advertisement
Installation/Owner’s Manual
Use this manual for circuit board 4502-010 Revision K or higher.
For operators manufactured July 2011and later.
Vehicular Swing Gate Operator
6050-065-V-7-11
Post Mount
MO
DE
L
SER
IAL
VO
LTS
AM
PS
CA
CO
NFO
AN
CER
SI/U
TIF
RM
C22
L-
S T
O
325
IED
TO
VE
HICU
CLA
SS
.2 N
LAR
GA
O. 24
TE O
7
HP
533
PER
ATO
82
R
MA
ATE
Doo rKin
AD g, I nc.
PH
AS
60 H
E
, In gle wo od
, C A
W
AR
NIN
G
SER
Op
VIN
IOU
G G
ATE and era
fre te g e o ate onl f p eop Do
no pe t a llow rate
ga Do no t s tan
Rea d o
ch te.
ildr y w le a hen nd o path
w hile
ga d in
ga
RY
OR
ga te a
AU
DE rea en t o p lay i n g ons ate are
SE
ATH n s igh wn er’s te i s m te p
m anu ath or walk
thr oug al a nd s afe ty ins tru ctio ns.
Pad Mount
Date Installed:
Installer/Company Name:
Phone Number:
Leave Manual with Owner
Circuit Board
Serial Number and Revision Letter:
Copyright 2011 DoorKing, Inc. All rights reserved.
UL 325 Compliant
Copyright 2009 DoorKing, Inc. All rights reserved.
TM
6050 / 6100 SPECIFICATIONS
Use this manual for the Model 6050/6100 operators with circuit board 4502-010 Rev K or higher ONLY.
For operators manufactured July 2011 and later.
UL325 Class of Operation Model 6050 Class I Only ; Model 6100 Class I, II, III, IV
Type of Gate
Entrapment Protection
Vehicular Swing Gates Only
Primary - Inherent adjustable clutch (Type C)
Secondary - Inherent entrapment protection system (Type A) and provision for connection of a non-contact sensor (Type B1)
Model #
6050-080
6050-081
Convenience
Open
No
No
Type
Operator
Primary
Secondary
6100-080
6100-081
6100-082
6100-083
No
No
Yes
Yes
Operator Cover Type
Standard
Standard
Horsepower - Volts Amp
1/2 HP - 115 VAC
1/2 HP - 115 VAC
4.3
4.3
Max Gate
Weight
400 Lbs.
400 Lbs.
Max Gate
Length
Cycles Per
Hour
10 Ft.
10
10 Ft.
10
Speed
90°
12-14 Sec
12-14 Sec
Primary
Secondary
Primary
Secondary
Standard
Standard
With Convenience Open
With Convenience Open
1/2 HP - 115 VAC
1/2 HP - 115 VAC
1/2 HP - 115 VAC
1/2 HP - 115 VAC
Pad Mount Kit
P/N 2600-671
27.75” with Convenience Open
23” Standard
5.4
5.4
5.4
5.4
500 Lbs.
500 Lbs.
500 Lbs.
500 Lbs.
14 Ft.
14 Ft.
14 Ft.
14 Ft.
13.5”
60
60
60
60
12-14 Sec
12-14 Sec
12-14 Sec
12-14 Sec
11”
Operator Covers
18”
Post Mount Kit
P/N 2600-674
11”
9.5” 6”
5”
Arm Assembly
6.25”
6.75”
7.25”
6.75”
10.5”
Note: 6100’s with Convenience Open:
Output shaft is offset 1” from center.
Dimensions are the same as shown above for the operator covers.
Arm Assembly
11”
5”
2.25”
Distance can vary.
6” minimum.
DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to this manual. This manual is copyrighted, all rights reserved. No portion of this manual may be copied, reproduced, translated, or reduced to any electronic medium without prior written consent from DoorKing, Inc.
6050-065-V-7-11 1
TABLE OF CONTENTS
SPECIFICATIONS
ASTM F2200 Standard for Gate Construction
Important Safety Instructions
Instructions regarding intended installation:
Important Notices
UL 325 Entrapment Protection
Glossary
Swing Gate Requirements
Swing Gate Protection
SECTION 1 - INSTALLATION
1.2 Post Mount or Pad Mount Base Assembly
1.3 Underground Conduit Requirements
2
1.6 Arm and Gate Bracket Installation
1.7 Manually Adjust the Open and Closed Gate Positions
1.8 Installation of Warning Signs
1.9 Gates Opening Wider Than 90°
SECTION 2 - AC POWER TO OPERATOR(S)
2.1 High Voltage Wire Runs
2.2 High Voltage Terminal Connection
2.3 Bi-Parting Gates Wiring - Dual Gate Operators
SECTION 3 - ADJUSTMENTS
3.1 4502 Circuit Board Description and Adjustments
3.2 DIP-Switch SW 1 Settings
3.3 DIP-Switch SW 2 Settings
3.4 Automatic Open / Close Limit Adjustment
3.6 Inherent Entrapment Protection System
10
10
10
11-12
13
13
14
14
14
15
16
16
16
17
18
18
19
20
21
22
22
6050-065-V-7-11
1
8
9
6
7
4
5
4
4
TABLE OF CONTENTS
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION
4.1 Main and Auxiliary Terminal Descriptions
4.2 Entrapment and Safety Device Locations
4.3 Loop Detector Wiring
SECTION 5 - CIRCUIT BOARD WIRING
5.1 Main Terminal Description
5.3 Auxiliary Terminal Description
5.4 Auxiliary Terminal Wiring
SECTION 6 - OPERATING INSTRUCTIONS
6.1 Power and Reset Switches
Soft Shutdown
Hard Shutdown
6.3 Manual Gate Operation
Emergency Vehicle Access Conditions
FAIL-SAFE Manual Operation
Manual Release
SECTION 7 - OPTIONAL CONVENIENCE OPEN SYSTEM
7.1 Circuit Board 2340 Setup
7.2 DC System Description
SECTION 8 - MAINTENANCE AND TROUBLESHOOTING
8.1 Maintenance
8.2 Troubleshooting
6050-065-V-7-11
Model 6050/6100 Wiring Diagrams
26
26
27
28
28
23
23
24
25
28
28
29-30
31-32
33
33
34
34
35
35
36-37
38
39-42
3
ASTM F2200 Standard for Gate Construction
Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard Specification for Automated
Vehicular Gate Construction. For a copy of this standard, contact ASTM directly at 610-832-9585; [email protected]; or www.astm.org
.
Important Safety Instructions
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object
activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust
and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate
hardware.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. SAVE THESE INSTRUCTIONS!
4
Instructions regarding intended installation:
• Install the gate operator only if:
1. The operator is appropriate for the construction of the gate and the usage class of the gate.
2. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet
(1.83 m) above the ground to prevent a 2 ¼ inch (57.2 mm) diameter sphere from passing through the openings
anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
3. All exposed pinch points are eliminated or guarded.
4. Guarding is supplied for exposed rollers.
• The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate
access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that
persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
• The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures
when opening and closing to reduce the risk of entrapment. Swinging gates should not open into public access areas.
• The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not
over-tighten the operator clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.
• For gate operators utilizing Type D protection:
1. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
2. A warning placard shall be placed adjacent to the controls.
3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.
4. No other activation device shall be connected.
• Controls intended for user activation must be located at least ten feet (10’) away from any moving part of the gate and
where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or
easily accessible controls should have a security feature to prevent unauthorized use.
• The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not
cause the operator to start.
• A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
• For gate operators utilizing a non-contact sensor:
1. See the instructions on the placement of non-contact sensors for each type of application.
2. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate
is still moving in the opening direction.
3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the
perimeter reachable by a moving gate or barrier.
6050-065-V-7-11
• For gate operators utilizing contact sensors:
1. One or more contact sensors shall be located where the risk of entrapment or obstruction exist, such as at the
leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate.
2. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
3. One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
4. A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor
and the gate operator is not subjected to mechanical damage.
5. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for
entrapment protection functions shall be located where the transmission of the signals are not obstructed or
impeded by building structures, natural landscaping or similar obstructions. A wireless contact sensor shall function
under the intended end-use conditions.
6. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).
Important Notices
Vehicular gate operator products provide convenience and security. However, gate operators must use high levels of force to move gates and most people underestimate the power of these systems and do not realize the potential hazards associated with an incorrectly designed or installed system. These hazards may include:
•
• Pinch points
Entrapment areas
•
•
•
• Reach through hazards
Absence of entrapment protection devices
Improperly located access controls
Absence of vehicle protection devices
• Absence of controlled pedestrian access
In addition to these potential hazards, automated vehicular gate systems must be installed in accordance with the UL-325
Safety Standard and the ASTM F2200 Construction Standard. Most lay persons are unaware of, or are not familiar with, these standards. If an automated vehicular gate system is not properly designed, installed, used and maintained, serious injuries or death can result. Be sure that the installer has instructed you on the proper operation of the gate and gate operator system.
Be sure that the installer has trained you about the basic functions of the required reversing systems associated with your gate operating system and how to test them. These include reversing loops, inherent reversing system, electric edges, photoelectric cells, or other external devices.
• This Owner’s Manual is your property. Keep it in a safe place for future reference.
• Be sure that all access control devices are installed a minimum distance of 10 feet away from the gate and gate operator, or in such a way that a person cannot touch the gate or gate operator while using the device. If access control devices are installed in violation of these restrictions, immediately remove the gate operator from service and contact your installing dealer.
• Loops and loop detectors, photo-cells or other equivalent devices must be installed to prevent the gate from closing on vehicular traffic.
• The speed limit for vehicular traffic through the gate area is 5 MPH. Install speed bumps and signs to keep vehicular traffic from speeding through the gate area. Failure to adhere to posted speed limits can result in damage to the gate, gate operator, and to the vehicle.
• Be sure that all persons who will use the gate system are familiar with the proper use of the gate and gate operator and are familiar with the possible hazards associated with the gate system.
• Be sure that warning signs are permanently installed on both sides of the gate in an area where they are fully visible to traffic.
• It is your responsibility to periodically check all entrapment protection devices. If any of these devices are observed to function improperly, remove the operator from service immediately and contact your installing or
• Follow the recommended maintenance schedule.
• Do not allow children to play in the area of the operator or to play with any gate-operating device.
• To remove the gate operator from service, operate the gate to the full open position and then shut off power to the operator at the service panel.
6050-065-V-7-11 5
UL 325 Entrapment Protection
Class I
A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or a garage or parking area associated therewith.
Class II
A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units) hotel, garages, retail store or other building servicing the general public.
STATE PRISON
Class III
A vehicular gate operator (or system) intended for use in a industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
Class IV
A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
This table illustrates the entrapment protection requirements for each of the four UL 325 classes.
6
UL 325
Classifications
Horizontal Slide, Vertical Lift, Vertical Pivot Swing and Vertical Barrier (arm)
Primary Protection Secondary Protection Primary Protection Secondary Protection
Class I and II
Class III
Class IV
A
A, B1 or B2
A, B1, B2 or D
B1, B2 or D
A, B1, B2, D or E
A, B1, B2, D or E
A or C
A, B1, B2 or C
A, B1, B2, C or D
A, B1, B2, C or D
A, B1, B2, C or D
A, B1, B2, C, D or E
A - Inherent entrapment protection system.
B1 - Provision for connection of, or supplied with, a non-contact sensor (photoelectric sensor or the equivalent).
When used as the PRIMARY device, must be monitored.
B2 - Provision for connection of, or supplied with, a contact sensor (edge device or the equivalent).
When used as the PRIMARY device, must be monitored.
C - Inherent adjustable clutch or pressure relief device.
D - Provision for connection of, or supplied with, an actuating device requiring continuous pressure to maintain
opening or closing motion of the gate.
E - An inherent audio alarm.
6050-065-V-7-11
Glossary
GATE - A moving barrier such as a swinging, sliding, raising, lowering, or the like, barrier, that is a stand-alone passage barrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles and completes the perimeter of a defined area.
RESIDENTIAL VEHICULAR GATE OPERATOR – CLASS I - A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or garage or parking area associated therewith.
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR - CLASS II - A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotels, garages, retail store, or other building servicing the general public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR - CLASS III - A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR - CLASS IV - A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
VEHICULAR BARRIER (ARM) OPERATOR (OR SYSTEM) - An operator (or system) that controls a cantilever type device (or system), consisting of a mechanical arm or barrier that moves in a vertical arc, intended for vehicular traffic flow at entrances or exits to areas such as parking garages, lots or toll areas.
VEHICULAR HORIZONTAL SLIDE-GATE OPERATOR (OR SYSTEM) - A vehicular gate operator (or system) that controls a gate which slides in a horizontal direction that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
VEHICULAR SWING-GATE OPERATOR (OR SYSTEM) - A vehicular gate operator (or system) that controls a gate which moves in an arc in a horizontal plane that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
SYSTEM - In the context of these requirements, a system refers to a group of interacting devices intended to perform a common function.
WIRED CONTROL - A control implemented in a form of fixed physical interconnections between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
WIRELESS CONTROL - A control implemented in means other than fixed physical interconnections (such as radio waves or infrared beams) between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
INHERENT ENTRAPMENT PROTECTION SYSTEM - A system, examples being a motor current or speed sensing system, which provides protection against entrapment upon sensing an object and is incorporated as a permanent and integral part of the operator.
EXTERNAL ENTRAPMENT PROTECTION DEVICE - A device, examples being an edge sensor, a photoelectric sensor, or similar entrapment protection device, which provides protection against entrapment when activated and is not incorporated as a permanent part of an operator.
ENTRAPMENT - The condition when an object is caught or held in a position that increases the risk of injury.
6050-065-V-7-11 7
Swing Gate Requirements
The operator is intended for installation only on gates used for vehicles.
Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
(ref. UL325 56.8.4.b)
Closed Gates
Closed Gate
A
If distance is greater than 4 inches, entrapment protection for this area is required. ASTM F2200 7.1.1.1
A
B
If distance is less than 16 inches, entrapment protection in this area is required. ASTM F2200 7.1.1.2
B
Not Allowed
Closed Gate
With the hinge mounted on the corner of the pilaster, eliminated and protection is NOT required for this area.
OK
8
Gates shall have smooth bottom edges, with vertical bottom edged protrusions not exceeding 0.50 inches. ASTM F2200 4.3
6050-065-V-7-11
Swing Gate Protection
D
Reverse Loop
Minimizes the potential of the gate closing when a vehicle is present.
Number and placement of loops is dependent on the application.
Shadow Loop
Provides a hold open command to the operator(s) only if the gate(s) are at the full open position.
C Non-contact Sensor
Minimizes the potential of the gate closing on vehicular or other traffic that loops cannot sense.
See pages 23 and 24 for typical layout locations.
C
D
D Warning Signs
Permanently mounted and easily visible from either side of the gate.
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time without prior warning.
Do not let children operate the gate or play in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
Reverse Loop
Minimizes the potential of the gate closing when a vehicle is present.
Number and placement of loops is dependent on the application.
Separate Pedestrian
Walkway
Located so pedestrians cannot come in contact with the vehicular gate.
Automatic Exit Loop
(Optional) will provide an open command to the gate operator(s) when a vehicle is exiting the property.
See page 25 for loop information.
6050-065-V-7-11 9
10
SECTION 1 - INSTALLATION
Prior to beginning the installation of the swing gate operator, we suggest that you become familiar with the instructions, illustrations, and wiring guide-lines in this manual. This will help insure that your installation is performed in an efficient and professional manner compliant with UL 325 safety and ASTM F2200 construction standards.
The proper installation of the vehicular swing gate operator is an extremely important and integral part of the overall access control system. Check all local building ordinances and building codes prior to installing this operator. Be sure your installation is in compliance with local codes.
1.1 Operator Position 6100 Convenience Open Operators ONLY:
For pad or post mount , convenience open or standard with the gate opening 90°.
See 1.9 for gate’s opening wider than 90°.
Output shaft is offset 1” from center.
The open gate will be 1” closer on one side of the operator OR 1” further away on opposite side of operator as shown.
90°
Open Gate
Gate Bracket
12”
Operator
Output
Shaft
Gate
Bracket
An imaginary straight line drawn from the closed gate bracket through the open gate bracket
MUST intersect the operator output shaft.
12”
Centerline
43”
1”
Offset
Gate Bracket
34”
Open Gate
90°
Imaginary Straight Line
90°
Note: 2” thick gate Illustrated.
Open Gate
12”
6100 convenience open cover is bigger and shaft is offset. (See above detail)
43”
Standard Cover
Operator
Output Shaft
35”
Minimum distance required for arm clearance in the open position.
Note: The operator can be placed further away from the open gate than shown as long as the imaginary straight line drawn from the closed gate bracket through the open gate bracket intersects the operator output shaft.
6050-065-V-7-11
1.2 Post Mount or Pad Mount Base Assembly
(2) 1” bolts through the main gear bracket mounting holes.
(2) 1 1/2” bolts through the main gear bracket mounting holes.
Post Support Base
Screw the posts to the support plate and mount into concrete
BEFORE attaching the operator.
Bottom of
Operator
Hardware for Post Mount:
(2) 1 1/2 inch bolts. For support plate.
(2) 1 inch bolts. For support plate.
(3) Non-slip nuts. For existing threaded studs on bottom of operator.
(2) 1” bolts through the main gear bracket mounting holes.
Pad Support Base
Remove the cover from the operator and GENTLY place the operator on its side before attaching the pad base.
Right
Support
Leg
(2) 1 1/2” bolts through the main gear bracket mounting holes.
Bott om of
Operator
1” Bolts
Hardware for Pad Mount:
(6) 1 inch bolts, lockwashers and nuts for support legs.
(2) 1 inch bolts and nuts for support plate.
(2) 1 1/2 inch bolts and nuts. For support plate.
(3) Non-slip nuts. For existing threaded studs on bottom of operator.
6050-065-V-7-11
Left Supp ort
Leg
11
1.3 Underground Conduit Requirements
Primary
Operator
Position
Secondary
Operator
Position
12
DoorKing’s Primary/Secondary Interconnection Cable (Dual Operator Application Only)
(Secondary Operator AC Power and Communication wires)
Control and/or P.A.M.S. Wires (Low Voltage wire insulation)
Loop Lead-In Wires (Low Voltage wire insulation)
AC Input Power (High Voltage wire insulation) Concrete Pad
Sweeps
• The conduit requirements are for a typical slide gate operator installation (the secondary operator is shown for
those applications where a secondary operator may be used). The conduit requirements for your application may
vary from this depending on your specific needs.
•
• Use only sweeps for conduit bends. Do not use 90° elbows as this will make wire pulls very difficult and can cause
damage to wire insulation.
DoorKing recommends using 3/4-inch conduit.
Sweep
YES
• Be sure that all conduits are installed in accordance with local codes.
Elbow
NO
• Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
1.4 Pad Mount
Note: 2” thick gate Illustrated.
3/8
Secure the operator to the concrete pad with four (4)
3/8” x 3” sleeve anchors
(not supplied).
90°
Important Note: These pad mount measurements will ONLY work when the standard or convenience open models are positioned using the
“1.1 Operator Position”
measurements on page 10.
Open Gate
2.5”
3” 3”
24”
43”
10”
Conduit
14”
12”
Output
Shaft
22”
Operator MUST be level.
Note: Right support leg removed from this illustration to show conduit detail.
Arm
Rotation
Area
Low
Volt
High
Volt
5”
11”
9.5” 6”
Gate Bracket Height
Depth of the concrete pad is determined by soil conditions and local building codes. Reinforced concrete recommended.
Right Support Leg
Concrete Pad
2.5”
24”
Concrete Pad Position
Note: If allowed by local codes, the top of the concrete pad can be flush with ground level, which will allow the gate bracket to be mounted lower on the gate.
6050-065-V-7-11
1.5 Post Mount
Note: 2” thick gate Illustrated.
Mount the post base into the concrete before installing the operator.
The post mount installation will allow the operator to be mounted low enough to attach the gate bracket to the lower gate rail if desired.
90°
Important Note: These post mount measurements will ONLY work when the standard or convenience open models are positioned using the
“1.1 Operator Position”
measurements on page 10.
Open Gate
26”
43”
Operator MUST be level.
Low
Volt
High
Volt
Gate Bracket Height
5”
Arm
Rotation Area
This distance can vary (6” minimum).
Depth of the concrete pad is determined by soil conditions and local building codes. Reinforced concrete recommended.
6”
Concrete
Concrete
Position
12”
Post Base
Conduit
2”
18.5”
Run all conduit on the opposite side of the open gate.
10”
1.6 Arm and Gate Bracket Installation
Closed Gate
60” Connecting Arm
Assemble arms as shown with the gate in the closed
position. The elbow assembly’s flange MUST be on the opposite side of the gate in the closed position. This is the physical stop used to set the open and close limits.
30” Crank Arm
Point arms towards gate bracket.
Crank Power Arm
Flange
Elbow
Assembly
60” Connecting Arm
34”
Adjust the locknut on the crank power arm so that it is snug against the washer, but will still allow the crank arm to rotate with little force. This is the operator’s manual release option when the crank arm is unlocked.
6050-065-V-7-11
Do not secure the elbow assembly to the arms until the arms have been adjusted. (See next page).
5”
Arms MUST be level.
Install gate bracket to gate.
Varies
Gate Rail
Do not insert the locking pin or padlock into the crank arm. It will be installed after arms have been adjusted.
13
1.7 Manually Adjust the Open and Closed Gate Positions
DO NOT
power up the operator to set the open and closed gate positions. The first time the operator is powered up and cycled, it will automatically set the open and close limits. To do this, the arms MUST already be in the correct configuration.
Closed Arms Position Open Arms Position
90°
Closed Gate
90°
Arms must be on the imaginary straight line.
37.5” Approximate pivot point distances.
Elbow flange MUST be in this position.
24”
Arms will be aligned on the SAME imaginary straight line when open or closed. Slide elbow assembly back and fourth, manually opening and closing gate until arms function as shown.
Once you are sure that the gate opens and closes correctly, trim off excess length from arms and secure the arms with the 6 allen screws. Install safety cover on elbow assembly. The arms are now in the correct configuration.
Arms must be on the imaginary straight line.
Crank Arm
Crank Power Arm
Locking Pin
Install the locking pin and padlock in the “Closed Arms Position”.
The operator is now ready for AC power.
14
1.8 Installation of Warning Signs
This DoorKing Swing Gate Operator is shipped with two warning signs. The purpose of the warning sign is to alert uninformed persons, and to remind persons familiar with the gate system, that a possible hazard exists so that appropriate action can be taken to avoid the hazard or to reduce exposure to the hazard. See page 9 for suggested mounting positions of signs.
• Permanently install the supplied warning signs in locations so
that the signs are visible by persons on both sides of the gate.
• Use appropriate hardware such as wood or sheet metal screws
(not supplied) to install the warning signs.
6050-065-V-7-11
1.9 Gates Opening Wider Than 90°
The installation of an operator opening gates wider that 90° is the same for 1.3 through 1.8 except the operator and concrete pad will be in a different position. Individual requirements can be calculated following this 105° demonstrated sample.
Connecting Arm
28”
Gate bracket should not be mounted any farther from the hinge than
28” for any configuration.
Gate
Bracket
Arm Assembly
3
Connecting arm’s pivot point measurement 40”
62.25” minus (crank arm) 22.25” = 40”
Imaginar 44.5”
105°
Open Gate y Line
Sample
1
An imaginary line drawn from the closed gate bracket through the open gate bracket MUST intersect the operator output shaft. The crank and connecting arm’s pivot point calculations will be made from the 2 measurements taken from this line.
62.25”
Elbow Assembly
2
Crank arm’s pivot point measurement
44.5” divided by 2 = 22.25”
22.25”
Crank Arm
24”
6100 convenience open cover is bigger and shaft is offset 1”.
(See 6100 detail on page 10)
4”
5”
6050-065-V-7-11
Operator
Output Shaft
Standard Cover
22.25”
Crank arm’s pivot point measurement in the open position on imaginary line.
36”
Note: Mount operator square to the fence line and NOT parallel to the open gate.
27”
Distance needed for arm clearance in the open position.
8.5”
Safety cover’s installed measurement for any configuration.
15
16
SECTION 2 - AC POWER TO OPERATOR(S)
Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a licensed electrical contractor perform this work.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
2.1 High Voltage Wire Runs
The distance shown in the chart is measured in Feet from the operator to the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. The wire run calculations are based on a power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
Model Type
6050 Single
This table illustrates the high voltage wire size and distance requirements.
Amps Required
4.3
12 AWG
225
Wire Size / Distance in Feet
10 AWG 8 AWG
365 610
6 AWG
915
6050 Dual
6100 Single
6100 Dual
8.6
5.4
10.8
112
180
90
182
290
145
305
485
242
457
725
362
Never
run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
“Optional” 3.3 Amp Heater Installation Note: When installing the heater(s), refer to the “high voltage AC power wire size and
distance requirements” table on the instruction sheet with the heater kit (P/N 1601-154) for AC power wire run requirements.
2.2 High Voltage Terminal Connection
DANGER
HIGH VOLTAGE!
115 VAC
Chassis
Ground
• Route incoming high voltage power through underground conduit and into
the operator as shown in Section 1.4 or 1.5 on page 12 or 13.
• Be sure wiring is installed in accordance with local codes. Be sure to color
code all wiring.
• It is recommended that a surge suppressor be installed on the high voltage
power lines to help protect the operator and circuit board from surges and
• Secondary operator in a dual operator application gets power through the
8-wire interconnection cable that links the 2 operators together. See
Section 2.3 Bi-Parting Gates Wiring - Dual Gate operators on the next page.
Section 1 MUST be completed before power can be turned on.
High Voltage
Conduit
Every time the operator is powered up, the First open command will
automatically set the open and close limits of the gate. (See page 21).
6050-065-V-7-11
2.3 Bi-Parting Gates Wiring - Dual Gate Operators
Connect the Primary/Secondary operators together with DoorKing’s interconnection cable as shown (Different lengths sold separately
P/N 2600-75x). High voltage power and low voltage communications are supplied to the secondary operator by DoorKing’s UL approved cable that is run in a single conduit. Two conduits (High voltage and low voltage) will need to Blue be provided to the secondary operator when NOT using DoorKing’s UL listed, wet Red environment interconnection cable.
1
White
2
3
4
Secondary
Operator Motor
Terminal
Operator
Chassis
Ground
(Green)
Purple
(On select models)
Yellow
5
6
7
8
4502
Brown
9
10
11
12
• All control, loop detector, safety and auxiliary
devices are wired to the primary operator.
• Secondary operator contains
NO 4502 control board.
Gray
(On select models)
Orange
13
14
15
16
17
18
19
20
NC
NO
PO
Secondary Operator
1 2 3
Terminal
4 5 6 7 8
Primary Operator’s
2340 Convenience Open
Circuit Board
Conduit
Primary Operator
Control Board
Primary
Operator
Operator
Chassis
Ground
(Green)
Conduit
6050-065-V-7-11
Secondary
Operator
17
18
SECTION 3 - ADJUSTMENTS
The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) is complete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then turned back on for the new setting to take effect.
3.1 4502 Circuit Board Description and Adjustments
How LEDs Work:
Power LED indicates that low voltage power is applied to the circuit board. Input LEDs should be OFF and will only illuminate when an input is activated. Pulse 1 and 2 LEDs will blink as the operator(s) are running. They can be either ON or OFF when the operator(s) are stopped. One pulse LED for each operator used (Primary/Secondary). Tracker LEDs will flash as operator data is sent to the access controller
(DoorKing models
1833, 1835, 1837 or
1838 only).
1
2
3
4
Board
Power
Secondary
Operator Motor
Terminal
See page 17.
Board
Ground
9410 Single
Channel
5
10
11
12
13
14
8
9
6
7
15
16
17
18
19
20
NC
Pulse 1 LED Primary Operator
Pulse 2 LED Secondary Operator
SW 1
NO
SW 2
Tracker
LEDs
Auxiliary Terminal
See pages 23, 24 and 28.
Power
LED
Loop
LED
Loop
LED
4502
See page 25.
9409 Dual
Channel
Dry Relay
Contact
NC
DIP-Switches
Auto-Close Timer
NO
Dry relay contacts (terminals
16-17) can be set for Normally
Open (NO) or Normally Closed
(NC) operation by placing the relay shorting bar on the N.O. or
N.C. pins respectively. (Standard shadow loop function, NO)
Set the DIP-switches on the circuit board to the desired setting.
See switch-setting charts on next 2 pages.
SW 1
SW 2
Auto-close timer
(when turned ON)
SW 1, switch 4 ON.
SW 1
Adjust from 1 second
(full counter clockwise) to approximately 23 seconds
(full clockwise).
1 23
6050-065-V-7-11
3.2 DIP-Switch SW 1 Settings
The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
Every time the operator is powered up, the First open command will
automatically set the open and close limits of the gate. (See page 21).
SW 1 (Top 8 Switches)
Switch Function Setting Description
1 and 2
3
4
5
6
7
8
Circuit
Board
Relay
Exit Loop Port
Output
Full Open Input
Auto-Close
Timer
Slide Gate
Swing Gate
3-Button
Single Button
Dual Operators
Single Operator
Tamper Protect
1-OFF 2-OFF
1-OFF 2-ON
1-ON 2-OFF
1-ON 2-ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Relay activates when gate is open (Shadow loop setting when used).
Relay activates when gate is not closed.
Relay activates when gate is opening and open.
Relay activates when gate is opening and closing.
The output wired to terminal #12 becomes the output from the exit loop detector plugged into the EXIT Loop port.
Normal Setting. Terminal #12 is a normal full open input.
Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
OFF for Slide gate operator (DO NOT use for 6050/6100).
Normal Setting. ON for Swing gate operator (Switch MUST be ON for 6050/6100).
OFF when using a 3-button station (DoorKing 3-button control stations only).
ON when using a single button control.
Switch must be OFF when bi-parting (dual) gates are used.
Switch must be ON for single operator.
Tamper protect is OFF.
Normal Setting. Tamper protect is ON.
Switches 1-2 These work in conjunction with each other and determine when the relay on the board will be activated. This relay can be used as a switch for various functions such as illuminating a warning light when the gate is moving, or turning on a green light when the gate is full open. This relay is NOT available for these uses if it is being used for the shadow loop function.
Switch 3 Determines that a device wired to terminal #12 is a normal full open command OR terminal #12 becomes the output from the exit loop detector that is plugged into the EXIT Loop port in the circuit board (Used for specialized functions).
Switch 4 Turns the auto close timer on or off. Maximum time that the close timer can be set for is approximately 23 seconds.
Switch 5 This switch enables the 4502 circuit board to be used in either a swing gate or slide gate application. Some older
DoorKing slide gate operators did use the 4501 circuit board for control. This switch is here to allow use of this board on these older products.
Switch 6 Sets up the circuit board for single button or 3-button (open-close-stop) logic (DoorKing 3-button control stations only). Keep this switch in the ON position for single button control.
Switch 7 Sets up the circuit board for single or primary / secondary (dual) gate operation.
Switch 8 If the gate is forced open, the tamper-protect system will start the motor in the close direction when the operator
6050-065-V-7-11 19
3.3 DIP-Switch SW 2 Settings
Switch Function
Every time the operator is powered up, the First open command will
automatically set the open and close limits of the gate. (See page 21).
Setting
SW 2 (Bottom 8 Switches)
Description
1
Primary
Operator
Opening
Direction
OFF
ON
Opens Counter-Clockwise using OFF setting.
Opens Clockwise using ON setting.
2
Secondary
Operator
Opening
Direction
OFF Opens Counter-Clockwise using OFF setting.
ON Opens Clockwise using ON setting.
20
3
4
5
6
Self-Test
Motor Control for Secondary
Operator
Reverse Loop
Shadow Loop
Gate Overlap
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
Normal Setting. Normal operation.
Self-test mode. Operator MUST be disconnected from gate to run self test.
Switch is OFF when both primary and secondary operator motors are powered from main terminals 4 and 5. Applies to operators originally manufactured with
4501, Rev O boards or lower).
Switch is ON when secondary operator motor is powered from the secondary motor terminals. Applies to operators manufactured with 4501, Rev P boards and higher, and all 4502 boards.
Terminal 15 is a normal Reverse input.
Terminal 15 is a Shadow input. Gate will NOT stop during the close cycle.
Primary and secondary operators start at the same time.
Secondary operator starts 1-2 seconds prior to primary operator.
Leave in the OFF position.
Leave in the OFF position.
7
8
Not Used
Not Used
Switch 1 Must OPEN the primary operator’s gate upon initial AC power up and open command. If the FIRST open command begins to close the gate, turn AC power off and reverse this switch.
Switch 2 Must OPEN the secondary operator’s gate upon initial AC power up and open command. If the FIRST open command begins to close the gate, turn AC power off and reverse this switch. This switch will be set the opposite of switch 1 (e.g. If switch 1 is OFF, then switch 2 will be ON).
Switch 3 This switch is a self-test feature that checks various functions of the circuit board and is used for bench test only.
Do not run this test with the operator connected to the gate.
Switch 4 This switch applies high voltage motor power to the secondary operator motor terminal located at the top of the board
(See page 17). If a primary / secondary system is in use, this switch should be ON and the secondary motor wires connected to the secondary operator motor terminal. For single gate applications, this switch can be turned OFF.
Switch 5 This switch sets the input at Terminal 15 to act as a normal reverse input OR to act as a shadow input. A shadow input will only hold the gate operator in the open position once it is in the full open position. A shadow input will not reverse the direction of the gate operator once it begins its close cycle.
Switch 6 Used in primary / secondary applications, turning this switch ON will cause the secondary operator to start 1-2 seconds before the primary operator. This allows the secondary gate to reach the full closed position before the primary gate, which is desirable when the gates are constructed with an overlap or if a magnetic lock is used to secure the gates.
Switches 7 and 8 Spare switches, leave in the OFF position.
6050-065-V-7-11
3.4 Automatic Open / Close Limit Adjustment
The 6050/6100’s open/close limits DO NOT have to be physically adjusted. The gate open and close positions are determined by the physical stop “Flange” on the elbow assembly (See below). The arms MUST already be in the correct closed configuration
(See Section 1.7 on page 14). DO NOT cycle the operator until the arms are in the correct configuration. Every time the operator is powered up, the first open command will automatically run an open and close cycle to locate and remember the
gate’s open and close positions.
Timer:
The Auto-Close Timer should be turned ON (SW 1, switch 4 ON) to allow the operator to run the automatic gate sequence, otherwise a manual close command will be required to complete this sequence.
Clutch:
The clutch’s factory setting will work correctly for most installations. The clutch must NOT slip while the gate is in mid-cycle or the gate limits will be incorrect. If the clutch slips during this period, it must be tightened before running this sequence (See section 3.5 on the next page).
Safety Devices:
Run this sequence before testing any safety features (primary inherent reverse sensor, secondary entrapment protection, entrapment alarm and reset features).
Elbow Assembly
Flange
Crank Arm
Crank Power Arm
Connecting Arm
Sequence of Automatic “Gate Cycle” to Set Gate Limits
CAUTION: Keep pedestrians and vehicles clear of the gate while this sequence is running!
After the first open command is given to the operator (gate can be in any position) :
Open
Gate MUST open until it contacts the physical stop “Flange”. (if gate starts to close, turn power off and change the direction operator opens (SW 2, switch 1). Turn power back on and give open command again).
After the gate cycles to the full OPEN position, the clutch will slip for approximately 2 seconds and shut off.
Close
Auto-close timer will close the gate until it contacts the physical stop “Flange”. (Manual close command required if timer is turned off). When the gate cycles to the full CLOSE position, the clutch will slip for approximately 2 seconds and shut off.
Sequence
Finished
Open and close gate positions are now set and will be remembered by the 6050/6100 (until it loses AC power).
Gate will function normally after automatic sequence has finished.
Cycle the operator again. Operator will reach the open and close positions and shut off without the clutch slipping.
Note: If gate encounters an obstruction during this sequencing, it will automatically continue after obstruction has been cleared.
6050-065-V-7-11 21
3.5 Clutch Adjustment
This vehicular gate operator is equipped with an inherent adjustable clutch (Type C) that is used as the Primary entrapment protection system. The clutch MUST slip upon sensing an obstruction during the open or close cycle which will cause the gate to reverse direction. For this system to function correctly, the gate must be properly installed and work freely in both directions.
A good set of roller bearing hinges is essential for proper swing gate operation.
1. Be sure AC power switch is turned OFF whenever adjustments to the clutch are being made.
Loosen the
upper jamb nut to “un-lock” the lower jamb nut. Loosen the lower jamb nut.
2. Manually move the gate so that it is positioned approximately half way open.
3. Tighten the lower jamb nut finger tight then tighten it ONE turn with a wrench. Re-tighten the upper jamb nut.
4. Turn AC power switch ON and momentarily jump across terminals 11 and 20. When the gate begins to open,
determine if the clutch is slipping. If the clutch is slipping, turn AC power OFF and tighten the lower jamb nut
one more turn. This process may have to be repeated several times to get the clutch adjusted correctly.
Always start the gate from the half open position when adjusting the clutch.
Jamb Nuts
Clutch Note: The ideal clutch adjustment will allow the operator to move the gate through its open and close travel cycle without slipping, but will slip upon contact with an obstruction with no more than 40 Lbs of force. This force can be measured with a gate scale, DoorKing
P/N 2600-225.
CAUTION: Keep pedestrians and vehicles clear of the gate while adjusting and testing the clutch!
Test the Clutch:
Obstruct the gate while it is in the OPENING cycle.
The clutch MUST slip with no more than 40 Lbs of force, then the gate will reverse direction for a quarter of a second and STOP. If the clutch does not slip, it is too tight. Repeat step 4 and re-adjust the clutch.
Note: After the gate has reversed and STOPPED, the operator will be in a “Soft Shutdown”. Momentarily jump across terminals 11 and 20 to continue the opening cycle after the obstruction has been cleared.
Clutch
Obstruct the gate while it is in the CLOSING cycle.
The clutch MUST slip with no more than 40 Lbs of force, then the gate will REVERSE direction back to the open position.
If the clutch does not slip, it is too tight. Repeat step 4 and re-adjust the clutch.
Note: After the gate has reversed back to the open position, the operator will be in a “Soft Shutdown”. Momentarily jump across terminals 11 and 20 to start the closing cycle again after the obstruction has been cleared.
22
3.6 Inherent Entrapment Protection System
In addition to the mechanical slip clutch, this operator uses an inherent entrapment protection system (Type A) to further reduce the possibility of injury should an entrapment occur. This Secondary entrapment protection system (Revering sensor) is
completely automatic and will be activated if the clutch fails to slip when an obstruction is sensed during the open or close cycle. This feature requires no adjustment by the installer or end user.
6050-065-V-7-11
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION
Secondary Entrapment Protection Device:
In addition to the inherent reversing sensor system, the Models 6050/6100 has terminal connections for photo sensors-Type B1 secondary entrapment protection device required by UL 325 standards. Entrapment protection devices must be installed to reduce the risk of injury. Install these devices where the risk of entrapment or a hazard exists while the gate is moving. Specific installations will vary.
4.1 Main and Auxiliary Terminals Description
(2) Two 115 VAC Convenience Outlets
On 6100 with Convenience Open
Model ONLY.
Main Terminal
#15 and #20
CLOSE Direction
Photo Sensor
B
12
13
14
15
16
Standard Reverse
(Normally Open)
17
NC
18
19
NO
20 Common 4502
A
Auxiliary Terminal #7 and #8
OPEN Direction Photo Sensor
Wall
A
OPEN Entrapment Sensor (Photo Sensor): Obstructed opening-direction photo beam will STOP the gate during the
opening-direction only. Gate will resume the open cycle when the obstructed photo beam has been cleared.
Entrapment Protection Device Note:
Specific gate installations may require more entrapment protection devices than are shown here. Install them where necessary to protect against ANY potential entrapment or hazard area.
Wall
B
CLOSE Entrapment Sensor (Photo Sensor): Obstructed closing-direction photo beam will REVERSE and OPEN the gate
during the closing-direction only. Note: If the auto-close timer is ON, when gate reaches the open position, timer will not close the gate.
Another input command is needed to reset and close the gate.
SW 2, switch 5
MUST be OFF.
SW 2
6050-065-V-7-11
Potential
Entrapment
Area
Potential
Hazard Area
Opening Gate
Potential
Pinch Point
Hazard Area
Opening-Direction
Photo Beam
Closing-Direction Photo Beam
Potential Pinch
Point Hazard Area
Potential
Hazard Area
Closing Gate
Potential Entrapment
Zone Hazard Area
23
4.2 Entrapment and Safety Protection Device Locations
5” or less
Typical UL Photo Sensor mounting height and distance away from gate.
Closing-Direction Photo Sensors Opening-Direction Photo Sensors
UL sensor mounted just above top of operator
Wall
21”
Typical
27.5”
Max.
Non-Secure Side
Outside Property
Secure Side
Inside Property
Photo Sensors Sample Setup
This diagram is for illustration purposes. The actual placement of the protection devices is dependent on the specific installation requirements.
Normally Open
SW 2, switch 5
MUST be OFF.
Closing-Direction Photo Beam
Closed Gate
SW 2
Wall
Common
11
12
13
14
15
16
17
18
19
20
Main Terminal
NC
NO
If this space is less than 16 inches, secondary entrapment protection is required in this area.
Auxiliary Terminal
7 8
4502
Opening-Direction
Photo Beam
Normally Open
Common
24
Photo Sensor Power Note: Photo sensors can be powered by Model 6100 with convenience open
ONLY. See previous page for the built-in 115 VAC convenience outlets location for that operator.
6050-065-V-7-11
4.3 Loop Detector Wiring
To help protect the operator from accidentally closing on vehicles in the gate’s path, DoorKing highly recommends that loops and loop detectors be installed. Loops are laid underneath, cut into asphalt or concrete driveways or buried beneath gravel and earth driveways. A loop detection system will sense a vehicle like a metal detector and send a signal to the gate operator preventing the gate from automatically opening or closing on a vehicle when it is in the gate’s path. DoorKing recommends that a licensed installer perform this work.
• Loop detector wiring is shown for DoorKing
plug-in loop detectors. If other loop detectors are
used, refer to the installation instructions supplied
with those detectors for wiring instructions.
• If other detectors are used, use a separate power
supply to power these detectors.
• Loop layout shown is for a typical swing gate
application with two-way traffic, or one-way exit
DoorKing offers a free “Loop and
Loop-Detectors Information
Manual” PDF located at
DoorKing’s web site for more information. www.dkaccess.com
Reverse
Shadow
Reverse
ference.
Automatic Exit Loop
Automatically opens the gate for exiting vehicles without having to use a transmitter or keypad. The exit loop can be placed a minimum of 4 feet away from the reverse loop or far enough away from the gate so the gate has started opening or even completely opened by the time you drive up to it
(Free exit).
Automatic exit loop lead in wires are twisted approx. 6 twists per foot.
LOOP 1
SW 2
4
5
6
7
8
9
10
11
12
1
Jumper Note:
2 SW 2, switch 5
3
Must be ON.
13
14
15 Shadow
16 Relay
17 Relay NC
18
NO
SW 1
SW 2 19
20
SW 1
Exit Loop Port
Relay Note:
SW 1, switches 1 and 2
Must be OFF.
Shadow Loop Note:
Circuit board relay MUST be used and set to N.O.
NC
NO
POWER
Reverse Loop Port
4502
N.O.
Com
6050-065-V-7-11
DoorKing Plug-In
Single Channel
Loop Detector
9410
DoorKing Plug-In
Dual Channel
Loop Detector
9409
Reverse Loops
are placed on each side of the gate to prevent the gate from closing on a vehicle in the gate’s path. They will stop or reverse the cycling of the gate while a vehicle is in or near the gate’s pathway.
Reverse loop lead in wires are twisted approx. 6 twists per foot and are wired in series.
LOOP 1
Shadow Loop
will ONLY HOLD the main gates in the Full Open
Position when a vehicle is on the shadow loop. However, it WILL NOT
stop or reverse the main gates once they start to close.
Shadow loop lead in wires are twisted approx. 6 twists per foot.
LOOP 2
25
26
SECTION 5 - CIRCUIT BOARD WIRING
5.1 Main Terminal Description
DANGER
HIGH VOLTAGE!
• When gate is closed, input will open gate.
• When gate is open and auto close timer
SW 1, switch 4 is turned ON, input will re-set and hold timer.
• When gate is open and auto close timer
SW 1, switch 4 is turned OFF, input will close gate.
SW 1
• When gate is closing, input will reverse gate.
11
Power - Neutral
Power - Neutral
Circuit Board Power
Motor
• lf SW 1, switch 3 is ON, functions as a normal full open input (Normal setting).
• lf SW 1, switch 3 is OFF, input to terminal #4 becomes the output from the
EXIT loop detector plugged into the EXIT loop port. (Used for specialized functions).
SW 1
12
Motor
Not Used
24 VAC - 250 ma. max.
This input ONLY functions when gate is fully
opened or in the closing cycle.
• When gate is closing: SW 2, switch 5 is OFF, an input to terminal #15 (e.g.: photo beam gets obstructed) will reverse and open the gate.
Note: If the auto-close timer is ON, when gate reaches the open position, timer will
not close the gate. Another input command is needed to reset and close the gate.
• When gate is closing: SW 2, switch 5 is
ON, an input to terminal #15 (e.g.: photo beam gets obstructed) has NO effect on the gate operator (Set for Shadow input).
SW 2
15
12 VAC - 150 ma. max.
Pulse 1 - Primary Operator
Pulse 2 - Secondary Operator
Full Open
Full Open
Open - DoorKing 3-Button station ONLY
Operation of the circuit board dry relay contact is dependent on setting of SW 1,
switches 1 and 2.
Relay contacts can be set for Normally
Open (NO) or
Normally Closed (NC) operation.
NC
Contact rating is
1 amp maximum at 24-volts DC.
NO
SW 1
CLOSE - DoorKing 3-Button station ONLY
Standard Reverse or Shadow
Dry Relay Contact
16
Dry Relay Contact
24 VDC Maglock Power
24-volt DC magnetic lock power is provided constantly except when the gate is
opening or open (Normally
Closed function). 1 Amp Max.
18
Low Voltage Common
Low Voltage Common
1
2
3
4
5
6
7
8
9
10
11
12
16
17
18
19
20
13
14
15
NC
NO
6050-065-V-7-11
5.2 Control Wiring
Important:
Controls must be installed a minimum of 10-feet from the gate or installed in such a way that the person using the control cannot come in contact with the gate or gate operator.
#11 - Access Control
Devices
Telephone
Entry
Key Switch
Stand-Alone
Keypad
3-Button Station
DoorKing ONLY
Stand-Alone
Card Reader
Note: All stand-alone and telephone entry devices must use a separate power source.
#12 - Safety
Opening Device
SW 1
SW 1, switch 3 must be ON.
6050-065-V-7-11
Com
Magnetic Lock
Power (24 Volt DC) and logic output. Power is shut off .5 sec. prior to gate starting and remains off while gate is opening and in the open position.
24 Volt
1 amp max.
Com
Red Open
Green Close
White Com
(2) Two 115 VAC
Convenience Outlets
On 6100 with Convenience
Open Model ONLY.
Antenna mounted outside operator cover.
Coax Antenna Kit
P/N 1514-073
3-Wire Radio Receiver
Limited to 250 ma.
Convenience Open Radio
Receiver Note:
Wiring may differ.
See section 7.1 on page 33 for more info.
1
2
3
4
5
6
7 Radio
Open
8
9
10
11
Access
Device
Open
12 Safety
Open
13
14
15
16
17
18
19
Com
20
Com
NC
NO
SW 1
SW 2
27
28
17 NC
5.3 Auxiliary Terminal Description
18
NO
Tracker LEDs
19
20
4502
1 2 3 4 5 6 7
Auxiliary Terminal
8
1. Alarm Output: Provides power to activate the entrapment alarm.
2. Alarm Reset Input: Input to reset the operator after an entrapment alarm.
3. Common: Common for alarm output and alarm reset input.
4. Tracker Data: Supplies gate operator data to Tracker expansion board (P/N 2351-010). Refer to the Tracker Installation
and Wiring Manual for detailed information.
5. Tracker Data: Supplies gate operator data to Tracker expansion board (P/N 2351-010). Refer to the Tracker Installation
and Wiring Manual for detailed information.
6. Tracker Data: Supplies gate operator data to Tracker expansion board (P/N 2351-010). Refer to the Tracker Installation
and Wiring Manual for detailed information.
7. Non-Contact Sensor (Photo Sensor Input): This input will cause the gate operator to stop when activated in either the
operator will resume normal operation (See pages 23 and 24).
8. Common: Common for photo sensor input.
5.4 Auxiliary Terminal Wiring
Red Alarm Output Terminal
Blue Alarm Reset Terminal
White Common Terminal
Remote Alarm Reset Station
(DoorKing P/N 1404-080 Only)
MUST be mounted in the line-of-sight of the gate operator.
DoorKing Access Control System (Model 1833, 1835, 1837 or
1838) tracker system can be connected.
This system can keep track of gate operator cycle count, shorted inputs, loop detector problems, any forced entry attempts, if the gate has struck anything during the open or close cycle, power interruptions, etc.
For more detailed information refer to the Tracker
Installation and Wiring
Manual, DoorKing P/N
2351-010.
Terminal 11 required only if the tracker board will activate the gate operator. Refer to the manual 2351-065 for detailed information.
Gate Tracker
(Quad Box Shown)
8
9
6
7
10
11
2
3
4
5
12
13
14
15
16
17
18
19
20
NC
NO
4502
Auxiliary Terminal
1 2 3 4 5 6 7 8
6050-065-V-7-11
SECTION 6 - OPERATING INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE .
4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving and power has been shut-off.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. .
6.1 Power and Reset Switches
Unlock the power switch cover and open to access the MAIN POWER,
DC POWER and the operator RESET switch.
VEH
CLA
CO
ICU
SS
MO
DE
L
SER
IAL
NF
CA
N/C
SA
SI/U MS
L-3
IED
2.2
TO
25
TO
NO
. 2
47
533
82
PER
HP R
AMP
MA
S
X G
AT
DoorK ing,
OA
D
PH
AS
60 H z
E lew ood
, C
A
W
ARNING
MOV
ING G
Do
Op and
Do path
fre
no
Rea d o te ate t st hile wn an
US gate d in
gate
on ly w
ch ildr er’s
m
IN
ga
JU hen en to te p ovi
ga bstr
pla ath
CA
RY
OR te are ucti y in
CA a is ons.
gate
ar anu al a ng. wal k th
US
ATH in s ea igh t nd s afet y in stru ctio ns.
Reset Switch - Used to turn off the entrapment alarm and to reset the operator after a hard shutdown has occurred.
DC
POWER
AC
POWER
Alarm Siren
OFF OFF
AC Power Switch - Powers the operator
ON (toggle up) or OFF (toggle down).
6050-065-V-7-11
DC Power Switch - Turns the DC system power ON (toggle up) or OFF (toggle down).
This switch is only installed on model 6100 operators with the DC convenience open system installed.
29
30
6.2 Shutdown Conditions
Under various entrapment conditions the operator will assume either a soft or hard (alarm) shutdown. To determine what type of reset action is required, you will need to understand how the different entrapment conditions affect the gate operator.
Soft Shutdown
This occurs in various situations where the inherent or secondary entrapment protection devices have been activated.
In a soft shutdown condition, the operator will not respond to any input that was present when the entrapment protection device sensed an obstruction. If the gate stops at the open position, the operator will not respond to the automatic close timer.
• Example 1 - A time clock keys the gate open in the morning and an entrapment protection device senses
an obstruction prior to the gate reaching the full open position. If the entrapment is sensed by the inherent
system, the gate will reverse and run back to the closed position. The time clock input is still present, but
the gate will not re-open.
Note: In some systems, the time clock input comes from the telephone entry system relay. This same relay may also provide open commands for a card reader, MicroPLUS transmitters and the visitor telephone entry. If so, these devices will also be disabled in a soft shutdown condition.
• Example 2 - If the gate is closing and an entrapment protection device is activated, the gate will either stop
or reverse and run back to the open position, depending upon if the secondary or inherent device was
activated. The automatic close timer will not close the gate.
• Example 3 - Vehicle arrives at open loop and gate runs towards the open position. The inherent entrapment
protection is activated. The gate reverses and runs back to the closed position. If the vehicle is still present
at the open loop a soft shutdown condition does not occur. The loop input provides an immediate reset of
the operator and the gate will again run to the open position.
Resetting a Soft Shutdown
In some conditions, a soft shutdown will reset as soon as the entrapment condition clears. For example, if a non-contact sensor (photo cell) is sensing an obstruction, the operator will stop the gate and assume a soft shutdown condition. When the photocell clears, the operator will return to normal operation.
When the operator is in a soft shutdown, activation of any "intended input" will reset the operator. An "intended input" includes any command, any standard safety input and any loop input. Activating any of these inputs will reset the gate. At that point the gate will return to normal operation. If the gate is open, the automatic close timer will then time out and close the gate.
Hard Shutdown (Alarm Activated)
A hard shutdown condition occurs when the inherent entrapment protection system has sensed TWO consecutive obstructions before the gate reaches the full open or closed position.
• Example - The gate is closing and the inherent entrapment protection system senses an obstruction and
causes the gate to reverse direction. As the gate begins to run in the open direction, a second obstruction
is sensed prior to the gate reaching the full open position. Once the second obstruction has been sensed,
the operator will stop, the audio alarm will be activated and all standard inputs are shut down (including
open commands, safety commands, loop inputs, etc.).
The audio alarm will sound for five minutes, or until the operator’s reset button is pushed. After (5) five minutes the alarm will “chirp every 5 sec.” and the hard shutdown condition will remain in affect until the reset button is pushed.
• After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard
shutdown condition and the reset switch must be activated to reset the operator and silence the alarm.
Continued on next page
6050-065-V-7-11
Resetting a Hard Shutdown
When the operator is in a hard shutdown condition (audio alarm activated or audio alarm “chirps” every 5 seconds), the only way to reset the gate operator and return it to normal operation is to activate the alarm reset input
(auxiliary terminals 2 and 3). An alarm-reset switch can be mounted external of the gate operator provided that it is installed in the line of sight of the gate and gate operator.
• Before resetting a hard shutdown, determine why the shutdown occurred. Inspect the gate for any
obstructions along its path that could have activated the inherent entrapment sensing system. Inspect
the gate and gate hardware.
Note: DoorKing operators have a built-in alarm reset push button mounted on the operator above the power ON-OFF toggle switch. Activating this button will return the gate operator to normal operation, but will not activate the gate operator.
Once the gate has been reset, an open or close command is needed to start the gate operator. Most activating commands will cause the gate operator to cycle to the open position. This includes activation of a key switch or open command and activation of an open loop. Activation of a close command will run the gate to the closed position.
Important Note: The gate operator will not lose its limit settings when a hard shutdown occurs.
6.3 Manual Gate Operation
This operator is equipped with a manual release system that will allow the gate to be pushed open in the event of a power outage or equipment failure.
Never attempt to manually push open any gate with an operator attached to it until you have verified that power to the operator has been shut-off.
Emergency Vehicle Access Conditions
The automatic vehicular gate system must be designed to allow access to emergency vehicles under different operating conditions.
1. During normal powered operation, emergency vehicles access the gate by use of the Emergency Vehicle
Access Device installed on your gate system. The type of device that is used in your community is dependent on your city codes. These devices may include (but are not limited to) Fire Department lock boxes, Click-2-
Enter radio receivers, strobe light sensors, siren sensors, etc.
Convenience Open
2340-010 Circuit Board
2. In the event of a power failure, the emergency vehicle access device may not be functional because the gate operator is un-powered. If the gate operator is equipped with a Convenience Open System , this system will automatically open the gate when primary (AC) power is removed. NOTE: DC convenience open systems are optional and your gate system may or may not be equipped with one. Check with your installer to determine if your gate system is equipped with a convenience open system.
3. In the event of a primary (AC) power failure and a back-up system (DC) power failure (low charged or dead batteries for example), the system must have a release system to allow the gate to be Manually
Operated .
6050-065-V-7-11 31
32
FAIL-SAFE Manual Operation
DC
POWER
The FAIL-SAFE manual operation system is the most reliable and safest method for placing an automated gate in manual operation and is the preferred method of emergency gate operation under worse case conditions by many Fire
Chiefs and Building Inspectors and is typically used in CLASS I and CLASS II applications. This system requires no keys, cranks or tools for manual gate operation and is completely automatic. This prevents any delays for emergency vehicle access in the event that a power outage has occurred.
• When AC power is removed (power failure or switch power off), the operator "FAILS" in a "SAFE" condition
allowing the gate to be manually pushed open without the need of any tools, keys, cranks or other devices.
This assures emergency vehicle access under the worst-case conditions.
AC
POWER
•
For manual FAIL-SAFE gate operation,
turn power to the operator OFF. If a convenience open system
is in use, be sure that DC power is turned OFF first. Once ALL power is OFF, the gate can be manually
operated.
OFF OFF
1
1. Pull the gate crank arm (arm that is attached to the operator shaft) away from the gate so the arms are not in a straight line.
2
Note: If an attempt is made to force the gate open under NORMAL operating conditions (AC power present), a tamper protect circuit
(SW 1, switch 8 ON) will detect the forced entry and will start the motor to return the gate to the closed position.
SW 1
If the Gate Tracker reporting is in use, a forced entry attempt transaction will be sent to the
DoorKing access control system at this time.
1
Pull Crank Arm
• NO AC power Available.
• NO DC power.
Manual Release
In addition to FAIL-SAFE manual operation, this operator also employs a locked release pin to place the gate in manual operation when primary (AC) power is removed.
• NO AC power.
• NO DC power.
To
Manually Release Arm,
turn AC power to the operator
OFF. If a convenience open system is used, be sure to turn
OFF DC power BEFORE turning
OFF AC power.
Crank Arm
Crank Power Arm
DC
POWER
AC
POWER
OFF OFF
Remove padlock and locking pin from crank arm and gate can be manually operated. Crank Power Arm will remain stationary during gate movement.
6050-065-V-7-11
SECTION 7 - OPTIONAL CONVENIENCE OPEN SYSTEM
The optional convenience open system installed in your vehicular gate operator is designed as a convenience enhancement only.
It is not designed or intended to provide continuous gate operation during a power outage. Its sole purpose is to provide a method to open the vehicular gate to allow unimpeded traffic flow when the gate and access control system is without power. If your access control system requires 100% power backup and continuous operation when primary (AC) power has failed, a power inverter / backup system, such as DoorKing’s Model 1000 or Model 2000, is required.
• The convenience open system cannot provide continuous gate operation during a power outage.
•
The gate will cycle (Manual or Automatic Mode) to the open position ONE TIME ONLY after
AC power failure.
• The convenience open system requires testing on a monthly basis to insure the batteries are fully charged and that the
system is operational.
• The convenience open system uses two 12-volt, 3.0 amp-hour gel-cell batteries. These batteries should be replaced
every two years on average, or sooner if required.
• Batteries are affected by temperature. Cold temperatures will reduce the effectiveness of the batteries. High temperatures
will result in a shortened battery life.
• Batteries are not covered under warranty.
7.1 Circuit Board 2340 Setup
Timer:
MUST be adjusted so the gate stops approximately six inches from the full open position. Clockwise increases the DC motor run time, counter-clockwise decreases the run time. Do not allow the DC motor to run long
enough to slip the operator clutch or stall the DC motor. Damage to the circuit board may result from this condition!
Timer
DIP-Switches
2340 Board Terminal
24 Volt
Relay
Com
2340
Automatic Mode after loss of AC Power, Switch 1 ON
The system will automatically open the gate approximately 3 seconds after loss of AC power (The timer will run the DC motor). Automatic mode is
always used for gates in general access applications such as gated communities, apartment complexes, etc.
ON
Manual Mode after loss of AC Power,
Switch 1 OFF, Residential Use ONLY.
1
The system will NOT automatically open the gate after loss of
AC power. A manual input is needed (Remote, push button or a key switch) to open the gate from one of the “Manual Mode
Devices” physically wired to the 2340 circuit board (The timer will run the
DC motor). Any control devices wired to the 4502 main terminal will NOT function after loss of AC power.
Note: If the gate operator is controlled by a DoorKing access controller
(Models 1833, 1835, 1837 or 1838), the “Manual Mode” will NOT function during a power outage.
Emergency
Vehicle Access
Dry Contact
Push Button
Dry Contact
Stand-Alone 3-Wire
Radio Receiver
This radio receiver will work during normal daily operation as well as during a power outage.
The radio receiver will be powered from the operator’s batteries during a power outage.
Manual Mode Device Connection
Restart Options once AC Power is restored,
Switch 3
ON
Once AC power is restored, the system’s control board can be set to “automatically re-key” the
1 2
3
4 5 6 7 8 gate operator (switch 3 ON) to establish normal operation, or can be set to require a “manual input” from the 2340 OR
4502 circuit board (switch 3 OFF) before the operator resumes normal operation.
6050-065-V-7-11 33
7.2 DC System Description
Do Not Adjust
Timer needs to be adjusted.
Do Not Adjust
Batteries
Charging LED
Timer 2340
DIP-Switches
Gate will automatically or manually OPEN and stay open during an AC power failure.
DIP-Switch 3 setting will determine how operator will return to normal operation once AC power has been restored.
Red
Secondary Operator
2340 Board Terminal
2340 Board Terminal
34
COM
See previous page.
Limit
Spare
8
7
DC ON/OFF
Power Switch
Black/White
Red/White
Limit
24VAC
Neutral
4
Motor
To Primary or Single Operator
White to Main Terminal #20
Purple to Main Terminal #7
Green to Main Terminal #11
Motor
Secondary Operator
Terminal
7.3 DIP-Switch Settings
Switch Function
1
Power Failure
Operating Modes
Setting
OFF
ON
Description
Manual input from 2340 board needed to open gate when a power outage occurs.
Gate will automatically open when a power outage occurs.
Opens Counter-Clockwise using OFF setting.
2
Changes
Arm’s
Opening
Direction
OFF
3
4
5-8
Restored
AC Power
Operator
Response
Operator Type
Not Used
ON Opens Clockwise using ON setting.
OFF
ON
OFF
OFF
When AC power is restored, a manual input (push button, loop, radio receiver, etc.) is required to return the gate to normal operation from 2340 or 4502 board.
When AC power is restored, a 1-second pulse is sent to the gate operator input to automatically restore normal operation.
Must be in the OFF position for the 6050 and 6100.
Must be in the OFF position.
6050-065-V-7-11
SECTION 8 - MAINTENANCE AND TROUBLESHOOTING
Inspection and service of this gate operator by a qualified technician should be performed anytime a malfunction is observed or suspected. High cycle usage may require more frequent service checks.
8.1 Maintenance
When servicing the gate operator, always check any secondary (external) reversing devices (loops, photo eyes, etc.) for proper operation. If external reversing devices cannot be made operable, do not place this operator in service until the malfunction can be identified and corrected.
Always check the inherent reversing system when performing any maintenance. If the inherent reversing system cannot be made operable, remove this operator from service until the cause of the malfunction is identified and corrected. Keeping this operator in service when the inherent reversing system is malfunctioning creates a hazard for persons which can result in serious injury or death should they become entrapped in the gate.
When servicing this gate operator, always turn power OFF!!
Every time the operator is powered up, the First open command will
automatically set the open and close limits of the gate. (See page 21).
Operator
Component
Alarm
Arms
Batteries
DC Open System
Drive Belt
Fire Dept.
Gate
Gear
Grease
Maintenance
Monthly Interval
3 6 12
Activate the primary (inherent) reverse system by blocking the gate with a solid object. When the gate reverses, block the gate in the opposite direction prior to the limit being reached. The entrapment alarm should activate. Press the reset button to silence the alarm.
Check set screws and nuts. Check bushings for wear.
If operator is equipped with optional DC open system, check the batteries for any leakage or loose connections. Batteries should be replaced every two years.
If operator is equipped with optional DC open system, check to be sure the system opens the gate upon loss of AC power.
Check for alignment, tightness and wear.
Check emergency vehicle access device for proper operation.
Inspect for damage. Check gate hinges for wear and grease if necessary.
Inspect for wear. Grease if necessary. Use only EP Molybdenum
Disulfide (Moly D) grease (DoorKing P/N 2600-770)
Main shaft zert fitting.
✓
✓
✓
✓
✓
✓
Primary Reverse System
Loop(s)
Release
Secondary Reverse Device
Worm Gear
Complete System
6050-065-V-7-11
Check that the gate reverses on contact with an object in both the opening and closing cycles. Adjust the clutch if necessary.
Check vehicular reverse and shadow loops for proper operation.
Check manual release for proper operation.
Check secondary (external) reverse device(s) stop or reverse the gate when activated.
Inspect for wear and proper alignment.
Complete check of gate and gate operating system.
✓ ✓
35
8.2 Troubleshooting
Have a good VOM meter to check voltages and continuity. A Meg-Ohm meter capable of checking up to 500 meg-ohms of resistance is necessary to properly check the integrity of the ground loops. When a malfunction occurs, isolate the problem to one of three areas: 1) the operator, 2) the loop system, 3) the keying devices. Use caution when checking high voltage areas: terminals 1 through 6, the motor capacitor and the motor.
1. Check the input indicator LEDs. They should only come ON when a keying device (card reader, push button, etc.) is activated. If any of the input LEDs are ON continuously, this will cause the gate operator to hold open. Disconnect the keying devices one at a time until the LED goes OFF.
2. Check any external secondary entrapment protection devices. Any short or malfunction in these devices can cause the gate operator to stop or to hold open.
3. A malfunction in a loop or loop detector can cause the gate operator to hold open, or to not detect a vehicle when it is present over the loop. The LEDs next to the loop detector ports on the operator circuit board will light only when the loop has detected an object above it. If the LEDs stays on after the object has gone, then the loop detector has malfunctioned.
Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction persists, the problem is not with the loop system. For more information on trouble shooting loops and loop detectors, refer to your loop detector instruction sheet and to the DoorKing Loop and Loop Detector Information Manual.
4. Check to be sure that there are no shorted or open control wires from the keying devices to the gate operator. If a keying device fails to open the gate, momentarily jumper across terminals 11 and 20 on the gate operator circuit board. If the gate operator starts, this indicates that a problem exist with the keying device and is not with the gate operator.
5. If a three-button control station (open-close-stop) is connected to this gate operator, check for proper wiring. Only a
DoorKing three button control station (P/N 1200-006) can be used with this gate operator. Others will cause a malfunction.
6. Check the high voltage supply. A voltage drop on the supply line (usually caused by using too small supply voltage wires) will cause the operator to malfunction. Refer to the wire size chart in section 2.1 on page 16.
36
Symptom Possible Solution(s)
Operator will not run.
Power LED is OFF.
• Check that power to the operator is turned ON.
• Transformer may be overheated. Turn power off and allow board to cool for several minutes then
retest. Check for low 115 VAC power and low voltage shorts.
• Check for 115 VAC at terminals 2 and 3. If voltage measures OK, check the terminal strip or
replace the circuit board.
Operator will not run.
Power LED is ON.
• Momentarily jumper terminal 11 to terminal 20. If the input LED does not come ON, check the
terminal strip or replace the circuit board. If LED does come ON, proceed to next steps.
• Check Motor:
Momentarily jumper terminal 11 to terminal 20. If the input LED does not come ON, check the
terminal strip or replace the circuit board. If LED does come ON, proceed to next steps.
Remove circuit board. With power ON, momentarily jumper terminal 3 to terminal 4 with a
14 AWG insulated jumper wire. CAUTION – HIGH VOLTAGE. The motor should run.
With power ON, momentarily jumper terminal 3 to terminal 5 with a 14 AWG insulated jumper wire.
CAUTION – HIGH VOLTAGE. The motor should run in the opposite direction of the above step.
If the motor runs in both steps above, replace the control board. If the motor does not run, or runs
in only one direction, problem can be a bad motor, motor capacitor, wire connections from the
control board to the motor or a bad control board.
Secondary operator motor will not run.
• Check that SW 1, switch 7 is OFF and SW 2, switch 4 is ON.
• Remove circuit board. Momentarily jumper terminal 3 to one of the secondary motor terminals,
then to the other secondary motor terminal with a 14 AWG insulated jumper wire.
CAUTION – HIGH VOLTAGE. The secondary motor should run one way, then the other way as
power is applied to each terminal.
• If the secondary motor runs in both directions, replace the control board. If secondary motor does
not run, or runs in only one direction, problem can be in the wiring from the primary to secondary
operator, bad secondary motor or motor capacitor.
Continued on next page
6050-065-V-7-11
Gate opens a short distance, then stops and reverses.
Gate opens but will not close.
Gate closes but will not open.
• Check that the clutch is adjusted properly and is not slipping.
• Disconnect the gate from the gate operator and check that the gate swings freely without any binding.
• Check that SW 1, switch 7 is set correctly.
• Check the PULSE LED on the circuit board. PULSE 1 should blink as the primary (or single) operator
is running. PULSE 2 should blink as the secondary operator is running. If either PULSE LED is not
blinking as the respective operator is running, check that the magnetic sensor is within 1/32 inch of
the magnetic counter ring.
• Replace the magnetic sensor.
• Continue troubleshooting or replace the circuit board.
• Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.
• Check the secondary safety devices. Any activated will hold the gate open and indicates a problem
with the safety device.
• Check the loop detectors. Any activated can hold the gate open and indicates a problem with the
loop detector or ground loop.
• Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns
to normal operation.
• If automatic close is desired, be sure SW 1, switch 4 is ON.
• Check motor as described on previous page.
• Operator may be in a “soft shutdown.” Check input LEDs on terminals 11-13. If any are ON,
momentarily disconnect, then re-connect the wire going to the respective terminal. Operator should
open.
• Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back
ON. Activate a keying device. Operator should run in the open direction. If operator runs in the
close direction, turn power OFF and change direction switch SW 2, switches 1 and/or 2. Go to
above section if operator now opens but will not close.
• Be sure that the respective LED on the control board lights when the keying device connected to the
respective terminal is activated. If LED does not light, momentarily place a jumper wire from
terminal 20 to the input terminal being checked. If LED lights and gate opens, problem is with the
keying device. If LED does not light, replace control board.
• Check motor as described on previous page.
Gate starts to close, then reverses to open.
• Check that the clutch is adjusted properly and is not slipping.
• Disconnect the gate from the operator and check that the gate operates freely without any binding.
• Check the loop detector LEDs and input LEDs. Any that flash ON will cause the gate to reverse.
• If a shadow loop is used, check for proper wiring. A mis-wired shadow loop detector will cause the
gate to reverse.
• Check the PULSE LED on the circuit board. PULSE 1 should blink as the primary (or single) operator
is running. PULSE 2 should blink as the secondary operator is running. If either PULSE LED is not
blinking as the respective operator is running, check that the magnetic sensor is within 1/32 inch of
the magnetic counter ring.
• Replace the magnetic sensor.
• Continue troubleshooting or replace the circuit board.
Gate closes and then re-opens.
• Check for any input or loop detector LEDs that are ON.
• Check that the operator is running in the proper direction (see “gate closes but will not open” above).
• Check that SW 1, switch 5 is set correctly.
Alarm sounds for 5 minutes and then beeps once every 5 seconds. Operator will not run.
• Operator is in a “hard shutdown” condition. Reset switch must be activated to return operator to
DC open system will not open gate upon
AC power outage.
• Check if the DC system is set to open gate automatically or requires an input to open.
• Check that the DC system power switch is in the ON position.
• Check the batteries for proper voltage. Replace if necessary.
• Replace the DC system circuit board.
6050-065-V-7-11 37
38
8.3 Accessory Items
The following accessory items are available for the model 6050 and 6100 swing gate operators.
Contact Sensors - For use as a secondary entrapment protection device. Miller Edge, Inc., MGO20, MGR20, MGS20
Photo Cell - Non-contact (photo-cells) sensors for use as a secondary entrapment protection device.
MMTC, Inc. Model IR55 P/N 8080-010
MMTC, Inc. Model 60-278
Carlo Gavazzi Type PMP12
Carlo Gavazzi Type PMT
P/N 8080-011
P/N 8080-030
P/N 8080-031
Loop Detector - Detectors plug directly into ports on circuit board simplifying wiring.
P/N 9410-010 - Single channel detector
P/N 9409-010 – Two-channel detector
Magnetic Lock - Magnetic Gate Lock Kit provides an excellent means to secure swing gates and is a fail-safe device allowing emergency vehicle access upon power outage.
P/N 1216-080 and P/N 1216-081
Remote Reset - Provides a remote station to reset an operator in a hard shutdown condition. Must be mounted in line-of-site of the gate and operator. Includes visual and audible signals.
Control Station - Three button interior and exterior control stations provide manual open-close-stop gate operation.
P/N 1200-006 (Exterior) and 1200-007 (Interior, mounts into single-gang electrical box)
Heater and Fan Assembly - Use for cold weather climates where temperatures routinely drop below 40°F (4°C). P/N 1601-154
Interconnect Cable - Interconnect wire cable contains all the necessary wires to interconnect primary / secondary operators.
Cable length 30 feet. P/N 2600-755
Cable length 40 feet. P/N 2600-756
Cable length 50 feet. P/N 2600-757
Time Clock - 7 day and 365 day time clocks can be used to automatically open gate at pre-set time and days. Compact clock fits inside the operator.
P/N 2600-791 - 7 day clock
P/N 2600-795 - 365 day clock
Torsion Rods - Torsion rod assembly is used on uphill swing gates for counter balance.
Hinges - Heavy-duty ball bearing hinges provide easy swing gate operation.
P/N 1200-009, P/N 1200-019, P/N 1200-039.
Surge Devices - High and low voltage surge suppressors help prevent circuit board failure caused by lightning strikes and power surges.
P/N 1876-010 - High Voltage
P/N 1878-010 - Low Voltage
Molly D Grease - Molybdenum Disulfide (Moly D) multi-purpose grease for worm gear. P/N 2600-770 - 14 oz. tube.
Gate Scale - Use to test torque required to move gate. P/N 2600-225
Speed Bumps - Prefabricated six-foot speed bump reduces traffic speed through gate system. P/N 1610-150
6050-065-V-7-11
Model 6050 / 6100
Red
White
Magnetic
Limit Sensor
White
Blue
Red
Yellow
Brown
Orange
6
7
8
9
10
11
12
3
4
5
1
2
13
14
15
16
17
18
19
20
NC
NO
Red
6050 30uf Capacitor
OR
6100 50uf Capacitor
Blue
6050 1/2 HP - 4.3 amp
OR
6100 1/2 HP - 5.4 amp
White
Blue
Red
Board
Ground
Ground
Ground
POWER
4502
Red
Yellow
White
Black
Chassis
Ground
NEU HOT
115 VAC
White
Yellow
Reset
Black
Black
Alarm
AC Power
6050-065-V-7-11 39
Model 6100 / Convenience Open
Batteries
Red
50uf Capacitor
Magnetic
Limit Sensor
Blue
Blue
Red
White
Red
Board
Ground
Black/White
Red/White
2340
White
Purple
Green
Blue
Red
Purple
Yellow
Brown
Green
Orange
White
6
7
8
9
10
11
12
3
4
5
1
2
13
14
15
16
17
18
19
20
NC
NO
1/2 HP
Ground
POWER
Ground
4502
Red
White
Red
Yellow
White
Convenience Outlets
White Brown
Neutral
Power
White
Yellow
Reset
Brown
Brown
Chassis
Ground
NEU HOT
115 VAC
40
Alarm
DC Power AC Power
6050-065-V-7-11
Model 6050 / 6100 Secondary Operator
6050 1/2 HP - 4.3 amp
OR
6100 1/2 HP - 5.4 amp
Ground
White
Blue
Red
Blue
Red
6050 30uf Capacitor
OR
6100 50uf Capacitor
Magnetic
Limit Sensor
Orange
Brown
Yellow
Orange
Brown
Yellow
White
Blue
Red
8. Gray
7. Orange
6. Brown
5. Yellow
4. Purple
3. White
2. Blue
1. Red
6050-065-V-7-11 41
42
Model 6100 Secondary Operator / Convenience Open
Ground
1/2 HP
White
Blue
Red
Blue
50uf Capacitor
Red
Magnetic
Limit Sensor
Orange
Brown
Yellow
Red/White
DC Power
Red/White
Black/White
Red
Black
Green
Orange
White
Brown
Yellow
Purple
White
Blue
Red
8. Gray
7. Orange
6. Brown
5. Yellow
4. Purple
3. White
2. Blue
1. Red
2340
Batteries
6050-065-V-7-11
6050-065-V-7-11 43
Installation/Owner’s Manual
Use this manual for circuit board 4502-010 Revision K or higher.
For operators manufactured July 2011and later.
Vehicular Swing Gate Operator
6050-065-V-7-11
www.doorking.com
DoorKing, Inc.
120 Glasgow Avenue
Inglewood, California 90301
U.S.A.
Phone: 310-645-0023
Fax: 310-641-1586
Copyright 2009 DoorKing, Inc. All rights reserved.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement