continued)
Peak Power
Peak Active Power
Demand
Peak Apparent
Power Demand
Peak Reactive
Power Demand
Peak Demand
Current
Advanced Demand
Predicted Demand Coincident Power Coincident Power
Factor
Predicted W
Demand
Predicted VA
Demand
Predicted VAR
Demand
VA Demand at
Peak Watt Demand
VAR Demand at
Peak Watt Demand
Watt Demand at
Peak VAR Demand
VA Demand at
Peak VAR Demand
Avg PF at Peak W
Demand
Avg PF at Peak
VAR Demand
Avg PF at Peak VA
Demand
VAR Demand at
Peak VA Demand
Watt Demand at
Peak VA Demand
Forward Fund. Freq. W Hrs
Forward Fund. Freq. VAR Hrs
Reverse Fund. Freq. W Hrs
Reverse Fund. Freq. VAR Hrs
Advanced Energy
6-20
CH 6/ Advanced Setup Options
Journal Interval for Timed Readings
Introduction
The Journal Interval screen allows users to define how often the PX5 saves data periodically, regardless of power quality disturbances and journal limits.
Definitions
Power Values
Power Values Interval - Power parameter values are based upon all cycles during a one second interval. Data is aggregated or summarized into min, max and avg values over the averaging period and stored at the end of the interval. Data measured include watts, power factors, as well as the one-second rms (not to be confused with the one cycle rms). Cyclic min, max and avg are based upon full cycle waveforms with a resolution of one half (1/2) cycle. They record the rms, crest, and waveshape parameters that are also used to capture a snapshot of the waveform. Note that if users did not set the thresholds for rms variations properly, the min, max and avg will still provide a record of what happened during the interval.
Waveform Snapshot- Contains properties that measure periodic sample or snapshot of the voltage and/or current waveform. Users are able to determine how often the instrument will record waveform snapshots by turning the function on or off.
Demand and Energy
Demand Sub-Interval and Sub-Intervals per Interval - Refer to the time interval used in calculating power demand values. Demand calculations are made every sub-interval on the values that occurred during the most recent Demand Interval. Values set for
Demand Sub-Interval must be an integer-divisor of the Demand Interval since the former applies when updating certain parameters of the latter.
Harmonics
Harmonics Journal Interval - Various harmonic parameters such as total harmonic distortion (THD), total interharmonic distortion (TID), and telephone influence factor
(TIF) can be trended using periodic readings that are stored in the journal. Depending on the harmonic journal interval set, the instrument records a sampling of the waveform synchronized to the fundamental frequency, to ensure accurate calculation of harmonic phase angles.
Flicker
Pst (Short Term) Interval - Pst is short term perceptibility, used to set the Pst calculation interval. Typical calculation is over a 10-minute interval, though users can specify Pst
Interval under Flicker.
Plt (Long Term) Interval - Plt is long term perceptibility, used to set the Plt calculation interval. Typical calculation is over a 2-hour interval, though users can specify Plt
Interval under Flicker.
The Plt interval must be an integer multiple of the Pst interval. Sliding Plt recalculates the Plt value at each Pst interval, rather than only at the Plt interval.
6-21
Journal Interval for Timed Readings, continued
Timed settings menu
The intervals for timed readings are user programmable.
Action...
STEP 1: From the Advanced
Options screen, press Journal
Interval. The Journal Interval menu will be displayed.
Press the parameter that you want to change. Each journal interval must be pressed repeatedly to display the available selection values.
Result...
• Selections for Power Values:
Power Values Interval: OFF,
1 SEC, 1 MIN, 2 MINS,
3 MINS, 5 MINS, 10 MINS,
15 MINS, 1 HR
Waveform Snapshot: OFF, ON
• Selections for Demand and
Energy:
Demand Sub-Interval (in
MINUTES): OFF, 3, 5, 10
Sub-Intervals per Interval:
OFF, 1, 2, 3, 4, 5, 6
• Selections for Harmonics:
Harmonics Journal Interval:
OFF, 30 SEC, 1 MIN, 2 MINS,
3 MINS, 5 MINS, 10 MINS,
15 MINS, 1 HR
• Selections for Flicker:
Pst (Short Term) Interval (in
MINUTES): OFF, 1, 2, 3, 5, 10,
15, 30
Plt (Long Term) Interval (in
HOURS): OFF, 1, 2, 3, 4, 8
• Press Finish to accept the new timed settings.
• Press Cancel to retain previous timed settings and return to
Advanced Options menu.
6-22
MARK112_401
CH 6/ Advanced Setup Options
EN50160 Power Quality (for strict EN50160 monitoring only)
Advanced setup options for
EN50160
EN50160 is a statistical analysis of power quality data based on the EN standard. The statistical package called Quality of Supply (QOS) is built into the PX5, with monitoring and setup protocols set to determine voltage measurement compliance required for EN50160 monitoring. The EN50160-required measurement parameters include Power Frequency, Supply Voltage Variations, Rapid Voltage Changes, Supply
Voltage Unbalance, Harmonic Voltage, Interharmonic Voltage, and Mains Signalling.
The monitoring site is said to be IN COMPLIANCE if the statistical value over one (1) week for the specified parameters is 95% or greater.
EN50160 Options setup allows users to define up to five mains signalling frequencies below 3 KHz. Users can also select pre-defined values for main voltage characteristics of electricity supplied by Low Voltage (LV) and Medium Voltage (MV) public networks.
NOTE
EN50160 is defined for the electricity supplied at the supply terminals, and does not deal with the supply system or consumer’s installation or electrical equipment itself.
Since the standard deals with the voltage characteristics which can be expected in public distribution networks, other aspects essential for supply quality (i.e. short circuit power) are not treated within the scope of the standard. EN50160 standard is applicable only under normal operating conditions of the supply system.
EN50160 optional settings
Action...
STEP 1: From the Choose
Monitoring Mode screen, select
EN50160 Power Quality, then press Next to display Advanced
Options for EN50160.
• If the default settings for the
EN50160 PQ monitoring are acceptable without change, press Next. The Site Name/
Memory Card screen will appear. See pages 5-20 to 5-23.
• To review and/or modify threshold settings for EN50160 monitoring, press EN50160
Options. Proceed to Step 2 on page 6-24.
Result...
• Press Cancel to quit and return to Start menu.
MARK112b
Continued on next page
6-23
EN50160 Power Quality, continued
EN50160 optional settings
(continued)
Action...
STEP 2: EN50160 Options allow you to define up to five frequency signals set in 5 Hz resolution.
Mains signalling compliance or non-compliance is determined by calculating/adding the status of each of the defined frequencies.
Result...
• To modify frequency settings for EN50160 monitoring, press the desired frequency field. Use the numeric keypad to enter new frequency values.
• Press to select from the following EN50160 monitoring voltage level: Leave as is (120
Vrms); Low Voltage (230
Vrms, +/-10%); Low Voltage
(230 Vrms, +10/-6%); Low
Voltage (230 Vrms, +6/
-10%); Medium Voltage
(11 kVrms). LV is defined
as <1kV nominal. MV is
1kV to 35kV nominal.
• Press to enable/disable miscellaneous option Islanded.
Islanded means isolated from the power grid. Islanded is disabled by default, indicating that the system being monitored is synchronized to grid.
• Press Next to accept changes in
EN50160 setup and return to the EN50160 Advanced
Options screen.
• Press Cancel to ignore changes in EN50160 setup and return to the EN50160 Advanced
Options screen.
MARK112c
MARK112d
Refer to Chapter 7 View Event Data - Section C Reports for a detailed discussion of the
EN50160 compliance bar charts and statistical reports.
6-24
C H A P T E R 7
View Event Data
Overview
Types of data display
PX5 offers a graphical, information-packed, and easy to navigate display of event data.
The firmware architecture of PX5 is designed to engage in various stages of acquisition, characterization, communication, and visualization of event data and journalled data. PX5 also does Quality of Supply or QOS compliance monitoring as specified by EN50160, which requires that measurement parameters must be within a specified percentage for 95% of the time.
Event: An event occurs when a programmed threshold is crossed. An event consists of pre-trigger cycle(s), trigger cycle (fault), and post-trigger cycle(s). A contiguous collection of cycles caused by events is recorded into memory. An event may also contain information about other channels depending on how the user sets up the application.
Trend: A trend is a graph of the value of one parameter and channel over time. Trends aim to show a macro view interface of timespan, trigger conditions, and channels of waveforms and rms that were recorded. Users can zoom in on trends for a more detailed view.
Reports: EN50160 and PQ Status report on data retrieved by the QOS functional components built into the PX5 firmware. Statistical data is calculated on seven parameters specified in EN50160 over one week interval to produce a PASS/FAIL decision of compliance. PQ Status displays the status summary for QOS using the annunciator panel. The color coded panel indicates whether or not the parameter is within limits and/or events have occured since the last time the panel was cleared. PQ
Status monitors QOS compliance on a continuous basis. The user may choose to clear or reset existing data on the panel and restart the time/date from which the panel will display status for journalled data and events.
View data icons
Events, Trend, and Reports are the icons used to view event data. All icons are accessible at the Home page.
The Events button will display event activity graphs, waveform display, event Detail magnification, and Options to change and/or add parameters/channels to plot. Buttons to view previous/next event and waveform/rms cycle display are also available.
NOTE: Event data becomes available while the instrument is monitoring or by loading a previously saved file from the data card. Otherwise, a status message appears indicating that there are no event data available to view.
Continued on next page
7-1
Overview, continued
View data icons
(continued)
The Trend button displays time plots or trend visualizations of journalled data. The parameters to plot consist of journal entries under the Journal Limit Setup (see pages
6-18 to 6-20). The Trend screen can display up to four plots, with a maximum of two parameters per plot. One parameter can have multiple channels to plot. Users have the option to enable/disable plot display, where display area will resize according to the number of plots enabled for display. The Trend screen also features a Zoom box, where users can expand or narrow the zoomed area via touch and drag. Users can select the trend coordinates to view in detail.
The Reports button allows users to view either the EN50160 or PQ Status reports on
QOS compliance. EN50160 displays the compliance statistical bar chart featuring the seven parameters required for determining QOS compliance: Power Frequency, Supply
Voltage Variations, Flicker, Supply Voltage Unbalance, Harmonic Voltage, Interharmonic
Voltage, and Mains Signalling. PQ Report uses the following measurement parameters:
Voltage rms, Frequency, Imbalance, Sags, Swells, Transients, Flicker, and Harmonics.
Downloading and viewing data on a computer
Event files stored in data card can also be viewed on the computer. Insert the card to a
Compact Flash card reader connected to the computer. No communication software protocol between PX5 and computer is necessary.
Dranetz-BMI NodeLink
®
and DranView
®
programs are required to retrieve event data in the computer. NodeLink
® transfers stored data from PX5 to a computer via a standard
RS-232 serial port, USB port, Ethernet, or modem connection. DranView
®
is a viewer and data analysis software that allows users to manage event data downloaded in the computer. See Section D - Downloading Events from PX5 to a Computer on page 7-38 for more information on NodeLink
®
and DranView
®
applications.
NodeLink
®
and DranView
® are owned and distributed by Dranetz-BMI. For pricing and availability, contact Dranetz-BMI Customer Service Department at (732) 287-3680 or
1-800-372-6832.
7-2
CH 7/ View Event Data
View data using
Events, Trend or
Reports
Follow these steps to display event data.
Action...
Result...
STEP 1: Events, Trend and
Reports are accessible from the
Home screen. Note that event data will be available for display while monitoring or upon reading a stored file from the data card.
A monitoring status message appears on the top section of the screen. Refer to Chapter 5 Start
Menu - Section C Monitor Same
Circuit on page 5-24 for the procedure on how to capture events by turning monitoring on.
• Press Events to view event list, graphs and waveform/rms display. Proceed to Section A -
Events on page 7-4.
• Press Trend to trend journal data and view time plots.
Proceed to Section B - Trend on page 7-15.
• Press Reports to view
EN50160 compliance status or
PQ status summary. Proceed to
Section C - Reports on page
7-20.
In this chapter
This chapter covers the following topics.
Section Topics
A
B
Events
Trend
C
D
Reports
Downloading Events from PX5 to a Computer
MARK002b
7-4
7-15
7-20
7-38
7-3
Overview
Section A
Events
Overview
What is displayed?
The event screen displays actual voltage or current waveforms that occurred when a certain threshold parameter was crossed. Event activity graphs, event list, waveform display, rms display, and time plots are visually interfaced showing event patterns and behaviors over threshold limits and time. The event screen also enables users to customize data plots, allowing users to change and/or add parameters/channels for each of the four plot areas. Zoom box features, wherein users can expand or narrow the size of a zoomed area via touch and drag, are also available for more thorough data analysis and interpretation. Users can select the number of waveform and rms cycles to view as well as display event textual summary as shown on pages 7-9 thru 7-11.
In this section
The following topics are covered in this section.
Topic
Event Data Display
Event Activity Graph
Event List
Event Detail
Event Options
See Page
7-5
7-6
7-7
7-9
7-12
7-4
CH 7/ View Event Data
Event Data Display
Event screen
The event screen will display an event activity graph, waveform detail, and buttons like
Detail magnification, Options to change and/or add parameters/channels to trend, buttons to view previous/next event, and RMS/Waveform toggle. From the Home screen, press Events. The following screen will be displayed: color coded blocks show triggered events in the record monitoring start time and date, monitoring end time and date
(or present time & date if monitoring is still on) trigger channels time, date, channel/ parameter, classification of displayed event event activity graph (p. 7-6) display event list (p. 7-7) event plot (p. 7-9) vertical axis for voltage plotted channels/ parameters
MARK500 view event detail display previous event toggle between waveform and rms display options to change/add parameter/channel to plot
(p. 7-13) display next event vertical axis for current event start and end time and date; horizontal axis time/division return to Home screen
NOTE: Event data is displayed only while monitoring or upon reading a stored file from the data card.
7-5
Event Activity Graph
Event Activity Graph
Event graph description
The event graph is located on the top section of the event screen (see page 7-5). Four timelines represent all events recorded from the time monitoring started. Events for voltage channels are displayed above the grid and current channels are displayed below the grid.
7-6
CH 7/ View Event Data
Event List
Event list description
Event list presents a summary of all captured events in the order that they occurred.
Each event contains a general heading indicating the time and date when the disturbance occured, the disturbance category, disturbance classification, and number of cycles of duration.
View event list
Follow these steps to access the event list. Note that event data becomes available only after monitoring has been turned on or upon reading a file from the data card.
Action...
STEP 1: From the Home screen, press Events. The down arrow button located on the top right section of the screen is used to access the Event List.
• Press the down arrow button to view the Event List screen.
Result...
The top section of the Event List screen features a summary description of the selected event
(in highlight).
Each entry is identified by the time and date when the event was captured, the color coded channel/ parameter of captured event, and the event classification.
• Press Up/Down arrow keys to scroll the page up or down by one line or press and drag the scroll bar to move the page up or down.
• Press to select (highlight) the desired event entry. Proceed to
Step 2 on page 7-8.
MARK501
MARK502
Continued on next page
7-7
Event List, continued
View event list
(continued)
Follow these steps to access the event list. Note that event data is displayed only while monitoring or upon reading a file from the data card.
Action...
STEP 2: The highlighted field indicates that the particular event entry has been selected.
Result...
• Press OK to view details of the selected event.
• Press Cancel to ignore event entry selection and return to the default event screen.
MARK503
MARK504
NOTE: The left and right arrow keys can be used to display previous/next event.
7-8
CH 7/ View Event Data
Event Detail
Event details
PX5 allows users to view events in graphic waveform/rms display. The Detail screen features zoom buttons to magnify event cycles, and a zoom box that users can resize via touch and drag. The Detail screen also allows viewing of events alternately in rms or waveform.
Horizontal axis
Auto-scaled to display all waveforms in file until range is narrowed by zoom in
.
Vertical axis
Auto-scaled to the minimum and maximum value within time range.
View event details
An event detail screen is generated for each event. The detail screen shows events in rms by default. Follow these steps to view event details.
Action...
STEP 1: From the Home screen, press Events. Events must already be loaded into memory to be available for display.
Result...
Use the event list to scroll through event entries OR use the left and right arrow keys to view previous/ next event display.
• Press Wave/RMS to toggle between waveform and rms display.
NOTE 1: The gray area marks the duration of the event displayed.
The dotted black lines indicate the start of event.
NOTE 2: The solid black lines in waveform display indicate high frequency sampling data. PX5 can detect and capture transients as small as 1 microsec in duration.
• Press Detail to use the zoom features and view waveform/ rms in detail. Proceed to Step 2 on page 7-10.
MARK505
MARK505b
Continued on next page
7-9
Event Detail, continued
View event details
(continued)
The magnification button allows users to select the number of waveform/rms cycles that they can zoom in. The Text button provides a color coded summary of event data.
Action...
STEP 2: A blue box showing the default zoomed area appears once the magnify button is pressed.
Result...
Touch any side of the zoom box to activate the drag function.
Touch and drag the sides of the zoom box to expand or narrow in on the waveform/rms cycle. The cycle duration (in seconds) of event covered in the zoom box is also displayed.
NOTE: The horizontal drag is locked between all graphs. This means the horizontal drag will apply consistently to all data plots. The vertical drag is independent by axis. Users have the option to lock/unlock the vertical drag.
• Press Lock Y if you want the vertical axis to apply consistently to all data plots.
• Press Unlock Y if you want to adjust the vertical axis differently for each data plot.
• Once the zoom area is determined, press the Magnify button once. Proceed to Step 3 on page 7-11.
MARK506b
MARK507b
Resize/move zoomed area by touching and dragging the sides of the zoom box.
7-10
MARK508b
Continued on next page
CH 7/ View Event Data
View event details
(continued)
Action...
STEP 3: The magnify buttons serve as zoom function keys, each of which feature a plus sign or a minus sign within.
Result...
• Press Zoom+ to display the zoomed area and view the event cycles in greater detail.
Users may repeatedly zoom in on a plot for up to seven (7) levels. To further zoom in on an event cycle, simply repeat the procedure on Step 1.
• Press Zoom-(n) to unzoom cycles display one increment at a time, where n is the counter of how many times the event cycles have been magnified.
MARK510b
• Use the Wave/RMS button to toggle between rms and waveform display.
NOTE: Pressing Wave will only display waveform data for channels that are enabled to record waveforms. For channels that do not have associated waveform data, the screen will maintain the format, but will leave the plot blank.
• Use the Text button to display the event threshold values and other details pertaining to the disturbance that occurred.
• Press Back to return to the event screen.
MARK519
NOTE: The event textual summary is color coded. Red indicates the threshold value(s) and parameter(s) that are out of limits. Green indicates the measurement parameters that are within limits.
7-11
Event Options
Event Options
Voltage and
Current channels to plot
A time plot is a graph of the value of one parameter and channel over time. PX5 is able to display time plots for individual Voltage and Current channels (Va, Vb, Vc, Vd, Ia,
Ib, Ic, Id) or phase-to-phase Voltage channels (Vab, Vbc, Vca), depending on the available channels for Voltage and the selected circuit type.
RMS trigger parameters
RMS variation is the most common type of disturbance and is identified as a specific type of event by IEEE and IEC. Event characterization implemented in PX5 adheres to the IEEE 1159 and IEC 61000-4-30 Class A standards (Refer to Appendix F Event
Classification). RMS values are updated at half-cycle rates, calculated over one cycle and compared against limits on a cycle-by-cycle basis. The high and low limits can be enabled and programmed individually for each phase and phase-to-phase value.
The following parameters are required to define how an rms variation is triggered:
Very Low limit
Low limit
High Limit
Cycles in range to end event
As per IEEE and IEC standards for multi-phase systems, the beginning of the voltage rms event occurs when any phase voltage goes outside the limits, and ends when all of the phases are within limits for an end-event number of cycles specified. This is only true for voltage, not current.
In addition, rms variations can have three stages of averaging or chart rates, which is particularly useful for long duration events to save memory in exchange for reduced resolution. This mode begins if the rms value remains out of limits for longer than the post-start number of cycles that were programmed.
Refer to Chapter 6 Advanced Setup Options for more information on rms variation limits.
What is displayed on a time plot?
A time plot consists of the timed and threshold waveforms for the parameter on display.
The instrument provides users Options to change and/or add parameters/channels to plot.
Channels
Voltage: A, B, C, D, A-B, B-C, C
-A
Current: A, B, C, D
7-12
CH 7/ View Event Data
View event options
Follow these steps to access event Options.
Action...
STEP 1: From the event screen, press Options.
Plot #s appear on the left side of the screen. Users have the option to enable/disable channels for any of the Plot #. The plot display area will resize according to the number of parameters/channels enabled/disabled for display.
Result...
• Press the Change button adjacent to the Plot # where you want to change and/or add parameters/channels to plot.
For example: Press Change adjacent to Plot #1. Proceed to
Step 2 on page 7-14.
• Press OK to accept changes and view new plot display.
• Press Cancel to ignore changes and return to the event screen.
MARK505
MARK511
Continued on next page
7-13
Event Options, continued
View event options
(continued)
Action...
STEP 2: Check the channels that you want to enable, uncheck those you want to disable.
Result...
For example, check to enable
Channel A-B Volts, in addition to
Channel A Volts for Plot #1.
• Press OK to accept parameter/ channel changes. Proceed to
Step 3.
• Press Clear if you want to reset channel selection.
• Press Cancel to ignore parameter/channel changes and return to the event screen containing the original plot.
Step 3: The parameter/channel changes are reflected in Plot #1.
• Press OK to accept changes and view event with the new configuration.
• Press Cancel to ignore parameter/channel changes and return to event screen with the original configuration.
NOTE: The event screen retains the present configuration every time it is accessed. The channel/ parameter configuration will reset to default anytime a new monitoring session starts.
7-14
MARK512
MARK513
CH 7/ View Event Data
Section B
Trend
Overview
Trend categories PX5 is able to display statistical trends or plots for the following parameter categories:
Standard: Parameters include basic volts and amps, displacement power factor, residual and net current, energy, harmonics, standard demand, and standard flicker. These power parameters are measured more accurately using a one (1) second interval, summarized by min, max and avg at the end of the interval.
Distortion TIF RMS, THD, Frequency: Parameters include voltage and current THD, voltage and current TID, voltage and current TIF rms, crest factor, signed and unsigned harmonic, and transformer factor.
User Specified Frequency: Users have the option to choose the numbers or range of harmonic frequencies to trend.
Imbalance: Parameters include positive, negative and zero sequence components for voltage and current.
Advanced Power: Parameters include power factor calculated using arithmetic and vector sums of the individual phases.
Advanced Demand: Parameters include peak power, predicted demand, coincident power, and coincident power factor parameters. These parameters measure the ratio of maximum demand of the power distribution system to the total connected load of the system.
Advanced Energy: Parameters include energy on per phase and total basis as well as in forward and reverse mode.
Advanced Harmonics: Voltage and current harmonics and interharmonics for each phase and neutral channel can be trended. Users can enter the number of harmonic frequencies to trend. Harmonics are measured in accordance with IEC 61000-4-7 Class
I.
NOTE: See pages 6-18 to 6-20 for the detailed list of parameters available for trending.
In this section
The following topics are covered in this section.
Topic
Trend Display
Trend Setup
See Page
7-16
7-17
7-15
Trend Display
Trend Display
What is displayed on a trend?
A trend consists of the timed and threshold waveforms for the parameter on display.
Users have the option to enable/disable a trend or plot display, wherein display area will resize according to the number of plots enabled for display. In addition, users have the option to enable/disable channels to trend in a select parameter. Each parameter can have one or multiple channels to plot.
The trend screen also features a Zoom box, wherein users can expand or narrow the size of a zoomed area via touch and drag. The zoom feature allows users to view trend coordinates of min, max and avg values in greater detail.
Sample trend screens
Sample screens below feature the same Voltage RMS parameter.
Example 1 - One Parameter, Multiple Channels plot: Voltage RMS parameter with enabled channels A (in red), B (in yellow), and C (in blue). The plot below has been zoomed in three times.
7-16
MARK443
Example 2 - One Parameter, One Channel plot: Voltage RMS parameter with enabled channel C (in blue). The plot below has been zoomed in five times.
threshold values
(Hi limit, Low limit) trigger parameter, trigger channel time and date when event was captured trend of max values trend of avg values trend of min values
MARK444
CH 7/ View Event Data
Trend Setup
Trend settings
Follow these steps to view data trends. The same procedure applies even when you select different journal categories to plot.
Action...
STEP 1: From the Home screen, press Trend.
Result...
• The default number of plots displayed in the trend screen is two. Press Param to show the current parameters and channels displayed on screen.
Proceed to Step 2.
• Press the Magnify button to use the zoom features and to view plot coordinates in detail.
• Press Exit to quit and return to
Home screen.
STEP 2: Individual plot numbers appear on the left hand section of the screen. Users have the option to change and/or add parameters/ channels to display.
• Press the parameter field that you want to change.
MARK431
For example: Press to change
Plot #2 - Parameter 1. Proceed to Step 3 on page 7-18.
• Press OK to accept changes and view plot display.
• Press Cancel to ignore parameter/channel changes and return to the screen containing the original plot.
MARK432
Continued on next page
7-17
Trend Setup, continued
Trend settings
(continued)
Action...
STEP 3: The Journal Categories allow users to select parameters/ channels to trend for display.
• Press the Disable button to clear the parameter display in
Plot #2 (from Example in Step
2). Proceed to Step 4.
• Users have the option to choose a journal category from which to select parameters/channels to plot.
For Standard List - RMS
parameters, see RMS Settings on page 7-19.
Result...
• Press Cancel to ignore changes and return to the previous screen.
STEP 4: Parameter/channels on
Plot #2 were disabled.
•
Press OK to accept changes and view new plot display. The plot area will resize according to the plot numbers enabled for display. (Whereas the original plot in Step 1 shows Plot #1 and Plot #2 on display, the screen auto-adjusts when parameters in Plot #2 were disabled.)
• Press Cancel to ignore parameter/channel changes and return to the screen containing the original plot.
7-18
MARK433
MARK434
MARK435
CH 7/ View Event Data
RMS settings
PX5 provides setup options to measure rms data per cycle or per second.
The RMS Voltage and RMS Current parameters are available under Journal Categories
- Standard List.
MARK436
MARK514
Cyclic RMS: RMS values are computed over 1 power frequency cycle (16.67 msec @
60 Hz) in 1/2 cycle steps (every 8.33 msec). The min/max/avg of these cyclic values are continually updated and saved every user-programmed journal interval (see Chapter
6 Advanced Setup Options - Journal Interval for Timed Readings on page 6-21).
1-Sec RMS: Similar to cyclic rms, except that each rms value is computed over 1 second’s worth of data points (which is 1/60th of a second @ 60 Hz), rather than over 1 cycle.
NOTE: Data for Cyclic or 1-Sec sampling rates apply only to rms parameters.
7-19
Overview
Section C
Reports
Overview
QOS compliance reports
PX5 is designed with a Quality of Supply or QOS statistical package that analyzes and determines voltage measurement compliance, while maintaining the power quality diagnostic capabilities expected from Dranetz-BMI. The QOS compliance monitoring functionality of PX5 is optimized to ensure error-free setup and reporting for EN50160 applications. PX5 also features a PQ Status report summary for QOS via a color coded annunciator panel.
View Reports options
Users have the option to view QOS compliance reports in two ways: via EN50160 or
PQ Status. Each report has their own method of presenting compliance data. Each also differs on the length of evaluation period to monitor compliance. From the Home screen, press Reports.
7-20
MARK470b
EN50160 displays statistical reports on QOS compliance. Statistical data is calculated on the required parameters specified in EN50160 over a one week interval to produce a
PASS/FAIL decision of compliance. The standard monitoring period is one complete week, beginning Sunday 00:00 (midnight). Monitoring periods of less than one week will render an evaluation status that is Incomplete and compliance marked as
Undetermined. Press EN50160 to access the EN50160 statistical reports. See page
7-22.
PQ Status uses a color coded annunciator panel to show a quick status summary of
QOS parameters. PQ Status monitors compliance continuously, until the user chooses
Continued on next page
CH 7/ View Event Data
View Reports options
(continued)
to clear or reset existing data on the panel and restart the time/date from which the panel will display status for journalled data and events. PQ Status automatically displays the time and date since the panel was last cleared. Each parameter on the annunciator panel is linked to a time plot that shows what the values of each of the parameters were over the interval, and at what time did they exceed limits. The plot shows actual voltage or current waveforms that occurred when a certain threshold parameter was crossed. Press PQ Status to access the PQ Status summary report. See page 7-35.
In this section
The following topics are covered in this section.
Topic
EN50160
EN50160 Compliance Limits
Compliance Statistical Bar Chart
Compliance History
Event Statistics
Min/Max Table for Power Frequency and RMS Voltage
PQ Status
PQ Status Trend Display
See Page
7-22
7-24
7-27
7-30
7-32
7-34
7-35
7-36
7-21
EN50160
EN50160
What is
EN50160?
EN50160 monitoring mode
EN50160 is a European standard that stipulates the voltage characteristics that can be expected in public distribution networks. The QOS functionality is equipped with monitoring and setup protocols to meet the measurements required for EN50160 monitoring. EN50160 specifies that various parameters must be within a specified percentage for 95% of the standard one week monitoring period.
EN50160 will be able to display data when the instrument has been configured to monitor EN50160 Power Quality. Refer to Chapter 5 Start Menu - Section B Wizard
Setup - Monitoring Mode on page 5-18 for the procedure on how to turn EN50160
Power Quality monitoring on.
EN50160 measurement parameters
Statistical data is calculated based on the parameters required by EN50160 for determining QOS compliance. PX5 displays the parameters in the form of a
Compliance Statistical Bar Chart. From the Reports screen, press EN50160.
7-22
MARK471
The bar chart indicates the percentage of the intervals passing the specified compliance criteria. The color of the bar indicates the compliance status. A green bar indicates that the parameter is within compliance. A red bar indicates that the parameter does not comply with EN50160 Standard. See below for the description of each measurement parameter. For the QOS compliance limit values of EN50160 parameters, refer to the table of Compliance Limits on page 7-24.
Power Frequency: In case of a fault operation, parts of an interconnected system may become isolated. Compliance will be assessed over an observation period of one week, by a statistical analysis carried out over the sequence of 10 seconds measurement.
Frequency is represented by a single value and a single bar. The bar is a hyperlink to the
Power Frequency Graph (see page 7-27).
Continued on next page
CH 7/ View Event Data
EN50160 measurement parameters
(continued)
Supply Voltage Variations: Under normal operating conditions, load changes cause variations of the 10 minute average supply voltage. Generally this is compensated by automatic voltage regulation within a period of a few tenths of seconds. Supply Voltage
Variations display a cluster of bars, one for each phase. The color of each bar indicates the compliance status for its phase. A green bar indicates that the parameter is within compliance. A red bar indicates the parameter does not comply with EN50160.
Flicker: Typical rapid voltage changes or flicker do not exceed a magnitude of +5% or
-5% of the nominal or declared voltage. This limitation is possible because connection of loads capable of creating rapid voltage changes is usually subjected to regulations.
However under certain conditions, higher values of up to 10% may occur. These higher values can occur for instance in areas where high power motor equipment (blower, pumps, compressors, etc.) is used. Flickers display a cluster of bars, one for each phase.
The color of each bar indicates the compliance status for each phase. A green bar indicates that the parameter is within compliance. A red bar indicates that the parameter does not comply with EN50160.
Supply Voltage Unbalance: The unbalance of a three phase supply voltage consists of a loss of symmetry of the phase voltage vectors (magnitude and/or angle), created mainly by unbalanced load. Compliance is verified when 95% of the sequence of valid 10 minute values are within the specified tolerance of normally 2% (in single phase/two phase supplies 3%). Supply Voltage Unbalance is represented by a single value and a single bar. The color of the bar indicates the compliance status for each phase. A green bar indicates that the parameter is within compliance. A red bar indicates that the parameter does not comply with EN50160.
Harmonic Voltage: Harmonic displays a cluster of bars, one for each phase. The color of each bar indicates the compliance status that is calculated by adding the status of
Total Harmonic Distortion (THD) and Harmonics 2 thru 25. The bars for Harmonic
Voltage is a hyperlink to the Harmonic graph (see page 7-27).
Interharmonic Voltage: Interharmonic displays a cluster of bars, one for each phase.
The color of each bar indicates the compliance status that is calculated by adding the status of Total Interharmonic Distortion (TID) and Interharmonics 2 thru 25. The bars for Interharmonic Voltage is a hyperlink to the Interharmonic graph (see page 7-27).
Mains Signalling: Mains Signalling is represented by a single value and a single bar.
The color of the bar indicates compliance status that is calculated by adding the status of each of the defined frequencies (a maximum of five) for its phase. Users can specify the signalling frequency values under Advanced Options (see Chapter 6 Advanced
Options for EN50160 Power Quality on pages 6-23 to 6-24). A green bar indicates that the parameter is within compliance. A red bar indicates that the parameter does not comply with EN50160.
7-23
EN50160 Compliance Limits
EN50160 Compliance Limits
Compliance limits
The table below indicates the limit numbers or range of values required for each parameter to pass QOS compliance and satisfy EN50160 standard.
Parameter Limits for QOS Compliance to Pass
Un = Low Voltage (LV) Supply nominal voltage, upper limit 1kV
Uc = Medium Voltage (MV) Supply Characteristics - declared voltage, range 1kV to 35kV
Power frequency with synchronous connection to an interconnected system
•
•
Mean value over 10 seconds
±
1% during 95% of one week
±
4% during 100% of one week
Power frequency with no synchronous connection to an interconnected system
Magnitude of the supply voltage
(In low voltage systems, declared and nominal voltage are equal)
Supply voltage variations (Under normal operating conditions, excluding situations arising from faults or voltage interruptions)
Flicker
Supply voltage dips
•
•
Mean value over 10 seconds
•
±
2% during 95% of one week
•
•
±
15% during 100% of one week
Mean rms over 10 minutes
±
10% of Un or Uc during 95% of one week
±
10% to 15% of Un during 100% of one week
Mean rms over 10 minutes
±
0% of Un or Uc during 95% of one week
• ±10% to 15% of Un during 100% of one week
Plt < 1 for 95% of the time
Also 5% normal, 10% infrequent for LV, 4 &6 for
MV
No criteria specified, just reported in DISDIP table
<1 second for 70% of the short interruptions Short interruptions of the supply voltage
Temporary power-frequency overvoltage between live conductors and earth
Transient overvoltages between live conductors and earth
Supply voltage unbalance
(Under normal operating conditions)
1.5kV for LV
170% for solid or impedance earth,
200% unearthed of resonate earth
Short duration surges: <1 us
Medium duration surges: >1 to <100 us
Long duration surges: >100 us
10 minute mean rms values of the negative phase sequence component/positive phase sequence component
• <2% during 95% each period of one week
Continued on next page
7-24
CH 7/ View Event Data
Compliance limits
(continued)
The table below indicates the limit numbers or range of values required for each parameter to pass QOS compliance and satisfy EN50160 standard.
Parameter Limits for QOS Compliance to Pass
Un = Low Voltage (LV) Supply nominal voltage, upper limit 1kV
Uc = Medium Voltage (MV) Supply Characteristics - declared voltage, range 1kV to 35kV
Harmonic voltage
(Under normal operating conditions)
Interharmonic voltage
10 minute mean rms values
Individual Harmonic voltage up to the 25th shall be < the value of Un given under Harmonic
Compliance Limits (see table below) during 95% of one week
• <8% THD (THD up to the 40th) < 8
Individual Interharmonic voltage up to the 24th-
25th shall be < the value of Un given under
Interharmonic Compliance Limits (see table on page 7-28) during 95% of one week
• <8% TID (TID up to the 39th/40th)
Mains signalling voltage on the supply voltage
3 second mean of signal voltages compared against the Meister curve
Harmonic compliance limit values
The general approach of EN50160 is to express all voltage characteristics by reference to the nominal voltage or declared voltage, as appropriate. The table below indicates the Harmonic Compliance Limit values in relation to the nominal voltage.
Limit Harmonic Number
DC
2
3
4
5
6 thru 24 (all even nos.)
7
17
19
21
23
25
9
11
13
15
2.0%
5.0%
1.0%
6.0%
0.5%
5.0%
1.5%
3.5%
3.0%
0.5%
2.0%
1.5%
0.5%
1.5%
1.5%
Continued on next page
7-25
EN50160 Compliance Limits, continued
Interharmonic compliance limit values
The general approach of EN50160 is to express all voltage characteristics by reference to the nominal voltage or declared voltage, as appropriate. The table below indicates the Interharmonic Compliance Limit values in relation to the nominal voltage.
Interharmonic Group Number
8-9
9-10
10-11
11-12
12-13
13-14
14-15
15-16
DC-1
1-2
2-3
3-4
4-5
5-6
6-7
7-8
16-17
17-18
18-19
19-20
All other groups
Limit
3.4%
3.2%
3.0%
2.8%
2.6%
2.4%
2.2%
2.0%
5.0%
4.8%
4.6%
4.4%
4.2%
4.0%
3.8%
3.6%
1.8%
1.6%
1.4%
1.2%
1.0%
7-26
CH 7/ View Event Data
Compliance Statistical Bar Chart
Chart description
The Compliance Statistical bar chart displays the seven parameters that are required for determining QOS compliance. See pages 7-22 to 7-23 for the description of each of the
EN50160 parameters. The bar chart indicates the percentage of the interval passing the specified compliance criteria. The color of the bar indicates compliance status. Select bars in the chart i.e. Power Frequency, Harmonic Voltage, and Interharmonic Voltage will further display component details when pressed.
View
Compliance
Statistics bar chart
Follow these steps to access the EN50160 Compliance Statistical Bar Chart.
Action...
STEP 1: From the Home screen, press Reports. Press EN50160 to display the EN50160 statistical reports.
Result...
The Compliance Statistics bar chart displays the parameters required for determining compliance. A green bar indicates that the parameter is within compliance. A red bar indicates that the parameter does not comply with EN50160.
Select bars will show component detail when pressed.
• Press the Power Frequency
bar to view the Power
Frequency Graph. Proceed to
Step 2 on page 7-28.
• Press the Harmonic Voltage
bar to view the Harmonic
Graph. Proceed to Step 3 on page 7-28.
• Press the Interharmonic
Voltage bar to view the
Interharmonic Graph. Proceed to Step 4 on page 7-29.
• Press History to view the
Compliance History table. Go to page 7-30.
MARK471
Continued on next page
7-27
Compliance Statistical Bar Chart, continued
View
Compliance
Statistics bar chart
(continued)
Action...
STEP 1 (continued):
• Press DISDIP to view the
Event Statistics. Go to page
7-32.
• Press Min/Max to view the min/max values for Power
Frequency and RMS Voltage.
Go to page 7-34.
• Press Exit to quit and return to
Home screen.
STEP 2: The Power Frequency parameter has two ranges considered for compliance. This graph displays the status of parameter with respect to each range. The bar chart indicates the percentage of intervals passing the specified compliance.
• Press Exit to return to the
Compliance Statistical bar chart.
Result...
STEP 3: The Harmonic graph displays the status of each of the individual harmonics and THD for each phase. The bar chart indicates the percentage of intervals passing the specified compliance.
• Press Prev/Next to display
Harmonic bars from 1st to
25th.
• Press Exit to return to the
Compliance Statistical bar chart.
7-28
MARK478
MARK479
Continued on next page
CH 7/ View Event Data
View Compliance
Statistics bar chart
(continued)
Action...
STEP 4: The Interharmonic graph displays the status of each individual Interharmonic and TID for each phase. The bar chart indicates the percentage of intervals passing the specified compliance.
Result...
• Press Prev/Next to display
Interharmonic bars from 1st to
25th.
• Press Exit to return to the
Compliance Statistical bar chart.
NOTE
MARK480
Many instruments used for harmonic measurements of power supply systems express their output with reference to the fundamental component of the voltage, especially those indicating the THD factor.
Harmonic and Interharmonic values are specified only up to order 25 (EN50160 limit), for the practical reason that for higher orders, the values are generally so small as to be impractical to measure. Another reason is because of the difficulty of giving values which would be relevant to all networks.
7-29
Compliance History
Compliance History
QOS Status
Summary
EN50160 provides a historical summary of the QOS compliance evaluations made. The standard monitoring period is one week, usually beginning Sunday at 00:00 (midnight).
Any compliance evaluation performed in less than one week will receive an Evaluation
Status marked as Incomplete, and Compliance marked as Undetermined. For completed monitoring periods, Compliance status may either be PASS or FAIL if all of the specified parameters is within limits for 95% or more of the monitoring time period.
A PASS or FAIL status is hyperlinked to the Compliance Statistical Bar Chart.
Compliance
History table
Compliance History displays a table that summarizes the QOS evaluation status. From the EN50160 screen on page 7-22, press History. The Compliance History table will appear as shown below.
7-30
MARK472 scroll through previous/ next items in the list
PASS (green) or FAIL (red) status is linked to the Compliance Statistical Bar Chart (p. 7-27)
Evaluation Status: The EN50160-specified compliance evaluation period is a 7-day
(one week) period. The evaluation status is Complete if monitoring is done within one full week, or Incomplete if monitoring is done in less than one week. An evaluation status is Incomplete under the following scenarios:
• It is the current evaluation period and it has simply not completed.
• It is a previous evaluation period but not enough data samples were included in the statistical analysis. This may be due to the following reasons: data was not collected or too many samples were tagged as unusable due to rms variations.
Continued on next page
CH 7/ View Event Data
Compliance
History table
(continued)
Evaluation Period: Displays the date and time of the beginning of the evaluation period.
Each evaluation period is independent of each other. The default length of evaluation period is a 7-day week period by which the unit calculates information in strict compliance with the EN50160 standard.
Compliance: Displays a PASS (green) or FAIL (red) mark if evaluation is done for a complete 7-day week period. Compliance displays an Undetermined (black) mark for incomplete periods. A PASS or FAIL compliance status is hyperlinked to the
Compliance Statistical Bar Chart that shows the seven parameters required for determining compliance. See Compliance Statistical Bar Chart on page 7-27.
RMS Event Count: Details of rms variation event count are shown in the EN50160
DISDIP table on page 7-32.
Transient Event Count: The complete table for Transient Overvoltages appears in the
EN50160 DISDIP table on page 7-33.
7-31
Event Statistics
Event Satistics
EN50160
DISDIP
The EN50160 DISDIP (distribution of dips) table is based upon the event statistics calculated by EN50160. It includes the UNIPEDE DISDIP Statistics and the table for
Transient Overvoltages. UNIPEDE DISDIP data is collected and saved on a weekly basis with the counts reset as the final save occurs. If additional data is detected for an evaluation period after that period has been saved, that internal data is retrieved and updated.
UNIPEDE
DISDIP
Statistics table
RMS variations shown in the UNIPEDE DISDIP table is a filtered version of the Event list. The DISDIP table includes those events of rms variation type (sags, swells, and interruptions). From the Compliance Statistics bar chart screen on page 7-27, press
DISDIP. The UNIPEDE DISDIP Statistics table will appear as shown below.
7-32
MARK473
Display table for Transient
Overvoltage (p. 7-33)
Display DISDIP 3D
Graph (p. 7-33)
RMS Event Count: The table shows rms variations of specified range of magnitude and duration, also called bins. For example, an rms variation with a magnitude of 80-90% of nominal and 1-5 cycles in duration is one bin, whereas 80-90% and 10-30 cycles is another, 70-80% and 10-30 cycles is another, and so on. Each time that the characteristics of an rms variation match the criteria of the bin, the counter is incremented. RMS phenomena are typically found in bin groupings such as:
• DIPS - classified in 5 Magnitudes x 8 Durations
• Interruptions - classified in 1 Magnitude x 8 Durations
• Temporary Overvoltages - classified in 5 Magnitudes x 8 Durations
Continued on next page
CH 7/ View Event Data
UNIPEDE
DISDIP
Statistics table
(continued)
The DISDIP table also includes those events of Transient type. Scroll down the next page of the UNIPEDE DISDIP Statistics table to display data for Transient
Overvoltage as shown below.
MARK474
Display table for RMS
Events (p. 7-32)
Display DISDIP 3D graph (see below)
Transient Event Count: Transient phenomena are typically found in bin groupings such as:
• Transient Overvoltage - classified in 5 Magnitudes x 1 Count
The EN50160 DISDIP 3D Graph is an object representation of the table for rms variations found in page 7-32. The graph offers a quick and visual way to see what category most of the rms disturbances fall into, whether as Dips, Interruptions, or
Temporary Overvoltages.
Display table for RMS
Events (p. 7-32)
Display table for Transient
Overvoltage (see above)
MARK475
7-33
Min/Max Table for Power Frequency and RMS Voltage
Min/Max Table for Power Frequency and RMS Voltage
Min/Max table
The Min/Max table displays the minimum and maximum values for Power Frequency and RMS Voltage along with the time and date of occurrence. Maximum phase values of Rapid Voltage Change, Flicker, Supply Voltage Unbalance, and Harmonic are also displayed along with time and date of occurrence.
From the Compliance Statistics bar chart screen on page 7-27, press Min/Max. The
Min/Max table will appear as shown below.
MARK476 press to show Harmonic values up to order no. 25
MARK477
7-34
CH 7/ View Event Data
PQ Status
PQ report on annunciator panel
The PQ status summary report is displayed using the color coded annunciator panel.
The measurement parameters used to determine QOS compliance are similar to the parameters used in EN50160. See Appendix F Event Classification for the range of values required for each parameter to fall within the limit and be in compliance. From the Reports screen, press PQ Status.
MARK471d
NOTE: The three values reported within a red or green square in the PQ Report screen refer to measurements on channels A, B, and C respectively. The measurement values for each channel are updated approximately once per second while monitoring is on.
Evaluation Period: The start time and date of compliance monitoring appear on the top right section of the screen (Since: hh/mm/ss, mm/dd/yy). PQ Status monitors QOS compliance on a continuous basis. The user may choose to press Clear to reset the annunciator panel data and restart the time/date from which the panel will display status for journalled data and events. PQ Status automatically displays the time and date since the panel was last cleared.
Compliance: The annunciator panel is color coded such that green indicates the parameter is within limits and/or no events have occurred since the last time the panel was cleared. Red indicates the parameter is out of limits and/or events of that type have occurred since the panel was last cleared. Each parameter on the panel is hyperlinked to a trend display that shows the values of each of the parameters over the interval, and the time they exceeded limits. The plot shows actual voltage or current waveforms that occurred when a certain threshold parameter was crossed. Users also have the option to enable/disable channels to plot.
7-35
PQ Status Trend Display
PQ Status Trend Display
PQ report data plot
PQ Status parameters use periodic readings stored in a journal. See Section B - Trend on page 7-15 for the description of the journal categories available for trending. The following procedure describes how to view a parameter status display. The same procedure applies even when you select different journal categories to plot.
Action...
STEP 1: From the Home screen press Reports. Select PQ Status to display the QOS summary report via the annunciator panel.
Proceed to Step 2.
Result...
7-36
MARK491b2
STEP 2: The panel is color coded.
Green indicates the parameter is within limits and/or no events have occurred since the panel was last cleared. Red indicates the parameter is out of limits and/or events have occurred since the panel was last cleared.
Press to select the parameter that you want to view in detail.
For example: Press Imbalance to view data trend. See sample illustration on page 7-37.
MARK491c
• Press Clear if you want to reset existing data on the panel and restart monitoring at a new time/date. The reset panel time and date appear on the top right section of the screen.
NOTE: An activity indicator periodically appears in the middle of the screen signifying that data monitoring is on and the unit is actively characterizing events.
• Press Exit to quit and return to
Home screen.
Continued on next page
PQ report data plot (continued)
Action...
FOR EXAMPLE:
Coordinates for Voltage
Unbalance event are displayed on screen.
Result...
NOTE: Imbalance is the rms deviation calculation per channel if the instrument is in Standard
PQ Mode. It will display the
ANSI definition of unbalance for channels A, B and C if the selected monitoring mode is other than EN50160. When monitoring under EN50160 mode, Imbalance will be a simple value as per IEC definition, defined as the sum of negative sequencing components divided by the sum of positive sequencing components (similar to meter readings under Meter
Mode).
• Press the Magnify button to use the zoom features and to view plot coordinates in detail.
• Press Param to show the trigger parameter and channel/s displayed on screen.
• Press Exit to return to the PQ
Report screen.
CH 7/ View Event Data
MARK491f
MARK491g
7-37
Overview
Section D
Overview
Downloading Events from PX5 to a Computer
In this section
PX5 allows users to download, archive and view event data in a computer
.
This section discusses the external communications device and software applications necessary to transfer and store PX5 data files to a computer.
Topic
External Communication Interface
Connection Setup via RS232
Connection Setup via USB
Connection Setup via Ethernet
Connection Setup via Modem
Downloading Events via NodeLink
®
Viewing Events via DranView
®
DranView
®
with HASP
See Page
7-39
7-40
7-41
7-42
7-43
7-47
7-48
7-49
7-38
CH 7/ View Event Data
External Communication Interface
Isolated
Communications
Module
To download events from PX5 through the optical port, you must have the following: a personal computer or laptop with Windows
®
operating system with either RS232 serial port or network adapter, NodeLink
®
, and the appropriate Isolated Communications
Module assemby as described below.
The Isolated Communications Module assembly consists of two parts:
1. A fiber optic cable (P/N 900406) which connects the PX5 optical serial port to the
PX5 communication module;
2. The PX5 communication module which is available in three types:
• a 9-pin RS232 Communication Module (P/N COMM-RS232)
• a USB Communication Module (P/N COMM-OUA)
• an Ethernet Communication Module (P/N COMM-OEA)
The PX5 communication modules are optically isolated devices using infrared light to transfer text and graphics to a computer running NodeLink
®
. These modules are designed to connect the PX5 optical serial port to the appropriate interface - either a standard RS232 serial port connector, USB adapter, or Ethernet adapter.
With NodeLink
®
you will be able to download data, upload or download instrument setups, or view real time meter data from PX5. The downloaded data can be viewed using the DranView
®
application.
Each adapter interface is supported using the computer’s standard serial ports.
7-39
External Communication Interface, continued
Connection setup via RS232
The following procedure and diagram describe how to connect the PX5 to a computer via RS232. Once the physical connection is done, see Chapter 4 Instrument Settings -
Communications on page 4-10 for instructions on how to enable PX5 settings to communicate with external devices.
1. Connect one end of the fiber optic cable (P/N 900406) into the Fiber Optic Serial
Data Port located on the left side panel of the PX5.
2. Connect the other end of the fiber optic cable into the Fiber Optic Port on the plastic housing of the 9-pin/RS232 Communication Module (P/N COMM-RS232).
3. Connect the 9-pin RS232 connector to any available serial COM port on your computer.
NOTE: If the RS232 COM port on your computer supplies voltage power, the battery charger/UPS for DC power input is not required. Otherwise, COMM-RS232 requires that an external power source be connected. For external power supply, use the optional accessory Battery Charger/UPS (P/N XBC-PX5) available from Dranetz-BMI.
Connect the DC plug from the battery charger/UPS to the 12V, 3W max input jack on the RS232 adapter. Configure the AC power plug of the battery charger by sliding the proper plug supplied (US, Euro, UK or Australia) and locking it into place. Connect the
AC power plug of the battery charger to the proper power source 120V AC for US type plug or 230V AC for Euro, UK or Australia type plug.
4. Refer to the NodeLink
®
User’s Guide (P/N UG-NODELINK) for instructions on how to set up a NodeLink/PX5 site.
DC PO W E R INPUT
RS 232 PLUG
RS 232 - FIB ER OP TIC
ADA PTER
FIBE R OP TIC CAB LE
TO P X5
O PTICAL
P ORT
7-40
CH 7/ View Event Data
Connection setup via USB
The following procedure and diagram describe how to connect the PX5 to a computer via USB. Once the physical connection is done, see Chapter 4 Instrument Settings -
Communications on page 4-10 for instructions on how to enable PX5 settings to communicate with external devices.
1. Connect one end of the fiber optic cable (P/N 900406) into the Fiber Optic Serial
Data Port located on the left side panel of the PX5.
2. Connect the other end of the fiber optic cable into the Fiber Optic Port on the plastic housing of the 9-pin/RS232 Communication Module (P/N COMM-RS232).
3. Connect the 9-pin RS232 connector to the USB to RS232 Serial Adapter.
4. Install the software on the compact disc that came with your USB to RS232 Serial
Adapter. This will create a virtual COM port on your computer at the next available serial port.
5. Connect the USB cable from a USB port on your computer to the USB socket of the
RS232 Serial Adapter.
6. Check the Device Manager in the Windows
®
control panel to identify the new COM port number created by the USB - RS232 Serial device. Use this COM number to connect the PX5 with NodeLink
®
.
7. Refer to the NodeLink
®
User’s Guide (P/N UG-NODELINK) for instructions on how to set up a NodeLink/PX5 site.
FIBER OPTIC CABLE
TO PX5
OPTICAL
PO RT
RS232 - FIBER OPTIC
ADAPTER
TO PC
USB POR T
USB TO RS232
ADAPTER
D B9
7-41
External Communication Interface, continued
Connection setup via
Ethernet
The following procedure and diagram describe how to connect the PX5 to a computer via Ethernet. Once the physical connection is done, see Chapter 4 Instrument Settings -
Communications on page 4-10 for instructions on how to enable PX5 settings to communicate with external devices.
1. Connect one end of the fiber optic cable (P/N 900406) into the Fiber Optic Serial
Data Port located on the left side panel of the PX5.
2. Connect the other end of the fiber optic cable into the Fiber Optic Port on the metal housing of the Ethernet Communication Module (P/N COMM-OEA).
3. The COMM-OEA requires connection to an external power source. Connect the DC plug from the AC adapter supplied (P/N 11707-G1) to the 12V, 3W max input jack on the Ethernet adapter. Configure the AC power plug of the battery charger by sliding the proper plug suppplied (US, EURO, UK or Australia) and locking it into place. Plug the
AC power plug of the battery charger to the proper source 120V AC for US type plug or 230V AC for Euro, UK or Australia type plug.
NOTE: For battery backup operation, replace the AC adapter with the optional accessory Battery Charger/UPS (P/N XBC-PX5) available from Dranetz-BMI.
4. Set the IP configuration of the Ethernet Communication Module. Consult your IT
Department for the appropriate setting of your local area network. See Chapter 4
Instrument Settings - Communications on page 4-10 for the procedure on how enter IP settings in PX5.
5. Connect the Ethernet port on the Ethernet Communication Module to the local area network to which your computer is connected to.
6. Install the software contained in the compact disc that came with your Ethernet
Communication Module. This will install the “Real COM Installer Program” plus some utility programs from MOXA Technology, Inc.
®
for the Ethernet Communication
Module on your computer.
7. Run the Real COM Installer. Map and activate a COM port to the first available
COM port on your computer.
8. Refer to the NodeLink
®
User’s Guide (P/N UG-NODELINK) for instructions on how to set up a NodeLink/PX5 site.
FIBER OPTIC CABLE
TO PX5
OPTICAL
PORT
DC POWER INPUT
7-42
CH 7/ View Event Data
Connection setup via
Modem
When configuring both the PX5 and NodeLink
®
for modem communications, keep in mind that the PX5 uses a fiber optic serial port in order to maintain electrical isolation.
This means that there are no control signals available to a modem to use for handshaking and flow control.
It is highly recommended that identical modems be used on the PX5 and the computer.
Identical modems will have the same internal buffering and are more likely to negotiate modulation, speed, and error correction suitable to both modems. If the modems used are not identical then both the PX5 and the computer should have modems with the same chipset (i.e. Rockwell, Lucent).
When configuring for modem communications, the first decision to be made is the port speed for both ends of the communications link. This is the speed at which the PX5 communicates with its modem and the speed at which the computer communicates with its modem. The same speed should be chosen for both. Ideally the speed should be at or just below the anticipated modem connect speed. Since most modems today will attempt to connect at least at 56 kbps, 38.4 kbps would be a good choice for the two port speeds. This helps to prevent possible modem buffer overflow.
Follow the steps below to configure the PX5 for a port speed of 38.4 kbps. See Chapter
4 Instrument Settings - Communications for the PX5 screen interface.
1. Connect the modem to the PX5 communications adapter.
2. Turn on the modem.
3. From the PX5 home screen, click on the Preferences icon.
4. Choose Communications from the Instrument Settings Setup Menu.
5. Verify that both the Enable Communications and External Modem Connected checkboxes are enabled (checkboxes checked).
6. Check to enable 38400 under Baud Rate (bps).
NOTE: The port speed of 38400 (38.4 kbps) used above may be substituted with
57600. Experiment to find the maximum port speeds that will work for the system.
7. Note the modem initialization string at the bottom of the screen. Do not exit this screen yet since you may be modifying this string after you have the Windows
®
modem configured.
Continued on next page
7-43
External Communication Interface, continued
Connection setup via
Modem
(continued)
NodeLink
®
uses Windows
®
TAPI when accessing modem communications resources.
The assumption is that the Windows
®
modem to be used for PX5 communications has been properly installed prior to executing this procedure.
If the modem is not on, or was not on when Windows
®
was started, it may be necessary to turn the modem on and restart Windows
®
. Windows
®
looks for installed serial modems at startup. If it does not find them, it may not allow them to be configured in the Control Panel.
Follow the steps below to configure the port speed for the Windows
®
modem in the computer:
1. Press the Start button.
2. Select Settings and then Control Panel.
3. Double-click on Phone and Modem Options.
4. Select Modems in the subsequent dialog box.
5. In the list of modems that is displayed, click to highlight the modem in question and select Properties.
6. On the General tab of the modem properties dialog box, select 38400 as the maximum port speed.
7. Click OK to exit from the open dialog boxes.
8. Close the Control Panel.
It is important to note that the port speed of 38400 (38.4 kbps) may be substituted with
57600. Experiment to find the maximum port speeds that will work for the system.
Continued on next page
7-44
CH 7/ View Event Data
Connection setup via
Modem
(continued)
Back at the PX5, the last step in configuring the modem communications is to modify the modem initialization string to match the modems and chipsets being used. The goal is to configure for the following:
• Restore factory settings.
• Set auto-answer to answer on one or two rings (more than two rings are allowed but at some point the number of rings may start to conflict with NodeLink
®
timeouts).
• Turn hardware flow control off since you are using a "two-wire" connection (fiber optic port).
• Set a modem inactivity timeout of 60 seconds. The modem will hang up after one minute of continuous inactivity on the line.
• Select the minimum allowable baud rate.
Follow the steps below to change the modem initialization string. See Chapter 4
Instrument Settings - Communications for the PX5 screen interface.
1. From the PX5 Communications Settings screen used to configure modem connection speed, click on the Change button to the right of the string field display.
2. Use the virtual keypad that appears on the screen to change and enter the new string command. The modem initialization string commands for the Conexant (Rockwell) chipset and the Agere (Lucent) chipset are discussed in the next section.
3. When done, click on OK to accept changes in modem communications settings.
Modem initialization string command
The following is the AT initialization string for a modem using the newer Conexant
(Rockwell) chipset:
AT&F;S0=2;+IFC=0,0;S30=6
Where:
AT is the modem attention command
&F instructs the modem to restore factory configuration
S0=2 turns auto-answer on and sets the number of rings to answer to two.
+IFC=0,0 turns flow control off.
S30=6 sets a 60 second inactivity modem hang up timeout.
; is a command delimiter.
NOTE: It may be necessary to adjust the modem connection speeds to specify a minimum baud rate. This is possible using the +MS modem command. Check the modem manual for use of the +MS command. There are several varieties of the command. Typically, a modem modulation scheme and minimum and maximum transmit and receive speeds can be specified. Using Hyperterminal, it is possible to get a list of the possible command ranges and syntax by typing AT+MS=?.
Continued on next page
7-45
External Communication Interface, continued
Modem initialization string command
(continued)
The following is the AT initialization string for a modem using the Agere (Lucent) chipset:
AT&F;S0=2;&K0;%E0;S30=6
Where
AT is the modem attention command.
&F instructs the modem to restore factory configuration.
S0=2 turns auto-answer on and sets the number of rings to answer to two.
&K0 turns flow control off.
%E0 disables baud rate fall back/fall forward.
S30=6 sets a 60 second inactivity modem hang up timeout.
; is a command delimiter.
A similar note regarding connect speeds applies. Try using the AT-V90= command and modifying the contents of S registers S37 and S38 .
7-46
CH 7/ View Event Data
Downloading Events via NodeLink
®
NodeLink
®
application
NodeLink
®
is a Windows
®
-based program enabling the user to download, archive and visualize (using DranView
®
) event-type data from a variety of Dranetz-BMI instruments including PX5.
Users are strongly advised to always keep their NodeLink
®
and PX5 programs current with the latest version released by Dranetz-BMI. Refer to the table below for the
NodeLink
®
version required to download events from PX5:
You must have ...
NodeLink V2.4 or higher
NodeLink V2.3
NodeLink V2.1 or 2.2
NodeLink V2.0
When using ...
PX5 firmware V1.8 or higher
PX5 firmware V1.5 to 1.7
PX5 firmware V1.4
PX5 firmware V1.3
Log on to the Dranetz-BMI website, www.dranetz-bmi.com, to download the latest
PX5 firmware version. See Chapter 1 Getting Started - Upgrading Firmware from a
Data Card on page 1-10 for instructions on how to download and install the latest PX5 firmware upgrade from the web. Contact the Dranetz-BMI Customer Service
Department for further information and assistance on upgrading PX5 firmware.
NodeLink
®
communicates directly with the PX5 using the external communications devices described on pages 7-39 to 7-46. Depending on the communication assembly used, NodeLink
®
can communicate with the PX5 either by RS232 serial port, USB,
Ethernet, or modem connection.
Data files downloaded by NodeLink
®
can then be seamlessly transferrred to a viewer application such as DranView
®
.
Contact the Dranetz-BMI Customer Service Department at (732) 287-3680 or 1-800-
372-6832 for more details on how to get a copy of the latest NodeLink
®
and DranView
® applications. Refer to the NodeLink
®
User’s Guide (P/N UG-NODELINK), included in the NodeLink
®
software package, for instructions on how to set up a NodeLink/PX5 site.
7-47
Viewing Events via DranView
®
Viewing Events via DranView
®
DranView
®
with
PX5 driver
DranView
®
is an optional viewer and data analysis software. Data collected by the PX5 must first be transferred to a computer via NodeLink
®
so that they can be archived and/ or viewed using DranView
®
.
Users are strongly advised to always keep their DranView
®
and PX5 programs current with the latest version released by Dranetz-BMI. Refer to the table below for the
DranView
®
version required to manage PX5 event data in the computer:
You must have ...
DranView V5.8 w/ PX5 driver
DranView V5.7 w/ PX5 driver
DranView V5.6 w/ PX5 driver
When using ...
PX5 firmware V1.5 or higher
PX5 firmware V1.3 to 1.4
PX5 firmware V1.0 to 1.2
DranView
®
is available in soft key version (without HASP) and in hard key version
(with HASP).
DranView
®
soft key version does not require a hardware lock or HASP in order to work properly in a computer.
DranView
®
hard key version can be installed in multiple computers, but can only be used in a computer where a HASP driver is properly installed. A HASP is available for installation to either the USB port or the Printer/Parallel port.
IMPORTANT: BEFORE ATTEMPTING TO INSTALL DRANVIEW WITH HASP,
READ THE INSTRUCTIONS FOUND ON PAGE 7-49 AND/OR THE
INSTALLATION GUIDE THAT CAME WITH YOUR DRANVIEW
®
SOFTWARE
PACKAGE.
DranView
®
application
DranView
®
is a Windows
®
98/NT/2000/XP compatible program that is used to access and retrieve files from a data card or from other disk media compatible with MS-
Windows
®
operating system. Following are the features and highlights of the
DranView
®
application:
• Direct interface with NodeLink
®
communications software
• Two-pane browser (timeplots and waveforms simultaneously)
• Multiple ZOOM levels (up to 15 times)
• Advanced Harmonic analysis (DFT/FFT) featuring phasor diagrams and flexible data presentation
• Toolbar and Button support
• Drop-down Events list
• Multi-parameter time plots
• Time measurement tool (delta measurement)
• Saves data to .DNV (DranView
®
compressed format) or converts to ASCII
• Status bar displays time, date and selected pane parameters
• Accelerator keys and right mouse button support
• Cut and paste to other applications
• Email .DNV data files directly from DranView
®
7-48
CH 7/ View Event Data
DranView
®
with HASP
DranView
®
system requirements
The minimum system specifications for proper installation and operation of DranView
® are shown below. Users are strongly advised to follow the recommended specifications for optimal DranView
®
operation. The recommended specifications are especially encouraged for use with instruments that allow generation of very large databases i.e. PX5, PG4400, and PP4300 Multi-DAQ. The Compact Flash storage media in these instruments are able to handle very large files.
Operating System
MS Windows
®
95, 98 SE, NT 4.0, ME;
Win 2000 or Win XP recommended
Processor
Clock Speed
Memory
Pentium class or higher
133 MHz or higher
128 MB or higher;
512 MB or higher recommended
Disk Requirements
Monitor
12 MB disk space for installation
128 MB disk free space for file conversion;
512 MB disk free space for file conversion recommended
VGA or better;
Hi-color 800x600 or higher recommended
Installation procedure
The DranView
®
with HASP software package includes the HASP and the CD-ROM containing the DranView
®
program and the User’s Guide.
WARNING: DO NOT insert the HASP before installing DranView
®
. Otherwise,
MS Windows
®
will fail to find the proper driver for the HASP but may still add a nonworking HASP driver to the Device Manager (Control Panel System). In this case, the HASP driver needs to be manually removed from the Device Manager. When done, restart the computer and reinstall DranView
®
from the CD-ROM.
NOTE: If you are running MS Windows
®
NT, ME, 2000 or XP, you must have administrator privileges to do a proper install.
STEP 1: Install the DranView
®
program from the CD-ROM. Follow the instructions below to install DranView.
•Insert the CD-ROM with the DranView
®
program in the disc drive.
•Auto Run will automatically start to install DranView
®
.
If not, click the START button and select RUN. Type d:\setup (or whatever disc drive DranView
®
is inserted), and press ENTER.
•Follow the on-screen instructions to continue installing DranView
®
.
Continued on next page
7-49
DranView
®
with HASP, continued
Installation procedure
(continued)
STEP 2: There are two types of HASP available: one which can be keyed to the USB port and another which goes into the Printer or Parallel port (see figure below). Depending on type of HASP, insert in the appropriate USB port or
Printer/Parallel port in the computer. Align the HASP to the keyed port and push gently to lock it in place. Keep the HASP in the port while using the
DranView
®
application.
The HASP is programmed to allow DranView
®
to work with a specific Dranetz-BMI product. The table on page 7-51 lists the HASP ID labels that go with the corresponding
Dranetz-BMI product.
NOTE: Make sure to write down the serial number of your HASP and keep this information in a secure place. The serial number is required to replace HASP in case it gets lost or destroyed.
HASP for USB Port
7-50
HASP for Printer or Parallel Port
Top Side Bottom Side
Continued on next page
CH 7/ View Event Data
Installation procedure
(continued)
The table below shows the HASP ID labels that go with the corresponding Dranetz-
BMI product.
Supports the following
Dranetz-BMI products
PP4300 PQLite; 808; Multi-DAQ
PX5; PX5-400; 4400
All Dranetz-BMI products including PX5 and 4400 with MATH, PQDIF driver
PX5; 4400; 658; PP1; 4300
HASP for
USB Port
DV4300HASP
ID Label
HASP for Printer or Parallel Port
DV4300HASP-P
DVPXHASP DVPXHASP-P
DVPXALLHASP DVPXALLHASP-P
DVDRANHASP DVDRANHASP-P
Customer service and support
STEP 3: Start DranView
®
. Double-click the DranView
®
icon at any time to start
DranView
®
.
For additional information, refer to the on-line Help documentation included in the DranView
®
application or the DranView
®
User’s Guide. The Getting
Started section of the User’s Guide provides a complete description of how to use DranView
®
.
NOTE: If the HASP is not inserted (or is not detected), DranView
®
will operate in DEMO mode only.
If any item is missing, or for installation or operating assistance with the DranView
® software package, please contact the Dranetz-BMI Customer Support at (732) 287-
3680 or 1-800-372-6832.
As part of our continuing quality development effort, and in the event of finding serious bugs, Dranetz-BMI may occassionally post a self-installing upgrade patch which users can download for free. The patch may be found at the Dranetz-BMI website www.dranetz-bmi.com under “Software Packages and Updates”. The upgrades are available to users who are registered owners of DranView
®
. They will not work for demo or unregistered installations of DranView
®
.
7-51
7-52
A P P E N D I X A
Optional Accessories
Overview
Introduction
This appendix lists the optional accessories for PX5. It covers the hardware accessories available for use with PX5 and the Dranetz-BMI software applications used to download and view event data in a computer.
Topic
Hardware Accessories List & Descriptions
Software Accessories List
See Page
A-2
A-8
Ordering information
To order accessories, contact Dranetz-BMI Customer Service Department
at:
Dranetz-BMI
1000 New Durham Road
Edison, NJ 08818-4019 USA
Attention: Customer Service
Tel: (732) 287-3680
Tel: 1-800-372-6832
FAX: (732) 248-1834 www.dranetz-bmi.com
A-1
Hardware Accessories List and Descriptions
Hardware Accessories List & Descriptions
Hardware
Accessories List
Accessory
Current Probes
Current Probe Assembly, 10 to 500 A RMS
Current Probe, 10 to 500 A
Current Probe Assembly, 0.1 to 10 A RMS
Current Probe, 1 to 10 A
Current Probe Assembly, 300 to 3000 A RMS
Current Probe, 10 to 3000 A
Current Probe Assembly, 1 to 30 A RMS
Current Probe Assembly, 1 to 300 A RMS
Current Probe Assembly, 10 to 1000 A RMS
Current Probe Assembly, 10 to 3000 A RMS
LEMFLEX Probes
LEMFLEX Current Probe, 30A/300A/3000A, 24”
LEMFLEX Current Probe, 30A/300A/3000A, 36”
LEMFLEX Current Probe, 30A/300A/3000A, 48”
LEMFLEX Current Probe, 60A/600A/6000A, 24”
LEMFLEX Current Probe, 60A/600A/6000A, 36”
LEMFLEX Current Probe, 60A/600A/6000A, 48”
Battery Powered DRANFLEX Probes
DRANFLEX Current Probe, 300A/3000A, 24”
DRANFLEX Current Probe, 300A/3000A, 36”
DRANFLEX Current Probe, 300A/3000A, 48”
DRANFLEX Current Probe, 600A/6000A, 24”
DRANFLEX Current Probe, 600A/6000A, 36”
DRANFLEX Current Probe, 600A/6000A, 48”
DRANFLEX Probes for use with External Battery
Charger (P/N DF-PSP)
DRANFLEX Current Probe, 300A/3000A, 24”
DRANFLEX Current Probe, 300A/3000A, 36”
DRANFLEX Current Probe, 300A/3000A, 48”
DRANFLEX Current Probe, 600A/6000A, 24”
DRANFLEX Current Probe, 600A/6000A, 36”
DRANFLEX Current Probe, 600A/6000A, 48”
Part Number
TR-2500
TR-2500A
TR-2510
TR-2510A
TR-2520
TR-2520A
TR-2021
TR-2019B
TR-2022
TR-2023
RR-3035A-24
RR-3035A-36
RR-3035A-48
RR-6035A-24
RR-6035A-36
RR-6035A-48
DRANFLEX4300-3K24
DRANFLEX4300-3K36
DRANFLEX4300-3K48
DRANFLEX4300-6K24
DRANFLEX4300-6K36
DRANFLEX4300-6K48
DRANFLEXPP1-3K24
DRANFLEXPP1-3K36
DRANFLEXPP1-3K48
DRANFLEXPP1-6K24
DRANFLEXPP1-6K36
DRANFLEXPP1-6K48
Continued on next page
A-2
APPENDIX A/ Optional Accessories
Hardware
Accessories List
(continued)
Accessory
AC/DC Current Probes
AC/DC Current Probe, 150A, Without AC Adapter
AC/DC Current Probe, 150A, Battery Powered
AC/DC Current Probe, 1500A, Without AC Adapter
AC/DC Current Probe, 1500A, Battery Powered
Current Probe Adapter Cables
Adapter Cable, 658 Current Probe to 4300
Adapter Cable, 4300/LEMFLEX
AC Adapter with 4 Phase Adapter Cable for LEMFLEX
Probes
Probe Adapter Cable for LEMFLEX, Hypertronics to
Redel
For Use with Current Probes PR150/SP1 and PR150/SP2
AC Adapter, 9V, US
AC Adapter, 9V, EURO
Voltage Probes
Fuse Voltage Adapter, for single phase connection
Fuse Voltage Adapter, for three phase connection
Single Phase Measurement Cord, 115V, US
Single Phase Measurement Cord, 250V, Europe
Single Phase Measurement Cord, 250V, UK
Single Phase Measurement Cord, 250V, Australia
Data Card
Compact Flash Data Card (32 MB)
Compact Flash Data Card (64 MB)
Compact Flash Data Card (128 MB)
Compact Flash Card Reader, Parallel
Compact Flash Card Reader, USB
Isolated Communications Module Assembly
Fiber Optic Cable
External Communication Adapter
RS232 - Fiber Optic Adapter
LAN - Fiber Optic Adapter
USB - Fiber Optic Adapter
Part Number
PR150/SP1
PR150/SP2
PR1500/SP7
PR1500/SP8
CA-4300
CA4300LEM
RR/PS/4P
TRTOREDEL
T402-P5P-ND
T408-P5P-ND
FVA-1
FVA-4
SPMEASCORD-US
SPMEASCORD-EURO
SPMEASCORD-UK
SPMEASCORD-AUST
32MDATA
64MDATA
128MDATA
FLASHREADER-P
FLASHREADER-USB
900406
COMM-RS232
COMM-OEA
COMM-OUA
Continued on next page
A-3
Hardware Accessories List & Descriptions, continued
Hardware
Accessories List
(continued)
Accessory
Miscellaneous Hardware
Weather Resistant Enclosure
Soft Carrying Case
Reusable Shipping Container
Battery Pack, 7.2V, 2.7Ah
Part Number
ENCL-HH
SCC-4300
RSC-4300
BP-PX5
External Battery Charger/UPS XBC-PX5
External Battery Charger with LEMFLEX Adapter Cables LF-PSP
External Battery Charger with DRANFLEX Probe Power
Adapter
DF-PSP
ISO-65X-5 Isolated Current Transformer 0.1A to 5A
Dranetz-BMI Reference Publications
Field Handbook for Electrical Energy Management
Field Handbook for Power Quality Analysis
HB114415
HB114414-S
A-4
APPENDIX A/ Optional Accessories
Current probes
Several Dranetz-BMI current probes can be used with PX5: models TR2500/A,
TR2510/A, TR2520/A, TR2019B, TR2021, TR2022, TR2023. PX5 supports both
LEMFLEX and DRANFLEX current probes. Typical current probes are illustrated in
Chapter 2.
TR2500, TR2510, TR2520 (TR2500A, TR2510A, TR2520A): These models will measure rms currents from 10 to 500 A, 0.1 to 500 A, 300 to 3000 A, respectively.
They plug directly into any of the current inputs on the rear panel. These probes are not recommended for measuring medium or high frequency transients.
TR2021, TR2019B, TR2022, TR2023: These four probes are made for the Dranetz-
BMI model 658 but can be used with the PX5 by using an adapter cable (part number
CA-4300). They can measure rms currents in ranges of 1 to 30 A, 1 to 300 A, 10 to
1000 A, and 10 to 3000 A, respectively, and are needed to accurately measure medium and high frequency transients.
LEMFLEX Current Probes: LEMFLEX optional current probes allow current measurements in the range of 5 to 3000 A full scale, or 10 to 6000 A full scale.
LEMFLEX probes are available in three sizes: 24” probe length - conductor(s) up to 8” diameter; 36” probe length - conductor(s) up to 11” diameter; 48” probe length - conductor(s) up to 17” diameter.
DRANFLEX Current Probes: DRANFLEX optional current probes allow current measurements in the range of 5 to 3000 A full scale, or 10 to 6000 A full scale.
DRANFLEX probes are available in three sizes: 24” probe length - conductor(s) up to
8” diameter; 36” probe length - conductor(s) up to 11” diameter; 48” probe length - conductor(s) up to 17” diameter.
DRANFLEX4300 probes are battery powered only, supplied with a standard 9V alkaline battery.
DRANFLEXPP1 probes require the use of the External Battery Charger with
DRANFLEX Probe Power Adapter (P/N DF-PSP) to connect with PX5. Contact
Dranetz-BMI Customer Service Department for more information on DRANFLEX
Probe Accessories and refer to Information Sheet 899121.
Voltage probes
Fuse Voltage Adapter: Two accessory kits available: FVA-1 and FVA-4. FVA-1 is used for a single voltage measurement input. It contains one fused voltage adapter and one measurement connecting cable (Red) 50 cm in length. FVA-4 is used for a three phase and neutral voltage measurement inputs. It contains four voltage adapters and four measurement connecting cables 50 cm in length (one Red, one Yellow, one Blue, one
Grey).
Single Phase Measurement Cord: Allows measurement of a single phase circuit using a standard AC outlet 115V for US and 250V for European, UK, and Australian countries.
Continued on next page
A-5
Hardware Accessories List & Descriptions, continued
Data card
Compact Flash Data Card: PX5 supports the use of Compact Flash cards in its native format, without the need for PC card adapter. Compact Flash cards are available in three sizes: 32MB, 64MB, and 128MB.
Compact Flash Card Readers: Two types of card readers are available for easy data manipulation and data transfer from the Compact Flash card to the computer: via USB port (FLASHREADER-USB) or via parallel port (FLASHREADER-P).
Communication interface
Allows connection to the PX5 mainframe via the Isolated Communications Module
Assembly.
Fiber Optic Cable: Connects the communication adapter described below to the PX5 optical serial data port connector.
External Communication Adapter: Consists of an enclosure containing the connector/ pcb assembly, with a cable connected to either of the following connector:
• RS232 - Fiber Optic Adapter
• USB - Fiber Optic Adapter
• LAN - Fiber Optic Adapter
Miscellaneous hardware
Weather Resistant Enclosure: This weatherproof enclosure is designed to keep the PX5 and its cable connections in place. It is made of fiber glass and is intended for indoor and outdoor use. This enclosure is sturdy, lightweight, corrosion-resistant. It is able to withstand windblown dust, rain, splashing water, and ice formation.
Soft Carrying Case: Heavy-duty, padded, nylon carrying case. Includes pockets for cable set, current probes, and other accessories.
Reusable Shipping Container: Lockable, high-impact plastic case with foam insulation for protecting the instrument during shipping.
Battery Pack: NiMH (Nickel Metal Hydride) battery cells are used in PX5. See
Appendix C Battery Specifications and Replacement Procedure.
External Battery Charger: The XBC-PX5 charges a battery pack while the instrument is in use and may be used to power specified Dranetz-BMI probes.
Isolated Current Transformer: Allows the connection of other industry-standard 0.1A to
5A output current transformers to Dranetz-BMI equipment.
Continued on next page
A-6
APPENDIX A/ Optional Accessories
Dranetz-BMI reference publications
Field Handbook for Electrical Energy Management: This reference handbook provides a comprehensive guide for information related to conducting a thorough energy audit, power distribution analysis, and methods of remedying inefficiencies of energy management.
Field Handbook for Power Quality Analysis: This handbook is divided into six sections containing step-by-step instructions for discovering and solving complex power quality problems. Example waveforms and case studies are included.
A-7
Software Accessories List
Software Accessories List
Accessories List
Accessory
NodeLink
NodeLink
®
V2.4 or higher with download, setups and meters
DranView
DranView
®
V5.8 or higher with PX5 and 4400 driver
[5-User Package]
DranView
®
Math Driver
[5-User Package]
DranView
®
Software Package with HASP for USB Port: supports PX5, PX5-400, 4400
[5-User Package]
Part Number
NODELINK
DV5DRANTOPX
5PK-DV5DRANTOPX
DVMATHDRIVER
5PK-DVMATH
DVPXHASP
5PK-DVPXHASP supports all Dranetz-BMI products including PX5 and
4400 with Math and PQDIF driver
[5-User Package] supports PX5, 4400, 658, PP1 and PP4300
[5-User Package]
DranView
®
Software Package with HASP for Parallel
Port: supports PX5, PX5-400, 4400
[5-User Package] supports all Dranetz-BMI products including PX5 and
4400 with Math and PQDIF driver
[5-User Package] supports PX5, 4400, 658, PP1 and PP4300
[5-User Package]
Replacement Hasp for PX5 and 4400
DVPXALLHASP
5PK-DVPXALLHASP
DVDRANHASP
5PK-DVDRANHASP
DVPXHASP-P
5PK-DVPXHASP-P
DVPXALLHASP-P
5PK-DVPXALLHASP-P
DVDRANHASP-P
5PK-DVDRANHASP-P
HASP-DVPX
A-8
APPENDIX A/ Optional Accessories
NodeLink
®
and
DranView
®
applications
NodeLink
®
is an easy-to-use Windows
®
application that allows users to transfer, download, or view real time data from PX5 to a computer. Users can also transfer setups from a computer to the PX5 using NodeLink
®
. PX5 firmware V1.8 or higher requires NodeLink
®
V2.4 or higher with download, setups, and meters. Users are strongly advised to always keep their PX5 program current with the latest firmware version released by Dranetz-BMI. Log on to the Dranetz-BMI website, www.dranetzbmi.com, to download the latest PX5 firmware upgrade version.
DranView
®
is a Windows
®
-based program that is used to archive, view and analyze event data downloaded in the computer. PX5 firmware V1.5 or higher requires
DranView
®
V5.8 or higher with PX5 driver.
DranView
®
is available in soft key version (without HASP) and in hard key version
(with HASP). DranView
®
soft key version does not require a hardware lock or HASP in order to work properly in a computer. The DranView
®
hard key version can be installed in multiple computers, but can only be used in a computer where a HASP driver is properly installed. A HASP is available for installation to either the USB port or the
Printer/Parallel port.
For more information on the NodeLink
®
and DranView
®
product applications, refer to
Chapter 7 View Event Data - Section D Downloading Events from PX5 to a Computer.
A-9
A-10
A P P E N D I X B
Technical Specifications
Overview
In this appendix The following specifications are covered in this appendix.
Topic
General
Interfaces
Measured Parameters
Computed Parameters
Parameter Settings in Each Monitoring Mode
TR2500 Current Probe
TR2510 Current Probe
See Page
B-2
B-3
B-4
B-6
B-10
B-12
B-13
B-1
General
General
Dimensions
Size: 12” Width x 2.5” Height x 8” Depth (30 x 6. 4 x 20.3 cm)
Weight: 4.2 pounds (1.9 kg)
Environmental
Operating: 0 to 50 °C (32 to 122 °F)
Storage: -20 to 55 °C (4 to 131 °F)
Humidity: 95% non-condensing
System Time
Clock
Crystal controlled. 1 second resolution.
Event time clock displays to 1 msec resolution
Time displayed in analog or digital (12 or 24 hour) format
Accurate to 60 seconds per month.
Compact Flash
Memory Card
Sizes range from 32MB to 128MB
Power
Requirements
Use external UL/CE approved battery charger with international plugs. Mechanical On/
Off switch shuts unit down, but allows battery to continue to charge with switch in the
Off position.
Voltage: 90-265V AC, 47/63 Hz, 120-175 V DC
Consumption: 10 watts max
Field replaceable batteries: More than 2 hours run-time (3 hours typical) when fully charged.
Input resistance
Voltage input: 16 M
Ω
Line to Line
Current input: 400 k
Ω
B-2
APPENDIX B/ Technical Specifications
Interfaces
Installation
Categories
Display
Alarm
Mains supply: Installation Category II, Pollution Degree 2
Measurement inputs: Installation Category III, Pollution Degree 2
Type: 1/4 VGA color graphic, touch screen Liquid Crystal Display (LCD) with compact fluorescent (CCFL) backlighting. Programmable backlight time-out to reduce power consumption. Reactivates with touch.
Resolution: 360 x 240 dot matrix
Size: 3.75 x 4.75 inches
Audible alarm of short (approximately 0.1 second) or long (approximately 1 second) duration to call attention to an error condition or event trigger, respectively.
Communication Connect to the PX5 mainframe using either of the following external interface:
• RS232 - Fiber Optic adapter
• USB - Fiber Optic adapter
• LAN - Fiber Optic adapter
• Modem
B-3
Measured Parameters
Measured Parameters
Voltage
Current
Type: 4 full differential, DC coupled
Channels A, B, C, D Input Range: 10 - 600 Vrms
Input impedance: 16 M
Ω, minimum, Input to Input
Crest factor: Maximum 1.7 at full scale
RMS Accuracy: ±0.1% of Reading, ±0.05% Full Scale, over 7KHz bandwidth
(1 second rms readings)
Transient Input: 50 - 1000 Vpeak
Transient Accuracy: ±10% of Reading, ±0.5% Full Scale for Pulses > 10uS
Transient Duration: 2uS minimum
CMMR: -80 dB
Supply rate: 256 samples per cycle; rms computed on 1/2 cycle step
Type: 4 full differential, DC coupled.
Channels A,B, C, D Input Range: 10 - 200% of Rated Probe Input (Dranetz-BMI probes)
Channels A,B,C, D crest factor: Maximum of 3 at full scale.
RMS Accuracy:
±0.1% of Reading ±0.05% Full Scale plus Probe Accuracy, 3KHz bandwidth (1 second rms readings)
Transient Input: 3 times Probe Rated Nominal Input (Dranetz-BMI probes)
Transient Accuracy: ±10% of Reading, ±0.5% Full Scale over 1MHz bandwidth
(option) > 10uS
Transient Duration: depends on probe bandwidth
CMMR: -80 dB
Supply rate: 256 samples per cycle; rms computed on 1/2 cycle step
B-4
APPENDIX B/ Technical Specifications
Phase
Frequency
Each voltage/current pair (i.e. Channel A voltage, Channel A current) are sampled simultaneously to preserve phase relationship.
Three ranges, user selectable.
For Model PX5-XFAST:
• 30 - 70 Hz default, with up to 25% Vthd
• 15 - 30 Hz
For Model PX5-400:
• 30 - 70 Hz default, with up to 25% Vthd
• 380 - 440 Hz (reduced accuracy with 32 samples/cycle)
Accuracy: ±0.2% of reading
Environmental
All specifications are met over the operating range with influence factors as per IEC
61000-4-30 Class A.
B-5
Computed Parameters
Computed Parameters
Single Channel
Parameters
The computations below apply to single channel parameters.
Note that 0
V
= Phase Angle of Voltage, while 0
I
= Phase Angle of Current.
True Average
Power
Average of the instantaneous power samples taken as the product of voltage and current samples. Includes sign to indicate direction of power flow: positive (+) from source to load, negative (-) from load to source.
WATT
=
1
N n
N
∑
=
1
V n
I n
where N = number of samples
Vn = Voltage at sample n
In = Current at sample n
Apparent Power Unsigned value calculated using the product of the rms values of the voltage and current.
I VA
=
A
+
I
RMS
B
I
+
I
Fundamental
Apparent Power
Unsigned value calculated using the product of the fundamental rms values of the voltage and current.
VA fund
=
V fund
I fund
Fundamental
Power
Signed value calculated using the product of the fundamental apparent power and the cosine of the phase angle between the fundamental frequency components of voltage with respect to current (0 = 0
V
- 0
I
).
WATT fund
=
VA fund
cos
θ
Volt Ampere
Reactive
Signed value calculated using the product of the fundamental apparent power and the sine of the phase angle between the fundamental frequency components of voltage with respect to current (0 = 0
V
- 0
I
).
VAR fund
=
VA fund
sin
θ
Continued on next page
B-6
APPENDIX B/ Technical Specifications
True Power
Factor
Calculated using the True Average Power divided by the Apparent Power. See Note below for sign information.
WATT
TPF
=
VA
Displacement
Power Factor
Calculated using cosine of the phase angle between the fundamental frequency components of voltage with respect to current (0 = 0
V
- 0
I
information.
). See Note below for sign
DPF
=
cos 0
NOTE
The sign is the exclusive OR of the sign of the Watts and Vars. Note that for Power
Factor, the words “Lead” and “Lag” are definitive. As far as the signs go, it is assumed that Lag (inductive) is plus and Lead (capacitive) is minus when energy is delivered to the load.
Quad 2 | Quad 1
PF Lead - | PF Lag +
Watts - | Watts +
Vars + | Vars +
--------------+--------------
Quad 3 | Quad 4
PF Lag + | PF Lead -
Watts - | Watts +
Vars - | Vars -
In the code, this is implemented as:
Signum Watts: cosine 0
Signum Vars: sine 0
Signum PF: (Signum Watts)
*
(Signum Vars) where signum denotes the positive or negative sign.
Source: The diagram above matches Figure 9-26 Relationships Between Watts, Vars, and Volt-
Amperes found on page 228 of the Handbook for Electricity Metering, Ninth Edition, ©1992,
Edison Electric Institute, Washington, D.C., USA.
Continued on next page
B-7
Computed Parameters, continued
Totals
The computations below apply to three phase wye configuration.
Totals for split phase can be determined by eliminating phase C (i.e. split phase
WATT
Tot
= WATT
A
+ WATT
B
)
Power Total
WATT
Tot
=
WATT
A
+
WATT
B
+
WATT
C
Fundamental
Power Total
WATT
Tot fund
=
WATT
A fund
+
WATT
B fund
+
WATT
C fund
Fundamental
Reactive Power
Total
VAR
Tot fund
=
VAR
A fund
+
VAR
B fund
+
VAR
C fund
Apparent Power,
Arithmetic Total
VA
Arithmetic Tot
=
VA
A
+
VA
B
+
VA
C
Apparent Power,
Vector Total
VA
Vector Tot
=
2
WATT
Tot
+
2
VAR
Tot fund
Fundamental
Apparent Power,
Arithmetic Total
VA
Arithmetic T ot fund
=
VA
A fund
+
VA
B fund
+
VA
C fund
Fundamental
Apparent Power,
Vector Total
VA
Vector Tot fund
=
2
WATT
Tot fund
+
2
VAR
Tot fund
Continued on next page
B-8
True Power
Factor,
Arithmetic Total
See Note on page B-7 for sign information.
TPF
Arithmetic Tot
=
WATT
Tot
VA
Arithmetic Tot
True Power
Factor, Vector
Total
See Note on page B-7 for sign information.
WATT
Tot
TPF
Vector-Tot
=
VA
Vector Tot
Displacement
Power Factor,
Arithmetic Total
See Note on page B-7 for sign information.
WATT
Tot
DPF
Arithmetic Tot
=
VA
Arithmetic Tot fund
Displacement
Power Factor,
Vector Total
See Note on page B-7 for sign information.
DPF
Vector Tot
=
WATT
Tot fund
VA
Vector Tot fund
APPENDIX B/ Technical Specifications
B-9
Parameter Settings in Each Monitoring Mode
Parameter Settings in Each Monitoring Mode
Setup parameters
The following table lists the default settings for the threshold parameters in each monitoring mode.
Parameters
High Limit
Low Limit
Very Low
Limit
RMS Pretrigger (cycles)
RMS In-Out
Post-trigger
(cycles)
RMS Out-In
Post-trigger
(cycles)
Waveform
Capture Pretrigger (cycles)
Waveform
Capture Posttrigger (cycles)
Standard
Power
Quality
110%
90%
10%
Current
Inrush
120%
Off
Off
Fault
Recorder
RMS Variation
110%
90%
10%
Long-term
Timed
Recording
Off
Off
Off
6
6
6
2
2
4
200
200
4
200
4
100
1000
4
1000
0
10 (50 Hz);
12 (60 Hz)
10 (50 Hz);
12 (60 Hz)
0
10 (50 Hz);
12 (60 Hz)
170% 350%
Transients
170% Off Absolute
Instantaneous
Peak
High
Frequency
Cycle-by-cycle
Waveshape
Magnitude
Cycle-by-cycle
Waveshape
Duration (% of cycle)
Waveform
Duration
100%
10%
10%
7%
Off
Off
Off
Off
100%
10%
10%
7%
Off
Off
Off
Off
Continuous
Data
Logging
EN50160
Off
Off
Off
1
2
2
1
2
Off
Off
Off
Off
Off
110%
90%
1%
6
6
6
2
2
170%
100%
10%
10%
7%
Continued on next page
B-10
APPENDIX B/ Technical Specifications
Setup parameters
(continued)
The following table lists the default settings for the threshold parameters in each monitoring mode.
Parameters
When Volts go out, record:
When Amps go out, record:
Volts
Amps
Power
Demand
Energy
Harmonics
Flicker (Pst)
Flicker (Plt)
Standard
Power
Quality
Fault
Amps
Channels
Current
Inrush
Fault
Amps
Channels
Fault
Recorder
Fault
Amps
Channels
Long-term
Timed
Recording
All Active
Channels
Waveform Capture Trigger Response
Off All Active
Volt
Channels
Off
Off
10 minutes
10 minutes
10 minutes
15 minutes
Off
Off
Off
Off
Journal Intervals
Off 10 minutes
Off
Off
10 minutes
10 minutes
10 minutes
10 minutes
10 minutes
2 hours
Off
Off
Off
Off
Off
Off
Off
Off
Off
15 minutes
10 minutes
10 minutes
10 minutes
2 hours
Continuous
Data
Logging
Off
Off
1 second
1 second
1 second
Off
Off
Off
Off
Off
Characterizer
Mode
IEEE 1159 None None IEEE 1159 None
*Numbers are in percent of nominal unless otherwise specified.
EN50160
All Active
Channels
Fault
Amps
Channels
10 minutes
10 minutes
10 minutes
15 minutes
10 minutes
10 minutes
10 minutes
2 hours
IEC
61000-4-30
B-11
TR2500 Current Probe
TR2500 Current Probe
Guidelines
NOTE
To achieve the rated accuracies, follow these guidelines:
• The conductor must be at a right angle to the probe
• The conductor must be centered in the probe core
• The jaw contact surfaces must be clean and properly aligned.
Specifications
Range: 1 to 500 Arms
Accuracy:
48 to 400 Hz: ±1.5% reading ±0.6A
400 to 3000 Hz: ±3% reading ±0.8A
Working voltage: 600 V max.
Frequency range: 48 to 3000 Hz
Output signal: 3 mV/A
Maximum conductor size: 1.18" (30 mm)
Maximum bus bar size: 2.5 x 0.20" (63 x 5 mm)
Phase shift (45 to 1000 Hz): Less than 4º
Operating temperature: 14 to 122 ºF (-10 to 50 ºC)
Storage temperature: -40 to 158 ºF (-40 to 70 ºC)
Dimensions: 2.60 x 7.68 x 1.34” (66 x 195 x 34 mm)
Weight: 14.82 oz. (420 g)
Current probe TR2500 can be used interchangeably with TR2500A.
B-12
APPENDIX B/ Technical Specifications
TR2510 Current Probe
Guidelines
NOTE
To achieve the rated accuracies, follow these guidelines:
• The conductor must be at a right angle to the probe
• The conductor must be centered in the probe core
• The jaw contact surfaces must be clean and properly aligned.
Specifications
Range: 0.1 to 10 Arms
Accuracy (at 60 Hz): 0.1 to 10A, ±1% reading ±0.01A
Working voltage: 600 V max.
Frequency range: 40 to 3000 Hz
Output signal: 150 mV/A
Maximum conductor size: 0.78" (20 mm)
Phase shift (at 60 Hz):
1 to 5A less than 1º
5 to 10A less than 1.5º
Operating temperature: 14 to 131 ºF (-10 to 55 ºC)
Storage temperature: -40 to 158 ºF (-40 to 70 ºC)
Dimensions: 5.47 x 2.00 x 1.18” (139 x 51 x 30 mm)
Weight: 6.5 oz. (180 g)
Current probe TR2510 can be used interchangeably with TR2510A.
B-13
B-14
A P P E N D I X C
Battery Specifications and Replacement Procedure
Overview
Introduction
The internal battery pack used in PX5 functions as the primary power source and UPS.
Always charge the battery fully before using the unit. PX5 will fully charge its internal battery in six (6) hours.
PX5 uses a non-volatile flash memory for backup that is not operator replaceable. The flash memory will store data temporarily.
In this appendix The following topics are covered in this appendix.
Topic
Battery Specifications
Battery Pack Safety Precautions
Battery Pack Replacement
See Page
C-2
C-3
C-4
C-1
Battery Specifications
Battery Specifications
Battery pack
Location: Battery compartment at the back of the unit.
Number of batteries in pack: 6
Type: Sealed, rechargeable NiMH (Nickel Metal Hydride) cells
Voltage: 7.2 V dc
Capacity: 2.7 Ah
Length of operation: More than two (2 ) hours when fully charged and with backlight on. When backlight is turned off, the unit can run continuously for more than three (3) hours.
Suggested replacement interval: Two years
Part Number: BP-PX5
NOTE: The length of time that the PX5 can operate on the battery pack degrades over the life of the batteries and the number of charge/discharge cycles.
Memory backup PX5 uses a non-volatile flash memory for data storage. Data will not be lost if the battery pack is removed.
C-2
APPENDIX C/ Battery Specifications and Replacement Procedure
Battery Pack Safety Precautions
WARNING
DO NOT intentionally short circuit the battery pack. The batteries are capable of providing hazardous output currents if short circuited. The PX5 is equipped with an internal battery charger circuit. Do not attempt to charge the batteries with an external charger other than the Dranetz-BMI battery charger, since improper charging could cause battery explosion.
ADVERTENCIA
NO ponga intencionalmente la batería en cortocircuito. Las baterías son capaces de proporcionar corrientes de salida peligrosas si están en cortocircuito. La PX5 está equipada con un circuito interno cargador de baterías. No intente cargar las baterías con un cargador externo que no sea el cargador de baterías Dranetz-BMI, puesto que la carga indebida podría hacer que explote la batería.
AVERTISSEMENT NE PAS court-circuiter délibérément le bloc-batterie. Lors d’un court-circuit, les batteries risquent d’émettre des courants effectifs dangereux. PX5 possède un circuit de chargeur de batterie intégré. Ne pas tenter de charger les batteries au moyen d’un chargeur externe autre que le chargeur de batterie Dranetz-BMI, car un rechargement fautif pourrait entraîner l’explosion de la batterie.
WARNUNG
Die Batterien dürfen NICHT kurzgeschlossen werden. Im Falle eines
Kurzschlusses können die Batterien lebensgefährliche Ausgangsströme leiten.
PX5 ist mit einem internen Batterieladegerät ausgestattet. Die Batterien sollten nur mit dem Ladegerät von Dranetz-BMI geladen werden. Die Verwendung eines externen Ladegeräts kann zu einer Explosion der Batterien führen.
Battery safety precautions
Observe the following precautions when inspecting or replacing the battery pack:
• Do not attempt to replace individual batteries of the pack or substitute other battery types.
• Do not dispose of battery in fire.
• Dispose of a used battery promptly in accordance with local Environmental
Protection Agency (EPA) regulations.
• Visually inspect the battery pack for corrosion.
The batteries have a safety pressure vent to prevent excessive gas build-up and corrosion indicates that venting has occurred. Possible causes of venting are: a defective charger, excessive temperature, excessive discharge rate, or a defective cell.
If corrosion is excessive, the battery pack may require replacement (contact Dranetz-
BMI Customer Service Department).
C-3
Battery Pack Replacement
Battery Pack Replacement
Introduction
PX5 contains an easily replaceable internal battery pack. See Appendix D for ordering information.
WARNING
Replace with Dranetz-BMI NiMH battery pack BP-PX5 only.
ADVERTENCIA
Reemplace con batería Dranetz-BMI NiMH BP-PX5 solamente.
AVERTISSEMENT
Remplacer par la batterie Dranetz-BMI NiMH BP-PX5 exclusivement.
WARNUNG
Nur mit Dranetz-BMI NiMH BP-PX5 Batteriesatz auswechseln.
NOTE
During normal operation, the battery pack will be slightly warm to the touch.
Procedure
Follow these steps to replace the battery pack.
Step
1
2
3
4
5
6
7
8
9
10
Action
Press the PX5 power button to off.
Turn off power to the circuit being measured.
Disconnect voltage and current probes from the circuit and the PX5’s rear panel.
On the bottom of the PX5, push the tab to release the battery cover. Refer to the diagram shown on page C-5.
Remove the cover.
Pull up on removal strap and remove battery pack.
Insert the new pack into the compartment making sure to observe polarity markings.
Replace the cover and press down until it latches closed.
Discard the old battery pack in accordance with Environmental
Protection Agency (EPA) regulations.
Press the PX5 power button to on.
Continued on next page
C-4
Battery removal diagram
APPENDIX C/ Battery Specifications and Replacement Procedure
C-5
C-6
A P P E N D I X D
User Replaceable Parts List
Introduction
The following parts are easily replaced by the operator and do not require special tools or access to the interior of the unit.
To order parts
Call Dranetz-BMI Customer Service at (732) 287-3680 or 1-800-372-6832 to order any of the following parts.
Parts List
Part Description
AC Adapter/Battery Charger
Battery Door
Battery Pack
Rubber Skin for PX5
Voltage Cable Assembly, 4 Pair w/ Alligator Probes
(See below for separate parts)
Part Number
XBC-PX5
116037-G1
BP-PX5
116035-G2
116042-G3
Measurement cable set, parts list
Part Description
Measurement Channel Cable Assembly
Alligator Clip, 4MM Plug-on, Red
Alligator Clip, 4MM Plug-on, Black
1000V Cable, Red
Yellow Cable/Plug
6FT Cable/Plug Blue
6FT Cable/Plug Gray
6FT Cable/Plug White
Carry Strap
Cable Pouch
Quantity
4
4
1
1
4
1
1
1
1
1
Part Number
114013-G1
900371
900372
900366
900367
900368
900369
900370
116040-G1
116043-G1
D-1
D-2
A P P E N D I X E
Common Circuit Connections
Overview
Who should read this section
If you are making power measurements, follow these diagrams so that your ABC values are calculated correctly.
WARNING Death, serious injury, or fire hazard could result from improper connection of this instrument. Read and understand this manual before connecting this instrument.
Follow all installation and operating instructions while using this instrument.
Connection of this instrument must be performed in compliance with the National
Electrical Code (ANSI/NFPA 70-2002) and any additional safety requirements applicable to your installation.
Installation, operation, and maintenance of this instrument must be performed by qualified personnel only. The National Electrical Code defines a qualified person as “one who has the skills and knowledge related to the construction and operation of the electrical equipment and installations, and who has received safety training on the hazards involved.”
Qualified personnel who work on or near exposed energized electrical conductors must follow applicable safety related work practices and procedures including appropriate personal protective equipment in compliance with the Standard for
Electrical Safety Requirements for Employee Workplaces (ANSI/NFPA 70E-2004) of USA and any additional workplace safety requirements applicable to your installation.
ADVERTENCIA Una conexión incorrecta de este instrumento puede producir la muerte, lesiones graves y riesgo de incendio. Lea y entienda este manual antes de conectar. Observe todas las instrucciones de instalación y operación durante el uso de este instrumento.
La conexión de este instrumento debe ser hecha de acuerdo con las normas del
Código Eléctrico Nacional (ANSI/NFPA 70-2002) de EE. UU., además de cualquier otra norma de seguridad correspondiente a su establecimiento.
La instalación, operación y mantenimiento de este instrumento debe ser realizada por personal calificado solamente. El Código Eléctrico Nacional define a una persona calificada como "una que esté familiarizada con la construcción y operación del equipo y con los riesgos involucrados."
E-1
Overview, continued
AVERTISSEMENT
Si l'instrument est mal connecté, la mort, des blessures graves, ou un danger d'incendie peuvent s'en suivre. Lisez attentivement ce manuel avant de connecter l'instrument. Lorsque vous utilisez l'instrument, suivez toutes les instructions d'installation et de service.
Cet instrument doit être connecté conformément au National Electrical Code
(ANSI/NFPA 70-2002) des Etats-Unis et à toutes les exigences de sécurité applicables à votre installation.
Cet instrument doit être installé, utilisé et entretenu uniquement par un personnel qualifié. Selon le National Electrical Code, une personne est qualifiée si "elle connaît bien la construction et l'utilisation de l'équipement, ainsi que les dangers que cela implique".
WARNUNG Der falsche Anschluß dieses Gerätes kann Tod, schwere Verletzungen oder Feuer verursachen. Bevor Sie dieses Instrument anschließen, müssen Sie die Anleitung lesen und verstanden haben. Bei der Verwendung dieses Instruments müssen alle
Installation- und Betriebsanweisungen beachtet werden.
Der Anschluß dieses Instruments muß in Übereinstimmung mit den nationalen
Bestimmungen für Elektrizität (ANSI/NFPA 70-2002) der Vereinigten Staaten, sowie allen weiteren, in Ihrem Fall anwendbaren Sicherheitsbestimmungen, vorgenommen werden.
Installation, Betrieb und Wartung dieses Instruments dürfen nur von
Fachpersonal durchgeführt werden. In dem nationalen Bestimmungen für
Elektrizität wird ein Fachmann als eine Person bezeichnet, welche "mit der
Bauweise und dem Betrieb des Gerätes sowie den dazugehörigen Gefahren vertraut ist."
Continued on next page
E-2
APPENDIX E/ Common Circuit Connections
WARNING
WARNING
WARNING
WARNING
Safety precautions
To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
For continued protection against risk of fire or shock hazard replace only with same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is
Littelfuse, part number KLKD.300 rated 600V AC/DC, 0.3A fast blow.
Do not replace fuse again if failure is repeated. Repeated failure indicates a defective condition that will not clear with replacement of the fuse. Refer condition to a qualified technician.
The following safety precautions must be followed whenever any type of voltage or current connection is being made to the PX5.
• Wear proper Personal Protective Equipment, including safety glasses and insulated gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
• Set the PX5 power switch to Off.
• Before connecting to electric circuits to be monitored, open their related circuit breakers or disconnects. DO NOT install any connection of the PX5 to live power lines.
• Connections must be made to the PX5 first, then connect to the circuit to be monitored.
Continued on next page
E-3
Overview, continued
Voltage and current connections
This section contains diagrams of both voltage and current probe connections that are required when power measurements are to be made.
Voltage: Voltage probes are connected to the individual source or load line and are referenced to the return (common) line voltage probe connection for greatest accuracy.
Current: Current probes are connected to each line and positioned to measure currents with reference to the voltage probe. Incorrectly positioned current probes may produce erroneous power measurement. Current probes are always oriented with the arrow pointing to the load.
Phasor diagrams
Correct phasor diagrams (for resistive loads) are shown for each connection.
In this appendix The following connections are shown in this appendix.
Topic
Verifying Voltage and Current Connections
Single Phase
Split Phase
3 Phase, Four Wire Wye
3 Phase (Floating or Grounded) Delta
3 Phase 2-Watt Delta
Generic Circuit
2 1/2 Element without Voltage Channel B
2 1/2 Element without Voltage Channel C
Connecting to a Potential Transformer (PT)
Connecting to a Current Transformer (CT)
Connecting to an Isolated Current Transformer (ISO)
E-12
E-13
E-14
E-15
E-17
E-18
See Page
E-5
E-7
E-8
E-9
E-10
E-11
E-4
APPENDIX E/ Common Circuit Connections
Verifying Voltage and Current Connections
Introduction
Correct voltage and current connection of single phase, split phase, or polyphase connections can be verified using phasor diagrams. Phasor diagrams are graphic representations that show the magnitude and angular relationship of voltage and current for each phase of a monitored connection. Each connection diagram on the following pages shows the correct voltage and current phasor diagrams (for resistive loads) for that circuit.
Displaying the screen
To display the Voltage and Current Phasor screen, from the Home screen press Phasor.
The following screen depicting Positive Sequence 3 Phase Delta resistive load will appear.
Split phase
MARK241
The touch screen Demo button presents an animated phasor demo rotation for resistive, capacitive and inductive loads.
Single Phase resistive load
A single phase voltage or current phasor is displayed as a single line showing a channel reference at 0 degrees and a magnitude relative to its measured value. An arrow head on the line indicates direction.
Split phase vectors are displayed as dual lines showing channel references and magnitudes and opposite (180 degrees) directions.
Three phase
Three phase vectors are displayed as three lines, 120 degrees apart in a resistive load
(unity power factor). Phase displacement will occur in a reactive or capacitive load.
Continued on next page
E-5
Verifying Voltage and Current Connections, continued
Incorrect current phasor diagram
Phasor displays that show incorrect current probe connection can be corrected by reconnecting the probe so that the arrow on the probe handle points toward the load.
PX5 is able to display diagrams of wiring configurations to assist users in the selection of circuit type appropriate for their application (see Chapter 5 Start Menu - Circuit Type
Selection on page 5-12). The instrument compares the detected voltages, currents, and phase sequence (if applicable) to the selected circuit type. PX5 issues a message if the specified circuit type and the actual voltage/current connections match.
The next pages describe and illustrate the wiring configurations available for set up in
PX5.
WARNING
Interconnect Jumpers bearing part number 114013-G1 supplied with the standard cable set can be used to bond the same conductor points together. To reduce the risk of fire, electric shock, or physical injury, it is strongly recommended that connections be made with all circuits de-energized and current carrying conductors fused. If it is necessary to make connections on energized circuits, these must be performed by Qualified
Personnel ONLY with proper Personal Protective Equipment.
E-6
APPENDIX E/ Common Circuit Connections
Single Phase
Introduction
When making voltage connections to a single phase circuit use channel A differential inputs as shown below. The figure also shows voltage connection using channel D as a differential input for measuring neutral to ground voltage. Neutral to ground measurements are important but optional.
NOTE
Be sure to connect the current probe with the arrow on the handle pointing towards the load or an erroneous power reading will result.
Connection diagram
Phasor diagrams
V
A
0º
I
A
0º
PX5-901
E-7
Split Phase
Split Phase
Introduction
When making split phase measurements, use both channels A and B for voltage and current connections. The neutral is chosen as the reference for measurement purposes.
The figure also shows voltage connection using channel D as a differential input for measuring neutral to ground voltage. Neutral to ground measurements are important but optional.
Connection diagram
Phasor diagrams
180º
V
B
V
A
0º
180º
I
B
I
A
0º
PX5-902
E-8
APPENDIX E/ Common Circuit Connections
3 Phase, Four Wire Wye
Introduction
Channels A, B, and C are connected to voltage and current probes. The neutral is connected to common and is the reference for the three channels. The figure also shows voltage connection using channel D as a differential input for measuring neutral to ground voltage. Neutral to ground measurements are important but optional.
Connection diagram
Phasor diagrams
V
C
V
B
240º
V
A
0º
I
C
I
B
240º
I
A
0º
PX5-903
E-9
3 Phase (Floating or Grounded) Delta
3 Phase (Floating or Grounded) Delta
Introduction
In this power connection, the PX5 uses voltage channels A, B, and C as differential inputs with channel A using source voltage A-B, channel B using B-C, and channel C using C-A as the reference. Current probes are connected to channels A, B, and C.
Neutral to ground measurements are important but optional.
Connection diagram
Floating Delta phasor diagrams
120º
V
C
V
B
240º
V
A
0º
E-10
I
B
210º
90º
I
C
I
A
330º
PX5-904
APPENDIX E/ Common Circuit Connections
3 Phase 2-Watt Delta
Introduction
The figure below shows the 3 Phase 2-Watt delta connection using phase channels A-
B-C. Current probes are connected to channels A and B. Neutral to ground measurements are important but optional.
Connection diagram
Phasor diagrams
PX5-905
60º
V
B
V
A
0º
90º
I
B
I
A
330º
E-11
Generic Circuit
Generic Circuit
Introduction
In the Generic circuit connection, the PX5 uses voltage channels A, B, C, and D as differential inputs. Current probes are connected to channels A, B, C, and D.
Connection diagram
E-12
PX5-906
APPENDIX E/ Common Circuit Connections
2 1/2 Element Without Voltage Channel B
Introduction
Channels A and C are connected to voltage. Current probes are connected to channels
A, B and C. The neutral is connected to common and is the reference for the three channels. The figure also shows voltage connection using channel D as a differential input for measuring neutral to ground voltage. Neutral to ground measurements are important but optional.
Connection diagram
Phasor diagrams
120º
V
C
V
A
0º
PX5-907
120º
I
C
I
B
240º
I
A
0º
E-13
2 1/2 Element Without Voltage Channel C
2 1/2 Element Without Voltage Channel C
Introduction
Channels A and B are connected to voltage. Current probes are connected to channels
A, B and C. The neutral is connected to common and is the reference for the three channels. The figure also shows voltage connection using channel D as a differential input for measuring neutral to ground voltage. Neutral to ground measurements are important but optional.
Connection diagram
Phasor diagrams
V
B
240º
V
A
0º
120º
I
C
I
B
240º
I
A
0º
PX5-908
E-14
APPENDIX E/ Common Circuit Connections
Connecting to a Potential Transformer
Safety
Precautions
NOTE
Follow the safety precautions listed on page E-3 when making all potential transformer connections.
Potential Transformers are not manufactured by Dranetz-BMI and are discussed here for informational purposes only.
Definition
WARNING
A potential transformer (PT), also referred to as a voltage instrument transformer, provides the necessary step-down ratio to reduce the high voltage of circuits above 600
Vrms to a level for safe measurement. A PT also provides isolation and proper connections for instrument attachment.
Connections
PTs are usually fixed in position and require that the voltage probe(s) be connected to their terminal connections.
Refer to the manufacturer’s instructions, related to the PT, for exact information for probe connection for voltage monitoring. Do not exceed 600 Vrms input to the
PX5 voltage inputs.
ADVERTENCIA Consulte las instrucciones del fabricante referentes a TP (transformador potencial), para la información exacta de la conexión de sonda a fin de monitorear
el voltaje. No supere la entrada de 600 Vrms a las entradas de voltaje de PX5.
AVERTISSEMENT
Se reporter aux instructions du fabricant relatives au transformateur de tension
(Potential Transformer - PT) pour obtenir les renseignements exacts sur la connexion de sonde utilisée pour la surveillance du courant. Ne pas dépasser
l’entrée de tension efficace de 600 RMS dans les entrées de tension de PX5 volts.
WARNUNG
Genaue Informationen zur Meßfühlerverbindung für die
Spannungsüberwachung entnehmen Sie bitte den Anleitungen des Herstellers
(siehe Spannungsteilertransformator). Die Eingangsspannung von 600 V
(Effektivwert) in die PX5 Spannungseingänge sollte nicht überschritten werden.
E-15
Connecting to a Potential Transformer, continued
Procedure
Follow these steps to connect voltage probes to a potential transformer.
Step
1
2
3
4
Action
Turn off power to the PT.
Connect the colored voltage probes to the channel inputs on the PX5 top panel.
Connect the colored voltage probes to the PT’s connections in accordance with the manufacturer’s instructions.
Turn on power to the PT.
Scale factor
The scale factor of the PT must be accounted for in making accurate voltage measurements. Because the monitored output voltage of the PT is stepped-down
(divided) from the original voltage, this ratio must be stepped-up (multiplied) by the
PX5 when voltage computations are performed. The PT scale factor is usually mounted on the PT assembly and is entered into the PX5 on the scale factors screen (refer to page 5-10). Refer to the PT manufacturer’s literature for the scale factor of the device you are using.
E-16
APPENDIX E/ Common Circuit Connections
Connecting to a Current Transformer (CT)
Safety precautions
WARNING
The following safety precautions apply to current transformer (CT) connections in addition to those safety precautions stated on page E-3.
• Never energize a CT with the secondary open.
• Never disconnect the secondary of a CT with primary energized.
Refer to the manufacturer’s instructions related to the CT for exact information for connections for current monitoring. Do not exceed manufacturer’s ratings.
ADVERTENCIA Consulte las instrucciones del fabricante referentes a TC (transformador de corriente) para la información exacta de las conexiones a fin de monitorear la corriente. No exceda las capacidades nominales del fabricante.
AVERTISSEMENT
Se reporter aux instructions du fabricant relatives au transformateur de courant
(Current Transformer - CT) pour obtenir les renseignements exacts sur les connexions utilisées pour la surveillance du courant. Ne pas dépasser la puissance recommandée par le fabricant.
WARNUNG
Genaue Informationen zu Verbindungen für die Stromüberwachung entnehmen
Sie bitte den Anleitungen des Herstellers (siehe Stromumwandler). Die
Grenzwerte des Herstellers sollten nicht überschritten werden.
NOTE
Description
Current Transformers are not manufactured by Dranetz-BMI and are discussed here for informational purposes only.
Current transformers, also known as instrument transformers, reduce high level currents to low level currents so they can be safely monitored. These devices are similar to PTs used for voltage measurements in that both reduce values for safe measurement. The reduction, or step-down ratio, is stated as a scale factor that is used by the PX5 to step-up the measured value to its original value.
Types of CTs
There are single-phase CTs and polyphase CTs dependent on the source transformer used. Current reduction ratios vary widely and are also dependent on the source transformer used. Rating plates attached to the CT provide information as to the ratio and current limitations.
E-17
Connecting to an Isolated Current Transformer
Connecting to an Isolated Current Transformer (ISO)
Introduction
Low current monitoring devices made by Dranetz-BMI are called isolated current transformers or ISO boxes. The Dranetz-BMI ISO box has a 5 A current range.
Safety precautions
WARNING
The following safety precautions apply to ISO box connections in addition to those safety precautions stated on page E-3.
• Never energize an ISO box with the secondary open.
• Never disconnect the secondary of an ISO box with primary energized.
Physical injury or equipment damage could result if ISO boxes are improperly connected. Do not connect an ISO box between two conductors which are at different voltage potentials.
ADVERTENCIA Podrían producirse lesiones físicas o daños al equipo si se conectan indebidamente las cajas del transformador aislado de corriente (ISO). No conecte una caja del
ISO entre dos conductores que tengan distintos potenciales de voltaje.
AVERTISSEMENT
Une mauvaise connexion des transformateurs d’intensité isolés (ISO) peut provoquer des blessures corporelles ou des dégâts matériels. Ne pas relier les transformateurs ISO entre deux conducteurs de tensions différentes.
WARNUNG
Falsch angeschlossene ISO-Kästen (Isolierte Stromumwandler) können zu körperlichen Verletzungen oder Geräteschäden fuehren. Schliessen Sie einen ISO-
Kasten nicht zwischen zwei Leiter mit unterschiedlichem Spannungspotential.
Connections to
ISO box
The ISO box has terminal posts labeled X1 and X2 that are connected in series only with an ac current source. In normal connections, where phasing of current and voltages are important for power measurements, the X1 terminal is connected towards the source input line.
Continued on next page
E-18
APPENDIX E/ Common Circuit Connections
Connections to
ISO box
(continued)
When connecting to CTs, the X1 terminal is normally connected to the H1 terminal of the device for correct reference phasing.
Where power measurements or voltage/current phase relationships are not important, the X1 and X2 terminals may be connected in series with the output device in any line
(hot or return) or in any relationship of X1/X2.
Applications
ISO boxes can be used in a number of ways. These methods include:
• connecting them to the secondary of CTs for metering by the PX5.
• inserting them in series with the load current to measure low current values.
• connecting them to a non-Dranetz clamp-on current transformer and using that CT to monitor current with the PX5.
ISO box connection to a current transformer
The figure on the next page shows an ISO box connected from any current channel input to a permanently installed CT. The connection shown is made in the load return line for current monitoring only. Polarities of the ISO box and CT are kept in-phase by matching markings of X1 to H1. Scale factors of both devices must be multiplied together to get the resultant scale factor. The scale factor value calculated for a CT is
3.375.
Continued on next page
E-19
Connecting to an Isolated Current Transformer, continued
CAUTION
DO NOT exceed current limits of the ISO box.
PRECAUCION
NO exceda los límites de corriente de la caja del ISO.
ATTENTION
NE PAS dépasser les limites d’intensité du transformateur ISO.
VORSICHT
Die aktuellen Grenzwerte für den ISO-Kasten sollten NICHT überschritten werden.
ISO box connection to a
CT
E-20
Scale factor = 3.375
to adapter cable
PX5-131
A P P E N D I X F
Event Classification
Range of
Variations as per
IEEE, IEC, &
Dranetz-BMI
Events characterization implemented in PX5 adheres to the IEEE 1159 and IEC 61000-
4-30 Class A measurement standards. The range of variations as per IEEE and IEC standards are featured below, along with quality test measurements for fast transients developed by Dranetz-BMI.
IEEE 1159 IEC 61000-4-30
(deviations from IEEE
1159 only are noted)
Short Duration Variations
Magnitudes
Sag/Dip
Swell
Interruption
(Sag) Vrms Below 90%
(or Low limit) to 10% of nominal
Vrms Above 110% (or
High limit) to 180% of nominal
Vrms Below 10% (or
Very Low limit) of nominal
Temporal
Instantaneous
Momentary
Temporary
Duration
0.5 - 30 cycles
0.5 - 30 seconds
3 - 60 seconds begins when any one phase is Out of Limits; ends when all phases are
Within Limits
Long Duration Variations
Magnitudes
Sag
Swell
Interruption same magnitude values as Short Duration
Variations (see above)
(Dip) Vrms Below 90%
(or Low limit) of nominal
Vrms Above 110% (or
High limit) of nominal
Vrms Below 1% (or
Very Low limit) of nominal
Dranetz-BMI
Duration
Sustained
Cold Load
Pickup is return from sustained
> 1 minute
Continued on next page
F-1
Event Classification, continued
Range of
Variations as per
IEEE, IEC, &
Dranetz-BMI
(continued)
IEEE 1159 IEC 61000-4-30
(deviations from IEEE
1159 only are noted)
Dranetz-BMI
Transients
Impulsive
Oscillatory no more than one transition in each direction ringing freq following initial transition
IEC classification for transients are undefined, as of version approved in
2003.
Peak - absolute value from zero axis
Width - time between 50% of peak rise and fall
High Frequency frequency range duration magnitude
0.5 - 5 MHz
5 us
0 - 4 pu above Vnom
Duration - total time of waveshape trigger
Medium
Frequency frequency range duration magnitude
5 - 500 KHz
20 us
0 - 8 pu above Vnom
Low Frequency frequency range duration magnitude
1/2 cycle - 5 KHz
0.3 - 50 ms
0 - 4 pu above Vnom
Rise - time between
10% and 90% of peak
Fall - time between
90% and 10% of peak
Direction:
Positive - adds energy to curve;
Negative - subtracts energy from curve
Ring frequency - dominant between
2nd and 128th harmonic
Continued on next page
F-2
APPENDIX F/ Event Classification
Range of
Variations as per
IEEE, IEC, and
Dranetz-BMI
(continued)
IEEE 1159 IEC 61000-4-30
(deviations from IEEE
1159 only are noted)
Dranetz-BMI
Waveform Distortion (measured as steady state values from 10/12 cycle calculations)
DC Offset frequency range magnitude
Harmonics frequency range magnitude
Interharmonics frequency range magnitude
Notching frequency range magnitude
Noise frequency range magnitude
0 - 0.1%
DC - 100th
0 - 20%
0 - 6 KHz
0 - 2%
35 KHz
Broadband
0 - 1%
F-3
F-4
A P P E N D I X G
PX5 Menu Structure
Menu structure description
PX5 menu screen maps are shown in the following pages. Use the Level number and Heading as guide to navigate through the different menu screens. Each screen contains touch screen buttons which lead to related functions.
In this appendix
The following screen maps are shown in this appendix.
300/2
300/3
300/4
300/5
220
240
112_101
112_201
112_301
112_401
112_501(a)
112_501(b)
112_601
112_701
400
401
430
470
Level No.
001
100/1
100/2(a)
100/2(b)
100/3(a)
100/3(b)
100/4
100/5
150
108
200
300/1
Home Screen
Heading
Start Menu - Automatic Setup
Start Menu - Wizard Setup
Start Menu - Monitor Same Circuit
Start Menu - Load setup template from card
Start Menu - Load data from card
Instrument Settings
Circuit Type Selection
Scope Mode
Meter Mode - Standard
Meter Mode - Distortion
Meter Mode - User Specified Frequency
Meter Mode - Imbalance
Meter Mode - Advanced
Harmonics
Phasor Display
Advanced Options - Transient Limit
Advanced Options - RMS Variation Limit
Advanced Options - Waveform Capture
Advanced Options - Characterizer Options
Advanced Options - Journal Limit
Advanced Options - Journal Interval
Advanced Options - EN50160
Events
Event Options
G-20
G-21
G-22
G-23
Trend G-24
Reports G-25
G-11
G-12
G-12
G-13
G-14
G-15
G-16
G-17
G-18
G-18
G-19/a
G-19/b
See Page
G-2
G-3
G-4/a
G-4/b
G-5/a
G-5/b
G-6
G-6
G-7
G-8
G-9
G-10
G-1
LEVEL 001
Home Screen
To Level 300
MARK301
To Level 220
MARK221
To Level 200
MARK201
MARK431
To Level 430
MARK501
To Level 400
To Level 100/1
MARK124b
To Level 240
MARK241
MARK151
MARK100
To Level 150
MARK470
To Level 470
G-2
LEVEL 100/1
Start Menu - Automatic Setup
MARK123b
MARK104 MARK104a
MARK103a
MARK100
MARK101a
To Level 001
G-3
LEVEL 100/2(a)
Start Menu - Wizard Setup
MARK104
MARK102
MARK103
MARK100
MARK101
To Level 001
MARK105
MARK107
MARK110
To Level 108 cont. next page
G-4/a
MARK105b
MARK108
LEVEL 100/2(b)
Start Menu - Wizard Setup
MARK109
MARK111 MARK111b
MARK112
To Level 112
MARK113 MARK114
MARK112b
MARK115
G-4/b
LEVEL 100/3a
Start Menu - Monitor Same Circuit
MARK122
MARK123
MARK121
MARK125a
MARK124b
TO LEVEL 100/3b
MARK136
MARK123b
MARK123c
MARK100
MARK141
G-5/a
LEVEL 100/3b
Start Menu - Monitor Same Circuit
MARK125a
MARK125c
MARK125d
MARK125b
MARK131b
MARK126
MARK132
MARK127
MARK129 monitoring turns on upon start time (see screen below)
MARK122
G-5/b
LEVEL 100/4
Start Menu - Load Setup Template from Card
MARK138
MARK139
MARK100
LEVEL 100/5
Start Menu - Load Data from Card
MARK140
MARK100
G-6
LEVEL 150
Instrument Settings
MARK151
MARK152
MARK155
MARK156
MARK158
MARK157
MARK159
MARK160
G-7
LEVEL 108
Circuit Type Selection
MARK108
MARK201
See Level 100/1
To Level 200
MARK241
To Level 240
MARK108d
MARK108e
MARK108f
MARK108g
MARK108a
MARK108b
MARK108c
G-8
LEVEL 200
Scope Mode
MARK202
MARK201
MARK205
G-9
LEVEL 300/1
Meter Mode - Standard
MARK302
MARK303
MARK304
MARK307
MARK306
MARK305
MARK301
G-10
LEVEL 300/2
Meter Mode - Distortion
MARK312
MARK31
3
MARK31
4
MARK316
MARK311
MARK315
G-11
LEVEL 300/3
Meter Mode - User Specified Frequency
MARK322
MARK321
LEVEL 300/4
Meter Mode - Imbalance
MARK332
MARK331
G-12
LEVEL 300/5
Meter Mode - Advanced
MARK342
MARK343
MARK344
MARK345
MARK348
MARK347
MARK346
MARK341
G-13
LEVEL 220
Harmonics
MARK221 switch channel display switch to V, I, or W
MARK235 toggle between graphical harmonics and list of harmonics
MARK236 MARK237
MARK235b
MARK235c
MARK235d
MARK237b
MARK236b
MARK236c
MARK236d
MARK236e toggle between Normalized and UnNormalized phase values
G-14
LEVEL 240
Phasor Display
MARK241 run demo to show rotating phasor relative to sine wave graph of 4 Wire Wye
MARK242
MARK245
Start/Stop demo plot waveforms as rotate phasors switch demo between Resistive, Inductive and Capacitive load effects
MARK243 switch demo between Resistive, Inductive and Capacitive load effects
MARK244
G-15
LEVEL 112_101
Advanced Options -
Transient Limit
MARK112_101
MARK112_102
MARK112_107
MARK112_103
MARK112_104
MARK112_105
MARK112_106
MARK112
G-16
LEVEL 112_201
Advanced Options -
RMS Variation Limit
MARK112_201
MARK112_204
MARK112_205
MARK112_202
MARK112_203
MARK112_206
MARK112_209
MARK112
G-17
LEVEL 112_301
Advanced Options -
Waveform Capture
MARK112_207
MARK112_208
LEVEL 112_401
Advanced Options -
Characterizer Options
MARK112_214
MARK112
MARK112
G-18
LEVEL 112_501(a)
Advanced Options -
Journal Limit
MARK112_302
MARK112_311
MARK112_312
MARK112_313
MARK112_314
MARK112_315
MARK112_316
MARK112_301
MARK112
MARK112_334
MARK112_335
MARK112_336
MARK112_331
MARK112_332
MARK112_333
MARK112_341
MARK112_342
MARK112_351
MARK112_352
G-19/a
LEVEL 112_501(b)
Advanced Options -
Journal Limit
MARK112_301
MARK112_361 MARK112_371 MARK112_381
MARK112_362 MARK112_372
MARK112_373
MARK112_374
MARK112
G-19/b
Level 112_601
Advanced Options -
Journal Interval
MARK112
MARK112_402
MARK112_403
MARK112_404
MARK112_405
MARK112_401
G-20
LEVEL 112_701
Advanced Options -
EN50160 Options
MARK112b
MARK112c
G-21
MARK124b
LEVEL 400
Events
MARK505b
MARK505
MARK502b
MARK506 toggle between waveform and rms display use scroll bar or up/down arrow keys to sort through event list, then press to select (highlight) desired event entry
MARK503
TO LEVEL 401
MARK507 MARK519
MARK504 touch/drag blue zoom box to desired proportion
MARK508
MARK510b
G-22
LEVEL 401
Event Options
MARK500
MARK511
MARK512 press Clear to reset all checkboxes press Cancel to ignore changes and return to original plot
MARK513
G-23
LEVEL 430
Trend
MARK439
MARK440
MARK441
MARK431
MARK432
MARK434
MARK435
MARK438
MARK433
MARK436
MARK437
MARK437b
G-24
LEVEL 470
Reports
MARK474
MARK475
MARK472
MARK473 until Harm #25
MARK491b MARK491c
MARK471 return to
Home screen
MARK476
MARK478
MARK479
MARK480
MARK477
G-25