advertisement
MODEL
MODEL
CODE
SH (NA) 030034-F (0709) MEE Printed in Japan
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
Specifications subject to change without notice.
General-Purpose AC Servo
J2-Super
Series
Program Compatible
MODEL
MR-J2S- CL
SERVO AMPLIFIER
INSTRUCTION MANUAL
F
Safety Instructions
(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the servo amplifier and servo motor until you have read through this Instruction Manual, Installation guide, Servo motor Instruction Manual and appended documents carefully and can use the equipment correctly. Do not use the servo amplifier and servo motor until you have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
WARNING
CAUTION
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight injury to personnel or may cause physical
damage.
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols:
: Indicates what must not be done. For example, "No Fire" is indicated by .
: Indicates what must be done. For example, grounding is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT".
After reading this installation guide, always keep it accessible to the operator.
A - 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier, whether the charge lamp is off or not.
Connect the servo amplifier and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, you may get an electric shock.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the power is off. The servo amplifier is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Install the servo amplifier, servo motor and regenerative resistor on incombustible material. Installing them directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal, Otherwise, a burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor, servo motor, etc.since they may be hot while power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their masses.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The servo amplifier and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts missing.
When you keep or use it, please fulfill the following environmental conditions.
Ambient
Environment temperature
Ambient humidity
Ambience
Altitude
In storage
In operation
In storage
Servo amplifier
In operation [ ] 32 to 131 (non-freezing)
[ ] 20 to 65 (non-freezing)
[ ] 4 to 149 (non-freezing)
90%RH or less (non-condensing)
90%RH or less (non-condensing)
Max. 1000m (3280 ft) above sea level
Conditions
Servo motor
0 to 40 (non-freezing)
32 to 104 (non-freezing)
15 to 70 (non-freezing)
5 to 158 (non-freezing)
80%RH or less (non-condensing)
Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
[m/s 2 ] 5.9 or less
HC-KFS Series
HC-MFS Series
HC-UFS13 to 73
HC-SFS81
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72 152
X Y : 49
X Y : 24.5
HC-SFS121 201
HC-SFS202 352
HC-SFS203 353
HC-UFS202
X : 24.5
Y : 49
HC-SFS301
(Note)
Vibration
X : 24.5
Y : 29.4
[ft/s 2 ] 19.4
HC-KFS Series
HC-MFS Series
HC-UFS 13 to 73
HC-SFS81
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72 152
X Y : 161
X Y : 80
HC-SFS121 201
HC-SFS202 352
HC-SFS203 353
HC-UFS202
X : 80
Y : 161
HC-SFS301
X : 80
Y : 96
Note. Except the servo motor with reduction gear.
A - 3
CAUTION
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the servo amplifier and servo motor.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF option) between the servo motor and servo amplifier.
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W) directly. Do not let a magnetic contactor, etc. intervene.
Servo amplifier
U
V
W
U
Servo motor
V
M
W
Servo amplifier
U
V
W
U
Servo motor
V
M
W
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in the specified direction. Otherwise, the forced stop (EMG) and other protective circuits may not operate.
Servo amplifier
COM
(24VDC)
Control output signal
RA
Servo amplifier
COM
(24VDC)
Control output signal
RA
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block
(connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified torque.
A - 4
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an accident.
A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break a servo amplifier.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ballscrew and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the servo amplifier signals but also by an external forced stop (EMG).
Contacts must be open when servo-off, when an trouble (ALM) and when an electromagnetic brake interlock (MBR).
Servo motor
RA EMG
Circuit must be opened during forced stop (EMG).
24VDC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
A - 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Specifications and Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Specifications and Instruction Manual.
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace, medicine, passenger movement vehicles or underwater relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Home position setting in the absolute position detection system
Write to the EEP-ROM due to device changes
Write to the EEP-ROM due to program changes
PRECAUTIONS FOR CHOOSING THE PRODUCTS
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
A - 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in
January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety requirements and carry the CE marks (CE marking). CE marking applies to machines and equipment into which servo amplifiers have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and equipment. This requires the EMC filters to be used with the servo-incorporated machines and equipment to comply with the EMC directive. For specific EMC directive conforming methods, refer to the EMC Installation Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with the low voltage directive.
This servo is certified by TUV, third-party assessment organization, to comply with the low voltage directive.
(3) Machine directive
Not being machines, the servo amplifiers need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier series :MR-J2S-10CL to MR-J2S-700CL
Servo motor series
MR-J2S-10CL1 to MR-J2S40CL1
:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HC-LFS
(2) Configuration
Control box
Reinforced insulating transformer
No-fuse breaker
NFB
Magnetic contactor
MC
Reinforced insulating type
24VDC power supply
Servo amplifier
Servo motor
M
(3) Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
A - 7
(4) Power supply
(a) Operate the servo amplifier to meet the requirements of the overvoltage category II set forth in
IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC or EN
Standard should be used in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked ) of the servo amplifier to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal (marked ). Always connect the cables to the terminals one-to-one.
PE terminals PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals
(marked ) of the servo amplifier must be connected to the corresponding earth terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard compliant power connector sets are available from us as options.
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant products of the models described in section 14.2.2.
(b) The sizes of the cables described in section 14.2.1 meet the following requirements. To meet the other requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [ ( )]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the servo amplifier has been installed, it must conform to the electromagnetic compatibility (immunity/emission) standards after it has satisfied the operating environment/electrical equipment specifications.
For the other EMC directive guidelines on the servo amplifier, refer to the EMC Installation
Guidelines (IB(NA)67310).
A - 8
CONFORMANCE WITH UL/C-UL STANDARD
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier series :MR-J2S-10CL to MR-J2S-700CL
Servo motor series
MR-J2S-10CL1 to MR-J2S-40CL1
:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
(2) Installation
Install a cooling fan of 100CFM (2.8m
3 /min) air flow 4 [in] (10.16 [cm]) above the servo amplifier or provide cooling of at least equivalent capability.
(3) Short circuit rating
This servo amplifier conforms to the circuit whose peak current is limited to 5000A or less. Having been subjected to the short-circuit tests of the UL in the alternating-current circuit, the servo amplifier conforms to the above circuit.
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for
15 minutes after power-off.
Servo amplifier Discharge time [min]
MR-J2S-10CL(1) 20CL(1) 1
MR-J2S-40CL(1) 60CL 2
MR-J2S-70CL to 350CL 3
MR-J2S-500CL 700CL 5
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE
WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual.
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual are required if you use the MR-J2S-CL for the first time. Always purchase them and use the MR-J2S-CL safely.
Relevant manuals
Manual name Manual No.
MELSERVO Servo Motor Instruction Manual
EMC Installation Guidelines
SH(NA)3181
IB(NA)67310
A - 9
MEMO
A - 10
CONTENTS
1. FUNCTIONS AND CONFIGURATION 1- 1 to 1-26
1.1 Introduction.............................................................................................................................................. 1- 1
1.1.1 Function block diagram ................................................................................................................... 1- 1
1.1.2 System configuration........................................................................................................................ 1- 4
1.1.3 I/O devices ......................................................................................................................................... 1- 9
1.2 Servo amplifier standard specifications ............................................................................................... 1-10
1.3 Function list ............................................................................................................................................ 1-12
1.4 Model code definition ............................................................................................................................. 1-13
1.5 Combination with servo motor.............................................................................................................. 1-14
1.6 Structure.................................................................................................................................................. 1-15
1.6.1 Part names ....................................................................................................................................... 1-15
1.6.2 Removal and reinstallation of the front cover .............................................................................. 1-19
1.7 Servo system with auxiliary equipment............................................................................................... 1-21
2. INSTALLATION 2- 1 to 2- 4
2.1 Environmental conditions....................................................................................................................... 2- 1
2.2 Installation direction and clearances .................................................................................................... 2- 2
2.3 Keep out foreign materials ..................................................................................................................... 2- 3
2.4 Cable stress .............................................................................................................................................. 2- 4
3. SIGNALS AND WIRING 3- 1 to 3-40
3.1 Standard connection example ................................................................................................................ 3- 2
3.2 Internal connection diagram of servo amplifier ................................................................................... 3- 3
3.3 I/O signals................................................................................................................................................. 3- 4
3.3.1 Connectors and signal arrangements............................................................................................. 3- 4
3.3.2 Signal (devices) explanations .......................................................................................................... 3- 5
3.4 Detailed description of signals (devices) .............................................................................................. 3-12
3.4.1 Forward rotation start Reverse rotation start Temporary stop/restart................................. 3-12
3.4.2 Movement complete......................................................................................................................... 3-13
3.4.3 Override ............................................................................................................................................ 3-14
3.4.4 Torque limit...................................................................................................................................... 3-15
3.5 Alarm occurrence timing chart ............................................................................................................. 3-17
3.6 Interfaces................................................................................................................................................. 3-18
3.6.1 Common line .................................................................................................................................... 3-18
3.6.2 Detailed description of the interfaces ............................................................................................ 3-19
3.7 Input power supply circuit..................................................................................................................... 3-23
3.7.1 Connection example ........................................................................................................................ 3-23
3.7.2 Terminals.......................................................................................................................................... 3-25
3.7.3 Power-on sequence........................................................................................................................... 3-26
3.8 Connection of servo amplifier and servo motor ................................................................................... 3-28
3.8.1 Connection instructions .................................................................................................................. 3-28
3.8.2 Connection diagram ........................................................................................................................ 3-28
3.8.3 I/O terminals .................................................................................................................................... 3-30
3.9 Servo motor with electromagnetic brake ............................................................................................. 3-32
1
3.10 Grounding ............................................................................................................................................. 3-36
3.11 Servo amplifier terminal block (TE2) wiring method....................................................................... 3-37
3.11.1 For the servo amplifier produced later than Jan. 2006 ............................................................. 3-37
3.11.2 For the servo amplifier produced earlier than Dec. 2005.......................................................... 3-39
3.12 Instructions for the 3M connector....................................................................................................... 3-40
4. OPERATION 4- 1 to 4-52
4.1 When switching power on for the first time.......................................................................................... 4- 1
4.1.1 Pre-operation checks ........................................................................................................................ 4- 1
4.1.2 Startup............................................................................................................................................... 4- 2
4.2 Program operation mode......................................................................................................................... 4- 5
4.2.1 What is program operation mode? .................................................................................................. 4- 5
4.2.2 Programming language.................................................................................................................... 4- 6
4.2.3 Basic setting of signals and parameters........................................................................................ 4-25
4.2.4 Program operation timing chart .................................................................................................... 4-26
4.3 Manual operation mode ......................................................................................................................... 4-27
4.3.1 Jog operation .................................................................................................................................... 4-27
4.3.2 Manual pulse generator operation................................................................................................. 4-29
4.4 Manual home position return mode ..................................................................................................... 4-31
4.4.1 Outline of home position return ..................................................................................................... 4-31
4.4.2 Dog type home position return....................................................................................................... 4-33
4.4.3 Count type home position return ................................................................................................... 4-35
4.4.4 Data setting type home position return ........................................................................................ 4-37
4.4.5 Stopper type home position return ................................................................................................ 4-38
4.4.6 Home position ignorance (servo-on position defined as home position)..................................... 4-39
4.4.7 Dog type rear end reference home position return....................................................................... 4-40
4.4.8 Count type front end reference home position return.................................................................. 4-41
4.4.9 Dog cradle type home position return ........................................................................................... 4-42
4.4.10 Home position return automatic return function....................................................................... 4-43
4.5 Absolute position detection system....................................................................................................... 4-44
4.6 Serial communication operation ........................................................................................................... 4-47
4.6.1 Positioning operation in accordance with programs .................................................................... 4-47
4.6.2 Multidrop system............................................................................................................................. 4-47
4.6.3 Group designation ........................................................................................................................... 4-48
4.7 Incremental value command system .................................................................................................... 4-50
5. PARAMETERS 5- 1 to 5-26
5.1 Parameter list .......................................................................................................................................... 5- 1
5.1.1 Parameter write inhibit ................................................................................................................... 5- 1
5.1.2 List ..................................................................................................................................................... 5- 2
5.2 Detailed explanation .............................................................................................................................. 5-21
5.2.1 Electronic gear ................................................................................................................................. 5-21
5.2.2 Changing the status display screen............................................................................................... 5-22
5.2.3 S-pattern acceleration/deceleration ............................................................................................... 5-23
5.2.4 Analog output................................................................................................................................... 5-23
5.2.5 Changing the stop pattern using a limit switch ...........................................................................5-26
5.2.6 Alarm history clear.......................................................................................................................... 5-26
5.2.7 Software limit................................................................................................................................... 5-26
2
6. MR Configurator (SERVO CONFIGURATION SOFTWARE) 6- 1 to 6-22
6.1 Specifications ........................................................................................................................................... 6- 1
6.2 System configuration............................................................................................................................... 6- 1
6.3 Station setting.......................................................................................................................................... 6- 3
6.4 Parameters............................................................................................................................................... 6- 4
6.5 Simple Program ....................................................................................................................................... 6- 6
6.5.1 Program data .................................................................................................................................... 6- 6
6.5.2 Indirect addressing........................................................................................................................... 6- 8
6.6 Device assignment method.................................................................................................................... 6-10
6.7 Test operation ......................................................................................................................................... 6-14
6.7.1 Jog operation .................................................................................................................................... 6-14
6.7.2 Positioning operation....................................................................................................................... 6-16
6.7.3 Motor-less operation........................................................................................................................ 6-18
6.7.4 Output signal (DO) forced output .................................................................................................. 6-19
6.7.5 Program test operation ................................................................................................................... 6-20
6.8 Alarm history .......................................................................................................................................... 6-22
7. DISPLAY AND OPERATION 7- 1 to 7-20
7.1 Display flowchart..................................................................................................................................... 7- 1
7.2 Status display .......................................................................................................................................... 7- 2
7.2.1 Display transition ............................................................................................................................. 7- 2
7.2.2 Display examples.............................................................................................................................. 7- 3
7.2.3 Status display list ............................................................................................................................. 7- 4
7.3 Diagnosis mode ........................................................................................................................................ 7- 5
7.3.1 Display transition ............................................................................................................................. 7- 5
7.3.2 Diagnosis mode list........................................................................................................................... 7- 6
7.4 Alarm mode .............................................................................................................................................. 7- 8
7.4.1 Display transition ............................................................................................................................. 7- 8
7.4.2 Alarm mode list................................................................................................................................. 7- 9
7.5 Parameter mode ..................................................................................................................................... 7-11
7.5.1 Parameter mode transition............................................................................................................. 7-11
7.5.2 Operation example .......................................................................................................................... 7-12
7.6 External I/O signal display.................................................................................................................... 7-14
7.7 Output signal (DO) forced output ......................................................................................................... 7-15
7.8 Test operation mode ............................................................................................................................... 7-16
7.8.1 Mode change..................................................................................................................................... 7-16
7.8.2 Jog operation .................................................................................................................................... 7-17
7.8.3 Positioning operation....................................................................................................................... 7-18
7.8.4 Motor-less operation........................................................................................................................ 7-19
8. GENERAL GAIN ADJUSTMENT 8- 1 to 8-12
8.1 Different adjustment methods ............................................................................................................... 8- 1
8.1.1 Adjustment on a single servo amplifier.......................................................................................... 8- 1
8.1.2 Adjustment using MR Configurator (servo configuration software) ........................................... 8- 2
8.2 Auto tuning .............................................................................................................................................. 8- 3
8.2.1 Auto tuning mode ............................................................................................................................. 8- 3
8.2.2 Auto tuning mode operation ............................................................................................................ 8- 4
3
8.2.3 Adjustment procedure by auto tuning............................................................................................ 8- 5
8.2.4 Response level setting in auto tuning mode .................................................................................. 8- 6
8.3 Manual mode 1 (simple manual adjustment)....................................................................................... 8- 7
8.3.1 Operation of manual mode 1 ........................................................................................................... 8- 7
8.3.2 Adjustment by manual mode 1 ....................................................................................................... 8- 7
8.4 Interpolation mode ................................................................................................................................. 8-10
8.5 Differences in auto tuning between MELSERVO-J2 and MELSERVO-J2-Super .......................... 8-11
8.5.1 Response level setting ..................................................................................................................... 8-11
8.5.2 Auto tuning selection....................................................................................................................... 8-11
9. SPECIAL ADJUSTMENT FUNCTIONS 9- 1 to 9-10
9.1 Function block diagram .......................................................................................................................... 9- 1
9.2 Machine resonance suppression filter ................................................................................................... 9- 1
9.3 Adaptive vibration suppression control................................................................................................. 9- 3
9.4 Low-pass filter ......................................................................................................................................... 9- 5
9.5 Gain changing function........................................................................................................................... 9- 5
9.5.1 Applications....................................................................................................................................... 9- 5
9.5.2 Function block diagram ................................................................................................................... 9- 6
9.5.3 Parameters ........................................................................................................................................ 9- 7
9.5.4 Gain changing operation.................................................................................................................. 9- 9
10. INSPECTION 10- 1 to 10- 2
11. TROUBLESHOOTING 11- 1 to 11-12
11.1 Trouble at start-up .............................................................................................................................. 11- 1
11.2 When alarm or warning has occurred ............................................................................................... 11- 2
11.2.1 Alarms and warning list .............................................................................................................. 11- 2
11.2.2 Remedies for alarms..................................................................................................................... 11- 3
11.2.3 Remedies for warnings................................................................................................................11-11
11.3 MR-DP60 external digital display error...........................................................................................11-12
12. OUTLINE DIMENSION DRAWINGS 12- 1 to 12- 8
12.1 Servo amplifiers................................................................................................................................... 12- 1
12.2 Connectors............................................................................................................................................ 12- 6
13. CHARACTERISTICS 13- 1 to 13- 8
13.1 Overload protection characteristics................................................................................................... 13- 1
13.2 Power supply equipment capacity and generated loss .................................................................... 13- 2
13.3 Dynamic brake characteristics........................................................................................................... 13- 4
13.3.1 Dynamic brake operation............................................................................................................. 13- 4
13.3.2 The dynamic brake at the load inertia moment........................................................................ 13- 6
13.4 Encoder cable flexing life .................................................................................................................... 13- 6
13.5 Inrush Currents at Power-On of Main Circuit and Control Circuit .............................................. 13- 7
4
14. OPTIONS AND AUXILIARY EQUIPMENT 14- 1 to 14-50
14.1 Options.................................................................................................................................................. 14- 1
14.1.1 Regenerative options .................................................................................................................... 14- 1
14.1.2 FR-BU2 brake unit....................................................................................................................... 14- 8
14.1.3 Power regeneration converter ....................................................................................................14-14
14.1.4 Cables and connectors.................................................................................................................14-17
14.1.5 Junction terminal block (MR-TB20) ..........................................................................................14-25
14.1.6 Maintenance junction card (MR-J2CN3TM) ............................................................................14-27
14.1.7 External digital display (MR-DP60) ..........................................................................................14-29
14.1.8 Manual pulse generator (MR-HDP01) ......................................................................................14-31
14.1.9 Battery (MR-BAT, A6BAT).........................................................................................................14-32
14.2 Auxiliary equipment ..........................................................................................................................14-33
14.2.1 Recommended wires....................................................................................................................14-33
14.2.2 No-fuse breakers, fuses, magnetic contactors...........................................................................14-35
14.2.3 Power factor improving reactors ................................................................................................14-35
14.2.4 Relays............................................................................................................................................14-36
14.2.5 Surge absorbers ...........................................................................................................................14-36
14.2.6 Noise reduction techniques.........................................................................................................14-37
14.2.7 Leakage current breaker ............................................................................................................14-44
14.2.8 EMC filter.....................................................................................................................................14-46
14.2.9 Setting potentiometers for analog inputs..................................................................................14-49
15. COMMUNICATION FUNCTIONS 15- 1 to 15-36
15.1 Configuration ....................................................................................................................................... 15- 1
15.1.1 RS-422 configuration.................................................................................................................... 15- 1
15.1.2 RS-232C configuration ................................................................................................................. 15- 2
15.2 Communication specifications............................................................................................................ 15- 3
15.2.1 Communication overview............................................................................................................. 15- 3
15.2.2 Parameter setting......................................................................................................................... 15- 4
15.3 Protocol ................................................................................................................................................. 15- 5
15.4 Character codes ................................................................................................................................... 15- 7
15.5 Error codes ........................................................................................................................................... 15- 8
15.6 Checksum ............................................................................................................................................. 15- 8
15.7 Time-out operation .............................................................................................................................. 15- 9
15.8 Retry operation .................................................................................................................................... 15- 9
15.9 Initialization........................................................................................................................................15-10
15.10 Communication procedure example ...............................................................................................15-10
15.11 Command and data No. list.............................................................................................................15-11
15.11.1 Read commands.........................................................................................................................15-11
15.11.2 Write commands........................................................................................................................15-14
15.12 Detailed explanations of commands...............................................................................................15-16
15.12.1 Data processing..........................................................................................................................15-16
15.12.2 Status display ............................................................................................................................15-18
15.12.3 Parameter...................................................................................................................................15-19
15.12.4 External I/O signal statuses.....................................................................................................15-21
15.12.5 Input devices ON/OFF ..............................................................................................................15-23
15.12.6 Disable/enable of I/O devices (DIO) .........................................................................................15-24
5
15.12.7 Input devices ON/OFF (test operation) ...................................................................................15-25
15.12.8 Test operation mode ..................................................................................................................15-26
15.12.9 Output signal pin ON/OFF output signal (DO) forced output..............................................15-29
15.12.10 Alarm history ...........................................................................................................................15-30
15.12.11 Current alarm..........................................................................................................................15-31
15.12.12 Current position latch data ....................................................................................................15-32
15.12.13 General-purpose register ........................................................................................................15-33
15.12.14 Servo amplifier group designation.........................................................................................15-35
15.12.15 Software version ......................................................................................................................15-36
APPENDIX App- 1 to App- 4
App 1. Status indication block diagram ................................................................................................. App- 1
App 2. Junction terminal block (MR-TB20) terminal block labels ...................................................... App- 2
App 3. Combination of servo amplifier and servo motor ...................................................................... App- 3
App 4. Change of connector sets to the RoHS compatible products .................................................... App- 4
6
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Motor Instruction Manual is introduced here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included in the Servo Amplifier Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
3. CONNECTORS USED FOR SERVO MOTOR WIRING
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7. OUTLINE DIMENSION DRAWINGS
8. CALCULATION METHODS FOR DESIGNING
7
MEMO
8
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The MR-J2S-CL program-compatible AC servo amplifier is based on the MR-J2S-CP AC servo amplifier with built-in positioning functions and incorporates program-driven, single-axis positioning functions.
These functions perform positioning operation by creating the position data (target positions), servo motor speeds, acceleration and deceleration time constants, etc. as a program and executing the program. The servo amplifier is the most appropriate to configure a simple positioning system or to simplify a system, for example.
Up to 16 programs can be created. The program capacity is 120 steps as a total of all programs.
All servo motors are equipped with an absolute position encoder as standard. An absolute position detection system can be configured by merely adding a battery to the servo amplifier. Once the home position has been set, home position return is not required at power on, alarm occurrence, etc.
1.1.1 Function block diagram
The function block diagram of this servo is shown below.
1 - 1
1. FUNCTIONS AND CONFIGURATION
(1) MR-J2S-350CL or less
(Note 2)
Power supply
NFB
Regenerative option
MC
L
2
L
3
Servo amplifier
L
1
Diode stack Relay
P C D
(Note 1)
CHARGE lamp
Regenerative
TR
(Note 3) Cooling fan
L
11
L
21
Control power supply
Current detector
Dynamic brake
Base amplifier
Voltage detection
Overcurrent protection
Current detection
Servo motor
U
V
W
U
V
W
M
B1
B2
Electromagnetic brake
Encoder
Current control
Speed control
Program
SPN (1000)
STA (200)
STB (300)
MOV (500)
SPN (1000)
MOVA (1000)
MOVA (0) Position control
STOP
Position command creation
Analog
(2 channels)
A/D
I/F
CN1A CN1B
RS-232C
RS-422 D/A
CN3
D I/O control
Servo on
Start
Failure, etc.
Analog monitor
(2 channels)
Controller
RS-422/RS-232C
To other servo amplifier
MR-BAT
Optional battery
(for absolute position)
Note 1. The built-in regenerative resistor is not provided for the MR-J2S-10CL (1).
2. For 1-p+hase 230VAC, connect the power supply to L
1
,L
2
and leave L
3
open.
L
3
is not provided for a 1-phase 100 to120VAC power supply. Refer to section 1.2 for the power supply specification.
3. Servo amplifiers MR-J2S-200CL have a cooling fan.
1 - 2
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-500CL MR-J2S-700CL
(Note)
Power supply
NFB
MC
Regenerative option
L
2
L
3
Servo amplifier
L
1
Diode stack Relay
P C
CHARGE lamp
Regenerative
TR
Cooling Fan
L
11
L
21
Control power supply
Current detector
Dynamic brake
Base amplifier
Voltage detection
Overcurrent protection
Current detection
Servo motor
U
V
W
U
V
W
M
B1
B2
Electromagnetic brake
Encoder
Current control
Speed control
Program
SPN (1000)
STA (200)
STB (300)
MOV (500)
SPN (1000)
MOVA (1000)
MOVA (0)
Position control
STOP
Position command creation
Analog
(2 channels)
A/D
I/F
CN1A CN1B
RS-232C
RS-422 D/A
CN3
D I/O control
Servo on
Start
Failure, etc.
Analog monitor
(2 channels)
Controller
RS-422/RS-232C
To other servo amplifier
Note. Refer to section 1.2 for the power supply specification.
1 - 3
MR-BAT
Optional battery
(for absolute position)
1. FUNCTIONS AND CONFIGURATION
1.1.2 System configuration
This section describes operations using this servo.
You can arrange any configurations from a single-axis to max. 32-axis systems. Further, the connector pins in the interface section allow you to assign the optimum signals to respective systems. (Refer to sections 1.1.3 and 3.3.2.) The MR Configurator (Servo configuration Software) (refer to chapter 6) and personal computer are required to change or assign devices.
(1) Operation using external input signals
(a) Description
The following configuration example assumes that external input signals are used to control all signals (devices).
The I/O signals are as factory-set.
(b) Configuration
The following configuration uses external I/O signals. The personal computer is used with MR
Configurator (Servo configuration Software) to set creation of a program, change and monitor the parameters.
External I/O signals
Servo amplifier
Personal computer
MR Configurator
(Servo configuration Software)
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1 - 4
1. FUNCTIONS AND CONFIGURATION
(2) Operation using external input signals and communication
(a) Description
Communication can be used to Selection of the program, change parameter values, and confirm monitor data, for example. Enter a forward rotation start (ST1) or reverse rotation start (ST2) through the external I/O. Use this system when position data/speed setting or the host personal computer or the like is used to change the parameter values, for example.
(b) Configuration
1) One servo amplifier is connected with the personal computer by RS-232C.
External I/O signals
Servo amplifier
Personal computer
MR Configurator
(Servo configuration Software)
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1 - 5
1. FUNCTIONS AND CONFIGURATION
2) Several (up to 32) servo amplifiers are connected with the personal computer by RS-422.
Use parameter No. 16 to change the communication system.
External I/O signals
Servo amplifier (axis 1)
Personal computer
MR Configurator
(Servo configuration Software)
CN1A CN1B
Power supply
CN2 CN3
RS–232C
RS–422
RS–232C/RS-422 converter
(to be prepared by the customer)
Servo motor
RS–422
External I/O signals
Servo amplifier (axis 2)
CN1A CN1B
Power supply
CN2 CN3
To the next axis
Servo motor
1 - 6
1. FUNCTIONS AND CONFIGURATION
(3) Operation using communication
(a) Description
Analog input, forced stop (EMG) and other signals are controlled by external I/O signals and the other devices controlled through communication. Also, you can set each program, selection of the program, and change or set parameter values, for example. Up to 32 axes may be controlled.
(b) Configuration
1) One servo amplifier is connected with the personal computer by RS-232C.
External I/O signals
Servo amplifier
Personal computer
MR Configurator
(Servo configuration Software)
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1 - 7
1. FUNCTIONS AND CONFIGURATION
2) Several (up to 32) servo amplifiers are connected with the personal computer by RS-422.
Use parameter No. 16 to change the communication system.
External I/O signals
Servo amplifier (axis 1)
Personal computer
MR Configurator
(Servo configuration Software)
CN1A CN1B
Power supply
CN2 CN3
RS–232C
RS–422
RS–232C/RS-422 converter
(to be prepared by the customer)
Servo motor
RS–422
External I/O signals
Servo amplifier (axis 2)
CN1A CN1B
Power supply
CN2 CN3
To the next axis
Servo motor
1 - 8
1. FUNCTIONS AND CONFIGURATION
1.1.3 I/O devices
This servo amplifier allows devices to be allocated to the pins of connector CN1A/CN1B as desired. The following devices can be allocated. For device details, refer to section 3.3.2.
Input device Symbol
Factoryallocated pin
Factorydevice Symbol allocated pin
Servo-on ALM CN1B-18
Reset RES CN1B-19
Forward rotation stroke end
Reverse rotation stroke end
Forward rotation start
LSP
LSN
ST1
CN1B-16
CN1B-17
CN1B-7
Movement complete
Zeroing completion
Program output 1
PED
ZP
OUT1
CN1B-6
CN1A-18
CN1B-4
Reverse rotation start
Proximity dog
Program No. selection 1
Program No. selection 2
Program No. selection 3
Program No. selection 4
Forced stop
Automatic/manual selection
Override selection
External torque limit selection
Internal torque limit selection
Proportion control
Temporary stop/restart
Manual pulse generator multiplication 1
Manual pulse generator multiplication 2
Gain switch
Current position latch input
Program input 1
Program input 2
Program input 3
ST2
DOG
DI0
DI1
DI2
DI3
EMG
MD0
OVR
TL
TL2
PC
STP
TP0
TP1
CDP
LPS
PI1
PI2
PI3
CN1A-8
CN1B-5
CN1B-14 Position range
CN1B-8
CN1B-9
Program output 2
Program output 3
Electromagnetic brake interlock
Warning
Battery warning
Limiting torque
Temporary stop
SYNC synchronous output
OUT2
OUT3
MBR
POT
WNG
BWNG
TLC
PUS
SOUT
1 - 9
1. FUNCTIONS AND CONFIGURATION
1.2 Servo amplifier standard specifications
Servo amplifier
MR-J2S- 10CL 20CL 40CL 60CL 70CL 100CL 200CL 350CL 500CL 700CL 10CL1 20CL1 40CL1
Item
Voltage/frequency
Permissible voltage fluctuation
Permissible frequency fluctuation
Power supply capacity
Inrush current
Control system
Dynamic brake
Protective functions
Program
Operational specifications
Position command input
Program operation mode
Manual
Manual home position return mode
Speed command input
System
Jog operation mode Manual pulse generator
Dog type
Count type
Data setting type
Stopper type
3-phase 200 to 230VAC, 50/60Hz or 1-phase 230VAC, 50/60Hz
3-phase 200 to 230VAC:
170 to 253VAC
1-phase 230VAC: 207 to 253VAC
3-phase 200 to 230VAC, 50/60Hz
3-phase 170 to 253VAC
1-phase 100 to
120VAC 50/60Hz
1-phase
85 to 127VAC
Within 5%
Refer to section 13.2
Refer to section 12.5
Sine-wave PWM control, current control system
Built-in
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay), servo motor overheat protection, encoder error protection, regenerative brake error protection, undervoltage, instantaneous power failure protection, overspeed protection, excessive error protection
Program language (Program with MR Configurator (Servo-configuration software)).
Program capacity: 120 steps
Setting by program language.
Movement setting range at 1 point: 1[ m] to 999.999[mm]
Servo motor speed, acceleration/deceleration time constant and S-pattern acceleration/deceleration time constant by program language.
S-pattern acceleration/deceleration time constant can set by parameter No.14 or by programming.
Signed absolute value command (signed incremental value command system can be specified), signed incremental value command system
Setting by programming language
Jog operation is performed in accordance with the parameter-set speed command by contact input or through RS-422 (232C) communication.
Manual feed is made by manual pulse generator.
Command pulse multiplication: 1, 10 or 100 is selected using parameter.
Home position return is made starting with Z-phase pulse after passage of proximity dog.
Home position return direction may be selected. Home position shift distance may be set.
Home position address may be set.
Automatic at-dog home position return, Automatic stroke return function
Home position return is made by counting encoder pulses after contact with proximity dog.
Home position address may be set. Home position shift value may be set. Home position return direction may be set.
Automatic at-dog home position return, Automatic stroke return function
Home position return is made without dog.
Home position may be set at any position by manual operation, etc. Home position address may be set.
Home position return is made by pressing machine part against stroke end.
Home position address may be set. Home position return direction may be set.
1 - 10
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
MR-J2S-
Item
Home position ignorance
(Servo-on position as home position)
Position where servo-on (SON) is switched on is defined as home position.
Home position address may be set.
Dog type rear end
Manual home reference position return mode Count type front end reference
Other functions
Structure
Ambient temperature
Dog cradle type
In operation
In storage
Home position return is made with respect to the rear end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position return direction may be set.
Automatic at-dog home position return, Automatic stroke return function
Home position return is made with respect to the front end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position return direction may be set.
Automatic at-dog home position return, Automatic stroke return function
Home position return is made with respect to the front end of a proximity dog by the first
Z-phase pulse.
Home position address may be set. Home position shift value may be set. Home position return direction may be set.
Automatic at-dog home position return, Automatic stroke return function
Absolute position detection, backlash function
Overtravel prevention using external limit switch
Software stroke limit, override using external analog signal
Self-cooled, open (IP00) Force-cooling, open (IP00)
Self-cooled, open (IP00)
[ ] 0 to 55 (non-freezing)
[ ] 32 to 131 (non-freezing)
[ ] 20 to 65 (non-freezing)
[ ] 4 to 149 (non-freezing)
Ambient humidity
In operation
In storage
90%RH or less (non-condensing)
Ambient
Altitude
Vibration
Mass
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280ft) above sea level
5.9 [m/s 2 ] or less
19.4 [ft/s 2 ] or less
[kg] 0.7 0.7 1.1 1.1 1.7 1.7 2.0 2.0 4.9 7.2 0.7 0.7 1.1
1 - 11
1. FUNCTIONS AND CONFIGURATION
1.3 Function list
The following table lists the functions of this servo. For details of the functions, refer to the reference field.
Positioning by program operation
Manual home position return
Multidrop communication
High-resolution encoder
Absolute position detection system
Gain changing function
Adaptive vibration suppression control
Low-pass filter
Machine analyzer function
Machine simulation
Gain search function
Slight vibration suppression control
Electronic gear
Auto tuning
S-pattern acceleration/deceleration time constant
Regenerative option
Brake unit
Return converter
Operation is performed in accordance with the contents of any program selected from among pre-created 16 programs.
Use the external input signal or communication function to choose the program.
Dog type, count type, data setting type, stopper type, home position ignorance, dog type rear end reference, count type front end reference, dog cradle type
Up to 32 axes of MR-J2S-CL are controllable simultaneously by
RS-422 communication.
High-resolution encoder of 131072 pulses/rev is used as a servo motor encoder.
By merely setting the home position once, home position return need not be done at each power on.
You can switch between gains during rotation and gains during stop or use an external signal to change gains during operation.
Servo amplifier detects mechanical resonance and sets filter characteristics automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo system response is increased.
Analyzes the frequency characteristic of the mechanical system by simply connecting a MR Configurator (servo configuration software)-installed personal computer and servo amplifier.
Can simulate machine motions on a personal computer screen on the basis of the machine analyzer results.
Personal computer changes gains automatically and searches for overshoot-free gains in a short time.
Vibration of 1 pulse at servo motor stop is suppressed.
The electronic gear is used to make adjustment so that the servo amplifier setting matches the machine moving distance. Also, changing the electronic gear value allows the machine to be moved at any multiplication ratio to the moving distance using the servo amplifier.
Automatically adjusts the gain to optimum value if load applied to the servo motor shaft varies. Higher in performance than MR-J2 series servo amplifier.
Section 4.2
Section 4.4
Section 4.6.2
Chapter 15
Section 4.5
Section 9.5
Section 9.3
Section 9.4
Parameter No. 20
Section 5.2.1
Chapter 8
Acceleration/deceleration can be made smoothly.
Section 4.2.2 (2) (a)
3)
Section 5.2.3
Used when the built-in regenerative resistor of the servo amplifier does not have sufficient regenerative capability for the regenerative power generated.
Used when the regenerative option cannot provide enough regenerative power.
Can be used with the MR-J2S-500CL MR-J2S-700CL.
Used when the regenerative option cannot provide enough regenerative power.
Can be used with the MR-J2S-500CL MR-J2S-700CL.
Section 14.1.1
Section 14.1.2
Section 14.1.3
1 - 12
1. FUNCTIONS AND CONFIGURATION
Analog monitor
Alarm history
I/O signal selection (Device setting)
Torque limit
Override (speed limit)
Status display
Test operation mode
Limit switch
Software limit
1.4 Model code definition
(1) Rating plate
MITSUBISHI
MODEL MR-J2S-60CL
POWER :
INPUT :
600W
3.2A 3PH 1PH200-230V 50Hz
3PH 1PH200-230V 60Hz
5.5A 1PH 230V 50/60Hz
OUTPUT :
SERIAL :
170V 0-360Hz 3.6A
A5
TC3 AAAAG52
PASSED
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
By using the MR Configurator (Servo configuration Software), the servo status is output in terms of voltage in real time.
By using the MR Configurator (Servo configuration Software), the current alarm and five past alarm numbers are stored and displayed.
By using the Servo configuration Software, any devices can be assigned to 9 input, 5 output and 1 I/O pins.
Servo motor-torque is limited.
Parameter 2 limit value
Analog input 1 limit value
The servo motor speed is limited by analog input.
The ratio of override to the set speed can be changed between 0 to
200%.
The servo status is displayed.
Jog, Positioning, Operation w/o motor, Forced output, Program test
The servo motor travel region can be limited using the forward rotation stroke end (LSP)/reverse rotation stroke end (LSN).
The travel region is limited using parameters in terms of address.
The function similar to that of a limit switch is limited by parameter.
Model
Capacity
Applicable power supply
Rated output current
Serial number
Section 5.2.4
Section 6.8
Section 6.6
Section 3.4.4
Section 3.4.3
Section 7.2
Section 6.7
Section 5.2.5
Section 5.2.7
1 - 13
1. FUNCTIONS AND CONFIGURATION
(2) Model
MR–J2S– CL
MR–J2S–100CL or less MR–J2S–200CL 350CL
Series
Power Supply
Symbol Power supply
None
3-phase 200 to 230VAC
(Note 1) 1-phase 230VAC
(Note 2)
1
1-phase 100V to 120VAC
Note 1. 1-phase 230V is supported by
750W or less.
2. 1-phase 100V to 120V is
supported by 400W or less.
Program compatibility operation function
Rated output
Symbol
10
20
40
60
70
Rated output [W]
100
200
400
600
750
Symbol
100
200
350
500
700
Rated output [W]
1000
2000
3500
5000
7000
MR-J2S-500CL
Rating plate
MR-J2S-700CL
Rating plate
Rating plate Rating plate
1.5 Combination with servo motor
The following table lists combinations of servo amplifiers and servo motors. The same combinations apply to the models with electromagnetic brakes and the models with reduction gears.
Servo motors
Servo amplifier
HC-KFS HC-MFS
1000r/min 2000r/min 3000r/min 2000r/min 3000r/min
MR-J2S-10CL (1)
MR-J2S-20CL (1)
053 13 053 13
23 23
MR-J2S-40CL (1) 43
MR-J2S-60CL
43
13
23
43
52
MR-J2S-70CL 73 73 72 73
MR-J2S-100CL
MR-J2S-200CL 121 201 152 202 153 203 103 153 152
MR-J2S-350CL
MR-J2S-500CL 502 353 503 352 502
MR-J2S-700CL 702
Servo motors
HA-LFS
Servo amplifier
(Note)
1000r/min
(Note)
1500r/min
MR-J2S-60CL
MR-J2S-100CL
MR-J2S-200CL
2000r/min
MR-J2S-350CL
MR-J2S-500CL (Note) 502
MR-J2S-700CL 601 701M 702
(Note)
HC-LFS
52
102
152
202
302
Note. Consult us since the servo amplifier to be used with any of these servo motors is optional.
1 - 14
1. FUNCTIONS AND CONFIGURATION
1.6 Structure
1.6.1 Part names
(1) MR-J2S-100CL or less
Name/Application Reference
Battery holder
Contains the battery for absolute position data backup.
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Display
The 5-digit, seven-segment LED shows the servo status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm and parameter setting operations.
Section 4.5
Section 4.5
Chapter 7
MODE UP DOWN SET
MODE UP DOWN SET
Used to set data.
Used to change the display or data in each mode.
Chapter 7
Used to change the mode.
Fixed part (2 places)
(For MR-J2S-70CL
100CL 3 places)
I/O signal connector (CN1A)
Used to connect digital I/O signals.
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Section 3.3
Section 3.3
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C) and output analog monitor data.
Chapter 6
Chapter 15
Section 14.1.4
Rating plate Section 1.4
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Main circuit terminal block (TE1)
Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and regenerative option.
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.3
Section 14.1.4
Section 3.7.2
Section 12.1
Section 3.7.2
Section 12.1
Section 14.1.1
Section 3.10
1 - 15
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200CL MR-J2S-350CL
POINT
This servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.6.2.
MODE UP DOWN SET
Name/Application Reference
Battery holder
Contains the battery for absolute position data backup.
Section 4.5
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Display
The 5-digit, seven-segment LED shows the servo status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm and parameter setting operations.
Section 4.5
Chapter 7
Cooling fan
Fixed part (4 places)
MODE UP DOWN SET
Used to set data.
Used to change the display or data in each mode.
Chapter 7
Used to change the mode.
I/O signal connector (CN1A)
Used to connect digital I/O signals.
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Section 3.3
Section 3.3
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C) and output analog monitor data.
Chapter 6
Chapter 15
Section 14.1.4
Rating plate Section 1.4
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Main circuit terminal block (TE1)
Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and regenerative option.
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.3
Section 14.1.4
Section 3.7.2
Section 12.1
Section 3.7.2
Section 12.1
Section 14.1.1
Section 3.10
1 - 16
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500CL
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.6.2.
MODE UP DOWN SET
Fixed part
(4 places)
Cooling fan
Name/Application Reference
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Section 4.5
Battery holder
Contains the battery for absolute position data backup. Section 4.5
Display
The 5-digit, seven-segment LED shows the servo status and alarm number.
Chapter 7
Operation section
Used to perform status display, diagnostic, alarm and parameter setting operations.
MODE UP DOWN SET
Used to set data.
Chapter 7
Used to change the display or data in each mode.
Used to change the mode.
I/O signal connector (CN1A)
Used to connect digital I/O signals.
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Section 3.3
Section 3.3
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C) and output analog monitor data.
Chapter 6
Chapter 15
Section 14.1.4
Section 3.3
Section 14.1.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and regenerative option.
Main circuit terminal block (TE1)
Used to connect the input power supply and servo motor.
Rating plate
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.7.2
Section 12.1
Section 3.7.2
Section 12.1
Section 14.1.1
Section 1.4
Section 3.10
1 - 17
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700CL
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to next page.
MODE UP DOWN SET
Cooling fan
Fixed part
(4 places)
Name/Application
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Battery holder
Contains the battery for absolute position data backup.
Display
The 5-digit, seven-segment LED shows the servo status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm and parameter setting operations.
Reference
Section 4.5
Section 4.5
Chapter 7
MODE UP DOWN SET
Used to set data.
Chapter 7
Used to change the display or data in each mode.
Used to change the mode.
I/O signal connector (CN1A)
Used to connect digital I/O signals.
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C) and output analog monitor data.
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
Section 3.3
Section 3.3
Chapter 6
Chapter 15
Section 14.1.4
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Rating plate
Section 3.7.2
Section 12.1
Section 3.3
Section 14.1.4
Section 1.4
Main circuit terminal block (TE1)
Used to connect the input power supply, regenerative option and servo motor.
Section 3.7.2
Section 12.1
Section 14.1.1
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.10
1 - 18
1. FUNCTIONS AND CONFIGURATION
1.6.2 Removal and reinstallation of the front cover
WARNING
Before removing or installing the front cover, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
(1) For MR-J2S-200CL or more
Removal of the front cover
1)
Reinstallation of the front cover
2)
Front cover hook
(2 places)
2)
Front cover
1) Hold down the removing knob.
2) Pull the front cover toward you.
(2) For MR-J2S-500CL
Removal of the front cover
1)
2)
1)
Front cover socket
(2 places)
1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
Reinstallation of the front cover
Front cover hook
(2 places)
2)
1)
Front cover
1) Hold down the removing knob.
2) Pull the front cover toward you.
Front cover socket
(2 places)
1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 19
1. FUNCTIONS AND CONFIGURATION
(3) For MR-J2S-700CL
Removal of the front cover Reinstallation of the front cover
Front cover hook
(2 places)
B)
2)
A)
1)
A)
1) Push the removing knob A) or B), and put you
finger into the front hole of the front cover.
2) Pull the front cover toward you.
2)
1)
Front cover socket
(2 places)
1) Insert the two front cover hooks at the bottom into the
sockets of the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 20
1. FUNCTIONS AND CONFIGURATION
1.7 Servo system with auxiliary equipment
To prevent an electric shock, always connect the protective earth (PE) terminal
WARNING (terminal marked ) of the servo amplifier to the protective earth (PE) of the control box.
(1) MR-J2S-100CL or less
(a) For 3-phase 200V to 230VAC or 1-phase 230VAC
(Note 2)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Regenerative option
Reference
Section 14.2.2
Section 14.2.2
Chapter 6
Section 14.1.1
Options and auxiliary equipment Reference
Cables
Manual pulse generator
External digital display
Section 14.2.1
Section 14.1.8
Section 14.1.7
Power factor improving reactor Section 14.2.3
No-fuse breaker
(NFB) or fuse
Servo amplifier Command device
Junction terminal block
To CN1A
Magnetic contactor
(MC)
Power factor improving reactor
(FR-BAL)
To CN1B
To CN3
Manual pulse generator
External digital display
To CN2
L
1
L 2
L
3
CHARGE
U V W
Personal computer
MR Configurator
(Servo configuration
software
MRZJW3-SETUP151E)
Protective earth (PE) terminal
(Note 1)
Encoder cable
(Note 1)
Power supply lead
Control circuit terminal block
L
21
L
11
D
P
Regenerative option
C Servo motor
Note 1. The HC-SFS, HC-RFS, HC-UFS 2000r/min series have cannon connectors.
2. A 1-phase 200V to 230VAC power supply may be used with the servo amplifier of MR-J2S-70CL or less.
For 1-phase 230VAC, connect the power supply to L
1
L
2
and leave L
3
open. Refer to section 1.2 for the power supply specification.
1 - 21
1. FUNCTIONS AND CONFIGURATION
(b) For 1-phase 100V to 120VAC
(Note 2)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Regenerative option
Reference
Section 14.2.2
Section 14.2.2
Chapter 6
Section 14.1.1
No-fuse breaker
(NFB) or fuse
Servo amplifier
Options and auxiliary equipment Reference
Cables
Manual pulse generator
Section 14.2.1
Section 14.1.8
External digital display Section 14.1.7
Power factor improving reactor Section 14.2.3
Command device
Junction terminal block
To CN1A
Magnetic contactor
(MC)
To CN1B
Manual pulse generator
External digital display
To CN3
CHARGE
Power factor improving reactor
(FR-BAL)
To CN2
L
1
L
2 U V W
Personal computer
MR Configurator
(Servo configuration
software
MRZJW3-SETUP151E)
Protective earth (PE) terminal
(Note 1)
Encoder cable
(Note 1)
Power supply lead
D Control circuit terminal block
L
21
L
11
Regenerative option
P
C
Note 1. The HC-SFS, HC-RFS, HC-UFS 2000 r/min series have cannon connectors.
2. Refer to section 1.2 for the power supply specification.
Servo motor
1 - 22
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200CL MR-J2S-350CL
(Note)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Regenerative option
Reference
Section 14.2.2
Section 14.2.2
Chapter 6
Section 14.1.1
No-fuse breaker
(NFB) or fuse
Servo amplifier
Options and auxiliary equipment Reference
Cables
Manual pulse generator
External digital display
Section 14.2.1
Section 14.1.8
Section 14.1.7
Power factor improving reactor Section 14.2.3
Command device
Junction terminal block
To CN1A
Magnetic contactor
(MC)
To CN1B
Manual pulse generator
External digital display
Power factor improving reactor
(FR-BAL)
To CN2
L
11
L
21
To CN3
Personal computer
MR Configurator
(Servo configuration
software
MRZJW3-SETUP151E)
L
1
L
2
L
3
U V W P C
Regenerative option
Note. Refer to section 1.2 for the power supply specification.
1 - 23
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500CL
(Note 2)
Power supply
No-fuse breaker
(NFB) or fuse
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Regenerative option
Reference
Section 14.2.2
Section 14.2.2
Chapter 6
Section 14.1.1
Options and auxiliary equipment Reference
Cables
Manual pulse generator
External digital display
Section 14.2.1
Section 14.1.8
Section 14.1.7
Power factor improving reactor Section 14.2.3
Magnetic contactor
(MC)
Power factor improving reactor
(FR-BAL)
(Note 1) C P
Regenerative option
L
1
L
2
L
3
U
V
W
Servo amplifier
To CN1A
To CN1B
To CN3
Command device
Junction terminal block
Manual pulse generator
External digital display
L
11
L
21
To CN2
Personal computer
MR Configurator
(Servo configuration
software
MRZJW3- SETUP151E)
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.2 for the power supply specification.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700CL
(Note 2)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Regenerative option
Reference
Section 14.2.2
Section 14.2.2
Chapter 6
Section 14.1.1
Options and auxiliary equipment Reference
Cables
Manual pulse generator
Section 14.2.1
Section 14.1.8
External digital display Section 14.1.7
Power factor improving reactor Section 14.2.3
Command device
No-fuse breaker
(NFB) or fuse
Junction terminal block
L
21
L
11
Servo amplifier
To CN1A
Magnetic contactor
(MC)
To CN1B
Manual pulse generator
External digital display
Power factor improving reactor
(FR-BAL)
To CN3
Personal computer
MR Configurator
(Servo configuration
software
MRZJW3- SETUP151E)
L
3
L
2
L
1
U
V
W
To CN2
C P
(Note 1) Regenerative option
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.2 for the power supply specification.
1 - 25
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 26
2. INSTALLATION
2. INSTALLATION
Stacking in excess of the limited number of products is not allowed.
Install the equipment on incombustible material. Installing them directly or close to combustibles will lead to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range. (For the environmental conditions, refer to section 2.1.)
CAUTION
Provide an adequate protection to prevent screws, metallic detritus and other conductive matter or oil and other combustible matter from entering the servo amplifier.
Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may occur.
Do not subject the servo amplifier to drop impact or shock loads as they are precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the corners of the servo amplifier.
2.1 Environmental conditions
Ambient temperature
Environment Conditions
In operation
In storage
[ ]
[ ]
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient humidity
In operation
In storage
90%RH or less (non-condensing)
Ambience
Altitude
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280 ft) above sea level
Vibration
[m/s 2
[ft/s 2
2 - 1
2. INSTALLATION
2.2 Installation direction and clearances
Do not hold the front cover to transport the controller. The controller may drop.
The equipment must be installed in the specified direction. Otherwise, a fault may occur.
CAUTION
Leave specified clearances between the servo amplifier and control box inside walls or other equipment.
(1) Installation of one servo amplifier
Control box Control box
40mm
(1.6 in.) or more
Servo amplifier
10mm
(0.4 in.) or more
10mm
(0.4 in.) or more
Wiring clearance
70mm
(2.8 in.)
Up
40mm
(1.6 in.) or more
Down
2 - 2
2. INSTALLATION
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the environmental conditions.
Control box
100mm
(4.0 in.) or more
10mm
(0.4 in.) or more
30mm
(1.2 in.) or more
30mm
(1.2 in.) or more
40mm
(1.6 in.) or more
(3) Others
When using heat generating equipment such as the regenerative option, install them with full consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.3 Keep out foreign materials
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or a cooling fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an air purge (force clean air into the control box from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the control box.
2 - 3
2. INSTALLATION
2.4 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own mass stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake) supplied with the servo motor, and flex the optional encoder cable or the power supply and brake wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or stamped by workers or vehicles.
(4) The flexing lives of the cables are shown below. In actuality, provide a little allowance for these values.
For installation on a machine where the servo motor will move, the flexing radius should be made as large as possible. Refer to section 13.4 for the flexing life.
2 - 4
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
WARNING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output should be fitted in the specified direction. Otherwise, the signal is not output due to a fault, disabling the forced stop (EMG) and other protective circuits.
Servo amplifier
COM
(24VDC)
Servo amplifier
COM
(24VDC)
CAUTION
Control output signal
RA
Control output signal
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF option) with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire.
Do not modify the equipment.
During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
POINT
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a failure. Connect them correctly.
3 - 1
3. SIGNALS AND WIRING
3.1 Standard connection example
Proximity dog
Servo-on
(Note 5)
Forward rotation stroke end
Reverse rotation stroke end
Program input 1
Program input 2
Forward rotation start
Program No. selection 1
Program No. selection 2
Reset
Upper limit setting
(Note 8) Override
Upper limit setting
(Note 9) Analog torque limit
(Note 11)
MR Configurator
(Servo Configuration
software)
Personal computer
Servo amplifier
10m (32.79ft.) or less
DOG
SON
SG
(Note 3, 7) (Note 3, 7)
CN1A CN1A
8
9 COM
19
18 ZP
10
(Note 2, 4)
RA5
10m (32.79ft.) or less
LSP
(Note 3, 7) (Note 3, 7)
CN1B CN1B
16 3 VDD
LSN
PI1
17
8
13
4
COM
OUT1
PI2
ST1
DI0
9
7
5
6
18
PED
ALM
DI1
RST
SG
14
15
10
19 RD
P15R
VC
11
2
(Note 3, 7)
CN1B
6 LA
16 LAR
LG
TLA
SD
2m (6.56ft.) or less
1
12
Plate
7 LB
17 LBR
5 LZ
15 LZR
1 LG
Plate SD
(Note 3, 7)
CN3
4 MO1
3
14
13
LG
MO2
LG
(Note 12)
(Note 2, 4)
RA1
RA2
RA3
RA4
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
A
10k
A
10k
Home position return completion
Program output 1
Movement complete
Trouble (Note 6)
Ready
Encoder Z-phase pulse
(differential line driver)
(Note 10)
Monitor output
Max. 1mA meter
Zero center
(Note 10)
Communication cable
CN3
Plate SD
2m (6.56ft.) or less
(Note 1)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth
(PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output signals, disabling the emergency stop and other protective circuits.
3. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
4. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, supply interface power from external.
5. When starting operation, always connect the forward/reverse rotation stroke end (LSN/LSP) with SG. (Normally closed contacts)
6. Trouble (ALM) is connected with COM in normal alarm-free condition.
7. The pins with the same signal name are connected in the servo amplifier.
8. When using override (VC), make the override selection (OVR) device available.
9. When using analog torque limit (TLA), make the external torque limit selection (TL) devices available.
10. When connecting the personal computer together with monitor outputs 1, 2, use the maintenance junction card (MR-J2CN3TM).
(Refer to section 14.1.6).
11. Use MRZJW3-SETUP 151E (Ver. E1 or more).
12. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external power.
Refer to section 3.6.2.
3 - 2
3. SIGNALS AND WIRING
3.2 Internal connection diagram of servo amplifier
This section gives the internal connection diagram where the signal assignment is in the initial status.
Servo amplifier
VDD
COM
CN1B
3
13
COM
DOG
SON
SG
CN1A
9
8
19
10, 20
24VDC
Approx. 4.7k
Approx. 4.7k
DI0
ST1
PI1
CN1B
5
7
8
PI2
DI1
RST
LSP
LSN
SG
9
14
15
16
17
10, 20
OPC
PP
NP
SD
CN1A
11
Approx. 100
3
Approx. 100
2
Casing
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 1.2k
Approx. 1.2k
CN1A
18
CN1A
6
16
7
17
5
15
14
1
ZP
CN1B
4
6
18
19
OUT1
PED
ALM
RD
LA
LAR
LB
LBR
LZ
LZR
OP
LG
CN3
4 MO1
VC
TLA
CN1B
2
12
14 MO2
P15R 11
LG
SD
1
Casing
P15R
CN1A
4
15VDC
2
12
9
19
5
15
PE
RXD
TXD
SDP
SDN
RDP
RDN
3 - 3
3. SIGNALS AND WIRING
3.3 I/O signals
3.3.1 Connectors and signal arrangements
POINT
The connector pin-outs shown above are viewed from the cable connector wiring section side.
(1) Signal arrangement
CN1A CN1B
1
2
LG
NP
3
4
PP
P15R
6
5
LZ
LA
7
8
LB
DOG
9
10
COM
SG
12
14
OP
16
LAR
18
ZP
20
SG
11
OPC
13
15
LZR
17
LBR
19
SON
Servo amplifier
1
2
LG
VC
3
4
OUT1
VDD
5
6
DI0
PED
7
8
ST1
PI1
9
10
PI2
SG
12
TLA
14
DI1
16
LSP
18
ALM
20
SG
11
P15R
13
COM
15
RST
17
LSN
19
RD
CN2
2
LG
4
1
LG
3
12
LG
14
11
LG
13
5 15
6 16
MD
8
10
7
MR
9
BAT
MDR
18
17
MRR
P5
19
20
P5
P5
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
CN3
1
2
RXD
LG
3
4
MO1
6
LG
5
RDP
12
TXD
14
MO2
16
11
LG
13
LG
15
RDN
7 17
8 18
9
10
TRE
SDP
19
20
P5
SDN
3 - 4
3. SIGNALS AND WIRING
3.3.2 Signal (devices) explanations
(1) I/O devices
POINT
The devices not indicated in the Connector Pin No. field of the I/O devices can be assigned to the connector CN1A/CN1B using the MR Configurator
(Servo Configuration software).
In the factory setting state, Forced stop (EMG) and Automatic/manual selection (MD0) are not assigned to the pins but are preset to turn on automatically.
(a) Pins whose devices can be changed
Refer to section 3.6.2 for the I/O interfaces (symbols in the I/O Division field in the table) of the corresponding connector pins.
Pin type Connector pin No.
CN1B-5
CN1B-14
I/O division Device in initial status
Program No. selection 1 (DI0)
Program No. selection 2 (DI1)
Input-only pins
I/O pin
CN1B-16
CN1B-17
CN1B-7
CN1B-8
CN1B-9
CN1A-19
CN1B-6
DI-1
DI-1 or DO-1
Forward rotation stroke end (LSP)
Reverse rotation stroke end (LSN)
Forward rotation start (ST1)
Program input 1 (PI1)
Program input 2 (PI2)
Servo-on (SON)
You can assign an I/O device using the MR
Configurator (Servo Configuration software).
Movement complete (PED)
Output-only pins
CN1A-18 Home position return completion(ZP)
(b) Input devices
Device name
Forced stop
Servo-on
Reset
Devices symbol
EMG
SON
RES
Connector pin No.
Functions/Applications
Turn EMG off (open EMG-common) to bring the motor to an Forced stop state, in which the servo is switched off and the dynamic brake is operated.
Turn EMG on (short EMG-common) in the Forced stop state to reset that state.
In the factory setting state, Forced stop (EMG) is preset to turn on automatically.
(Refer to section 6.6 (2) (c).)
CN1B-19 Turn SON on to power on the base circuit and make the servo amplifier ready to operate (servo-on).
Turn it off to shut off the base circuit and coast the servo motor (servo off).
CN1B-15 Turn RES on for more than 50ms to reset the alarm.
Some alarms cannot be deactivated by the reset signal. Refer to section 11.2.1.
Turning RES on in an alarm-free status shuts off the base circuit. The base circuit is not shut off when " 1 " is set in parameter No. 55.
Since this device is not designed for stopping. Do not switch it on during operation.
3 - 5
3. SIGNALS AND WIRING
Device name
Forward rotation stroke end
Reverse rotation stroke end
Program input1
Program input2
Program input3
Forward rotation start
Reverse rotation start
Automatic/manual selection
Proximity dog
Devices symbol
Connector pin No.
Functions/Applications
LSP CN1B-16 To start operation, turn LSP/LSN on. Turn it off to bring the motor to a sudden stop and make it servo-locked.
Set " 1" in parameter No. 22 to make a slow stop.
(Refer to section 5.2.5.)
(Note) Input signals Operation
LSP LSN
CCW direction
CW direction
LSN CN1B-17
Note. 0: OFF
1: ON
PI1
PI2
CN1B-8 Turn PI1 on to resume the step stopped by the SYNC (1) command in the program.
CN1B-9 Turn PI2 on to resume the step stopped by the SYNC (2) command in the program.
PI3 Turn PI3 on to resume the step stopped by the SYNC (3) command in the program.
ST1 CN1B-7 1. In program operation mode
When ST1 is turned on, the operation of the program selected with DI0 to DI3 is executed.
2. Jog operation in manual operation mode
While ST1 is kept on, the servo motor rotates in the forward rotation direction.
Forward rotation indicates an address increasing direction.
ST2
MD0
While ST2 is kept on in jog operation of the manual operation mode, the servo motor rotates in the reverse rotation direction. Reverse rotation indicates an address decreasing direction.
ST2 is invalid in any other operation mode.
Turn MD0 on to select the program operation mode, or turn it off to select the manual operation mode.
In the factory setting state, Forced stop (EMG) is preset to turn on automatically.
(Refer to section 6.6 (2) (c).)
DOG CN1A-8 Turn DOG on to bring, the proximity dog signal is detected. The polarity of dog detection input can be changed with the parameter.
Parameter No.8
Polarity of proximity dog detection input
0 (initial value) OFF
1 ON
3 - 6
3. SIGNALS AND WIRING
Device name
Devices symbol
Connector pin No.
Functions/Applications
Program No. selection 1 Select the program number from among those combined by DI0, DI1, DI2 and DI3 to start operation on the leading edge of ST1 in the program operation mode.
Program No. selection 2 DI1 CN1B-14
Program No. selection 3
Program No. selection 4
Override selection
External torque limit selection
Internal torque limit selection
Proportion control
DI2
DI3
OVR
TL
TL2
PC
Input signal (Note)
DI3 DI2 DI1 DI0
Program No.
0 0 0 0 1
0 0 0 1 2
0 0 1 0 3
0 0 1 1 4
0 1 0 0 5
0 1 0 1 6
0 1 1 0 7
0 1 1 1 8
1 0 0 0 9
1 0 0 1 10
1 0 1 0 11
1 0 1 1 12
1 1 0 0 13
1 1 0 1 14
1 1 1 0 15
1 1 1 1 16
Note. 0: OFF
1: ON
Turn OVR on to make override (VC) valid.
Turn TL on to make analog torque limit (TLA) valid.
For details, refer to section 3.4.4.
Turn TL2 off to make parameter No.28 (Internal torque limit 1) valid, or turn it on to make parameter No.29 (Internal torque limit 2) valid.
For details, refer to section 3.4.4.
Turn PC on to bring the speed amplifier from the proportional integral type to the proportional type.
If the servo motor at a stop is rotated even one pulse due to any external factor, it generates torque to compensate for a position shift. In such a case where the axis will be locked mechanically after Movement complete (PED) has turned off, turning
Proportion control (PC) on as soon as Movement complete (PED) turns off can suppress unnecessary torque that attempts to compensate for a position shift.
When the shaft is to be locked for a long time, switch on the proportion control (PC) and External torque limit selection (TL) at the same time to make the torque less than the rated by the analog torque limit (TLA).
3 - 7
3. SIGNALS AND WIRING
Device name
Temporary stop/Restart
Manual pulse generator multiplication 1
Manual pulse generator multiplication 2
Devices symbol
STP
Connector pin No.
TP0
Functions/Applications
Turn STP on during program operation to make a temporary stop.
Turn it on again to make a restart.
If any of Program inputs 1 to 3 (PI1 to PI3) is turned on during a temporary stop, it is ignored.
When the program operation mode is switched to the manual operation mode during a temporary stop, the remaining moving distance is erased. During home position return and jog operation, the temporary stop/restart input is ignored.
Refer to section 3.4.1.
Used to select the multiplication factor of the manual pulse generator.
When it is not selected, the parameter No.1 setting is made valid.
TP1
(Note) Input signal Manual pulse generator
TP1 TP0 multiplication factor
0 0 Parameter No.1 setting
Gain switch CDP
Current position latch input
LPS
Note. 0: OFF
1: ON
Turn CDP on to change the load inertia moment ratio into parameter No. 64 (load inertia moment ratio to servo motor 2) and the gain values into the values multiplied by parameter No. 65 to 67.
Turn LPS on during execution of the LPOS command to latch the current position on its leading edge. The latched current position can be read using the communication command.
3 - 8
3. SIGNALS AND WIRING
(c) Output devices
Device name
Devices symbol
Connector pin No.
Functions/Applications
Movement complete PED shut off the base circuit. Without alarm occurring, ALM turns on within about 1s after power-on. operate.
CN1B-6 PED turns on when the droop pulse value is within the movement complete output range and the command remaining distance is "0". (Refer to section 3.4.2.)
The movement complete output range can be changed with parameter No. 6.
INP turns on at servo-on.
When a home position return is not completed, PED is off in a servo-off status.
Home position return completion
Electromagnetic brake interlock
Position range
Battery warning
Limiting torque
Temporary stop
Program output 1
Program output 2
Program output 3
MBR
POT
In the absolute position system, ZP turns on when the servo amplifier is ready to operate, but turns off if.
1) SON is turned off.
2) EMG is turned off.
3) RES is turned on.
4) Alarm occurs.
5) Limit switch opens.
6) Home position set has not been made after the purchase of the product.
7) Home position set has not been made after the occurrence of absolute position erasure (AL. 25) or absolute position counter warning
(AL. E3).
8) Home position set has not been made after the setting of the electronic gear value.
9) Home position set has not been made after the absolute position system was made valid. or
10) The ST1 coordinate system ("000 " in parameter No.1) has been changed.
11) Software limit is valid.
12) Home position return completion.
13) Home position set has not been made after home position return position data
(parameter No. 42) setting.
If the status is not any of 1) to 13) and the home position setting has already been completed at least once, home position return completion (ZP) is placed in the same output status as ready (RD).
MBR turns off when the servo is switched off or an alarm occurs.
When an alarm occurs, they are turned off independently of the base circuit status.
Position range (POT) is on when the current position is within the range set in parameters No. 50 to 53. If the current position is within the set range, the device is off when a home position return is not yet complete or while the base circuit is off (during servo off, alarm occurrence or alarm reset).
BWNG
TLC
PUS
OUT1
OUT2
OUT3
When there is no warning, WNG turns off within about 1s after power-on.
BWNG turns on when battery cable breakage warning (AL. 92) or battery warning
(AL. 9F) has occurred. When there is no battery warning, BWNG turns off within about 1s after power-on.
TLC-SG are connected when the torque generated reaches the value set to the internal torque limit 1 (parameter No. 28), internal torque limit 1 (parameter No.
29) or analog torque limit (TLA).
PUS turns on when deceleration to a stop is started by Temporary stop/restart
(STP). PUS turns off when Temporary stop/restart (STP) is enabled again to resume operation.
CN1B-4 OUT1 turns on when the OUTON (1) command in the program is given. OUT1 turns off when the OUTOF command is given.
The time to turn it off can be set in parameter No. 74.
OUT2 turns on when the OUTON (2) command in the program is given. OUT2 turns off when the OUTOF command is given.
The time to turn it off can be set in parameter No. 75.
OUT3 turns on when the OUTON (3) command in the program is given. OUT3 turns off when the OUTOF command is given.
The time to turn it off can be set in parameter No. 76.
3 - 9
3. SIGNALS AND WIRING
(2) Input signal
For the input interfaces (symbols in I/O column in the table), refer to section 3.6.2.
Signal Connector
Signal Functions/Applications symbol pin No.
Manual pulse generator
I/O division
Apply 10[V] for 0[%] override, 0[V] for 100[%], or 10[V] for 200[%].
Analog torque limit TLA CN1B-12 To use this signal, set any of MR Configurator (servo configuration software) to make the external torque limit selection (TL) available.
When the analog torque limit (TLA) is valid, torque is limited in the full servo motor output torque range. Apply 0 to 10VDC across TLA-LG.
Connect the positive terminal of the power supply to TLA. Maximum torque is generated at 10V. (Refer to in section 3.4.4.) Resolution:10bits
(3) Output signal
For the output interfaces (symbols in I/O column in the table), refer to section 3.6.2.
Signal Connector
Signal Functions/Applications symbol pin No.
Encoder Z-phase pulse
(open collector)
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
Encoder Z-phase pulse
(differential line driver)
Analog monitor 1
Analog monitor 2
OP CN1A-14 Outputs the zero-point signal of the encoder. One pulse is output per servo motor revolution. OP and LG are connected when the zero-point position is reached. (Negative logic)
The minimum pulse width is about 400 s. For home position return using this pulse, set the creep speed to 100r/min. or less.
LA
LAR
LB
LBR
CN1A-6 Outputs pulses per servo motor revolution set in parameter No. 27 in the
CN1A-16 differential line driver system. In CCW rotation of the servo motor, the
CN1A-7 encoder B-phase pulse lags the encoder A-phase pulse by a phase angle
CN1A-17 of /2.
The relationships between rotation direction and phase difference of the
A- and B-phase pulses can be changed using parameter No. 58.
LZ
LZR
MO1
CN1A-5
CN1A-15
The same signal as OP is output in the differential line driver system.
CN3-4 Used to output the data set in parameter No.17 to across MO1-LG in terms of voltage. Resolution 10 bits
MO2 CN3-14 Used to output the data set in parameter No.17 to across MO2-LG in terms of voltage. Resolution 10 bits
Analog input
Analog input
I/O division
DO-2
DO-2
DO-2
DO-2
Analog output
Analog output
3 - 10
3. SIGNALS AND WIRING
(4) Communication
POINT
Refer to chapter 15 for the communication function.
Signal
RS-422 I/F
RS-422 termination
Signal symbol
Connector pin No.
Functions/Applications
SDP
SDN
RDP
RDN
CN3-9
CN3-19
CN3-5
CN3-15
RS-422 and RS-232C functions cannot be used together.
Choose either one in parameter No. 16.
TRE CN3-10 Termination resistor connection terminal of RS-422 interface.
When the servo amplifier is the termination axis, connect this terminal to RDN
(CN3-15).
TXD
RXD
CN3-2
CN3-12
RS-422 and RS-232C functions cannot be used together.
Choose either one in parameter No. 16.
RS-232C I/F
(5) Power supply
Signal
I/F internal power supply
Digital I/F power supply input
Open collector power input
Digital I/F common
15VDC power supply
Control common
Shield
Signal symbol
Connector pin No.
Functions/Applications
When using this power supply for digital interface, connect it with COM.
Permissible current : 80mA
CN1B-13 Connect the positive ( ) terminal of the 24VDC external power supply.
24VDC 10%
OPC CN1A-11 When you use a manual pulse generator , supply this terminal with the positive ( ) power of 24VDC.
SG CN1A-10 Common terminal for input signals such as SON and EMG. Pins are connected
20 internally.
CN1B-10 Separated from LG.
20
P15R CN1A-4 Outputs 15VDC to across P15R-LG. Available as power for VC and VLA.
CN1B-11 Permissible current: 30mA
LG CN1A-1
CN1B-1
CN3-1,
11
3,
13
Common terminal for TLA, VC, OP, MO1, MO2 and P15R.
Pins are connected internally.
SD Plate Connect the external conductor of the shield cable.
3 - 11
3. SIGNALS AND WIRING
3.4 Detailed description of signals (devices)
3.4.1 Forward rotation start Reverse rotation start Temporary stop/restart
(1) A forward rotation start (ST1) or a reverse rotation start (ST2) should make the sequence which can be used after the main circuit has been established. These signals are invalid if it is switched on before the main circuit is established.
Normally, it is interlocked with the ready signal (RD).
(2) A start in the servo amplifier is made when the external start signal changes from OFF to ON. The delay time of the servo amplifier's internal processing is max. 3ms. The delay time of other signals is max. 10ms.
3ms or less 3ms or less
Servo motor speed
Forward rotation start (ST1) or reverse rotation start (ST2)
Temporary stop/Restart (STP)
5ms or more
10ms or less
(3) When a programmable controller is used, the ON time of the start/stop signal should be 5ms or longer to prevent a malfunction.
(4) During operation, the forward rotation start (ST1) or reverse rotation start (ST2) is not accepted. The next operation should always be started after the Movement complete (PED) is output.
3 - 12
3. SIGNALS AND WIRING
3.4.2 Movement complete
POINT
If an alarm cause, etc. are removed and servo-on occurs after a stop is made by servo-off, alarm occurrence or Forced stop (EMG) ON during automatic operation, Position end (PED) is turned on. To resume operation, confirm the current position and the selected point table No. for preventing unexpected operation.
The following timing charts show the output timing relationships between the position command generated in the servo amplifier and the Movement complete (PED). This timing can be changed using parameter No. 6 (Movement complete output range). Turn PED on to bring in the servo-on status.
Forward rotation start (ST1) or reverse rotation start (ST2)
ON
OFF
3ms or less
Position command
Servo motor speed
Position command and servo motor speed
Movement complete range
Movement complete (PED)
ON
OFF
When parameter No. 6 is small
Forward rotation start (ST1) or reverse rotation start (ST2)
ON
OFF
3ms or less
Position command and servo motor speed
Position command
Servo motor speed
Movement complete range
Movement complete (PED)
ON
OFF
When parameter No. 6 is large
3 - 13
3. SIGNALS AND WIRING
3.4.3 Override
POINT
When using the override (VC), make the override selection (OVR) device available.
The override (VC) may be used to change the servo motor speed. The following table lists the signals and parameter related to the override.
Item Name Remarks
Analog input signal
Contact input signal
Override (VC)
Override selection (OVR)
MR Configurator (Servo Configuration Software) setting required.
Parameter No.25 override offset 999 to 999mV
(1) Override (VC)
By applying a voltage ( 10 to 10V) to the override (VC) terminal, change values can be set from outside consecutively. The following graph shows the relationship between the input voltage and the ratio of actual speed to preset speed.
[%]
200
Servo amplifier
100
Override selection (OVR)
Override (VC)
10 to 10V
OVR
SG
VC
LG
SD
0
10 0 10
[V]
Override (VC) application voltage
(2) Override selection (OVR)
Used to make the override (VC) valid or invalid.
Servo amplifier
Motor
Override selection
(OVR)
Override (VC)
10 to 10V
Using the override selection (OVR), choose a change value as follows.
External input signal
OVR
Speed change value
1 Override (VC) setting is made valid.
Note. 0 : OFF
1 : ON
(3) Override offset (parameter No.25)
Using parameter No.25, the offset voltage can be set relative to the input voltage for the override (VC).
The setting is between 999 to 999mV.
3 - 14
3. SIGNALS AND WIRING
3.4.4 Torque limit
POINT
To use the torque limit, make the external torque limit selection (TL) and internal torque limit selection (TL2) available.
The following table lists the signals and parameters related to the torque limit.
Item Name Remarks
Analog input signal
Contact input signals
Contact output signal
Analog torque limit (TLA)
External torque limit selection (TL)
Internal torque limit selection (TL2)
Limiting torque (TLC)
No.28 (internal torque limit 1)
MR Configurator (Servo Configuration Software) setting required.
0 to 100%
No.29 (internal torque limit 2) 0 to 100%
Parameters No.26 (torque limit offset)
No.59 (function selection 2)
999 to 999mV
Selection of the rotation direction in which torque limit is executed.
The torque limit is available in two types: internal torque limit set in parameters and analog torque limit
(TLA) using analog input signal. This function limits torque on the assumption that the maximum torque of the servo motor is 100%.
(1) Internal torque limits 1, 2
Use parameter No.28 and 29 to set the internal torque limit values. The following graph shows the torque relative to the setting.
Max. torque
0
0 100
Torque limit value [%]
(2) Analog torque limit (TLA)
By applying a voltage (0 to 10V) to the analog torque limit (TLA) terminal, limit values can be set from outside consecutively. The following graph shows the relationship between input voltage and limit value.
Depending on the servo amplifier, the limit value has about 5% variations to the input voltage. As this may not cause torque to be limited sufficiently at less than 0.05V, use this function at the voltage of
0.05V or more.
Refer to the following diagram when using the 15V power output (P15R) of the servo amplifier.
100
Servo amplifier
5%
0
0 0.05
10
TLA application voltage [V]
TLA Application Voltage and
Torque Limit Value
2k
2k
Japan Resistor RRS10 or equivalent
TL
SG
P15R
TLA
LG
SD
Connection Example
3 - 15
3. SIGNALS AND WIRING
(3) External torque limit selection (TL), internal torque limit selection (TL2)
To use the external torque limit selection (TL) and internal torque limit selection (TL2), make them available using the MR Configurator (Servo Configuration Software) (refer to chapter 6).
These input signals may be used to choose the torque limit values made valid.
(Note) External input signals
TL2 TL
0 0
Torque limit value made valid
0 1
1 0
1 1
Internal torque limit value 1 (parameter No. 28)
TLA Parameter No. 28: Parameter No. 28
TLA Parameter No. 28: TLA
Parameter No. 29 Parameter No. 28: Parameter No. 28
Parameter No. 29 Parameter No. 28: Parameter No. 29
TLA Parameter No. 29: Parameter No. 29
TLA Parameter No. 29: TLA
Note. 0: OFF
1: ON
(4) External torque limit offset (parameter No.26)
Using parameter No.26, the offset voltage can be set relative to the input voltage of the analog torque limit (TLA). The setting is between 999 to 999mV.
(5) Selection of rotation direction for torque limit execution (parameter No.59)
Using parameter No.59, the rotation direction for torque limit execution can be selected.
Parameter No.59 setting
Rotation direction for torque limit execution
CCW direction CW direction
0 (initial value)
1
2
For example, when “ 1 ” is set in parameter No.59, torque limit is executed in the CCW direction but not in CW direction.
CCW rotation: Torque limit is executed.
CW rotation: Torque limit is not executed.
3 - 16
3. SIGNALS AND WIRING
3.5 Alarm occurrence timing chart
CAUTION
When an alarm has occurred, remove its cause, make sure that the operation signal is not being input, ensure safety, and reset the alarm before restarting operation.
As soon as an alarm occurs, turn off Servo-on (SON) and power off.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a stop. Switch off the main circuit power supply in the external sequence. To reset the alarm, switch the control circuit power supply from off to on, press the "SET" button on the current alarm screen, or turn the reset (RES) from off to on. However, the alarm cannot be reset unless its cause is removed.
(Note)
Main circuit control circuit power supply
ON
OFF
Base circuit
ON
OFF
Dynamic brake Valid
Invalid
Servo-on
(SON)
Ready
(RD)
Trouble
(ALM)
Reset
(RES)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1s
Alarm occurs.
Brake operation
50ms or more
Power off
Brake operation
60ms or more
Power on
Remove cause of trouble.
Note. Switch off the main circuit power as soon as an alarm occurs.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent
(AL.32), overload 1 (AL.50) or overload 2 (AL.51) alarm after its occurrence, without removing its cause, the servo amplifier and servo motor may become faulty due to temperature rise.
Securely remove the cause of the alarm and also allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative
(AL.30) alarm after its occurrence, the external regenerative resistor will generate heat, resulting in an accident.
(3) Instantaneous power failure
Undervoltage (AL.10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer and the control circuit is not completely off.
The bus voltage dropped to 200VDC or less for the MR-J2S- CL, or to 158VDC or less for the
MR-J2S- CL1.
(4) Incremental system
When an alarm occurs, the home position is lost. When resuming operation after deactivating the alarm, make a home position return.
3 - 17
3. SIGNALS AND WIRING
3.6 Interfaces
3.6.1 Common line
The following diagram shows the power supply and its common line.
Dl-1
Manual pulse generator
MR-HDP01
5V
A(B)
0V
CN1A
CN1B
VDD
COM
SON,etc.
SG
OPC
PP(NP)
SG
5V
24VDC
<Isolated>
15VDC 10% 30mA
P15R
ALM,etc
Analog input
( 10V/max. current)
TLA
VC, etc.
LG
SD
SG
CN1A
CN1B
OP
LG
LA,etc
LAR,etc
LG
SD
MO1
MO2
LG
SDP
SDN
RDP
RDN
LG
SD
CN3
RA
DO-1
Differential line driver output
35mA or less
Analog monitor
RXD
RXD
TXD
TXD
LG
L
1
L
2
E
Single-phase
100 to 200VAC
Servo motor
M
Ground
MR
MRR
CN2
SD
Servo motor encoder
3 - 18
3. SIGNALS AND WIRING
3.6.2 Detailed description of the interfaces
This section gives the details of the I/O signal interfaces (refer to I/O Division in the table) indicated in sections 3.3.2. Refer to this section and connect the interfaces with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor. Source input is also possible. Refer to (6) in this section.
For use of internal power supply For use of external power supply
Servo amplifier
VDD
24VDC
Do not connect
VDD-COM.
Servo amplifier
COM
R: Approx. 4.7k
24VDC
(Note)
For a transistor
SON, etc.
24VDC
200mA or more
VDD
COM
R: Approx. 4.7k
Approx. 5mA
SON, etc.
Switch
TR SG
Switch
V
CES
1.0V
I
CEO
100 A
SG
Note. This also applies to the use of the external power supply.
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Provide a diode (D) for an inductive load, or an inrush current suppressing resister (R) for a lamp load. (Permissible current: 40mA or less, inrush current:
100mA or less) A maximum of 2.6V voltage drop occurs in the servo amplifier.
(a) Inductive load
For use of internal power supply For use of external power supply
Servo amplifier
24VDC
VDD
Servo amplifier
24VDC
VDD
Do not connect
VDD-COM.
COM COM
ALM, etc
Load
ALM, etc
Load
(Note)
24VDC
10%
SG
If the diode is not connected as shown, the servo amplifier will be damaged.
SG
If the diode is not connected as shown, the servo amplifier will be damaged.
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to 26.4V) from external source.
3 - 19
3. SIGNALS AND WIRING
(b) Lamp load
For use of internal power supply
Servo amplifier
24VDC
VDD
COM
R
ALM, etc
SG
For use of external power supply
Servo amplifier
24VDC
VDD
Do not connect
VDD-COM.
COM
ALM, etc
R (Note)
24VDC
10%
SG
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to 26.4V) from external source.
(3) Encoder pulse output DO-2
(a) Open collector system
Interface
Max. output current : 35mA
Servo amplifier Servo amplifier
OP
LG
SD
(b) Differential line driver system
1) Interface
Max. output current: 35mA
Servo amplifier
LA
(LB, LZ)
Am26LS32 or equivalent
Servo amplifier
LA
(LB, LZ)
150
LAR
(LBR, LZR)
LG
SD
LAR
(LBR, LZR)
SD
OP
LG
SD
5 to 24VDC
Photocoupler
100
High-speed photocoupler
3 - 20
3. SIGNALS AND WIRING
2) Output pulse
Servo motor CCW rotation
LA
LAR
LB
T
LBR
/2
LZ
LZR
OP
400 s or more
(4) Analog input
Input impedance 10k to 12k
Servo amplifier
2k
Upper limit setting 2k
15VDC
P15R
VC‚ etc
LG
SD
Approx.
10k
The time cycle (T) is determined by the setting of the parameter No. 27 and 58.
(5) Analog output
Output voltage 10V
Max.1mA
Max. output current
Resolution : 10bits
Servo amplifier
MO1
(MO2)
LG
10k
Reading in one or both directions
1mA meter
A
SD
3 - 21
3. SIGNALS AND WIRING
(6) Source input interface
When using the input interface of source type, all Dl-1 input signals are of source type. Source output cannot be provided.
For use of internal power supply For use of external power supply
Servo amplifier Servo amplifier
SG
SG
R: Approx. 4.7k
(Note)
For a transistor
Approx. 5mA
COM
SON,
etc.
COM
R: Approx. 4.7k
Switch
Switch
SON,etc.
24VDC
VDD
TR
V
CES
1.0V
I
CEO
100 A
24VDC
200mA or more
Note. This also applies to the use of the external power supply.
Since source output is not provided, make the following circuit.
For use of internal power supply For use of external power supply
Servo amplifier
24VDC
VDD
Servo amplifier
VDD
Do not connect
VDD-COM.
COM
24VDC
Load
COM
ALM, etc.
(Note)
24VDC
10%
ALM, etc.
Load
SG
If the polarity of diode is not correct, the servo amplifier will become faulty.
SG
If the polarity of diode is not correct, the servo amplifier will become faulty.
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to 26.4V) from external source.
3 - 22
3. SIGNALS AND WIRING
3.7 Input power supply circuit
CAUTION
Always connect a magnetic contactor (MC) between the main circuit power supply and L
1 , L
2 , and L
3 of the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions.
3.7.1 Connection example
Use the trouble (ALM) to switch power off. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as alarm occurrence is detected and power is shut off.
A no-fuse breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230VAC power supply
RA
Forced stop OFF
ON
MC
MC
SK
NFB MC
3-phase
200 to 230 VAC
L
1
L
2
L
3
L
11
L
21
Servo amplifier
Forced stop
Servo-on
EMG
SON
SG
VDD
COM
ALM RA Trouble
3 - 23
3. SIGNALS AND WIRING
(2) For 1-phase 100 to 120VAC or 1-phase 230VAC power supply
RA
Forced stop OFF
ON
MC
Power supply
1-phase 100 to
120VAC or
1-phase 230VAC
NFB
Forced stop
Servo-on
MC
L
1
Servo amplifier
L
2
L
3
L
11
(Note)
L
21
EMG
SON
SG
VDD
COM
ALM
MC
SK
RA Trouble
Note. Not provided for 1-phase 100 to 120VAC.
3 - 24
3. SIGNALS AND WIRING
3.7.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo amplifier. Refer to section 12.1.
Connection Target
Symbol Description
(Application)
Supply L
1
, L
2
and L
3
with the following power.
For 1-phase 230VAC, connect the power supply to L
1
/L
2
and leave L
3
open.
Servo amplifier MR-J2S-10CL MR-J2S-100CL MR-J2S-10CL1
Power supply to 70CL to 700CL to 40CL1
L
1
, L
2
, L
3
Main circuit power supply
U, V, W Servo motor output
3-phase 200 to 230VAC,
50/60Hz
1-phase 230VAC,
50/60Hz
L
1
L
2
L
1
L
2
L
3
1-phase 100 to 120VAC,
50/60Hz
L
1
L
2
Connect to the servo motor power supply terminals (U, V, W). During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
Power supply
Servo amplifier
MR-J2S-10CL to 700CL
MR-J2S-10CL1 to
40CL1
L
11
, L
21
Control circuit power supply
P, C, D
N
Regenerative option
Return converter
Brake unit
1-phase 200 to 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
L
11
L
21
L
11
L
21
1) MR-J2S-350CL or less
When using servo amplifier built-in regenerative resistor, connect between P-D terminals. (Wired by default)
When using regenerative option, disconnect between P-D terminals and connect regenerative option to P terminal and C terminal.
2) MR-J2S-500CL or 700CL
MR-J2S-500CL and 700CL do not have D terminal.
When using servo amplifier built-in regenerative resistor, connect P terminal and C terminal. (Wired by default)
When using regenerative option, disconnect P terminal and C terminal and connect regenerative option to P terminal and C terminal.
Refer to section 14.1.1 for details.
When using return converter/brake unit, connect to P terminal and N terminal.
Do not connect to servo amplifier MR-J2S-200CL or less.
Refer to sections 14.1.2 and 14.1.3 for details.
Protective earth (PE)
Connect this terminal to the protective earth (PE) terminals of the servo motor and control box for grounding.
3 - 25
3. SIGNALS AND WIRING
3.7.3 Power-on sequence
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.7.1 using the magnetic contactor with the main circuit power supply (three-phase 200V: L 1 , L 2 , L 3 , single-phase 230V single-phase
100V: L 1 , L 2 ). Configure up an external sequence to switch off the magnetic contactor as soon as an alarm occurs.
2) Switch on the control circuit power supply L 11 , L 21 simultaneously with the main circuit power supply or before switching on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on (SON) about 1 to 2s after the main circuit power supply is switched on. Therefore, when servo-on (SON) is switched on simultaneously with the main circuit power supply, the base circuit will switch on in about 1 to 2s, and the ready (RD) will switch on in further about 20ms, making the servo amplifier ready to operate. (Refer to paragraph (2) in this section.)
4) When the reset (RES) is switched on, the base circuit is shut off and the servo motor shaft coasts.
(2) Timing chart
SON accepted
(1 to 2s)
Power supply
ON
OFF
Base circuit
ON
OFF
Servo-on
(SON)
Reset
(RES)
ON
OFF
ON
OFF
Ready
(RD)
ON
OFF
20ms
10ms
10ms
60ms
20ms
10ms
10ms
60ms
20ms 10ms
3 - 26
3. SIGNALS AND WIRING
(3) Forced stop
CAUTION
Provide an external forced stop circuit to ensure that operation can be stopped and power switched off immediately.
Forced stop (EMG) can be used by making device setting on the MR Configurator (Servo Configuration
Software).
Make up a circuit which shuts off main circuit power as soon as EMG-SG are opened at a forced stop.
To ensure safety, always install an external emergency stop switch across EMG-SG. By disconnecting
EMG-SG, the dynamic brake is operated to bring the servo motor to a sudden stop. At this time, the display shows the servo emergency stop warning (AL.E6).
During ordinary operation, do not use the external forced stop (EMG) to alternate stop and run.
The servo amplifier life may be shortened.
Servo amplifier
Forced stop
VDD
COM
EMG
SG
3 - 27
3. SIGNALS AND WIRING
3.8 Connection of servo amplifier and servo motor
3.8.1 Connection instructions
WARNING
Insulate the connections of the power supply terminals to prevent an electric shock.
CAUTION
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier and servo motor. Otherwise, the servo motor will operate improperly.
Do not connect AC power supply directly to the servo motor. Otherwise, a fault may occur.
POINT
Do not apply the test lead bars or like of a tester directly to the pins of the connectors supplied with the servo motor. Doing so will deform the pins, causing poor contact.
The connection method differs according to the series and capacity of the servo motor and whether or not the servo motor has the electromagnetic brake. Perform wiring in accordance with this section.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal of the servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo amplifier
Servo motor
PE terminal
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3.8.2 Connection diagram
CAUTION
During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
The following table lists wiring methods according to the servo motor types. Use the connection diagram which conforms to the servo motor used. For cables required for wiring, refer to section 14.2.1. For encoder cable connection, refer to section 14.1.4. For the signal layouts of the connectors, refer to section
3.8.3.
For the servo motor connector, refer to chapter 3 of the Servo Motor Instruction Manual.
3 - 28
3. SIGNALS AND WIRING
Servo motor
HC-KFS053 (B) to 73 (B)
HC-MFS053 (B) to 73 (B)
HC-UFS13 (B) to 73 (B)
HC-SFS121 (B) to 301 (B)
HC-SFS202 (B) 702 (B)
HC-SFS203 (B) 353 (B)
HC-UFS202 (B) to 502 (B)
HC-RFS353 (B) to 503 (B)
HC-SFS81 (B)
HC-SFS52 (B) to 152 (B)
HC-SFS53 (B) to 153 (B)
HC-RFS103 (B) to 203 (B)
HC-UFS72 (B) 152 (B)
Connection diagram
Servo amplifier
U
V
W
Servo motor
U (Red)
V (White)
W (Black)
(Green)
(Note 1) 24VDC
B1
EMG
B2
To be shut off when servo-off or Trouble (ALM)
Motor
(Note 2)
Electromagnetic brake
CN2
Encoder cable Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo motor Servo amplifier
U
V
W
U
V
W
Motor
(Note 1) 24VDC
B1
B2
EMG
To be shut off when servo-off or Trouble (ALM)
(Note 2)
Electromagnetic brake
CN2
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
U
V
W
U
V
W
Servo motor
Motor
(Note 1)
24VDC
B1
B2
EMG
To be shut off when servo-off or Trouble (ALM)
(Note 2)
Electromagnetic brake
CN2
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
3 - 29
3. SIGNALS AND WIRING
3.8.3 I/O terminals
(1) HC-KFS HC-MFS HC-UFS3000r/min series a
Encoder cable 0.3m (0.98ft.)
With connector 1-172169-9
(Tyco Electronics)
Power supply connector
5557-04R-210
1
2
3
4
View b
Pin
3
4
1
2 b
Signal
U
V
W
(Earth)
Power supply lead
4-AWG19 0.3m (0.98ft.)
Power supply connector (Molex)
Without electromagnetic brake
5557-04R-210 (receptacle)
5556PBTL (Female terminal)
With electromagnetic brake
5557-06R-210 (receptacle)
5556PBTL (Female terminal)
Power supply connector
5557-06R-210
1 4
2 5
3 6
View b
Encoder connector signal arrangement
1
MR
4
MD
7
P5
2 3
MRR BAT
5
MDR
6
8 9
LG SHD
View a
Pin Signal
1
2
U
V
3
4
W
(Earth)
5 (Note) B1
6 (Note) B2
Note. Supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 30
3. SIGNALS AND WIRING
(2) HC-SFS HC-RFS HC-UFS2000 r/min series a
Encoder connector b
Brake connector c
Power supply connector
Servo motor
HC-SFS81(B)
HC-SFS52(B) to 152(B)
HC-SFS53(B) to 153(B)
Servo motor side connectors
For power supply For encoder
Electromagnetic brake connector
CE05-2A22-
23PD-B
HC-SFS121(B) to 301(B)
HC-SFS202(B) to 502 (B)
HC-SFS203(B) 353(B)
CE05-2A24-
10PD-B
HC-SFS702(B)
CE05-2A32-
17PD-B
HC-RFS103(B) to 203 (B)
CE05-2A22-
23PD-B
HC-RFS353(B) 503(B)
HC-UFS72(B) 152(B)
CE05-2A24-
10PD-B
CE05-2A22-
23PD-B
HC-UFS202(B) to 502(B)
CE05-2A24-
10PD-B
MS3102A20-
29P
The connector for power is shared.
MS3102A10SL-
4P
The connector for power is shared.
MS3102A10SL-
4P
Power supply connector signal arrangement
CE05-2A22-23PD-B CE05-2A24-10PD-B CE05-2A32-17PD-B
Key
F
G
H
E
D
View c
A
B
C
Pin Signal
Key
D
E
F
G
H
A
B
C
U
V
W
(Earth)
E
F
D
G
View c
(Note) B1
(Note) B2
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
A
C
B
Pin
C
D
A
B
E
F
G
Signal
U
V
W
(Earth)
(Note) B1
(Note) B2
D
C
Key
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
A
B
Pin
A
B
C
D
Signal
U
V
W
(Earth)
Encoder connector signal arrangement
MS3102A20-29P
Key
L
M
K
J
T
H
N
A
S R
G
P
B
C
D
F
E
View a
Pin
C
D
E
G
H
J
A
B
Signal
MD
MDR
MR
MRR
BAT
LG
Pin
S
T
P
R
K
L
M
N
Signal
SD
LG
P5
Electromagnetic brake connector signal arrangement
MS3102A10SL-4P
Key
A
View b
B
Pin Signal
A
B
(Note)
(Note)
B1
B2
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 31
3. SIGNALS AND WIRING
3.9 Servo motor with electromagnetic brake
CAUTION
Configure the electromagnetic brake operation circuit so that it is activated not only by the servo amplifier signals but also by an external forced stop (EMG).
Contacts must be open when servo-off, when an trouble (ALM) and when an electromagnetic brake interlock (MBR).
Servo motor
RA EMG
Circuit must be opened during forced stop (EMG).
24VDC
Electromagnetic brake
The electromagnetic brake is provided for holding the motor shaft. Do not use it for ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake operates properly.
POINT
For the power supply capacity, operation delay time and other specifications of the electromagnetic brake, refer to the Servo Motor
Instruction Manual.
Note the following when the servo motor equipped with electromagnetic brake is used.
1) In the device setting of the MR Configurator (Servo Configuration software), make the electromagnetic brake interlock (MBR) available.
2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake. Always use the power supply designed exclusively for the electromagnetic brake.
3) The brake will operate when the power (24VDC) switches off.
4) While the reset (RES) is on, the base circuit is shut off. When using the servo motor with a vertical shaft, use the electromagnetic brake interlock (MBR).
5) Turn off the servo-on (SON) after the servo motor has stopped.
(1) Connection diagram
Servo amplifier Servo motor
VDD
RA
Forced stop
B1
COM
MBR RA
24VDC
B2
3 - 32
3. SIGNALS AND WIRING
(2) Setting
1) In the device setting of the MR Configurator (Servo Configuration Software), make the electromagnetic brake interlock (MBR) available.
2) Using parameter No. 33 (electromagnetic brake sequence output), set a time delay (Tb) at servooff from electromagnetic brake operation to base circuit shut-off as in the timing chart shown in
(3) in this section.
(3) Timing charts
(a) Servo-on (SON) command (from controller) ON/OFF
Tb (ms) after servo-on (SON) is switched off, servo lock is released and the servo motor coasts.
If the electromagnetic brake is made valid in the servo lock status, the brake life may be shorter.
For use in vertical lift and similar applications, therefore, set delay time (Tb) to the time which is about equal to the electromagnetic brake operation delay time and during which the load will not drop.
Servo motor speed 0 r/min
(60ms)
Coasting
Tb
Base circuit
ON
OFF
Electromagnetic brake interlock
(MBR)
(Note 1) ON
OFF
Servo-on (SON)
ON
OFF
Forward rotation start
(ST1) or reverse rotation start (ST2)
ON
OFF
Electromagnetic brake
Release
Activate
(80ms)
(Note 3)
Electromagnetic brake operation delay time
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. Electromagnetic brake is released after delaying for the release delay time of electromagnetic brake and operation time of external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual.
3. After the electromagnetic brake is released, turn ON the ST1 or ST2.
3 - 33
3. SIGNALS AND WIRING
(b) Forced stop (EMG) ON/OFF
Servo motor speed
Base circuit
Forward rotation
0r/min
(10ms)
ON
OFF
Electromagnetic brake interlock (MBR)
(Note) ON
OFF
Invalid (ON)
Forced stop (EMG)
Valid (OFF)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake release
(180ms)
Electromagnetic brake operation delay time
(180ms)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
(c) Alarm occurrence
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Servo motor speed
Base circuit
Electromagnetic brake interlock (MBR)
Trouble (ALM)
Forward rotation
0r/min
(10ms)
ON
OFF
(Note) ON
OFF
No (ON)
Yes (OFF)
Electromagnetic brake operation delay time
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 34
3. SIGNALS AND WIRING
(d) Both main and control circuit power supplies off
Servo motor speed
Forward rotation
0r/min
(Note 1)
15 to 60ms
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
ON
Base circuit
OFF
Electromagnetic brake interlock (MBR)
(Note 2) ON
OFF
Trouble (ALM)
No (ON)
Yes (OFF)
Electromagnetic brake operation delay time
Main circuit
Control circuit power
ON
OFF
Note 1. Changes with the operating status.
2. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
(e) Only main circuit power supply off (control circuit power supply remains on)
Servo motor speed
Forward rotation
0r/min
(Note 1)
15 or more
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
ON
Base circuit
OFF
Electromagnetic brake interlock (MBR)
(Note 3) ON
OFF
Trouble (ALM)
No (ON)
Yes (OFF)
Electromagnetic brake operation delay time
(Note 2)
Main circuit power supply
ON
OFF
Note 1. Changes with the operating status.
2. When the main circuit power supply is off in a motor stop status, the main circuit off warning (AL.E9) occurs and the trouble (ALM) does not turn off.
3. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 35
3. SIGNALS AND WIRING
3.10 Grounding
Ground the servo amplifier and servo motor securely.
WARNING To prevent an electric shock, always connect the protective earth (PE) terminal of the servo amplifier with the protective earth (PE) of the control box.
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB (NA) 67310).
Control box
Servo motor
NFB MC Servo amplifier
L
1
CN2
(Note)
Power supply
L
2
Encoder
L
3
L
11
L
21
CN1A CN1B
U
V
W
U
V
W
M
Ensure to connect it to PE terminal of the servo amplifier.
Do not connect it directly to the protective earth of the control panel.
Protective earth(PE)
Outer box
Note. For 1-phase 230VAC, connect the power supply to L
1
L
2
and leave L
3
open.
There is no L
3
for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
3 - 36
3. SIGNALS AND WIRING
3.11 Servo amplifier terminal block (TE2) wiring method
POINT
Refer to Table 14.1 in section 14.2.1 for the wire sizes used for wiring.
3.11.1 For the servo amplifier produced later than Jan. 2006
(1) Termination of the cables
(a) Solid wire
After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
Approx. 10mm
(b) Twisted wire
1) When the wire is inserted directly
Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
2) When the wires are put together
Using a bar terminal.
Cable Size
[mm 2 ] AWG
1.25/1.5 16 AI1.5-10BK
Bar Terminal Type
For 1 cable
AI-TWIN 1.5-10BK
For 2 cables
Crimping Tool Manufacturer
CRIMPFOX ZA 3 Phoenix Contact
Cut the wire running out of bar terminal to less than 0.5mm.
Less than 0.5mm
When using a bar terminal for two wires, insert the wires in the direction where the insulation sleeve does not interfere with the next pole and pressure them.
Pressure
Pressure
3 - 37
3. SIGNALS AND WIRING
(2) Termination of the cables
(a) When the wire is inserted directly
Insert the wire to the end pressing the button with a small flat blade screwdriver or the like.
Button
Small flat blade screwdriver or the like
Twisted wire
When removing the short-circuit bar from across P-D, press the buttons of P and D alternately pulling the short-circuit bar. For the installation, insert the bar straight to the end.
(b) When the wires are put together using a bar terminal
Insert a bar terminal with the odd-shaped side of the pressured terminal on the button side.
Bar terminal for one wire or solid wire
Bar terminal for two wires
3 - 38
3. SIGNALS AND WIRING
3.11.2 For the servo amplifier produced earlier than Dec. 2005
(1) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Approx. 10mm
(0.39inch)
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
Cable size Bar terminal type
Crimping tool Manufacturer
[mm 2 ] AWG For 1 cable For 2 cables
1.25/1.5 16 AI1.5-10BK AI-TWIN 1.5-10BK CRIMPFOX ZA 3 or
CRIMPFOX UD 6
Phoenix Contact
(2) Connection
Insert the core of the cable into the opening and tighten the screw with a flat-blade screwdriver so that the cable does not come off. (Tightening torque: 0.3 to 0.4N m (2.7 to 3.5Ib in)) Before inserting the cable into the opening, make sure that the screw of the terminal is fully loose.
When using a cable of 1.5mm
2 or less, two cables may be inserted into one opening.
Flat-blade screwdriver
Tip thickness 0.4 to 0.6mm (0.016 to 0.024in.)
Overall width 2.5 to 3.5mm (0.098 to 0.138in.)
To loosen.
To tighten.
Cable
Opening
Control circuit terminal block
3 - 39
3. SIGNALS AND WIRING
Use of a flat-blade torque screwdriver is recommended to manage the screw tightening torque.
The following table indicates the recommended products of the torque screwdriver for tightening torque management and the flat-blade bit for torque screwdriver. When managing torque with a
Phillips bit, please consult us.
Torque screwdriver
Bit for torque screwdriver
3.12 Instructions for the 3M connector
N6L TDK
B-30, flat-blade, H3.5 X 73L
Nakamura Seisakusho
Shiro Sangyo
When fabricating an encoder cable or the like, securely connect the shielded external conductor of the cable to the ground plate as shown in this section and fix it to the connector shell.
External conductor Sheath
Strip the sheath.
Screw
Core
External conductor
Sheath
Pull back the external conductor to cover the sheath.
Cable
Ground plate
Screw
3 - 40
4. OPERATION
4. OPERATION
4.1 When switching power on for the first time
4.1.1 Pre-operation checks
Before starting operation, check the following.
(1) Wiring
(a) A correct power supply is connected to the power input terminals (L
1
, L
2
, L
3
, L
11
, L
21
) of the servo amplifier.
(b) The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the power input terminals (U, V, W) of the servo motor.
(c) The servo motor power supply terminals (U, V, W) of the servo amplifier are not shorted to the power input terminals (L
1
, L
2
, L
3
) of the servo motor.
(d) The earth terminal of the servo motor is connected to the PE terminal of the servo amplifier.
(e) Note the following when using the regenerative option, brake unit or power regeneration converter.
1) For the MR-J2S-350CL or less, the lead has been removed from across D-P of the control circuit terminal block, and twisted cables are used for its wiring.
2) For the MR-J2S-500CL or more, the lead has been removed from across P-C of the servo amplifier built-in regenerative resistor, and twisted cables are used for its wiring.
(f) When stroke end limit switches are used, the signals across LSP-SG and LSN-SG are on during operation.
(g) 24VDC or higher voltages are not applied to the pins of connectors CN1A and CN1B.
(h) SD and SG of connectors CN1A and CN1B are not shorted.
(i) The wiring cables are free from excessive force.
(2) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
(3) Machine
(a) The screws in the servo motor installation part and shaft-to-machine connection are tight.
(b) The servo motor and the machine connected with the servo motor can be operated.
4 - 1
4. OPERATION
4.1.2 Startup
WARNING Do not operate the switches with wet hands. You may get an electric shock.
CAUTION
Before starting operation, check the parameters. Some machines may perform unexpected operation.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor, servo motor, etc.since they may be hot while power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
Connect the servo motor with a machine after confirming that the servo motor operates properly alone.
For startup reference, a single machine structure will be described. Refer to this section and start up the machine safely.
(1) Machine conditions
P
Servo amplifier
Reduction ratio
1/n 1/2
P B
Servo motor
HC-MFS131072pulse/rev
Regenerative option MR-RB032
Servo motor speed
Ta
Program No. 2
Tb
Ballscrew
P
B
10mm(0.39inch)
V
Position data (P) 200mm(787.40inch)
Speed (V) 2500r/min
Acceleration time constant (Ta) 200ms
Deceleration time constant (Tb) 300ms
0r/min
1) Absolute position detection system used
2) Command resolution: 10 m
3) Command system: Absolute value command system
4) Electronic gear calculation
CMX(pulse)
CDV( m)
131072
1 n P
B
1000
1
2
131072
10 1000
131072
5000
32768
1250
........................................................(4.1)
CMX 32768
CDV 1250
5) External input signals are used by the program selection, forward rotation start (ST1), servo-on
(SON) and other commands.
6) Program No.2 is used to execute program operation once.
4 - 2
4. OPERATION
(2) Startup procedure
(a) Power on
1) Switch off the servo-on (SON).
2) When main circuit power/control circuit power is switched on, "PoS" (Current position) appears on the servo amplifier display.
In the absolute position detection system, first power-on results in the absolute position lost
(AL.25) alarm and the servo system cannot be switched on. This is not a failure and takes place due to the uncharged capacitor in the encoder.
The alarm can be deactivated by keeping power on for a few minutes in the alarm status and then switching power off once and on again.
Also in the absolute position detection system, if power is switched on at the servo motor speed of 500r/min or higher, position mismatch may occur due to external force or the like. Power must therefore be switched on when the servo motor is at a stop.
(b) Test operation
Using jog operation in the "test operation mode" of the MR Configurator (Servo Configuration
Software), confirm that the servo motor operates at the slowest speed. (Refer to section 6.7.1, 7.8.2)
(c) Parameter setting
Set the parameters according to the structure and specifications of the machine. Refer to chapter 5 for the parameter definitions and to sections 6.4 and 7.6 for the setting method.
Parameter Name Setting Description
No.0
No.2
No.4
No.5
Command system, regenerative option selection
Function selection 1
Electronic gear numerator (CMX)
Electronic gear denominator (CDV)
20
Absolute value command system.
MR-RB032 regenerative option is used.
10
When forward rotation start (ST1) is valid, address is incremented in CCW direction.
Since command resolution is 10 times, feed length multiplication factor of 10 times is selected.
1
Absolute position detection system.
32768 From calculation result of formula (4.1)
1250 From calculation result of formula (4.1)
After setting the above parameters, switch power off once. Then switch power on again to make the set parameter values valid.
(d) Program setting
Set the program according to the operation pattern. Refer to section 4.2 for the program definitions and to sections 4.2 and 6.5 for the setting method.
Program Description
SPN (2500)
STA (200)
STB (300)
MOV (20000)
STOP
Speed (Motor speed)
Acceleration time constant
Deceleration time constant
Absolute move command
Program end
2500 [r/min]
200 [ms]
300 [ms]
20000 [ 10 STM m]
4 - 3
4. OPERATION
(e) Servo-on
Switch the servo-on in the following procedure.
1) Switch on main circuit/control circuit power.
2) Switch on the servo-on (SON).
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is locked. By using the sequence in the diagnostic mode in section 7.3, the ready status can be shown on the servo amplifier display. In the operation-ready status, the following screen appears.
(f) Home position return
Perform home position return as required. Refer to section 4.4 for home position return types. A parameter setting example for dog type home position return is given here.
Parameter Name Setting
000
No.8
No.9
No.10
No.11
No.42
No.43
Home position return type
Home position return speed
Creep speed
Home position shift distance
Home position return position data
Moving distance after proximity dog
1000
10
0
Description
Dog type home position return is selected.
Home position return is started in address incremented direction.
Proximity dog (DOG) is valid at OFF.
Motion is made up to proximity dog at 1000r/min.
Motion is made up to home position at 10r/min.
No home position shift
Used to set the current position on completion of home position return.
Not used in dog type home position return.
After setting the above parameters, switch power off once. Then switch power on again to make the set parameter values valid.
Create a program that executes a home position return. Here, create it as program No. 1.
Program Description
ZRT Zeroing
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute home position return.
Device name
Automatic/manual selection
Program No. selection 1
Program No. selection 2
Forward rotation stroke end
Reverse rotation stroke end
Symbol
MD0
DI0
DI1
LSP
LSN
ON/OFF
ON
OFF
OFF
ON
ON
Description
Program operation mode is selected.
Program No.1 is selected.
CCW rotation side limit switch is turned on.
CW rotation side limit switch is turned on.
4 - 4
4. OPERATION
(g) Automatic operation
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute automatic operation in accordance with program No.2.
Device name
Automatic/manual selection
Symbol
MD0
ON/OFF
ON
Description
Automatic operation mode is selected.
Forward rotation stroke end
Reverse rotation stroke end
LSP
LSN
ON
ON
CCW rotation side limit switch is turned on.
CW rotation side limit switch is turned on.
Program No. selection 1 DI0 ON
Program No.2 is selected.
Program No. selection 2 DI1 OFF
(h) Stop
In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo motor.
When the servo motor used is equipped with an electromagnetic brake, refer to section 3.9 (3). Note that forward rotation stroke end (LSP), reverse rotation stroke end (LSN) off has the same stopping pattern as described below.
1) Servo-on (SON) OFF
The base circuit is shut off and the servo motor coasts.
2) Alarm occurrence
When an alarm occurs, the base circuit is shut off and the dynamic brake is operated to bring the servo motor to a sudden stop.
3) Forced stop (EMG) OFF
The base circuit is shut off and the dynamic brake is operated to bring the servo motor to a sudden stop. Servo forced warning (AL.E6) occurs.
4) Forward rotation stroke end (LSP), reverse rotation stroke end (LSN) OFF
The droop pulse value is erased and the servo motor is stopped and servo-locked. It can be run in the opposite direction.
4.2 Program operation mode
4.2.1 What is program operation mode?
Make selection with the input signals or by communication from among the programs that have been created in advance using the MR Configurator (Servo Configuration software), and perform operation with Forward rotation start (ST1).
This servo is factory-set to the absolute value command system.
As the position data, the absolute move command ("MOV" command) used to specify the target address or the incremental move command ("MOVI" command) used to specify the moving distance can be set. Note that the movable range is -999999 to 999999 [ 10 STM m]. Positioning is enabled within this range.
Setting range: 999999 to 999999 [ 10 STM m] (STM feed length multiplication parameter No.1)
999999 999999
Position data setting range
[ 10 m]
4 - 5
4. OPERATION
4.2.2 Programming language
The maximum number of program steps is 120. Though up to 16 programs can be created, the total number of program steps is up to 120.
The set program can be selected using Program No. selection 1 (DI0) to Program No. selection 4 (ID3).
(1) Command list
Command Name Setting
Setting range
Unit
Indirect
Addressing
Description
SPN
(Note 2)
STD
(Note 2)
STC
(Note 2)
STA
(Note 2)
STB
(Note 2)
MOV
MOVA
MOVI
Speed
(Motor speed)
SPN
(Set value)
S-pattern
Acceleration/
Deceleration time constant
STD
(Set value)
0 to
Max speed
0 to 100
Acceleration/
Deceleration time constant
STC
(Set value)
0 to 20000
Acceleration time constant
STA
(Set value)
0 to 20000
Deceleration time constant
STB
(Set value)
0 to 20000
Absolute move command
Absolute continuous move command
Incremental move command
MOV
(Set value)
MOVA
(Set value)
MOVI
(Set value)
-999999 to 999999
-999999 to 999999
-999999 to 999999 r/min ms ms ms ms
10 STM m
10 STM m
10 STM m
Use to set the command speed given to the motor for positioning.
The set value should not be more than the maximum speed of the motor.
S-pattern acceleration/deceleration time constant.
Set this command when inserting an S-pattern time constant for the acceleration/deceleration time constant of the program.
Use to set both the acceleration time constant and deceleration time constant.
The set value is the time from when the used servo motor is at a stop until it reaches the rated speed, or the time from when the servo motor is running at the rated speed until it stops.
When this command is used, the acceleration time constant and deceleration time constant are equal.
"STA" and "STB" commands can set the acceleration time constant and deceleration time constant individually. It can not be changed during command output.
Use to set the acceleration time.
The set value is the time from when the used servo motor is at a stop until it reaches the rated speed.
It can not be changed during command output.
Use to set the deceleration time constant.
The set value is the time from when the servo motor is running at the rated speed until it stops.
It can not be changed during command output.
The set value is regarded as an absolute value for movement.
The set value is regarded as an absolute value for continuous movement.
Always use this command with the "MOV" command.
The set value is regarded as an incremental value for movement.
4 - 6
4. OPERATION
Command Name Setting
Setting range
MOVIA
Incremental continuous move command
MOVIA
(Set value)
-999999 to 999999
Unit
10 STM m
Indirect
Addressing
SYNC
(Note 1)
OUTON
(Note 1 3)
Waiting external signal to switch on
External signal ON output
SYNC
(Set value)
OUTON
(Set value)
1 to 3
1 to 3
Description
The set value is regarded as an incremental value for movement.
Always use this command with the "MOVI" command.
Stops the next step until any of Program input 1
(PI1) to Program input 3 (PI3) turns ON after the output of SYNC synchronous output (SOUT).
Set value Input signal
1
2
3
Program input 1 (PI1)
Program input 2 (PI2)
Program input 3 (PI3)
Turns ON any of Program output 1 (OUT1) to
Program output 3 (OUT3).
By setting the ON time with parameter No. 74 to No.
76, the signal can also be turned OFF in the preset time.
Set value Input signal
OUTOF
(Note 1)
External signal OFF output
OUTOF
(Set value)
1 to 3
Turns OFF any of Program output 1 (OUT1) to
Program output 3 (OUT3) that has been turned ON by the "OUTON" command.
Set value Input signal
TRIP
(Note 1)
Absolute trip point
TRIP
(Set value)
-999999 to 999999
10 STM m
TRIPI
(Note 1)
Incremental
Trip point
TRIPI
(Set value)
-999999 to 999999
10 STM m
ITP
(Note 1 4)
Interrupt positioning command
ITP
(Set value)
0 to
999999
10 STM m
When the trip point is reached, the next step will be executed.
Executes the next step when the moving distance set to the "TRIPI" command is traveled from when
"MOVI" and "MOVIA" started during the movement executed by the "MOVI" and "MOVIA" commands.
The command should be programmed after "MOVI" and "MOVIA" command, otherwise program error occurs.
Makes a stop using the interrupt signal when the preset moving distance is reached. Use this command in combination with the "SYNC" command, and describe it after "SYNC". An error will occur if this command is described after any other command.
4 - 7
4. OPERATION
Command Name Setting
Setting range
Unit
Indirect
Addressing
Description
Executes the next step when the pulse counter value
COUNT
(Note 1)
External pulse counter
COUNT
(Set value)
-999999 to 999999
COUNT (0) is clearing of the pulse counter.
Repeats the steps located between the "FOR (set
FOR
NEXT
LPOS
(Note 1)
Step repeat command
FOR
(SET value)
NEXT
0, 1 to
10000
Position latch LPOS
Setting "0" selects endless repetition.
Latches the current position on the leading edge of
Input device current latch (LPS).
The latched current position data can be read by the communication command.
There are some error values between the latched data and the actual exact position, due to the sampling time and motor speed.
Holds the next step until the preset time elapses.
TIM
Dwell command time
Zeroing
TIM
(Set value)
1 to 2000 10ms
ZRT
TIMES
Program repeat command
ZRT
TIMES
(Set value)
0, 1 to
10000
Times
Executes a manual home position return.
Place the "TIMS (setting value)" command at the beginning of the program and set the number of program execution times.
Setting "0" selects endless repetition.
Program stops signal, and it must be at end of the program. (Required)
Always describe this command on the last line.
Note 1. "SYNC" "OUTON" "OUTOF" "TRIP" "TRIPI" "COUNT" "LPOS" and "ITP" commands are available to be validated during command outputting.
2. The "SPN" command is valid when the "MOV", "MOVA", "MOVI" or "MOVIA" command is executed. The "STA", "STB", "STC" and "STD" commands are valid when the "MOV" or "MOVI" command is executed.
3. When the ON time has been set in parameter No. 74 to No. 76, the next command is executed after the preset time has elapsed.
4. The remaining moving distance by ITP command is lower than setting value, the command would be ignored and skip to the next program command.
4 - 8
4. OPERATION
(2) Details of programming languages
(a) Details of the command (SPN STA STB STC STD)
"SPN" "STA" "STB" "STC" and "STD" commands will be validated, when the "MOV" and "MOVA" commands are executing. The setting numbers will be validated, expect resetting the numbers.
1) Program example 1
When operation is to be performed in two patterns that have the same servo motor speed, acceleration time constant and deceleration time constant but different move commands.
Program Description
SPN (1000)
STA (200)
STB (300)
MOV (1000)
TIM (10)
MOV (2000)
STOP Program end
1000 m] d)
2000 m] f) b) Acceleration time
constant (200ms) c) Deceleration time
constant (300ms) b) Acceleration time
constant (200ms) c) Deceleration time
constant (300ms)
Forward rotation a) Speed
(Motor speed)
(1000r/min)
Servo motor speed
0r/min d) Absolute move command
(1000 10 STM m) e) Dwell command
time (100ms) a) Speed (Motor speed)
(1000r/min) f) Absolute move command
(2000 10 STM m)
4 - 9
4. OPERATION
2) Program example 2
When operation is to be performed in two patterns that have different servo motor speeds, acceleration time constants, deceleration time constants and move commands.
Program Description
SPN (1000)
STA (200)
STB (300)
MOV (1000)
TIM (10)
1000 m] d)
SPN (500)
STC (200)
MOV (1500)
STOP
Acceleration/deceleration time constant 200 [ms] g)
1500 m] h)
Program end b) Acceleration time
constant (200ms)
Forward rotation c) Deceleration time
constant (300ms) a) Speed
(Motor speed)
(1000r/min)
Servo motor speed
0r/min d) Absolute move command
(1000 10 STM m) e) Dwell command
time (100ms) g) Acceleration/
deceleration time
constant
(200ms) f) Speed (Motor speed)
(500r/min) h) Absolute move command
(1500 10 STM m)
3) Program example 3
Use of an S-pattern acceleration/deceleration time constant allows sudden operation to be eased at the time of acceleration and deceleration. When the "STD" command is used, parameter No.
14 (S-pattern acceleration/deceleration time constant) is ignored.
Program Description
SPN (1000)
STC (100) Acceleration/deceleration time constant 1000 [ms] b)
STD (10) S-pattern acceleration/deceleration time constant 10 [ms] c)
MOV (2000) 2000 m] d)
STOP Program end c) c) b) Acceleration/deceleration
time constant
(1000ms)
Forward rotation
Servo motor speed
0r/min c) S-pattern acceleration/
deceleration time
constant (10ms) a) Speed
(Motor speed)
(1000r/min) b) Acceleration/deceleration
time constant
(1000ms) d) Absolute move command
(2000 10 STM m) c)
4 - 10
4. OPERATION
(b) Continuous move command (MOVA MOVIA)
POINT
"MOV" cannot be used with "MOVIA", and "MOVI" cannot be used with
"MOVA".
The "MOVA" command is a continuous move command for the "MOV" command. After execution of the movement by the "MOV" command, the movement of the "MOVA" command can be executed continuously without a stop.
The speed changing point of the "MOVA" command is the deceleration starting position of the operation performed by the preceding "MOV" and "MOVA" commands.
The acceleration/deceleration time constant of the "MOVA" command is the value at execution of the preceding "MOV" command.
The "MOVIA" command is a continuous move command for the "MOVI" command. After execution of the movement by the "MOVI" command, the movement of the "MOVIA" command can be executed continuously without a stop.
The speed changing point of the "MOVIA" command is the deceleration starting position of the operation performed by the preceding "MOVI" and "MOVIA" commands.
The acceleration/deceleration time constant of the "MOVIA" command is the value at execution of the preceding "MOVI" command.
Command Name Setting Unit Description
MOV
MOVA
MOVI
MOVIA
Absolute move command
Absolute continuous move command
Incremental move command
Incremental continuous move command
MOV
(Set value)
MOVA
(Set value)
MOVI
(Set value)
MOVIA
(Set value)
Forward rotation b) Acceleration time
constant (200ms)
10 STM command
10 STM m Absolute continuous move command
10 STM m Incremental
1) Program example 1
Use of an S-pattern time constant allows sudden operation to be eased at the time of acceleration and deceleration.
Program Description
SPN (500)
STA (200)
STB (300)
500 m] d) MOV (500)
SPN (1000)
MOVA (1000)
MOVA (0)
STOP Program end
1000 m] f)
0 m] g) c) Deceleration time
constant (300ms) a) Speed(Motor speed)
(500r/min)
10 STM command e) Speed
(Motor speed)
(1000r/min)
Servo motor speed
0r/min
Reverse rotation d) Absolute move
command
(500 10 STM m) f) Absolute continuous
move command
(1000 10 STM m) b) Acceleration time
constant (200ms)
4 - 11 e) Speed
(Motor speed)
(1000r/min) g) Absolute continuous
move command
(0 10 STM m)
4. OPERATION
2) Program example 2 (Wrong usage)
In continuous operation, the acceleration or deceleration time constant cannot be changed at each speed change. Hence, the "STA", "STB" or "STD" command is ignored if it is inserted for a speed change.
Program Description
SPN (500)
STA (200)
STB (300)
500 m] d) MOV (500)
SPN (1000)
STC (500)
MOVA (1000)
Acceleration/deceleration time constant
Absolute continuous move command
500 [ms]
1000 [ 10 STM f) m] g)
Ignored.
SPN (1500)
STC (100)
MOVA (0)
STOP
Acceleration/deceleration time constant
Absolute continuous move command
Program end
100 [ms]
0 [ 10 STM i) m] j)
Ignored.
b) Acceleration time
constant (200ms) c) Deceleration time
constant (300ms)
Forward rotation a) Speed(Motor speed)
(500r/min) e) Speed
(Motor speed)
(1000r/min)
Servo motor speed
0r/min
Reverse rotation d) Absolute move command
(500 10 STM m) g) Absolute continuous
move command
(1000 10 STM m) h) Speed
(Motor speed)
(1500r/min) j) Absolute continuous
move command
(0 10 STM m)
(c) Input/output command (OUTON/OUTOF), trip point command (TRIP/TRIPI)
1) Program example 1
As soon as the program is executed, Program output 1 (OUT1) is turned ON. When the program ends, Program output 1 (OUT1) turns OFF.
Program Description
SPN (1000)
STA (200)
STB (300)
MOV (500)
OUTON (1)
TIM (10)
MOV (250)
TIM (5)
STOP
Acceleration/deceleration time constant
Program end
200 [ms]
500
Program output 1 (OUT 1) is turned ON.
250 m] m] a)
Forward rotation
Servo motor speed
0r/min
Program output1
(OUT1)
ON
OFF
Dwell command time
(100ms)
Dwell command time
(50ms) a) b)
4 - 12
4. OPERATION
2) Program example 2
Using parameter No. 74 to 76, Program output 1 (OUT1) to Program out 3 (OUT3) can be turned off automatically.
Parameter No. Name Setting Description
74
75
76
OUT1 output time setting
OUT2 output time setting
OUT3 output time setting
20
10
50
OUT1 is turned off in 200ms.
OUT2 is turned off in 100ms.
OUT3 is turned off in 500ms. a) b) c)
Program Description
SPN (500)
STA (200)
STB (300)
MOV (1000)
OUTON (1)
OUTON (2)
OUTON (3)
STOP
Acceleration time constant 200 [ms]
1000
Program output 1 (OUT 1) is turned ON.
Program output 2 (OUT 2) is turned ON.
Program output 3 (OUT 3) is turned ON.
Program end m]
Forward rotation
Servo motor speed
0r/min
Program output1
(out1)
ON
OFF
Program output2
(out2)
ON
OFF
Program output3
(out3)
ON
OFF a) 200ms b) 100ms c) 500ms
4 - 13
4. OPERATION
3) Program example 3
When the "TRIP" and "TRIPI" commands are used to set the position addresses where the
"OUTON" and "OUTOF" commands will be executed.
Program Description
SPN (1000)
STA (200)
STB (300)
MOV (500)
TRIP (250)
OUTON (2)
TRIP (400)
OUTOF (2)
TIM (10)
MOVI (500)
TRIPI (300)
OUTON (2)
STOP
Acceleration time constant
Incremental trip point
Program output 2 (OUT 2) is turned ON.
Program end
200 [ms]
500
250
Program output 2 (OUT 2) is turned ON.
Program output 2 (OUT 2) is turned OFF.
300 [ 10
400
500
STM m] m] a) m] b) m] c) d) m] e) f) g) a) 250 10 STM m c) 400 10 STM m e) 300 10 STM m
Forward rotation
Servo motor speed
0r/min
100ms
Program output2
(OUT2)
ON
OFF b) d) f) g)
4 - 14
4. OPERATION
4) Program example 4
POINT
"MOV" cannot be used with "TRIPI".
Note that the "TRIP" and "TRIPI" commands do not execute the next step unless the axis passes the preset address or travels the preset moving distance.
Program Description
SPN (500)
STA (200)
STB (300)
MOVI (600)
TRIPI (300)
OUTON (3)
SPN (700)
MOVIA (700)
TRIPI (300)
OUTOF (3)
STOP
Acceleration time constant
Program output 3 (OUT 3) is turned ON.
Incremental continuous move command
Incremental trip point
Program output 3 (OUT 3) is turned OFF.
Program end
200 [ms]
600
300
700 [ 10
300 [ 10
STM
STM m] a) m] b) c) m] d) m] e) f)
Forward rotation a) Incremental move
command
(600 10 STM m) b) 300 10 STM m
900
10 STM m d) Incremental continuous
move command
(700 10 STM m)
Servo motor speed
0r/min
Program output3
(OUT3)
ON
OFF c) f)
4 - 15
4. OPERATION
(d) Dwell (TIM)
To the "TIM (setting value)" command, set the time from when the command remaining distance is
"0" until the next step is executed.
For reference, the following examples show the operations performed when this command is used with the other commands.
1) Program example 1
Program Description
TIM (20)
SPN (1000)
STC (20)
MOV (1000)
STOP
Acceleration/deceleration time constant
Program end
20 [ms]
1000 m]
Forward rotation
Servo motor speed
0r/min a) 200ms
Forward rotation start
(ST1)
ON
OFF
2) Program example 2
Program Description
SPN (1000)
STC (20)
MOVI (1000)
TIM (20)
OUTON (1)
MOVI (500)
STOP
Acceleration/deceleration time constant
Program output 1 (OUT 1) is turned ON.
Program end
20 [ms]
1000 m] b)
Forward rotation
Servo motor speed
0r/min a) 200ms
Program output1
(OUT1)
ON
OFF b)
4 - 16
4. OPERATION
3) Program example 3
Program Description
SPN (1000)
STC (20)
MOVI (1000)
OUTON (1)
TIM (20)
MOVI (500)
STOP
Acceleration/deceleration time constant
Program output 1 (OUT 1) is turned ON.
Program end
20 [ms]
1000
500 m] m] a)
Forward rotation
Servo motor speed
0r/min b) 200ms
Program output1
(OUT1)
ON
OFF a)
4) Program example 4
Program Description
SPN (1000)
STC (20)
MOVI (1000)
TIM (20)
OUTON (1)
TIM (30)
MOVI (500)
STOP
Acceleration/deceleration time constant
Program output 1 (OUT 1) is turned ON.
Program end
20 [ms]
1000
500 m] m] b)
Forward rotation
Servo motor speed
0r/min a) 200ms c) 300ms
Program output1
(OUT1)
ON
OFF b)
4 - 17
4. OPERATION
5) Program example 5
Program Description
SPN (1000)
STC (20)
MOVI (1000)
TIM (20)
SYNC (1)
MOVI (500)
STOP
Acceleration/deceleration time constant 20 [ms]
1000
Step is suspended until Program input (PI1) turns ON.
Program end
500 m] m]
Forward rotation
Servo motor speed
0r/min
Program input1
(PI1)
ON
OFF a) PI1 is accepted in 200ms or later.
6) Program example 6
Program Description
SPN (1000)
STC (20)
MOVI (1000)
SYNC (1)
TIM (20)
MOVI (500)
STOP
Acceleration/deceleration time constant
Program end
20 [ms]
1000
Step is suspended until Program input (PI1) turns ON.
500 m] m]
Forward rotation
Servo motor speed
0r/min a) 200ms
Program input1
(PI1)
ON
OFF
4 - 18
4. OPERATION
(e) Interrupt positioning command (ITP)
POINT
When Interrupt positioning (ITP) is used for positioning, a stop position differs depending on the servo motor speed provided when the "ITP" command is enabled.
When the "ITP" command is used in a program, the axis stops at the position by the set value farther from the position where any of Program input 1 to 3 (PI1 to PI3) turned ON.
If the move command set with the "MOV", "MOVI", "MOVA" or "MOVIA" command is less than the set value of the "ITP (set value)" command, the program proceeds to the next step without executing the "ITP (set value)" command.
When using the "ITP" command, always place the "SYNC" command immediately before the "ITP" command.
1) Program example 1
Program Description
SPN (500)
STA (200)
STB (300)
MOV (600)
SPN (100)
MOVA (600)
SYNC (1)
ITP (200)
STOP
Acceleration time constant
600
Absolute continuous move command
Interrupt positioning command
Program end
200 [ms] m]
600 [ 10 STM m]
Step is suspended until Program input (PI1) turns ON. a)
200 [ 10 STM m] b)
Forward rotation
Servo motor speed
0r/min
P1
P1 b) (200 10 STM m)
Program input1
(PI1)
ON
OFF
Waiting for PI1 to be turned ON by SYNC(1) (a))
4 - 19
4. OPERATION
2) Program example 2
If the moving distance of the "ITP" command is less than the moving distance necessary for deceleration, the actual deceleration time constant becomes less than the set value of the "STB" command.
Program Description
SPN (500)
STA (200)
STB (300)
MOV (1000)
SYNC (1)
ITP (50)
STOP
Acceleration time constant 200 [ms]
Step is suspended until Program input (PI1) turns ON.
Interrupt positioning command
Program end
1000
50 [ 10 STM m] a) m] b)
P1
Forward rotation
Servo motor speed
0r/min
P1 b) (50 10 STM m)
Program input1
(PI1)
ON
OFF
Waiting for PI1 to be turned ON by SYNC(1) (a))
(f) External pulse counter (COUNT)
When the number of input pulses of the manual pulse generator becomes greater than the value set with the "COUNT" command, the next step is started. Set "0" to erase the accumulated input pulses.
Program Description
COUNT (500)
SPN (500)
STA (200)
STB (300)
MOV (1000)
TRIP (500)
COUNT (0)
STOP
The next step is held until the number of input pulses of the manual pulse generator reaches
Acceleration time constant
Waiting for PI1 to be turned ON by SYNC(1) (a))
Program end
200 [ms]
1000 m] point 500 m] b) c) b) 500 [ 10 STM m]
ƒT [ ƒ{ ƒ‚ [ ƒ^
³
“]
0r/min
ON generator
OFF a) 500 [pulse] c) Accumulated input pulses are erased.
4 - 20
4. OPERATION
(g) Step repeat command (FOR NEXT)
POINT
"FOR ... NEXT" cannot be placed within "FOR ... NEXT".
The steps located between the "FOR (set value)" command and "NEXT" command is repeated by the preset number of times.
Program Description
SPN (1000)
STC (20)
MOV (1000)
TIM (10)
FOR (3)
MOVI (100)
TIM (10)
NEXT
FOR (2)
MOVI (200)
TIM (10)
NEXT
STOP
Acceleration/deceleration time constant
Step repeat command start
Step repeat command start
Program end
20 [ms]
500
100
3 [times]
2 [times]
200 m] a) m] b) d) m] e) b) Incremental move command
(100 10 STM m) d) Incremental move command
(200 10 STM m)
Forward rotation
Servo motor speed
0r/min
1000 1100 1200 a) c)
1300 1500 e) f)
1700
4 - 21
4. OPERATION
(h) Program count command (TIMES)
By setting the number of times to the "TIMES (setting value)" command placed at the beginning of a program, the program can be executed repeatedly. When the program is to be executed once, the
"TIMES (setting value)" command is not necessary. Setting "0" selects endless repetition.
Program Description
TIMES (2)
SPN (1000)
STC (20)
MOVI (1000)
TIM (10)
STOP
Acceleration/deceleration time constant
Program end
20 [ms]
1000 m] b) b) Incremental move command
(100 10 STM m)
Forward rotation
Servo motor speed
0r/min
1000 a)
1200
4 - 22
4. OPERATION
(i) Position latch (LPOS)
POINT
When Current position latch input (LPS) is used to store the current position, the value differs depending on the servo motor speed provided when LPS has turned ON.
The current position where Current position latch input (LPS) is turned ON is stored. The stored position data can be read by the communication function. (Refer to section 15.12.12)
The current position latch function set in a program is canceled at the end of that program. It is also canceled when the operation mode is changed, a forced stop is made, an alarm occurs, or the servo switches off. It is not canceled when a temporary stop is merely made.
Program Description
SPN (500)
STA (200)
STB (300)
MOV (1000)
LPOS
STOP
Acceleration time constant
Current position latch is set.
Program end
200 [ms]
1000 m] a)
Current position 300 [ 10 STM m] is stored.
Forward rotation
Servo motor speed
0r/min
Current position latch input (LPS)
ON
OFF
1000
Latched when LPS is turned ON edge by
LPOS. (a))
4 - 23
4. OPERATION
(j) Indirect addressing using general-purpose registers (R1-R4, D1-D4)
The set values of the "SPN", "STA", "STB", "STC", "STD", "MOV", "MOVI", "MOVA", "MOVIA",
"TIM" and "TIMES" commands can be addressed indirectly.
The values stored in the general-purpose registers (R1-R4, D1-D4) are used as the set values of the commands.
Change the values of the general-purpose registers using the communication command when the program is not being executed by the communication command. (Refer to section 15.12.13)
The data of the general-purpose registers are erased at power-off of the servo amplifier. Note that the data of the general-purpose registers (R1-R4, D1-D4) can be saved in the EEP-ROM.
The setting ranges of the general-purpose registers are the setting ranges of the instructions with which the general-purpose registers are used.
The following explains the case where the general-purpose registers are set as indicated below before execution of the program.
General-purpose register Setting
R1 1000
R2 2000
D1 200
D2 300
Program Description
SPN (1000)
STA (D1)
STB (D2)
MOVI (R1)
TIM (10)
MOVI (R2)
STOP Program end
R1=1000
R2=2000 m] d) m] f) a) 1000r/min b) D1=200ms
Forward rotation
Servo motor speed
0r/min c) D2=300ms b) D1=200ms c) D2=300ms d) R1=1000 10 STM m e) Dwell command
time (100ms) f) R2=2000 10 STM m
4 - 24
4. OPERATION
4.2.3 Basic setting of signals and parameters
Create programs in advance using the MR Configurator (Servo Configuration software). (Refer to section 4.2.2 and section 6.5)
(1) Parameter
(a) Command mode selection (parameter No.0)
Make sure that the absolute value command system has been selected as shown below.
Parameter No. 0
0
Absolute value command system (initial value)
(b) ST1 coordinate system selection (parameter No.1)
Choose the servo motor rotation direction at the time when the forward rotation start (ST1) is switched on.
Parameter No. 1 setting
0
(Initial value)
1
Servo motor rotation direction when forward rotation start (ST1) is switched on
CCW rotation with position data
CW rotation with position data
CW rotation with position data
CCW rotation with position data
CCW
CW
(c) Feed length multiplication selection (parameter No.1) Set the unit multiplication factor (STM) of position data. The actual moving distance is the result of multiplying the entered position data by the unit multiplication factor.
Parameter No.1 setting Position data input range [mm]
0
(Initial value)
1
999.999 to 999.999
9999.99 to 9999.99
2 99999.9 to 99999.9
3 999999 to 999999
(2) Operation
Choose the program using DI0 to DI3 and turn ON ST1 to perform positioning operation according to the set program. At this time, reverse rotation start (ST2) is invalid.
Selection of program operation mode.
Program selection
Start
Automatic/manual selection (MD0)
Program No. selection 1 (DI0)
Program No. selection 2 (DI1)
Program No. selection 3 (DI2)
Program No. selection 4 (DI3)
Program No. selection 5 (DI4)
Forward rotation start (ST1)
MD0 is switched on.
Refer to section 3.3.2 (1).
Turn ON ST1 to start.
4 - 25
4. OPERATION
4.2.4 Program operation timing chart
(1) Operation conditions
The timing chart shown below assumes that the following program is executed in the absolute value command system where a home position return is completed.
Description Program No.1
SPN (1000)
STC (100)
MOV (5000)
SYNC (1)
STC (50)
MOV (7500)
STOP
Acceleration time constant 100 [ms]
5000 m] Move command 1
Step is suspended until Program input (PI1) turns ON.
Acceleration/deceleration time constant 50 [ms]
7500 m] Move command 2
Program end
Program No.2
SPN (1000)
STC (100)
MOV (2500)
SYNC (1)
STC (50)
MOV (5000)
STOP
Description
Acceleration time constant 100 [ms]
2500 m] Move command 3
Step is suspended until Program input (PI1) turns ON.
Acceleration/deceleration time constant 50 [ms]
5000 m] Move command 4
Program end
Automatic/manual selection (MD0)
Servo-on (SON)
ON
OFF
ON
OFF
Forward rotation start (ST1)
Program input1
(PI1)
ON
OFF
ON
OFF
(Note)
3ms or more
5ms or more
(Note)
3ms or more
5ms or more
5ms or more 5ms or more
Program No.
1 2
3ms or less 3ms or less 3ms or less 3ms or less
Servo motor speed
Forward rotation
0 r/min
Reverse rotation
Move command
1
Move command
2
Move command
4
Move command
3
Movement complete
(PED)
ON
OFF
Ready (RD)
ON
OFF
Trouble (ALM)
ON
OFF
Note: External input signal detection delays by the input filter setting time of parameter No. 2. Also, make up a sequence
that will change the program selection earlier by the time that takes into account the output signal sequence from
the controller and the variation of a signal change due to the hardware.
4 - 26
4. OPERATION
4.3 Manual operation mode
For machine adjustment, home position matching, etc., jog operation or a manual pulse generator may be used to make a motion to any position.
4.3.1 Jog operation
(1) Setting
Set the input signal and parameters as follows according to the purpose of use. In this case, the program No. selection 1 to 4 (DI0 to DI3) are invalid.
Manual operation mode selection
Servo motor rotation direction
Jog speed
Automatic/manual selection (MD0)
Parameter No.1
Parameter No.13
Acceleration/deceleration time constant Parameter No.40
MD0 is switched off.
Refer to (2) in this section.
Set the speed of the servo motor.
Use the acceleration/deceleration time constants.
(2) Servo motor rotation direction
Parameter No. 1 setting
0
1
Servo motor rotation direction
Forward rotation start (ST1) ON
CCW rotation
CW rotation
Reverse rotation start (ST2) ON
CW rotation
CCW rotation
ST1:ON
CCW
ST2:ON
CCW
CW
ST2:ON
Parameter No. 1
CW
ST1:ON
Parameter No. 1 0 1
(3) Operation
When ST1 is turned on, operation is performed under the conditions of the jog speed set in the parameter and the acceleration and deceleration time constants in set parameter No.40. For the rotation direction, refer to (2) in this section. When ST2 is turned ON, the servo motor rotates in the reverse direction to forward rotation start (ST1).
4 - 27
4. OPERATION
(4) Timing chart
Servo-on (SON)
Ready (RD)
Trouble (ALM)
Automatic/manual selection (MD0)
Movement complete
(PED)
Forward rotation
Servo motor speed 0r/min
Reverse rotation
Forward rotation start
(ST1)
ON
OFF
Reverse rotation start
(ST2)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
80ms
Forward rotation jog
Reverse rotation jog
4 - 28
4. OPERATION
4.3.2 Manual pulse generator operation
(1) Setting
Set the input signal and parameters as follows according to the purpose of use. In this case, the program No. selection 1 to 4 (DI0 to DI3) are invalid.
Manual operation mode selection Automatic/manual selection (MD0)
Manual pulse generator multiplication
Parameter No.1
MD0 is switched off.
Set the multiplication ratio of servo motor rotation to the pulses generated by the manual pulse generator.
For more information, refer to (3) in this section.
Refer to (2) in this section. Servo motor rotation direction
(2) Servo motor rotation direction
Parameter No. 1 setting
0
1
Parameter No.1
Servo motor rotation direction
Manual pulse generator: forward rotation Manual pulse generator: reverse rotation
CCW rotation
CW rotation
CW rotation
CCW rotation
CCW
Forward rotation
CW
(3) Manual pulse generator multiplication
(a) Using the parameter for setting
Use parameter No.1 to set the multiplication ratio of the servo motor rotation to the manual pulse generator rotation.
Multiplication ratio of servo motor rotation to manual
Parameter No. 1 setting Moving distance pulse generator rotation
1[ m] 0
1
2
4 - 29
4. OPERATION
(b) Using the input signals for setting
Set the pulse generator multiplication 1 (TP0) and pulse generator multiplication 2 (TP1) to the input signals in "Device setting" on the MR Configurator (Servo Configuration Software) (refer to chapter 6).
Pulse generator multiplication 2
(across TP1)
Pulse generator multiplication 1
(across TP0)
0 0
Multiplication ratio of servo motor rotation to manual pulse generator rotation
Parameter No.1 setting valid
Moving distance
Note. 0: OFF
1: ON
(4) Operation
Turn the manual pulse generator to rotate the servo motor. For the rotation direction of servo motor, refer to (2) in this section.
4 - 30
4. OPERATION
4.4 Manual home position return mode
4.4.1 Outline of home position return
Home position return is performed to match the command coordinates with the machine coordinates. In the incremental system, home position return is required every time input power is switched on. In the absolute position detection system, once home position return is done at the time of installation, the current position is retained if power is switched off. Hence, home position return is not required when power is switched on again.
This servo amplifier has the home position return methods given in this section. Choose the most appropriate method for your machine structure and application.
This servo amplifier has the home position return automatic return function which executes home position return by making an automatic return to a proper position if the machine has stopped beyond or at the proximity dog. Manual motion by jog operation or the like is not required.
(1) Manual home position return types
Choose the optimum home position return according to the machine type, etc.
Features
Dog type home position return
Count type home position return
Data setting type home position return
With deceleration started at the front end of a proximity dog, the position where the first
Z-phase signal is given past the rear end of the dog or a motion has been made over the home position shift distance starting from the Z-phase signal is defined as a home position.(Note)
With deceleration started at the front end of a proximity dog, the position where the first Z-phase signal is given after advancement over the preset moving distance after the proximity dog or a motion has been made over the home position shift distance starting from the Z-phase signal is defined as a home position.
The position reached after any automatic motion is defined as a home position.
General home position return method using a proximity dog.
Repeatability of home position return is excellent.
The machine is less burdened.
Used when the width of the proximity dog can be set greater than the deceleration distance of the servo motor.
Home position return method using a proximity dog.
Used when it is desired to minimize the length of the proximity dog.
No proximity dog required.
Stopper type home position return
The position where the machine stops when its part is pressed against a machine stopper is defined as a home position.
Since the machine part collides with the machine be fully lowered.
The machine and stopper strength must be increased.
Home position ignorance
(Servo-on position as home position)
The position where servo is switched on is defined as a home position.
Dog type rear end reference
Count type front end reference
Dog cradle type
The position where the axis, which had started decelerating at the front end of a proximity dog, has moved the after-proximity dog moving distance and home position shift distance after it passed the rear end is defined as a home position.
The position where the axis, which had started decelerating at the front end of a proximity dog, has moved the after-proximity dog moving distance and home position shift distance is defined as a home position.
The position where the first Z-phase signal is issued after detection of the proximity dog front end is defined as a home position.
The Z-phase signal is not needed.
The Z-phase signal is not needed.
Note. The Z-phase signal is a signal recognized in the servo amplifier once per servo motor revolution and cannot be used as an output signal.
4 - 31
4. OPERATION
(2) Home position return parameter
When performing home position return, set parameter No.8 as follows.
Parameter No. 8
0
Home position return method························································1)
0: Dog type
1: Count type
2: Data setting type
3: Stopper type
4: Home position ignorance (Servo-on position as home position)
5: Dog type rear end reference
6: Count type front end reference
7: Dog cradle type
Home position return direction ······················································2)
0: Address increment direction
1: Address decrement direction
Proximity dog input polarity ·····································3)
0: Dog is detected when DOG is turned off.
1: Dog is detected when DOG is turned on.
1) Choose the home position return method.
2) Choose the starting direction of home position return. Set "0" to start home position return in the direction in which the address is incremented from the current position, or "1" to start home position return in the direction in which the address is decremented.
3) Choose the polarity at which the proximity dog is detected. Set "0" to detect the dog when the proximity dog device (DOG) is turned off, or "1" to detect the dog when the device is turned on.
(3) Program
Choose a program including the "ZRT" command that executes the home position return.
(4) Instructions
1) Before starting home position return, always make sure that the limit switch operates.
2) Confirm the home position return direction. Incorrect setting will cause the machine to run reversely.
3) Confirm the proximity dog input polarity. Otherwise, misoperation can occur.
4 - 32
4. OPERATION
4.4.2 Dog type home position return
A home position return method using a proximity dog. With deceleration started at the front end of the proximity dog, the position where the first Z-phase signal is given past the rear end of the dog or a motion has been made over the home position shift distance starting from the Z-phase signal is defined as a home position.
(1) Signals, parameters
Set the input signals, parameters and program as follows.
Manual home position return mode selection
Automatic/manual selection (MD0) MD0 is switched on.
Dog type home position return Parameter No.8
0 :Dog type home position return is selected.
Home position return direction Parameter No.8
Dog input polarity
Home position return speed
Creep speed
Home position shift distance
Parameter No.8
Parameter No.9
Parameter No.10
Parameter No.11
Refer to section 4.4.1 (2) and choose home position return direction.
Refer to section 4.4.1 (2) and choose dog input polarity.
Set speed until detection of dog.
Set speed after detection of dog.
Set when shifting the home position starting at the first Z-phase signal after passage of proximity dog rear end.
Home position return acceleration/deceleration time constants
Home position return position data
L
1
Parameter No.41
Parameter No.42
Use the acceleration/deceleration time constants set in parameter No. 41.
Program
Select the program including the "ZRT" command that executes a home position return.
(2) Length of proximity dog
To ensure that the Z-phase signal of the servo motor is generated during detection of the proximity dog (DOG), the proximity dog should have the length which satisfies formulas (4.2) and (4.3).
V
60
Used to set the current position on completion of home position return.
L
1
: Proximity dog length [mm]
V : Home position return speed [mm/min] td : Deceleration time [s]
L
2
2 S ................................................................................... (4.3)
L
2
: Proximity dog length [mm]
S : Moving distance per servo motor revolution [mm]
4 - 33
4. OPERATION
(3) Timing chart
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Movement complete (PED)
ON
OFF
Home position return completion (ZP)
Servo motor speed
ON
OFF
Parameter No. 41
Acceleration time constant
Forward rotation
0 r/min
Home position return speed Parameter No. 9
Parameter No. 41
Deceleration time constant
Creep speed
Parameter No. 10
3ms or less td
Proximity dog
Home position shift distance Parameter No. 11
Home position
Home position address
Parameter No. 42
Z-phase
Proximity dog (DOG)
Forward rotation start (ST1)
Reverse rotation start (ST2)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
5ms or more
Proximity dog
The address on completion of home position return is the value automatically set in parameter No.42
(home position return position data).
(4) Adjustment
In dog type home position return, adjust to ensure that the Z-phase signal is generated during dog detection. Locate the rear end of the proximity dog (DOG) at approximately the center of two consecutive Z-phase signals.
The position where the Z-phase signal is generated can be monitored in "Within one-revolution position" of "Status display".
0 65536 0
Servo motor
Z-phase
Proximity dog
(DOG)
ON
OF
4 - 34
4. OPERATION
4.4.3 Count type home position return
In count type home position return, a motion is made over the distance set in parameter No.43 (moving distance after proximity dog) after detection of the proximity dog front end. The position where the first Zphase signal is given after that is defined as a home position. Hence, if the proximity dog (DOG) is 10ms or longer, there is no restriction on the dog length. This home position return method is used when the required proximity dog length cannot be reserved to use dog type home position return or when the proximity dog (DOG) is entered electrically from a controller or the like.
(1) Signals, parameters
Set the input signals and parameters as follows.
Manual home position return mode selection
Automatic/manual selection (MD0)
Count type home position return Parameter No.8
Home position return direction
Dog input polarity
Home position return speed
Creep speed
Home position shift distance
Moving distance after proximity dog
Home position return acceleration/deceleration time constants
Home position return position data
Program
Parameter No.8
Parameter No.8
Parameter No.9
Parameter No.10
Parameter No.11
Parameter No.43
MD0 is switched on.
1 : Count type home position return is selected.
Refer to section 4.4.1 (2) and choose home position return direction.
Refer to section 4.4.1 (2) and choose dog input polarity.
Set speed until detection of dog.
Set speed after detection of dog.
Set when shifting the home position, starting at the first Z-phase signal given after passage of the proximity dog front end and movement over the moving distance.
Set the moving distance after passage of proximity dog front end.
Parameter No.41
Use the acceleration/deceleration time constants set in parameter No. 41.
Parameter No.42
Select the program including the "ZRT" command that executes a home position return.
Used to set the current position on completion of home position return.
4 - 35
4. OPERATION
(2) Timing chart
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Movement complete (PED)
ON
OFF
Home position return ON completion (ZP) OFF
Parameter No. 41
Acceleration time constant
Servo motor speed
Forward rotation
0 r/min
Home position return speed Parameter No. 9
Parameter No. 41
Deceleration time constant
Creep speed
Parameter No. 10
3ms or less
Moving distance after proximity dog
Parameter No. 43
Proximity dog
Home position shift distance
Parameter No. 11
Home position
Home position address
Parameter No. 42
Z-phase
Proximity dog (DOG)
Forward rotation start (ST1)
Reverse rotation start (ST2)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
5ms or more
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 36
4. OPERATION
4.4.4 Data setting type home position return
Data setting type home position return is used when it is desired to determine any position as a home position. JOG operation, manual pulse generator operation or like can be used for movement.
(1) Signals, parameters
Set the input signals and parameters as follows.
Manual home position return mode Automatic/manual selection selection (MD0)
MD0 is switched on.
Data setting type home position return Parameter No.8
2 : Data setting type home position return is selected.
Home position return position data Parameter No.42
Used to set the current position on completion of home position return.
Program
Select the program including the
"ZRT" command that executes a home position return.
(2) Timing chart
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Automatic/manual selection
(MD0)
Movement complete (PED)
Home position return completion
(ZP)
ON
OFF
ON
OFF
ON
OFF
Servo motor speed
Forward rotation
0 r/min
Forward rotation start (ST1)
Reverse rotation start (ST2)
ON
OFF
ON
OFF
3ms or less
Home position address
Parameter No. 42
5ms or more
Movement to the home position Operation for home position return
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 37
4. OPERATION
4.4.5 Stopper type home position return
In stopper type home position return, a machine part is pressed against a stopper or the like by jog operation, manual pulse generator operation or the like to make a home position return and that position is defined as a home position.
(1) Signals, parameters
Set the input signals and parameters as follows.
Description
Manual home position return mode selection
Stopper type home position return
Automatic/manual selection (MD0)
Parameter No.8
MD0 is switched on.
3 : Stopper type home position return is selected.
Home position return direction
Parameter No.8
Home position return speed Parameter No.9
Stopper time Parameter No.44
Refer to section 4.4.1 (2) and choose the home position return direction.
Set the speed till contact with the stopper.
Time from when the part makes contact with the stopper to when home position return data is obtained to output home position return completion (ZP).
Set the servo motor torque limit value for execution of stopper type home position return.
Stopper type home position return torque limit
Home position return acceleration/deceleration time constant
Home position return position data
Parameter No.45
Parameter No.41
Use the acceleration/deceleration time constants set in parameter No. 41.
Parameter No.42
Used to set the current position on completion of home position return.
Program
Select the program including the "ZRT" command that executes a home position return.
(2) Timing chart
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Automatic/manual selection (MD0)
Movement complete (PED)
ON
OFF
ON
OFF
ON Home position return completion (ZP)
Forward rotation
Servo motor speed 0r/min
Acceleration time constant
Home position return speed Parameter No.9
3ms or less
Home position address
Parameter No. 42
Forward rotation start (ST1)
Reverse rotation start (ST2)
Limiting torque (TLC)
ON
OFF
ON
OFF
ON
OFF
5ms or more
Stopper time
Parameter No. 44
Stopper
Torque limit value Parameter No. 28 Parameter No. 45 Parameter No. 28
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 38
4. OPERATION
4.4.6 Home position ignorance (servo-on position defined as home position)
POINT
When a home position-ignored home position return is executed, the program including the "ZRT" command need not be selected.
The position where servo is switched on is defined as a home position.
(1) Signals, parameter
Set the input signals and parameter as follows.
Item Device/Parameter Description
Parameter No.8 Home position ignorance
Home position return position data
(2) Timing chart
Parameter No.42
4 : Home position ignorance is selected.
Used to set the current position on completion of home position return.
Servo-on (SON)
ON
OFF
Automatic/manual selection
(MD0)
Movement complete (PED)
ON
OFF
ON
OFF
Home position return completion
(ZP)
ON
OFF
Servo motor speed
Home position address
Parameter No. 42
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 39
4. OPERATION
4.4.7 Dog type rear end reference home position return
POINT
This home position return method depends on the timing of reading
Proximity dog (DOG) that has detected the rear end of a proximity dog.
Hence, if a home position return is made at the creep speed of 100r/min, an error of 200 pulses will occur in the home position. The error of the home position is larger as the creep speed is higher.
The position where the axis, which had started decelerating at the front end of a proximity dog, has moved the after-proximity dog moving distance and home position shift distance after it passed the rear end is defined as a home position. A home position return that does not depend on the Z-phase signal can be made.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Description
Manual home position return mode selection
Dog type rear end reference home position return selection (MD0)
Automatic/manual selection (MD0) MD0 is switched on.
Parameter No.8 5: Select the dog type rear end reference.
Dog input polarity
Home position return speed
Creep speed
Home position shift distance
Home position return acceleration/ deceleration time constants
Parameter No.8
Parameter No.9
Parameter No.10
Parameter No.11
Moving distance after proximity dog Parameter No.43
Parameter No.41
Home position return position data Parameter No.42
Refer to section 4.4.1 (2) and select the home position return direction.
Refer to section 4.4.1 (2) and select the dog input polarity.
Set the speed till the dog is detected.
Set the speed after the dog is detected.
Set when the home position is moved from where the axis has passed the proximity dog rear end.
Set the moving distance after the axis has passed the proximity dog rear end.
Use the acceleration/deceleration time constants set in parameter
No. 41.
Used to set the current position on completion of home position return.
Program
(2) Timing chart
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Automatic/manual
ON
Select the program including the
"ZRT" command that executes a home position return.
OFF
ON
Movement complete (PED)
Home position return completion (ZP)
OFF
ON
OFF
Moving distance after proximity dog
Home position return speed
Home position shift distance
Creep speed
Servo motor speed
Forward rotation
0 r/min
3ms or less
Proximity dog
Home position address
Parameter No. 42
Proximity dog (DOG)
Forward rotation start (ST1)
ON
OFF
ON
OFF
Reverse rotation ON
5ms or more start (ST2) OFF
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 40
4. OPERATION
4.4.8 Count type front end reference home position return
POINT
This home position return method depends on the timing of reading
Proximity dog (DOG) that has detected the front end of a proximity dog.
Hence, if a home position return is made at the home position return speed of
100r/min, an error of 200 pulses will occur in the home position. The error of the home position is larger as the home position return speed is higher.
The position where the axis, which had started decelerating at the front end of a proximity dog, has moved the after-proximity dog moving distance and home position shift distance is defined as a home position. A home position return that does not depend on the Z-phase signal can be made. The home position may change if the home position return speed varies.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Description
Manual home position return mode selection
Count type dog front end reference home position return
Dog input polarity
Home position return speed
Creep speed
Home position shift distance
Automatic/manual selection (MD0) MD0 is switched on.
Parameter No.8
Parameter No.8
Parameter No.9
Parameter No.10
Parameter No.11
Moving distance after proximity dog Parameter No.43
6: Select the count type dog front end reference.
Refer to section 4.4.1 (2) and select the home position return direction.
Refer to section 4.4.1 (2) and select the dog input polarity.
Set the speed till the dog is detected.
Set the speed after the dog is detected.
Set when the home position is moved from where the axis has passed the proximity dog rear end.
Set the moving distance after the axis has passed the proximity dog rear end.
Use the acceleration/deceleration time constants set in parameter
No. 41.
Home position return acceleration/ deceleration time constants
Parameter No.41
Home position return position data
Program
Parameter No.42
Select the program including the
"ZRT" command that executes a home position return.
Used to set the current position on completion of home position return.
(2) Timing chart
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Automatic/manual ON selection (MD0)
OFF
Movement complete (PED)
ON
OFF
Home position return completion (ZP)
ON
OFF
Home position return speed
Moving distance after proximity dog
Home position shift distance
Creep speed
Servo motor speed
Forward rotation
0 r/min
3ms or less
Proximity dog (DOG)
Home position address
Parameter No. 42
Proximity dog (DOG)
ON
OFF
Forward rotation start (ST1)
ON
OFF
Reverse rotation
5ms or more
ON start (ST2)
OFF
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 41
4. OPERATION
4.4.9 Dog cradle type home position return
The position where the first Z-phase signal is issued after detection of the proximity dog front end can be defined as a home position.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item Device/Parameter Description
Manual home position return mode selection
Dog cradle type home position return
Automatic/manual selection (MD0) MD0 is switched on.
Parameter No.8 7: Select the dog cradle type.
Home position return direction
Dog input polarity
Home position return speed
Creep speed
Home position shift distance
Parameter No.8
Parameter No.8
Parameter No.9
Parameter No.10
Parameter No.11
Refer to section 4.4.1 (2) and select the home position return direction.
Refer to section 4.4.1 (2) and select the dog input polarity.
Set the speed till the dog is detected.
Set the speed after the dog is detected.
Set when the home position is moved from the Zphase signal position.
Home position return acceleration/deceleration time constants
Parameter No.41
Use the acceleration/deceleration time constants set in parameter No. 41.
Home position return position data Parameter No.42
Used to set the current position on completion of home position return.
Program
OFF
Select the program including the
"ZRT" command that executes a
(2) Timing chart home position return.
The following shows the timing chart that starts after selection of the program including the "ZRT" command.
Automatic/manual ON selection (MD0)
Movement complete (PED)
ON
OFF
Home position return completion (ZP)
ON
OFF
Home position return speed
Home position shift distance
Creep speed
Servo motor speed
Forward rotation
0r/min
Reverse rotation
3ms or less
Proximity dog
Home position address
Parameter No. 42
Z-phase
Proximity dog (DOG)
Forward rotation start (ST1)
ON
OFF
ON
OFF
ON
OFF
Reverse rotation
5ms or more
ON start (ST2) OFF
The parameter No.42 setting value is the positioning address after the home position return is completed.
4 - 42
4. OPERATION
4.4.10 Home position return automatic return function
If the current position is at or beyond the proximity dog in dog or count type home position return, you need not make a start after making a return by jog operation or the like.
When the current position is at the proximity dog, an automatic return is made before home position return.
Home position return direction
Proximity dog
Home position
Home position return start position
At a start, a motion is made in the home position return direction and an automatic return is made on detection of the limit switch. The motion stops past the front end of the proximity dog, and home position return is resumed at that position. If the proximity dog cannot be detected, the motion stops on detection of the opposite limit switch and AL. 90 occurs.
Home position return direction
Proximity dog
Limit switch
Limit LS
Home position
Home position return start position
Software limit cannot be used with these functions.
4 - 43
4. OPERATION
4.5 Absolute position detection system
CAUTION
If an absolute position erase alarm (AL.25) or an absolute position counter warning
(AL.E3) has occurred, always perform home position setting again. Not doing so can cause runaway.
POINT
When the following parameters are changed, the home position is lost when turning on the power after the change. Execute the home position return again when turning on the power.
First digit of parameter No.1 (ST1 coordinate system selection)
Parameter No. 4 (Electronic gear numerator)
Parameter No. 5 (Electronic gear denominator)
Parameter No. 42 (Home position return position data)
This servo amplifier contains a single-axis controller. Also, all servo motor encoders are compatible with an absolute position system. Hence, an absolute position detection system can be configured up by merely loading an absolute position data back-up battery and setting parameter values.
(1) Restrictions
An absolute position detection system cannot be built under the following conditions.
1) Stroke-less coordinate system, e.g. rotary shaft, infinite positioning.
2) Operation performed in incremental value command type positioning system.
(2) Specifications
Item Description
System
Battery
Maximum revolution range
(Note 1) Maximum speed at power failure
(Note 2) Battery backup time
(Note 3) Data holding time during battery replacement
Battery storage period
Electronic battery backup system
1 piece of lithium battery ( primary battery, nominal 3.6V)
Type: MR-BAT or A6BAT
Home position 32767 rev.
500r/min
Approx. 10,000 hours (battery life with power off)
2 hours at delivery, 1 hour in 5 years after delivery
5 years from date of manufacture
Note 1. Maximum speed available when the shaft is rotated by external force at the time of power failure or the like.
2. Time to hold data by a battery with power off. It is recommended to replace the battery in three years independently of whether power is kept on or off.
3. Period during which data can be held by the super capacitor in the encoder after power-off, with the battery voltage low or the battery removed, or during which data can be held with the encoder cable disconnected.
Battery replacement should be finished within this period.
(3) Structure
Component Description
Servo amplifier
Servo motor
Use standard models.
Encoder cable
Use a standard model.
When fabricating, refer to (2), section 14.1.4.
4 - 44
4. OPERATION
(4) Outline of absolute position detection data communication
For normal operation, as shown below, the encoder consists of a detector designed to detect a position within one revolution and a cumulative revolution counter designed to detect the number of revolutions.
The absolute position detection system always detects the absolute position of the machine and keeps it battery-backed, independently of whether the general-purpose programming controller power is on or off. Therefore, once the home position is defined at the time of machine installation, home position return is not needed when power is switched on thereafter.
If a power failure or a fault occurs, restoration is easy.
Also, the absolute position data, which is battery-backed by the super capacitor in the encoder, can be retained within the specified period (cumulative revolution counter value retaining time) if the cable is unplugged or broken.
Servo amplifier
Program No. selection
(DI0 to DI3), etc.
I/O circuit
Position data, speed data
(current position read)
Home position return data
EEP-ROM memory
LSO
1XO
Backup at power off
Current position
LS
Speed detection
1X
Detection of position within one revolution
Battery MR-BAT
Servo motor
1 pulse/rev. Cumulative revolution counter
Super capacitor
Within one-revolution counter
High-speed serial communication
(5) Battery installation procedure
WARNING
Before installing a battery, turn off the main circuit power while keeping the control circuit power on. Wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others.
Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
POINT
The internal circuits of the servo amplifier may be damaged by static electricity. Always take the following precautions.
Ground human body and work bench.
Do not touch the conductive areas, such as connector pins and electrical parts, directly by hand.
4 - 45
4. OPERATION
1) Open the operation window. (When the model used is the MR-J2S-200CL MR-J2S-350CL or more, also remove the front cover.)
2) Install the battery in the battery holder.
3) Install the battery connector into CON1 until it clicks.
Battery connector
Operation window
Battery connector
CON1
CON1
Battery Battery holder
For MR-J2S-100CL or less
Battery connector
CON1
Battery
Battery holder
For MR-J2S-200CL MR-J2S-350CL
Battery holder Battery
For MR-J2S-500CL MR-J2S-700CL
(6) Parameter setting
Set parameter No.2 (Function selection 1) as indicated below to make the absolute position detection system valid.
Parameter No.2
1
Selection of absolute position detection system
0: Incremental system
1: Absolute position detection system
4 - 46
4. OPERATION
4.6 Serial communication operation
The RS-422 or RS-232C communication function may be used to operate the servo amplifier from a command device (controller) such as a personal computer. Note that the RS-422 and RS-232C communication functions cannot be used at the same time.
This section provides a data transfer procedure. Refer to chapter 15 for full information on the connection and transferred data between the controller and servo amplifier.
4.6.1 Positioning operation in accordance with programs
By selecting the program No. and switching on the forward rotation start (ST1) using the communication function, positioning operation in accordance with programs can be started.
(1) Selection of programs
Using the device forced output from the controller (command [9][2], data No. [6][0]), choose programs from among No.1 to 16.
(2) Timing chart
5ms or more 5ms or more 5ms or more
Transmission data
1) 4) 5) 2) 4) 5) 3) 4) 5)
Servo motor speed 3ms
Program No. 2
Program No. 1 Program No. 3
1) Program No.2 selection
2) Program No.1 selection
3) Program No.3 selection
4) Forward rotation start (ST1) ON
5) Forward rotation start (ST1) OFF
4.6.2 Multidrop system
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
The RS-422 communication function can be used to operate several servo amplifiers on the same bus. In this case, set the station numbers to the servo amplifiers to determine the destination servo amplifier of the currently transmitted data. Use parameter No.15 to set the station numbers.
Always set one station number to one servo amplifier. Normal communication cannot be made if one station number is set to two or more servo amplifiers. When using one command to operate several servo amplifiers, use the group designation function described in section 4.6.3.
MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI
To CN3 To CN3 To CN3 To CN3
CHARGE CHARGE CHARGE
Axis 1
(Station 0)
Axis 2
(Station 1)
Controller
For cable connection diagram, refer to section 15.1.1.
RS-422
Axis 3
(Station 2)
CHARGE
Axis 32
(Station 31)
4 - 47
4. OPERATION
4.6.3 Group designation
When using several servo amplifiers, command-driven parameter settings, etc. can be made on a group basis.
You can set up to six groups, a to f. Set the group to each station using the communication command.
(1) Group setting example
Group a Group b
MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI
To CN3 To CN3 To CN3 To CN3 To CN3
CHARGE
Axis 1
(Station 0)
CHARGE
Axis 2
(Station 1)
CHARGE
Axis 3
(Station 2)
CHARGE
Axis 4
(Station 3)
CHARGE
Axis 5
(Station 4)
Controller
RS-422
For cable connection diagram, refer to section 15.1.1.
MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI
CHARGE To CN3
Axis 10
(Station 9)
CHARGE To
Axis 9
(Station 8)
CN3
Group d
CHARGE
Axis 8
(Station 7)
To CN3 CHARGE To
Axis 7
CN3
(Station 6)
Group c
Servo amplifier station No.
Station 0
Station 1
Station 2
Station 3
Station 4
Station 5
Station 6
Station 7
Station 8
Station 9
Group setting a b c d
CHARGE To CN3
Axis 6
(Station 5)
4 - 48
4. OPERATION
(2) Timing chart
In the following timing chart, operation is performed group-by-group in accordance with the values set in program No.1.
Transmission data 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12)
Group a
Group b
Group c
Group d
Station 0
Servo motor speed
Station 1
Servo motor speed
Station 2
Servo motor speed
Station 3
Servo motor speed
Station 4
Servo motor speed
Station 5
Servo motor speed
Station 6
Servo motor speed
Station 7
Servo motor speed
Station 8
Servo motor speed
Station 9
Servo motor speed
1) Selection of program No.1 of group a
2) Forward rotation start (ST1) ON
3) Forward rotation start (ST1) OFF
4) Selection of program No.1 of group b
5) Forward rotation start (ST1) ON
6) Forward rotation start (ST1) OFF
7) Selection of program No.1 of group c
8) Forward rotation start (ST1) ON
9) Forward rotation start (ST1) OFF
10) Selection of program No.1 of group d
11) Forward rotation start (ST1) ON
12) Forward rotation start (ST1) OFF
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
In addition, parameter values common to the stations of each group can be written and alarm reset can be made, for example.
(3) Group setting instructions
Only one servo amplifier may send a reply in any group. If two or more servo amplifiers send reply data at the same time, they may become faulty.
4 - 49
4. OPERATION
4.7 Incremental value command system
To use this servo amplifier in the incremental value command system, the setting of parameter No. 0 must be changed.
As the position data, set the moving distance of (target address - current address). Fixed-pitch feed of infinite length is enabled in the incremental value command system.
Setting range: 999999 to 999999 [ 10 STM m] (STM = feed length multiplication parameter No. 1)
Current address Target address
Position data = | target address - current address |
This section describes the points that differ from the absolute value command system (factory setting) in using this servo amplifier in the incremental value command system.
(1) Parameter setting
Set parameter No. 0 as shown below to select the incremental value command system.
Parameter No. 0
1
Incremental value command system
(2) Commands
The "MOV" and "MOVA" commands change as described below. The other commands remain unchanged. Hence, "MOV" and "MOVI" have the same function, and "MOVA" and "MOVIA" have the same function.
Command Name Setting
Setting
Range
Unit
Indirect
Addressing
Description
MOV
MOVA
Incremental move command
MOV (Set value)
Incremental continuous move MOVA (Set value) command
999999 to 999999
999999 to 999999
10 STM m
10 STM m
The set value is regarded as an incremental value for movement.
This command has the same function as the "MOVI" command.
The set value is regarded as an incremental value for continuous movement.
Always describe this command after the "MOV" command.
Describing it after any other command will result in an error.
This command has the same function as the "MOVIA" command.
4 - 50
4. OPERATION
(3) Program example
Program Description
SPN (1000)
STA (200)
STB (300)
MOV (1000)
TIM (10)
SPN (500)
STA (200)
STB (300)
MOVI (1000)
SPN (1000)
MOVIA (1000)
STOP
Incremental continuous move command
Program end
1000 m] d)
1000 m] i)
1000 [ 10 STM m] k)
Forward rotation b) Acceleration time
constant
(200ms) a) Speed
(Motor speed) c) Deceleration time
constant
(300ms) g) Acceleration time
constant
(200ms)
(1000r/min) f) Speed(Motor speed)
(500r/min)
Servo motor speed
0r/min d) Incremental
move command
(1000 10 STM m) e) Dwell command time
(100ms) i) Incremental j) Speed h) Deceleration time
constant
(300ms)
(Motor speed)
(1000r/min)
move command
(500 10 STM m) k) Incremental
move command
(1000 10 STM m)
4 - 51
4. OPERATION
MEMO
4 - 52
5. PARAMETERS
5. PARAMETERS
CAUTION
5.1 Parameter list
Never adjust or change the parameter values extremely as it will make operation instable.
5.1.1 Parameter write inhibit
POINT
Set "000E" when using the MR Configurator (Servo Configuration
Software) to make device setting.
After setting the parameter No.19 value, switch power off, then on to make that setting valid.
In the servo amplifier, its parameters are classified into the basic parameters (No.0 to 19), expansion parameters 1 (No.20 to 53), expansion parameters 2 (No.54 to 77) and special parameters (No.78 to 90) according to their safety aspects and frequencies of use. In the factory setting condition, the customer can change the basic parameter values but cannot change the expansion parameter 1,2 values and special parameter values. When fine adjustment, e.g. gain adjustment, is required, change the parameter No.19 setting to make the expansion parameters write-enabled.
The following table lists the parameters whose values are made valid for reference/write by setting parameter No. 19. Operation can be performed for the parameters marked .
Parameter No.19 setting
0000
(initial value)
000A
000B
000C
000E
Operation
Reference
Write
Reference
Write
Reference
Write
Reference
Write
Basic parameters
No.0 to No.19
Expansion parameters 1
No.20 to No.53
Expansion parameters 2
No.54 to No.77 special parameters (No.78 to 90)
5 - 1
5. PARAMETERS
5.1.2 List
POINT
The parameters marked * before their symbols are made valid by switching power off once and then switching it on again after parameter setting.
Refer to the corresponding reference items for details of the parameters.
(1) Item list
Class No. Symbol
2
7
8
9
4
5
6
11
16
*OP1 Function selection 1
Name and Function
*CMX Electronic gear numerator
*CDV Electronic gear denominator
PED Movement complete output range
PG1 Position control gain 1
*ZTY Home position return type
ZRF Home position return speed
ZST Home position shift distance
*BPS Communication baud rate selection, alarm history clear
Initial value Unit
Customer setting
0000
0000
0002
0105
1
1
100 m
35
0010 rad/s
500 r/min
10 r/min
0 m
0
100 r/min
0 ms
0 station
0000
0100
0000
0000
5 - 2
5. PARAMETERS
Class No. Symbol
20
22
23
28
29
31
32
34
35
40
50
51
52
53
46
47
48
49
42
43
44
45
*OP2 Function selection 2
*OP4
SIC
TL1
TL2
MO1
MO2
GD2
PG2
JTS
*ZPS
DCT
ZTM
ZTT
Function selection 4
Name and Function
Serial communications time-out selection
Internal torque limit 1
Internal torque limit 2
Analog monitor 1 offset
Analog monitor 2 offset
Ratio of load inertia moment to Servo motor inertia moment
Position control gain 2 control control
1
2
JOG operation acceleration/deceleration time constant
Home position return position data
Moving distance after proximity dog
Stopper type home position return stopper time
Stopper type home position return torque limit value
Initial value Unit
Customer setting
0000
0002
0000
0
0 %
0 mV
0 mV
4000 pulse/rev
100
100
%
%
0 pulse
0 mV
0 mV
100 ms
70
35
0.1 times rad/s
177 rad/s
817 rad/s
48 ms
980
100 ms
100 ms
0
1000
100
15
10 STM m
10 STM m ms
%
*LPP Position range output address 0
*LNP m
5 - 3
5. PARAMETERS
Class No. Symbol Name and Function
55 *OP6 Function selection 6
57
58
*OP8
*OP9
Function selection 8
Function selection 9
59 *OPA Function selection A
84
85
86
87
80
81
82
83
61
62
NH1 Machine resonance suppression filter 1
NH2 Machine resonance suppression filter 2
63 LPF Low-pass filter, adaptive vibration suppression control
64 GD2B Ratio of load inertia moment to Servo motor inertia moment 2
69
70
71
72
65 PG2B Position control gain 2 changing ratio
66 VG2B Speed control gain 2 changing ratio
67 VICB Speed integral compensation changing ratio
68 *CDP Gain changing selection
CDS Gain changing condition
CDT Gain changing time constant
For manufacturer setting
73
74 OUT1 OUT1 output time selection
75 OUT2 OUT2 output time selection
76 OUT3 OUT3 output time selection
77 *SYC1 Selected to program input polarity selection 1
78
79
88
89
90
For manufacturer setting
Note. Depends on the parameter No. 68 setting.
100
100
100
0000
10
1
100
10000
10
0
0
0
0000
0001
0209
Initial value Unit
0000
0000
0000
0000
0000
0000
0000
0000
0000
0000
70 0.1 times
%
%
%
(Note) ms
Customer setting
10ms
10ms
10ms
060A
1918
030B
0504
0102
0000
0005
120E
0102
0
0
5 - 4
5. PARAMETERS
(2) Detail list
Class No. Symbol Name and Function
0 *STY
Used to select the command system and regenerative option.
0
Program edit
0: Valid
1: Invalid
Selection of command system
(Refer to section 4.2)
0: Absolute value command system
1: Incremental value command system
Selection of regenerative option (Refer to section 14.1.1)
0: Not used
(However, this is irrelevant to the MR-J2S-10CL, as it does
not include the built-in regenerative resistor.)
1: FR-RC, FR-BU2
2:MR-RB032
3:MR-RB12
4:MR-RB32
5:MR-RB30
6:MR-RB50(Cooling fan is required)
8:MR-RB31
9:MR-RB51(Cooling fan is required)
If the regenerative option selected is not for use with the
servo amplifier, parameter error occurs.
Initial value
0000
Unit
Setting range
Name and function column.
5 - 5
5. PARAMETERS
Class No. Symbol Name and Function
1 *FTY
Used to set the feed length multiplication factor and manual pulse generator multiplication factor.
Initial value
0000
Unit
Setting range
Name and function column.
ST1 coordinate system selection
(Refer to section 4.2.2 to 4.2.4)
0: Address is incremented in CCW direction
1: Address is incremented in CW direction
Feed length multiplication factor (STM)
(Refer to section 4.2.3)
0: 1 time
1: 10 times
2: 100 times
3: 1000 times
Manual pulse generator multiplication factor
(Refer to section 4.3.2)
0: 1 time
1: 10 times
2: 100 times
Servo-on (SON) -off, forced stop (EMG) -off follow-up for absolute value command in incremental system or absolute value command/ incremental value command specifying system
0: Invalid
1: Valid
Normally, when this servo amplifier is used in the absolute value command method of the incremental system, placing it in a servo off or forced stop status will erase the home position.
When "1" is set in this parameter, the home position will not be erased if the servo amplifier is placed in a servo off or forced stop status.
Operation can be resumed when servo-on (SON) is turned on again or forced stop (EMG) is canceled.
5 - 6
5. PARAMETERS
Class No. Symbol Name and Function
2 *OP1
Used to select the input filter and absolute position detection system.
0 0
Input filter
If external input signal causes chattering due to noise, etc., input filter is used to suppress it.
0: None
1: 0.88[ms]
2: 1.77[ms]
3: 2.66[ms]
4: 3.55[ms]
5: 4.44[ms]
Selection of absolute position detection system
(Refer to section 4.5)
0: Incremental system
1: Absolute position detection system
Auto tuning
Used to selection the response level, etc. for execution of auto tuning.
(Refer to chapter 7)
0 0
1
2
Set value
D
E
F
B
C
9
A
7
8
5
6
3
4
1
2
Response level
Low response
Middle
response
High response
Machine resonance frequency guideline
15Hz
20Hz
25Hz
30Hz
35Hz
45Hz
55Hz
70Hz
85Hz
105Hz
130Hz
160Hz
200Hz
240Hz
300Hz
If the machine hunts or generates large gear sound, decrease the set value.
To improve performance, e.g. shorten the settling time, increase the set value.
Gain adjustment mode selection
(For more information, refer to section 8.1.1.)
Set value Gain adjustment mode
0 Interpolation mode
Auto tuning mode 1
Auto tuning mode 2
Description
GD2 (parameterNo.34), PG2 (parameterNo.35),
VG2 (parameterNo.37), VIC (parameterNo.38)
PG1 (parameterNo.7), GD2 (parameterNo.35),
PG2 (parameterNo.35), VG1 (parameterNo.36),
VG2 (parameterNo.37), VIC (parameterNo.38)
PG1 (parameterNo.7), PG2 (parameterNo.35),
VG1 (parameterNo.36), VG2 (parameterNo.37),
VIC (parameterNo.38)
3
4
Auto tuning response level setting
Manual mode 1
Manual mode 2
PG2 (parameterNo.35)
5 - 7
Initial value
0002
Unit
Setting range
Name and function column.
Name and function column .
5. PARAMETERS
Class No. Symbol
0
Name and Function
*4 CMX Electronic gear numerator
Set the value of electronic gear numerator. Setting "0" automatically sets the resolution of the servo motor connected. (Refer to section 5.2.1)
*5 CDV Electronic gear denominator
Set the value of electronic gear denominator. (Refer to section 5.2.1)
6 PED Movement complete output range
Used to set the droop pulse range when the movement complete output range
(PED) is output.
7 PG1 Position control gain 1
Used to set the gain of position loop 1. (Refer to chapter 8)
Increase the gain to improve tracking performance in response to the position command.
8 *ZTY Home position return type
Used to set the home position return system, home position return direction and proximity dog input polarity.
Initial value
1
1
100
36
Setting range
0 to
65535 rad/s 4 to 1000
0010
Unit
65535
10000
Name and function column.
Home position return system
0: Dog type
1: Count type
2: Data setting type
3: Stopper type
4: Home position ignorance
(Servo-on position as home position)
5: Dog type rear end reference
6: Count type front end reference
7: Dog cradle type
Home position return direction
0: Address increment direction
1: Address decrement direction
Proximity dog input polarity
0: Dog is detected when DOG is turned off.
1: Dog is detected when DOG is turned on.
Used to set the servo motor speed for home position return.
(Refer to section 4.4)
10 CRF Creep speed
Used to set the creep speed after proximity dog detection.
(Refer to section 4.4)
11 ZST Home position shift distance
Used to set the shift distance starting at the Z-phase pulse detection position inside the encoder.
500 r/min 0 to permissible speed
10 r/min 0 to
0 m permissible speed
0 to 65535
0
Do not change this value by any means.
13 JOG Jog speed
Used to set the jog speed command.
14 *STC S-pattern acceleration/deceleration time constant
Set when inserting S-pattern time constant into the acceleration/deceleration time constant of the point table. (Refer to section 5.2.3)
This time constant is invalid for home position return.
15 *SNO RS-422 station number setting
Used to specify the station number for RS-422 multidrop communication.
(Refer to section 4.6.2)
Always set one station to one axis of servo amplifier. If one station number is set to two or more stations, normal communication cannot be made.
100 r/min 0 to
0 ms permissible speed
0 to 100
0 Station 0 to 31
5 - 8
5. PARAMETERS
Class No. Symbol Name and Function
16 *BPS Serial communication function selection, alarm history clear
Used to select the serial communication baud rate, select various communication conditions, and clear the alarm history.
Serial baud rate selection
(Refer to section 15.2.2)
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
4: 4800[bps] (For MR-DP60)
Alarm history clear (Refer to section 5.2.6)
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting is automatically made invalid (reset to 0).
Serial communication standard selection
(Refer to section 15.2.2)
0: RS-232C used
1: RS-422 used
Serial communication response delay time
(Refer to section 15.2.2)
0: Invalid
1: Valid, reply sent after delay time of 800 s or
more
Used to select the signals to be output to the analog monitor 1 (MO1) and analog monitor 2 (MO2). (Refer to section 5.2.4)
0 0
Initial value
Unit
Setting range
Name and function column.
Name and function column.
Setting
0
1
4
5
2
3
8
9
6
7
Analog monitor 2 (MO2) Analog monitor 1 (MO1)
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note)
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note)
Current command ( 8V/max. current command)
Command pulse frequency ( 10V/500kpulse/s)
Droop pulses ( 10V/128 pulses)
Droop pulses ( 10V/2048 pulses)
Droop pulses ( 10V/8192 pulses)
Droop pulses ( 10V/32768 pulses)
A Droop pulses ( 10V/131072 pulses)
B Bus voltage ( 8V/400V)
Note. 8V is outputted at the maximum torque. However, when parameter
No. 28 29 are set to limit torque, 8V is outputted at the torque highly limited.
5 - 9
5. PARAMETERS
Class No. Symbol Name and Function
Used to select the status display shown at power-on. (Refer to section 7.2)
Initial value
Unit
Setting range
Name and function column. Status display on servo amplifier display at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Program No.
04: Step No.
05: Cumulative feedback pulses
06: Servo motor speed
07: Droop pulses
08: Override voltage
09: Analog torque limit voltage
0A: Regenerative load ratio
0B: Effective load ratio
0C: Peak load ratio
0D: Instantaneous torque
0E: Within one-revolution position low
0F: Within one-revolution position high
10: ABS counter
11: Load inertia moment ratio
12: Bus voltage
Status display of MR-DP60 at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Program No.
04: Step No.
05: Cumulative feedback pulses
06: Servo motor speed
07: Droop pulses
08: Override voltage
09: Analog torque limit voltage
0A: Regenerative load ratio
0B: Effective load ratio
0C: Peak load ratio
0D: Instantaneous torque
0E: Within one-revolution position
0F: ABS counter
10: Load inertia moment ratio
11: Bus voltage
5 - 10
5. PARAMETERS
Class No. Symbol
000E
Name and Function
Used to select the reference and write ranges of the parameters.
Operation can be performed for the parameters marked .
Basic Expansion
Expansion parameters 2
Set No.54 to 77
Operation parameters parameters 1 value special parameters
No.0 to 19 No.20 to 53
(No. 78 to 90)
0000
Reference
(initial value)
Write
Write No.19
Write
Write
Write
Initial value
Unit
Setting range
0000 Refer to
Name and function column.
Note. Set this parameter when making device setting using the MR Configurator
(Servo Configuration Software).
20 *OP2 Function selection 2
Used to select slight vibration suppression control.
0 0 0
Slight vibration suppression control selection
0: Invalid
1: Valid
Name and function column.
Do not change this value by any means.
22 *OP4 Function selection 4
Used to select stop processing at forward rotation stroke end (LSP), reverse rotation stroke end (LSN) off.
0 0 0
0002
Name and function column.
Stopping method used when forward rotation stroke end (LSP), reverse rotation stroke end (LSN) device or software limit is valid
(Refer to section 5.2.5)
0: Sudden stop
1: Slow stop
0 0 to 60
Used to choose the time-out period of communication protocol.
Setting Description
0
1 to 60
No time-out check
Time-out check period setting
Check period setting [s]
5 - 11
5. PARAMETERS
Class No. Symbol Name and Function
Initial value
0
Unit
%
Setting range
0 to 100
Set the feed forward gain. When the setting is 100%, the droop pulses during operation at constant speed are nearly zero. However, sudden acceleration/deceleration will increase the overshoot. As a guideline, when the feed forward gain setting is 100%, set 1s or more as the acceleration/deceleration time constant up to the rated speed.
Used to set the offset voltage to analog override.
Used to set the offset voltage to analog torque limit (TLA).
27 *ENR Encoder output pulses
Used to set the encoder pulses (A-phase, B-phase) output by the servo amplifier.
Set the value 4 times greater than the A-phase or B-phase pulses.
You can use parameter No. 58 to choose the output pulse designation or output division ratio setting.
The number of A/B-phase pulses actually output is 1/4 times greater than the preset number of pulses.
The maximum output frequency is 1.3Mpps (after multiplication by 4). Use this parameter within this range.
For output pulse designation
Set " 0 " (initial value) in parameter No. 58.
Set the number of pulses per servo motor revolution.
Output pulse set value [pulses/rev]
At the setting of 5600, for example, the actually output A/B-phase pulses are as indicated below.
A B-phase output pulses
5600
4
For output division ratio setting
1400[pulse]
Set " 1 " in parameter No. 58.
The number of pulses per servo motor revolution is divided by the set value.
Output pulse
Resolution per servo motor revolution
Set value
[pulses/rev]
At the setting of 8, for example, the actually output A/B-phase pulses are as indicated below.
A B-phase output pulses
131072
8
1
4
4096[pulse]
28 TL1 Internal torque limit 1
Used to limit servo motor-torque on the assumption that the maximum torque is 100%. When 0 is set, torque is not produced.
29 TL2 Internal torque limit 2
Used to limit servo motor-torque on the assumption that the maximum torque is 100%. When 0 is set, torque is not produced.
Made valid by switching on the internal torque limit selection (TL2).
0 mV 999 to
999
0 mV 999 to
4000 pulse/ rev
999
1 to
65535
0 pulse (Note)
0 to
1600
Used to set the backlash compensation made when the command direction is reversed.
This function compensates for the number of backlash pulses in the opposite direction to the home position return direction. In the absolute position detection system, this function compensates for the backlash pulse count in the direction opposite to the operating direction at power-on.
Note. The setting range differs depending on the software version of servo amplifiers.
Version A1 or later: 0 to 1600
Version A0 or before: 0 to 1000
5 - 12
5. PARAMETERS
Class No. Symbol Name and Function
31 MO1 Analog monitor 1 (MO1) offset
Used to set the offset voltage of the analog monitor 1 (MO1) output.
32 MO2 Analog monitor 2 (MO2) offset
Used to set the offset voltage of the analog monitor 2 (MO2) output.
Initial value
Unit
Setting range
0 mV 999 to
999
0 mV 999 to
999
Used to set the delay time (Tb) between when the electromagnetic brake interlock (MBR) switches off and when the base circuit is shut off.
(Refer to section 3.9)
34 GD2 Ratio of load inertia moment to servo motor inertia moment
Used to set the ratio of the load inertia moment to the servo motor shaft inertia moment. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
35 PG2 Position control gain 2
Used to set the gain of the position loop. (Refer to chapter 8)
Set this parameter to increase the position response level to load disturbance.
Higher setting increases the response level but is liable to generate vibration and/or noise.
When auto tuning is selected, the result of auto tuning is automatically set.
70 0.1 times
0 to 1000
8000 Normally this parameter value need not be changed.
Higher setting increases the response level but is liable to generate vibration and/or noise. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
Set this parameter when vibration occurs on machines of low rigidity or large backlash. Higher setting increases the response level but is liable to generate vibration and/or noise. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
Used to set the integral time constant of the speed loop. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
20000
Used to set the differential compensation. (Refer to chapter 8)
Made valid when the proportion control (PC) is switched on.
40 JTS JOG operation acceleration/deceleration time constant
Used to set the acceleration/deceleration time when JOG operation.
41 ZTS Home position return operation acceleration/deceleration time constant
Used to set the acceleration/deceleration time when Zero point return operation.
42 *ZPS Home position return position data
Used to set the current position on completion of home position return.
(Refer to section 4.4)
43 DCT Moving distance after proximity dog
Used to set the moving distance after proximity dog in count type home position return. (Refer to section 4.4.3)
44 ZTM Stopper type home position return stopper time
In stopper type home position return, used to set the time from when the machine part is pressed against the stopper and the torque limit set in parameter No.45 is reached to when the home position is set.
(Refer to section 4.4.5)
45 ZTT Stopper type home position return torque limit
Used to set the torque limit value relative to the max. torque in [%] in stopper type home position return. (Refer to section 4.4.5)
0
100
15
10 STM m
1000 10 STM m ms
%
20000
20000
32768 to
32767
0 to
65535
5 to 1000
1 to 100
5 - 13
5. PARAMETERS
Class No. Symbol Name and Function
46
47
48
49
Used to set the address increment side software stroke limit. The software limit is made invalid if this value is the same as in "software limit ".
(Refer to section 5.2.7)
Set the same sign to parameters No.46 and 47. Setting of different signs will result in a parameter error.
Set address:
Upper 3 digits
Lower 3 digits
Parameter No. 47
Parameter No. 46
*LMN Software limit
Used to set the address decrement side software stroke limit. The software limit is made invalid if this value is the same as in "software limit ".
(Refer to section 5.2.7)
Set the same sign to parameters No.48 and 49. Setting of different signs will result in a parameter error.
Set address:
Upper 3 digits
Lower 3 digits
Parameter No. 49
Parameter No. 48
Initial value
0
0
50
51
52
53
*LPP Position range output address
Used to set the address increment side position range output address. Set the same sign to parameters No.50 and 51. Setting of different signs will result in a parameter error.
In parameters No. 50 to 53, set the range where position range (POT) turns on.
Set address:
Upper 3 digits
Lower 3 digits
Parameter No. 51
Parameter No. 50
*LNP Position range output address
Used to set the address decrement side position range output address. Set the same sign to parameters No.52 and 53. Setting of different signs will result in a parameter error.
Set address:
Upper 3 digits
Lower 3 digits
Parameter No. 53
Parameter No. 52
0
0
Unit
10 STM m
Setting range
999999 to
999999
10 STM m
999999 to
999999
10 STM m
999999 to
999999
10 STM m
999999 to
999999
5 - 14
5. PARAMETERS
Class No. Symbol Name and Function
54 For manufacturer setting
Do not change this value by any means.
55 *OP6 Function selection 6
Used to select how to process the base circuit when reset (RES) is valid.
0 0 0
Processing of the base circuit when reset (RES) is valid.
0: Base circuit switched off
1: Base circuit not switched off
56
Do not change this value by any means.
57 *OP8 Function selection 8
Used to select the protocol of serial communication.
0 0
Protocol checksum selection
0: Yes (checksum added)
1: No (checksum not added)
Protocol checksum selection
0: With station numbers
1: No station numbers
58 *OP9 Function selection 9
Use to select the encoder output pulse direction and encoder pulse output setting.
0 0
Encoder pulse output phase changing
Changes the phases of A, B-phase encoder pulses output.
Set value
Servo motor rotation direction
CCW CW
0
A-phase
B-phase
A-phase
B-phase
1
A-phase
B-phase
A-phase
B-phase
Encoder output pulse setting selection
(Refer to parameter No. 27)
0: Output pulse setting
1: Division ratio setting
Initial value
0000
Unit
Setting range
Name and function column.
0000
0000
Name and function column.
Refer to
Name and function column.
5 - 15
5. PARAMETERS
Class No. Symbol
59 OPA Function selection A
Used to select the alarm code.
0 0
Name and Function
Setting
Rotation direction in which torque limit is made valid
CCW direction CW direction
0
1
2
Set value
0
1
Setting of alarm code output
Connector pins
CN1B-19 CN1A-18 CN1A-19
Signals assigned to corresponding pins are output.
Alarm code is output at alarm occurrence.
(Note) Alarm code
CN1B pin 19
CN1A pin 18
CN1A pin 19
Alarm display
0
0
0
0
1
1
1
0
0
1
1
0
0
1
0
1
0
1
0
1
0
Name
88888
AL.12
AL.13
AL.15
Watchdog
Memory error 1
Clock error
Memory error 2
AL.17
Board error 2
AL.19 Memory error 3
AL.37 Parameter error
AL.39
Program error
AL.8A
Serial communication time-out error
AL.8E
Serial communication error
AL.30
Regenerative error
AL.33 Overvoltage
AL.10 Undervoltage
AL.45
Main circuit device overheat
AL.46 Servo motor overheat
AL.50
AL.51
AL.24
AL.32
Overload 1
Overload 2
Main circuit
Overcurrent
AL.31
AL.35
AL.52
Overspeed
Command pulse frequency error
Error excessive
AL.63
AL.64
AL.16
AL.1A
AL.20
AL.25
Home position return incomplete
Home position setting error
Encoder error 1
Motor combination error
Encoder error 2
Absolute position erase
Note. 0: OFF
1: ON
5 - 16
Initial value
Unit
Setting range
Name and function column.
5. PARAMETERS
Class No. Symbol Name and Function
Do not change this value by any means.
61 NH1 Machine resonance suppression filter 1
Used to selection the machine resonance suppression filter.
(Refer to section 9.2.)
0
Notch frequency selection
Set "00" when you have set adaptive vibration suppression control to be "valid" or "held"
(parameter No. 63: 1 or 2 ).
Setting value
Frequency
Setting value
Frequency
Setting value
Frequency
Setting value
Frequency
04
05
06
07
00
01
02
03
Invalid
4500
2250
1500
1125
900
750
642.9
0C
0D
0E
0F
08
09
0A
0B
562.5
500
450
409.1
375
346.2
321.4
300
14
15
16
17
10
11
12
13
281.3
264.7
250
236.8
225
214.3
204.5
195.7
1C
1D
1E
1F
18
19
1A
1B
187.5
180
173.1
166.7
160.1
155.2
150
145.2
Notch depth selection
Setting value
Depth Gain
0
1
2
3
Deep to
Shallow
40dB
14dB
8dB
4dB
62 NH2 Machine resonance suppression filter 2
Used to set the machine resonance suppression filter.
0
Notch frequency
Same setting as in parameter No. 61
However, you need not set "00" if you have set adaptive vibration suppression control to be "valid" or "held".
Notch depth
Same setting as in parameter No. 61
Initial value
Unit
0000
Setting range
Name and function column.
Name and function column.
5 - 17
5. PARAMETERS
Class No. Symbol Name and Function
63 LPF Low-pass filter/adaptive vibration suppression control
Used to selection the low-pass filter and adaptive vibration suppression control. (Refer to chapter 9)
0
Initial value
Unit
Setting range
Name and function column.
Low-pass filter selection
0: Valid (Automatic adjustment)
1: Invalid
When you choose "valid", the filter of the handwidth represented by the following expression is set automatically.
For 1kW or less
VG2 setting 10
2 (1 GD2 setting 0.1)
[H z ]
For 2kW or more
VG2 setting 5
2 (1 GD2 setting 0.1)
[H z ]
Adaptive vibration suppression control selection
Choosing "valid" or "held" in adaptive vibration suppression control selection makes the machine resonance control filter 1 (parameter No. 61) invalid.
0: Invalid
1: Valid
Machine resonance frequency is always detected
and the filter is generated in response to resonance
to suppress machine vibration.
2: Held
The characteristics of the filter generated so far are held,
and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
Used to set the sensitivity of machine resonance detection.
0: Normal
1: Large sensitivity
64 GD2B Ratio of load inertia moment to servo motor inertia moment 2
Used to set the ratio of load inertia moment to servo motor inertia moment when gain changing is valid.
65 PG2B Position control gain 2 changing ratio
Used to set the ratio of changing the position control gain 2 when gain changing is valid.
Made valid when auto tuning is invalid.
66 VG2B Speed control gain 2 changing ratio
Used to set the ratio of changing the speed control gain 2 when gain changing is valid.
Made valid when auto tuning is invalid.
67 VICB Speed integral compensation changing ratio
Used to set the ratio of changing the speed integral compensation when gain changing is valid. Made valid when auto tuning is invalid.
70 0.1 times
0 to 3000
1000
5 - 18
5. PARAMETERS
Class No. Symbol Name and Function
Initial value
Unit
Setting range
68 *CDP Gain changing selection
Used to select the gain changing condition. (Refer to section 9.5)
0 0 0
Name and function column.
Gain changing selection
Gains are changed in accordance with the settings of parameters No. 64 to 67 under any of the following conditions:
0: Invalid
1: Gain changing (CDP) signal is ON
2: Command frequency is equal to higher than
parameter No. 69 setting
3: Droop pulse value is equal to higher than
parameter No. 69 setting
4: Servo motor speed is equal to higher than
parameter No. 69 setting
69 CDS Gain changing condition
Used to set the value of gain changing condition (command frequency, droop pulses, servo motor speed) selected in parameter No. 68. The set value unit changes with the changing condition item. (Refer to section 9.5)
70 CDT Gain changing time constant
Used to set the time constant at which the gains will change in response to the conditions set in parameters No. 68 and 69.
(Refer to section 9.5)
71
72
73
For manufacturer setting
Do not change this value by any means.
10 kpps 10 to pulse r/min
9999
1 ms 100
74 OUT1 OUT1 output time setting
Used to set the output time of OUT1. The OUT1 is turned on by OUTON program command.
If "0" is set, it keeps ON.
75 OUT2 OUT2 output time setting
Used to set the output time of OUT2. The OUT2 is turned on by OUTON program command.
If "0" is set, it keeps ON.
76 OUT3 OUT3 output time setting
Used to set the output time of OUT3. The OUT3 is turned on by OUTON program command.
If "0" is set, it keeps ON.
77 *SYC1 Program input polarity selection 1
Used to select the device that reverses the input polarity of Program input 1
(PI1), Program input 2 (PI2), Program input 3 (PI3).
10
10000
10
0 10ms 2000
0 10ms
0 10ms
2000
2000
0000 0000h to
FFFFh
0 0 0
Signal name
Initial value
BIN HEX
Program input 1
Program input 2
Program input 3
BIN 0 : Positive logic
BIN 1 : Negative logic
0
0
0
0
0
5 - 19
5. PARAMETERS
Class No. Symbol
78
79
80
85
86
87
88
81
82
83
84
89
90
Name and Function
For manufacturer setting
The settings are automatically changed.
For manufacturer setting
Do not change this value by any means.
Initial value
0001
0209
060A
1918
030B
0504
0102
0000
0005
120E
0102
0
0
Unit
Setting range
5 - 20
5. PARAMETERS
5.2 Detailed explanation
5.2.1 Electronic gear
CAUTION False setting will result in unexpected fast rotation, causing injury.
POINT
The range of the electronic gear setting is
1
10
CMX
CDV
1000.
If you set any value outside this range, a parameter error (AL.37) occurs.
After setting the parameter No.4, 5 value, switch power off, then on to make that setting valid. In this case, execute a home position return again. The absolute position detection system also requires a home position return.
(1) Concept of electronic gear
Use the electronic gear (parameters No.4, 5) to make adjustment so that the servo amplifier setting matches the moving distance of the machine. Also, by changing the electronic gear value, the machine can be moved at any multiplication ratio to the moving distance on the servo amplifier.
Motor
CMX
CDV
Parameter No. 4
Parameter No. 5
CMX
CDV
+
-
Deviation counter
Encoder feedback pulses
Electronic gear
Parameters No. 4, 5
The following examples are used to explain how to calculate the electronic gear value.
Encoder
POINT
The following specification symbols are needed for electronic gear calculation.
Pb : Ballscrew lead [mm(in.)] n : Reduction ratio
Pt : Servo motor resolution [pulse/rev]
S : Travel per servo motor revolution [ m/rev]
(a) Ballscrew setting example n
Machine specifications n=NL/NM=1/2
NL
Ballscrew lead: Pb 10 (0.39) [mm(in.)]
Pb=10(0.39)[mm(in.)]
Reduction ratio: n 1/2
Servo motor resolution: Pt 131072 [pulse/rev]
NM
Servo motor 131072[pulse/rev]
CMX
CDV p
t
S p p
t
131072
1/2 10 1000
Hence, set 32768 to CMX and 1250 to CDV.
131072
5000
32768
1250
(b) Conveyor setting example
Machine specifications
r=160(6.30)[mm(in.)]
Pulley diameter: r 160 (6.30) [mm(in.)]
Reduction ratio: n 1/3
Servo motor resolution: Pt 131072 [pulse/rev]
n
NL NM n=NL/NM=1/3
Servo motor
131072[pulse/rev]
CMX
CDV p
t
S p
t
n r 1000
131072
1/3 160 1000
Hence, set 32768 to CMX and 41888 to CDV.
131072
167551.61
32768
41888
Reduce CMX and CDV to the setting range or less, and round off the first decimal place.
5 - 21
5. PARAMETERS
5.2.2 Changing the status display screen
The status display item of the servo amplifier display and the display item of the external digital display
(MR-DP60) shown at power-on can be changed by changing the parameter No.18 (status display selection) settings. In the initial condition, the servo amplifier display shows the servo motor speed and the MR-DP60 shows the current position.
For display details, refer to section 7.2.
Parameter No. 18
Status display on servo amplifier display at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Program No.
04: Step No.
05: Cumulative feedback pulses
06: Servo motor speed
07: Droop pulses
08: Override voltage
09: Analog torque limit voltage
0A: Regenerative load ratio
0B: Effective load ratio
0C: Peak load ratio
0D: Instantaneous torque
0E: Within one-revolution position low
0F: Within one-revolution position high
10: ABS counter
11: Load inertia moment ratio
12: Bus voltage
Status display of MR-DP60 at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Program No.
04: Step No.
05: Cumulative feedback pulses
06: Servo motor speed
07: Droop pulses
08: Override voltage
09: Analog torque limit voltage
0A: Regenerative load ratio
0B: Effective load ratio
0C: Peak load ratio
0D: Instantaneous torque
0E: Within one-revolution position
0F: ABS counter
10: Load inertia moment ratio
11: Bus voltage
5 - 22
5. PARAMETERS
5.2.3 S-pattern acceleration/deceleration
In servo operation, linear acceleration/deceleration is usually made. By setting the S-pattern acceleration/deceleration time constant (parameter No.14), a smooth start/stop can be made. When the Spattern time constant is set, smooth positioning is executed as shown below. When the S-pattern acceleration/deceleration time constant is set, the time from a start to the output of Movement complete
(PED) increases by the S-pattern acceleration/deceleration time constant.
Acceleration time constant
Deceleration time constant
Rated speed
Preset speed
Servo motor speed
0 [r/min]
Ta
Ta Ts
Tb Ts
Tb
Ta: Time until preset speed is reached
Tb: Time until stop
Ts: S-pattern acceleration/deceleration time constant
(parameter No. 14)
Setting range 0 to 100ms
5.2.4 Analog output
The servo status can be output to two channels in terms of voltage. The servo status can be monitored using an ammeter.
(1) Setting
Change the following digits of parameter No.17.
Parameter No. 17
Analog monitor 1 (MO1) output selection
(Signal output to across MO1-LG)
Analog monitor 2 (MO2) output selection
(Signal output to across MO2-LG)
Parameters No.31 and 32 can be used to set the offset voltages to the analog output voltages. The setting range is between 999 and 999mV.
Parameter
Parameter No.31
Parameter No.32
Description
Used to set the offset voltage for the analog monitor 1 (MO1) output.
Used to set the offset voltage for the analog monitor 2 (MO2) output.
Setting range [mV]
999 to 999
5 - 23
5. PARAMETERS
(2) Contents of a setting
The servo amplifier is factory-set to output the servo motor speed to analog monitor 1 and the torque to analog monitor 2. The setting can be changed as listed below by changing the parameter No.17
(analog monitor output) value.
Refer to (3) for the measurement point.
Setting Output item Description Setting Output item Description
0 Servo motor speed
8[V]
CCW direction pulses
10[V]
CCW direction
( 10V/128pulse)
Max. speed
0 Max. speed
128[pulse]
0 128[pulse]
1 Torque
CW direction
-8[V]
Driving in CCW direction
8[V]
Max. torque
0 Max. torque pulses
( 10V/2048pulse)
CW direction
10[V]
-10[V]
CCW direction
2048[pulse]
0 2048[pulse]
2 Servo motor speed
Driving in CW direction
-8[V]
CW direction
8[V]
CCW direction pulses
( 10V/8192pulse)
CW direction
10[V]
-10[V]
CCW direction
8192[pulse]
0 8192[pulse]
3 Torque
Max. speed 0 Max. speed
Driving in
CCW direction 8[V]
Driving in
CW direction pulses
( 10V/32768pulse)
CW direction
-10[V]
CCW direction
10[V]
32768[pulse]
0 32768[pulse]
Max. torque 0 Max. torque
8[V]
Max. command
current
CCW direction
0 Max. command
current pulses
( 10V/131072pulse)
CW direction
10[V]
-10[V]
CCW direction
131072[pulse]
0
131072[pulse]
CW direction
-8[V]
CCW direction
8[V]
B Bus voltage
CW direction
-10[V]
8[V]
Max. speed
0 Max. speed
0 400[V]
CW direction
-8[V]
Note 1. Encoder pulse unit.
2. 8V is outputted at the maximum torque. However, when parameter No. 28 29 are set to limit torque, 8V is outputted at the torque highly limited.
5 - 24
5. PARAMETERS
Command speed
Command position differentiation
Droop pulse
Position control
Speed command
Current command
Speed control
Current control
Bus voltage
PWM
Current encoder
M Servo Motor
Current feedback
Encoder
Differ- ential
Position feedback
Servo Motor
speed
Torque
5 - 25
5. PARAMETERS
5.2.5 Changing the stop pattern using a limit switch
The servo amplifier is factory-set to make a sudden stop when the limit switch or software limit is made valid. When a sudden stop is not required, e.g. when there is an allowance from the limit switch installation position to the permissible moving range of the machine, a slow stop may be selected by changing the parameter No.22 setting.
Parameter No. 22 setting Description
0 (initial value)
1
5.2.6 Alarm history clear
Droop pulses are reset to make a stop. (Sudden stop)
Droop pulses are drawn out to make a slow stop. (Slow stop)
The alarm history can be confirmed by using the MR Configurator (Servo Configuration Software) or communication function. The servo amplifier stores one current alarm and five past alarms from when its power is switched on first. To control alarms which will occur during operation, clear the alarm history using parameter No.16 (alarm history clear) before starting operation. Clearing the alarm history automatically returns to “ 0 ”.
This parameter is made valid by switching power off, then on after setting.
Parameter No. 16
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleared)
5.2.7 Software limit
A limit stop using a software limit is made as in stroke end operation. When a motion goes beyond the setting range, the motor is stopped and servo-locked. This function is made valid at power-on but made invalid during home position return. This function is made invalid when the software limit setting is the same as the software limit setting. A parameter error (AL. 37) will occur if the software limit setting is less than the software limit setting.
Inhibited area
Unmovable
Current position
Software limit
Movable area
Movable
5 - 26
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
The MR Configurator (Servo Configuration software MR2JW3-SETUP151E Ver.E1 or more) uses the communication function of the servo amplifier to perform parameter setting changes, graph display, test operation, etc. on a personal computer.
6.1 Specifications
Item Description
Communication signal Conforms to RS-232C
Baud rate 57600, 38400, 19200, 9600
Alarm
Diagnostic
Parameters
Test
Advanced-function
Program-data
File operation
Display, history, amplifier data
I/O display, function device display, no motor rotation, total power-on time, software number display, motor data display, tuning data, absolute encoder data, axis name setting
Parameter list, tuning, change list, detailed information, device setting
Jog, positioning, operation w/o motor, forced output, program test
Machine analyzer, gain search, machine simulation
Program data, indirect-addressing
Data read, save, print
6.2 System configuration
(1) Components
To use this software, the following components are required in addition to the servo amplifier and servo motor.
Model (Note 1) Description
(Note 2)
Personal computer
OS
Display
Keyboard
Mouse
Printer
Communication cable
IBM PC-AT compatible where the English version of Windows ® 95, Windows ® 98, Windows ® Me,
Windows NT ® Workstation 4.0, Windows ® 2000 Professional, Windows ® XP Professional or Windows ®
XP Home Edition operates
Processor: Pentium ® 133MHz or more (Windows ® 95, Windows ® 98, Windows NT ® Workstation 4.0,
Windows ® 2000 Professional)
Pentium ® 150MHz or more (Windows ® Me)
Memory: 16MB or more (Windows ® 95), 24MB or more (Windows ® 98)
32MB or more (Windows ® Me, Windows NT ® Workstation 4.0, Windows ® 2000 Professional)
128MB or more (Windows ® XP Professional, Windows ® XP Home Edition)
Free hard disk space: 60MB or more
Serial port used
Windows ® 95, Windows ® 98, Windows ® Me, Windows NT ® Workstation 4.0, Windows ® 2000
Professional, Windows ® XP Professional, Windows ® XP Home Edition (English version)
One whose resolution is 800 600 or more and that can provide a high color (16 bit) display.
Connectable with the above personal computer.
Connectable with the above personal computer.
Connectable with the above personal computer. Note that a serial mouse is not used.
Connectable with the above personal computer.
MR-CPCATCBL3M
When this cannot be used, refer to section 14.1.4 (3) and fabricate.
Note 1. Windows and Windows NT are the registered trademarks of Microsoft Corporation in the United State and other countries.
Pentium is the registered trademarks of Intel Corporation.
2. On some personal computers, this software may not run properly.
6 - 1
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(2) Configuration diagram
(a) For use of RS-232C
Personal computer
Servo amplifier
U
V
W
Communication cable
CN3 CN2
To RS-232C connector
(b) For use of RS-422
Up to 32 axes may be multidropped.
Personal computer
RS-232C/RS-422 converter
(Note)
Communication cable
Servo amplifier
CN3 CN2
(Axis 1)
To RS-232C
connector
Servo amplifier
Servo motor
Servo motor
Servo motor CN3 CN2
(Axis 2)
Servo amplifier
CN3 CN2
(Axis 32)
Servo motor
Note. Refer to section 15.1.1 for cable connections.
6 - 2
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.3 Station setting
Click “System” on the menu bar and click “Station Selection” on the menu.
When the above choices are made, the following window appears.
(1) Station number setting
Choose the station number in the combo box and click the “Station Settings” button to set the station number.
POINT
This setting should be the same as the station number which has been set in the parameter in the servo amplifier used for communication.
(2) Closing of the station setting window
Click the “Close” button to close the window.
6 - 3
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.4 Parameters
Click “Parameters” on the menu bar and click “Parameter List” on the menu.
When the above choices are made, the following window appears. a) b) c) d) e) f) g) i) h)
(1) Parameter value write ( a) )
Click the parameter whose setting was changed and press the “Write” button to write the new parameter setting to the servo amplifier.
(2) Parameter value verify ( b) )
Click the “Verify” button to verify all parameter values being displayed and the parameter values of the servo amplifier.
6 - 4
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(3) Parameter value batch-read ( c) )
Click the “Read All” button to read and display all parameter values from the servo amplifier.
(4) Parameter value batch-write ( d) )
Click the “Write All” button to write all parameter values to the servo amplifier.
(5) Parameter change list display ( e) )
Click the “Change List” button to show the numbers, names, initial values and current values of the parameters whose initial value and current value are different. In the offline mode, the parameter change list is not shown.
(6) Parameter detail information ( f) )
Click the “Help” button or double-click the display field to show the detailed explanation of each parameter.
(7) Parameter default value indication ( g) )
Click the “Set to default” button to show the initial value of each parameter.
(8) Parameter value change ( h) )
Choose the parameter to be changed, enter a new value into the “Parameter value” input field, and press the enter key or Enter Data button.
(9) Parameter data file read
Used to read and display the parameter values stored in the file. Use the file selection window to read.
(10) Parameter value storage
Used to store all parameter values being displayed on the window into the specified file. Use the file selection window to store.
(11) Parameter data list print
Used to print all parameter values being displayed on the window. Use the “File” menu on the menu bar to print.
(12) Parameter list window closing ( i) )
Click the “Close” button to close the window. If the “Close” button is clicked without (1) parameter value write or (4) parameter value batch-write being performed, the parameter value changed is made invalid.
6 - 5
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.5 Simple Program
6.5.1 Program data
The following screen is designed to set the program of the MR-J2S-CL.
(1) How to open the setting screen
Click "Program-Data" on the menu bar and click "Program-Data" in the menu.
(2) Explanation of Program Data window a) b) c) e) g) d) f)
(a) Reading the program (a))
Click the "Read All" button to read the program stored in the servo amplifier.
(b) Writing the program (b))
Click the "Write All" button to write the program, whose setting has been changed, to the servo amplifier.
(c) Verifying the programs (c))
Click the "Verify" button to verify the program contents on the personal computer and the program contents of the servo amplifier.
(d) Selecting the program No. (d))
Used to select the program No. to be edited.
(e) Editing the program (e))
Used to edit the program selected in d). Click the "Write All" button to open the Program Edit window. Refer to (3) in this section for the edit screen.
(f) Reading and saving the program file
A program can be saved/read as a file. Perform save/read in the "File" menu of the menu bar.
6 - 6
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(g) Printing the program
The read and edited program can be printed. Perform print in the "File" menu of the menu bar.
(h) Referring to the number of steps (f))
Click the "Steps" button to display the number of used steps and number of remaining steps in all programs.
(i) Closing the Program Data window (g))
Click the "Close" button to close the window.
(3) Explanation of Program Edit window
Create a program in the Program Edit window. c) d) e) f) a)
(a) Editing the program (a))
Enter commands into the program edit area in a text format.
(b) Copying the text (b))
Select the text of the program edit area and click the "Copy" button to store the selected text into the clipboard.
(c) Pasting the text (c))
Click the "Paste" button to paste the text stored in the clipboard to the specified position of the program edit area.
(d) Deleting the text (d))
Select the text of the program edit area and click the "Cut" button to delete the selected text.
(e) Closing the Program Data window (e))
Click the "OK" button to end editing and close the Program Data window.
(f) Canceling the Program Edit window (f))
Click the "Cancel" button to discard the program being edited and close the Program Edit window.
6 - 7 b)
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.5.2 Indirect addressing
The following screen is designed to set the general-purpose registers (R1 to R4, D1 to D4) of the MR-J2S-
CL.
(1) How to open the setting screen
Click "Program-Data" on the menu bar and click "Indirect-Addressing" in the menu.
(2) Explanation of Indirect Addressing window a) b) c) d) e)
(a) Setting the general-purpose registers D1 to D4 (a))
Set the values of the general-purpose registers D1 to D4.
(b) Setting the general-purpose registers R1 to R4 (b))
Set the values of the general-purpose registers R1 to R4. The write destination memory can be selected.
Selecting "RAM" writes the set values to the volatile memory. In this case, the set values are lost when the servo amplifier is powered off.
Selecting "EEPROM" writes the set values to the non-volatile memory (EEP-ROM). In this case, the set values are not lost if the servo amplifier is powered off.
POINT
The limited number of time to write to EEP-ROM is 100,000.
6 - 8
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(c) Read from the general-purpose registers (c))
Click the "Read All" button to read the values of the general-purpose registers (R1 to R4, D1 to D4) stored in the servo amplifier.
(d) Write to the general-purpose registers (d))
Click the "Write All" button to write the set values of the general-purpose registers (R1 to R4, D1 to
D4) to the servo amplifier.
(e) Closing the Indirect Addressing window (e))
Click the "Close" button to close the window.
6 - 9
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.6 Device assignment method
POINT
When using the device setting, preset “000E” in parameter No. 19.
(1) How to open the setting screen
Click “Parameters” on the menu bar and click “Device setting” in the menu.
Making selection displays the following window.
Click “Yes” button reads and displays the function assigned to each pin from the interface unit and extension IO unit.
Click “No” button displays the initial status of the interface unit and extension IO unit.
Click “Cancel” button terminates the processing.
Click “Yes” button or “No” button displays the following two windows.
6 - 10
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(2) Screen explanation
(a) DIDO device setting window screen
This is the device assignment screen of the servo amplifier displays the pin assignment status of the servo amplifier. c)
1) Read of function assignment ( a) )
Click the “Read” button reads and displays all functions assigned to the pins from the servo amplifier.
2) Write of function assignment ( b) )
Click the “Write” button writes all pins that are assigned the functions to the servo amplifier.
3) Verify of function assignment ( c) )
Click the “Verify” button verifies the function assignment in the servo amplifier with the device information on the screen.
4) Initial setting of function assignment ( d) )
Click the “Set to Default” button initializes the function assignment. a) b) d)
6 - 11
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(b) DIDO function display window screen
This screen is used to select the device to the pins.
The functions displayed below * and * are assignable. a) b)
Move the pointer to the place of the function to be assigned. Drag and drop it as-is to the pin you want to assign in the DIDO device setting window.
1) Assignment checking, automatic ON setting ( a) )
Press this button to display the screen that shows the assignment list and enables auto ON setting.
Refer to (4) in this section for more information.
2) Quitting
Click “Close” button to exit from the window. ( b) )
6 - 12
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(C) Function device assignment checking auto ON setting display
Click the “ / ” button in the DIDO function display window displays the following window.
The assigned functions are indicated by .
The functions assigned by auto ON are grayed. When you want to set auto ON to the function that is enabled for auto ON, click the corresponding cell. Clicking it again disables auto ON.
1) Auto ON read of function assignment ( a) )
Click “Auto ON read” button reads the functions set for auto ON from the interface unit and extension IO unit.
2) Auto ON write of function assignment ( b) )
Click “Auto ON write” button writes the functions currently set for auto ON to the interface unit and extension IO unit.
3) Auto ON verify of function assignment ( c) )
Click “Auto ON verify” button verifies the current auto ON setting in the interface unit and extension IO unit with the auto ON setting on the screen.
4) Auto ON initial setting of function assignment ( d) )
Click “Auto ON initial setting” button initializes the auto ON setting.
5) Quitting the function device assignment checking/auto ON setting window ( e) )
Click “Close” button exits from the window. c) d) a) b) e)
6 - 13
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7 Test operation
CAUTION
When confirming the machine operation in the test operation mode, use the machine after checking that the safety mechanism such as the forced stop (EMG) operates.
If any operational fault has occurred, stop operation using the forced stop (EMG).
6.7.1 Jog operation
POINT
For the program operation, refer to the manual of MR Configurator.
The servo motor will not operate if the forced stop (EMG), forward rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device setting to assign them as external input signals and turn off across these signals and SG. (Refer to section 6.6.)
When an alarm occurs, the JOG operation is automatically canceled.
Hold down the “Forward” or “Reverse” button to rotate the servo motor. Release the “Forward” or
“Reverse” button to stop.
Click “Test” on the menu bar and choose “Jog” on the menu.
When the above choices are made, the following window appears. a) b) c) d) e) f)
6 - 14
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(1) Servo motor speed setting ( a) )
Enter a new value into the “Motor speed” input field and press the enter key.
(2) Acceleration/deceleration time constant setting ( b) )
Enter a new value into the “Accel/decel time” input field and press the enter key.
(3) Servo motor start ( c), d) )
Hold down the “Forward” button to rotate the servo motor in the CCW rotation direction.
Hold down the “Reverse” button to rotate the servo motor in the CW rotation direction.
(4) Servo motor stop ( e) )
Release the “Forward” or “Reverse” button to stop the rotation of the servo motor.
(5) Jog operation window closing ( f) )
Click the “Close” button to cancel the jog operation mode and close the window.
6 - 15
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.2 Positioning operation
POINT
The servo motor will not operate if the forced stop (EMG), forward rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device setting to assign them as external input signals and turn off across these signals and SG. (Refer to section 6.6.)
When an alarm occurs, the positioning operation is automatically canceled.
Click the “Forward” or “Reverse” button to start and rotate the servo motor by the preset moving distance and then stop.
Click “Test” on the menu bar and click “Positioning” on the menu.
When the above choices are made, the following window appears. a) b) c) d) e) f) g)
6 - 16
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(1) Servo motor speed setting ( a) )
Enter a new value into the “Motor speed” input field and press the enter key.
(2) Acceleration/deceleration time constant setting ( b) )
Enter a new value into the “Accel/decel time” input field and press the enter key.
(3) Moving distance setting ( c) )
Enter a new value into the “Move distance” input field and press the enter key.
(4) Servo motor start ( d), e) )
Click the “Forward” button to rotate the servo motor in the forward rotation direction.
Click the “Reverse” button to rotate the servo motor in the reverse rotation direction.
(5) Temporary stop of servo motor ( f) )
Click the “Pause” button to stop the servo motor temporarily.
(6) Positioning operation window closing ( g) )
Click the “Close” button to cancel the positioning operation mode and close the window.
6 - 17
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.3 Motor-less operation
POINT
When this operation is used in an absolute position detection system, the home position cannot be restored properly.
Without a servo motor being connected, the output signals are provided and the servo amplifier display shows the status as if a servo motor is actually running in response to the external I/O signals.
The sequence of the host programmable controller can be checked without connection of a servo motor.
Click “Test” on the menu bar and click “Operation w/o Motor” on the menu.
When the above choices are made, the following window appears. a) b)
(1) Execution of motor-less operation ( a) )
Click “Start” to perform motor-less operation.
(2) Termination of motor-less operation ( b) )
Click “Close” to close the window.
(3) Cancel of motor-less operation
To cancel motor-less operation, switch off the power of the servo amplifier.
6 - 18
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.4 Output signal (DO) forced output
Each servo amplifier output signal is forcibly switched on/off independently of the output condition of the output signal.
Click “Test” on the menu bar and click “Forced Output” on the menu.
When the above choices are made, the following window appears.
Since this window shows the precautions for use of the MR-J2S-B, click the "OK" button.
Clicking it displays the next window. a) b) c)
(1) Signal ON/OFF setting ( a), b) )
Choose the signal name or pin number and click the “ON” or “OFF” button to write the corresponding signal status to the servo amplifier.
(2) DO forced output window closing ( c) )
Click the “Close” button to cancel the DO forced output mode and close the window.
6 - 19
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.5 Program test operation
POINT
The servo motor will not operate if the forced stop (EMG), forward rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device setting to assign them as external input signals and turn off across these signals and SG. (Refer to section 6.6.)
The program of the MR-J2S-CL can be test-operated.
(1) How to open the setting screen
Click "Test" on the menu bar and click "Program-Test" in the menu.
Clicking it displays the next window.
Then, click the "OK" button to display the next window.
6 - 20
6. MR Configurator (SERVO CONFIGURATION SOFTWARE) a) b)
The signal can be turned ON or OFF by clicking the check button before the signal symbol.
(1) Displaying the program (a))
Click the "Display" button to display the contents of the currently selected program No.
To close the window, click the "Close" button.
(2) Closing the Program Test window (b))
Click the "OK" button to close the Program Test window.
6 - 21
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.8 Alarm history
Click “Alarms” on the menu bar and click “History” on the menu.
When the above choices are made, the following window appears. a) b)
(1) Alarm history display
The most recent six alarms are displayed. The smaller numbers indicate newer alarms.
(2) Alarm history clear (a))
Click the “Clear” button to clear the alarm history stored in the servo amplifier.
(3) Closing of alarm history window (b))
Click the “Close” button to close the window.
6 - 22
7. DISPLAY AND OPERATION
7. DISPLAY AND OPERATION
7.1 Display flowchart
Use the display (5-digit, 7-segment LED) on the front panel of the servo amplifier for status display, parameter setting, etc. Set the parameters before operation, diagnose an alarm, confirm external sequences, and/or confirm the operation status. Press the "MODE" "UP" or "DOWN" button once to move to the next screen. Refer to section 7.2 and later for the description of the corresponding display mode.
To refer to or set the expansion parameters 1, expansion parameters 2 and special parameters, make them valid with parameter No.19 (parameter write disable).
Display mode transition Initial screen Function Reference
MODE button
Status display
Diagnosis
Alarm
Basic parameter
Expansion parameter 1
Expansion parameter 2
Special parameter
Servo status display.
appears at power-on.
Alarm display, external signal display, output signal (DO) forced output, test operation, software version display, VC automatic offset, motor series ID display, motor type ID display, encoder ID display
Current alarm display, alarm history display, parameter error No. display.
Display and setting of basic parameters.
Display and setting of expansion parameters 1.
Display and setting of expansion parameters 2.
Display and setting of special parameters.
Section 7.2
Section 7.3
Section 7.4
Section 7.5
7 - 1
7. DISPLAY AND OPERATION
7.2 Status display
The servo status during operation is shown on the 5-digit, 7-segment LED display. Press the "UP" or
"DOWN" button to change display data as desired. When the required data is selected, the corresponding symbol appears. Press the "SET" button to display its data. At only power-on, however, data appears after the symbol of the status display selected in parameter No. 18 has been shown for 2[s].
The servo amplifier display shows the lower five digits of 19 data items such as the motor speed.
7.2.1 Display transition
After choosing the status display mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the display as shown below.
To Bus voltage
Current position Regenerative load ratio
Effective load ratio Command position
Command remaining distance
Program No.
Step No.
Cumulative feedback pulses
UP
DOW
Servo motor speed
Droop pulses
Peak load ratio
Instantaneous torque
Within one-revolution position low
Within one-revolution position high
ABS counter
Override
Analog torque limit voltage
Load inertia moment ratio
To current position
Bus voltage
7 - 2
7. DISPLAY AND OPERATION
7.2.2 Display examples
The following table lists display examples.
Item Status
Servo amplifier display
Forward rotation at 2500r/min
Servo motor speed
Reverse rotation at 3000r/min
Reverse rotation is indicated by " ".
Load inertia moment
15.5 times
Displayed data
11252pulse
Multirevolution counter
12566pulse
Lit
Negative value is indicated by the lit decimal points in the upper four digits.
MR-DP60
7 - 3
7. DISPLAY AND OPERATION
7.2.3 Status display list
The following table lists the servo statuses that may be shown.
Status display Symbol
Current position
Command position
Command remaining distance
Program No.
Step No.
PoS
CPoS rn
Pno
Sno
Unit Description
10 STM mm
10 STM mm
The current position from the machine home position of 0 is displayed.
The command position is displayed.
10 STM mm
The command remaining distance of the currently selected program is displayed.
The program No. being executed is displayed.
The step No. being executed is displayed.
Feedback pulses from the servo motor encoder are counted
Display range
Servo amplifier display
MR-DP60
99999 to
99999
99999 to
99999
999999 to
999999
999999 to
999999
99999 to
99999
1 to 16
1 to 120
999999 to
999999
1 to 16
1 to 120
Cumulative feedback pulses
99999 to
99999
999999 to
999999
Press the "SET" button to reset the display value to zero.
The servo motor speed is displayed.
Servo motor speed
5400 to
5400
5400 to
5400
Droop pulses E pulse
CW rotation.
The number of droop pulses in the deviation counter is displayed.
" " is added to the droop pulses in the CW rotation.
The displayed number of pulses is not yet multiplied by the electronic gear value.
99999 to
99999
999999 to
999999
0 to 200 0 to 200
Analog torque limit voltage
Regenerative load ratio
0.00 to 10.00 0.00 to 10.00
0 to 100 0 to 100
Effective load ratio
The continuous effective load torque is displayed.
0 to 300 0 to 300
Peak load ratio b % relative to the rated torque of 100%.
The maximum torque generated during acceleration/deceleration, etc.
The highest value in the past 15 seconds is displayed relative to the rated torque of 100%.
Torque that occurred instantaneously is displayed.
0 to 300 0 to 300
Instantaneous torque
0 to 400 0 to 400 time relative to the rate torque of 100%.
Position within one revolution is displayed in encoder pulses. Within onerevolution position low
Within onerevolution position high
ABS counter
Cy2
LS
100 pulse rev number of pulses.
The value is incremented in the CCW direction of rotation.
The within one-revolution position is displayed in 100 pulse increments of the encoder.
The value returns to "0" when it exceeds the maximum number of pulses.
The value is incremented in the CCW direction of rotation.
Travel value from the home position in the absolute position detection systems is displayed in terms of the absolute position detectors counter value.
0 to 99999
0 to 1310
32768 to
32767
(Note)
0 to 131071
32768 to
32767
Load inertia moment ratio
0.0 to 300.0 0.0 to 300.0
Bus voltage Pn V
The voltage (across P-N) of the main circuit converter is displayed.
0 to 450
Note. The MR-DP60 can display the status without dividing it into the high and low orders. The unit is [pulse].
7 - 4
0 to 450
7. DISPLAY AND OPERATION
7.3 Diagnosis mode
7.3.1 Display transition
After choosing the diagnosis mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the display as shown below.
To Encoder ID
Sequence Software version Low
Software version High External I/O signal display
Output signal (DO) forced output
Test operation mode
Jog feed UP
DOWN
Test operation mode
Positioning operation
Test operation mode
Motorless operation
Test operation mode
Machine analyzer operation
To Sequence
For manufacturer setting
Motor series ID
Motor type ID
Encoder ID
7 - 5
7. DISPLAY AND OPERATION
7.3.2 Diagnosis mode list
Name Display Description
Not ready.
Indicates that the servo amplifier is being initialized or an alarm has occurred.
Sequence
Ready.
Indicates that the servo was switched on after completion of initialization and the servo amplifier is ready to operate.
External I/O signal display
Output signal (DO) forced output
Refer to section 7.6.
Indicates the ON-OFF states of the external I/O signals.
The upper segments correspond to the input signals and the lower segments to the output signals.
Lit: ON
Extinguished: OFF
The I/O signals can be changed using the MR Configurator (servo configuration software).
The digital output signal can be forced on/off. (Refer to section
7.7)
Test operation mode
Jog feed
Positioning operation
Motorless operation
Machine analyzer operation
Jog operation can be performed when there is no command from the external command device. (Refer to section 7.8.2)
The MR Configurator (servo configuration software MRZJW3-
SETUP151E) is required for positioning operation. This operation cannot be performed from the operation section of the servo amplifier.
Positioning operation can be performed once when there is no command from the external command device.
Without connection of the servo motor, the servo amplifier provides output signals and displays the status as if the servo motor is running actually in response to the external input signal. (Refer to section 7.8.4)
Merely connecting the servo amplifier allows the resonance point of the mechanical system to be measured.
The MR Configurator (servo configuration software MRZJW3-
SETUP151E or later) is required for machine analyzer operation.
Indicates the version of the software.
Software version Low
Indicates the system number of the software.
Software version High
For manufacturer setting
Manufacturer setting screen. Do not perform operation on this screen.
7 - 6
7. DISPLAY AND OPERATION
Encoder
Name Display
Motor series
Motor type
Description
Press the "SET" button to show the motor series ID of the servo motor currently connected.
For indication details, refer to the optional MELSERVO Servo
Motor Instruction Manual.
Press the "SET" button to show the motor type ID of the servo motor currently connected.
For indication details, refer to the optional MELSERVO Servo
Motor Instruction Manual.
Press the "SET" button to show the encoder ID of the servo motor currently connected.
For indication details, refer to the optional MELSERVO Servo
Motor Instruction Manual.
7 - 7
7. DISPLAY AND OPERATION
7.4 Alarm mode
The current alarm, past alarm history and parameter error are displayed. The lower 2 digits on the display indicate the alarm number that has occurred or the parameter number in error. Display examples are shown below.
7.4.1 Display transition
After choosing the alarm mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the display as shown below.
To Parameter error No.
Current alarm
Alarm history
(Fourth alarm in past)
Alarm history
(Last alarm)
Alarm history
(Second alarm in past)
UP
DOWN
Alarm history
(Third alarm in past)
Alarm history
(Fifth alarm in past)
Alarm history
(Sixth alarm in past)
Parameter error No.
To Current alarm
7 - 8
7. DISPLAY AND OPERATION
7.4.2 Alarm mode list
Name Display Description
Indicates no occurrence of an alarm.
Current alarm
Alarm history
Indicates the occurrence of overvoltage (AL.33).
Flickers at occurrence of the alarm.
Indicates that the last alarm is overload 1 (AL.50).
Indicates that the second alarm in the past is overvoltage
(AL.33).
Indicates that the third alarm in the past is undervoltage
(AL.10).
Indicates that the fourth alarm in the past is overspeed (AL.31).
Parameter error No.
Indicates that there is no fifth alarm in the past.
Indicates that there is no sixth alarm in the past.
Indicates no occurrence of parameter error.
Indicates that the data of parameter No. 1 is faulty.
7 - 9
7. DISPLAY AND OPERATION
Functions at occurrence of an alarm
(1) Any mode screen displays the current alarm.
(2) Even during alarm occurrence, the other screen can be viewed by pressing the button in the operation section. At this time, the decimal point in the fourth digit remains flickering.
(3) For any alarm, remove its cause and clear it in any of the following methods (for clearable alarms, refer to section 11.2.1).
(a) Switch power OFF, then ON.
(b) Press the "SET" button on the current alarm screen.
(c) Turn on the reset (RES) signal.
(4) Use parameter No. 16 to clear the alarm history.
(5) Pressing "SET" button on the alarm history display screen for 2s or longer shows the following detailed information display screen. Note that this is provided for maintenance by the manufacturer.
(6) Press "UP" or "DOWN" button to move to the next history.
7 - 10
7. DISPLAY AND OPERATION
7.5 Parameter mode
POINT
To use the expansion parameters, change the parameter No. 19 (parameter write inhibit) value. (Refer to section 5.1.1)
7.5.1 Parameter mode transition
After choosing the corresponding parameter mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the display as shown below.
To status display mode
MODE
Basic parameters Expansion parameters 1 Expansion parameters 2 Special parameters
Parameter No. 0 Parameter No. 20 Parameter No. 54 Parameter No. 78
Parameter No. 1 Parameter No. 21 Parameter No. 55 Parameter No. 79
UP
DOWN
Parameter No. 18 Parameter No. 52 Parameter No. 76 Parameter No. 89
Parameter No. 19 Parameter No. 53 Parameter No. 77 Parameter No. 90
The parameter whose abbreviation is marked * is made valid by switching power off, then on after changing its setting. (Refer to section 5.1.2)
7 - 11
7. DISPLAY AND OPERATION
7.5.2 Operation example
(1) Parameter of 5 or less digits
The following example shows the operation procedure performed after power-on to change the home position setting method (Parameter No.8) into the data setting type. Press the "MODE" button to switch to the basic parameter screen.
Press MODE four times. Select parameter No.8 with UP or DOWN.
The parameter number is displayed.
Press UP or DOWN to change the number.
Press SET twice.
The set value of the specified parameter number flickers.
Press UP twice.
During flickering, the set value can be changed.
Use UP or DOWN .
( 2: Data setting type)
Press SET to enter.
To shift to the next parameter, press the "UP" or "DOWN" button.
When changing the parameter No.8 (home position return type) setting, change its set value, then switch power off once and switch it on again to make the new value valid.
7 - 12
7. DISPLAY AND OPERATION
(2) Signed 5-digit parameter
The following example gives the operation procedure to change the home position return position data
(parameter No. 42) to "-12345".
(Note)
Press MODE three times. Press UP or DOWN to choose parameter No. 42.
Press SET once.
Setting of upper 1 digits
Press MODE once.
Setting of lower 4 digits
Press SET once.
The screen flickers.
Press UP or DOWN to change the setting.
Press SET once.
Enter the setting.
Press MODE once.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
When changing the parameter No. 42 setting, change its set value, then switch power off once and switch it on again to make the new value valid.
7 - 13
7. DISPLAY AND OPERATION
7.6 External I/O signal display
The ON/OFF states of the digital I/O signals connected to the servo amplifier can be confirmed.
(1) Operation
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
Press UP once.
External I/O signal display screen
(2) Display definition
The segments of the seven-segment LEDs correspond to the pins.
CN1A
19
CN1B
15
CN1B
9
CN1B
8
CN1B
7
CN1A
8
CN1B
14
CN1B
5
CN1B
17
CN1B
16
Input signals
Always lit
Output signals
CN1A
14
CN1B
18
CN1B
4
CN1B
6
CN1B
19
CN1A
18
CN1A
19
Lit: ON
Extinguished: OFF
The 7-segment LED shown above indicates ON/OFF.
Each segment at top indicates the input signal and each segment at bottom indicates the output signal. The signals corresponding to the pins in the respective control modes are indicated below.
7 - 14
7. DISPLAY AND OPERATION
7.7 Output signal (DO) forced output
POINT
When the servo system is used in a vertical lift application, turning on the electromagnetic brake interlock (MBR) after assigning it to pin CN1B-19 will release the electromagnetic brake, causing a drop. Take drop preventive measures on the machine side.
The output signal can be forced on/off independently of the servo status. This function is used for output signal wiring check, etc. This operation must be performed in the servo off state (SON off).
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
Press UP twice.
CN1A
14
CN1B
18
CN1B
4
CN1B
6
CN1B
19
CN1A
18
CN1A
19
Press SET for more than 2 seconds.
Switch on/off the signal below the lit segment.
Always lit
Indicates the ON/OFF of the output signal. The correspondences between segments and signals are as in the output signals of the external I/O signal display.
(Lit: ON, extinguished: OFF)
Press MODE once.
The segment above CN1A-pin 18 is lit.
Press UP once.
CN1A-pin 18 is switched on.
(CN1A-pin 18-SG conduct.)
Press DOWN once.
CN1A-pin 18 is switched off.
Press SET for more than 2 seconds.
7 - 15
7. DISPLAY AND OPERATION
7.8 Test operation mode
CAUTION
The test operation mode is designed to confirm servo operation and not to confirm machine operation. In this mode, do not use the servo motor with the machine.
Always use the servo motor alone.
If any operational fault has occurred, stop operation using the forced stop (EMG) .
POINT
The test operation mode cannot be used in the absolute position detection system. Use it after choosing "Incremental system" in parameter No. 1.
The MR Configurator (servo configuration software) is required to perform positioning operation.
Test operation cannot be performed if the servo-on (SON) signal is not turned OFF.
7.8.1 Mode change
Call the display screen shown after power-on. Choose jog operation/motor-less operation in the following procedure. Using the "MODE" button, show the diagnostic screen.
Press UP three times.
Press SET for more than 2s.
When this screen appears, jog feed can be performed.
Flickers in the test operation mode.
Press UP five times.
Press SET for more than 2s.
When this screen is displayed, motor-less operation can be performed.
7 - 16
7. DISPLAY AND OPERATION
7.8.2 Jog operation
Jog operation can be performed when there is no command from the external command device.
(1) Operation
Connect EMG-SG, LSP-SG and LSN-SG to start jog operation and connect VDD-COM to use the internal power supply.
Hold down the "UP" or "DOWN" button to run the servo motor. Release it to stop. When using the MR
Configurator (servo configuration software), you can change the operation conditions. The initial conditions and setting ranges for operation are listed below.
Speed [r/min]
Acceleration/deceleration time constant [ms]
200
1000
0 to instantaneous permissible speed
0 to 50000
How to use the buttons is explained below.
Button Description
"UP"
Press to start CCW rotation.
Release to stop.
"DOWN"
Press to start CW rotation.
Release to stop.
If the communication cable is disconnected during jog operation performed by using the MR
Configurator (servo configuration software), the servo motor will be decelerated to a stop.
(2) Status display
You can confirm the servo status during jog operation.
Pressing the "MODE" button in the jog operation-ready status calls the status display screen. With this screen being shown, perform jog operation with the "UP" or "DOWN" button. Every time you press the "MODE" button, the next status display screen appears, and on completion of a screen cycle, pressing that button returns to the jog operation-ready status screen. For full information of the status display, refer to section 7.2. In the test operation mode, you cannot use the "UP" and "DOWN" buttons to change the status display screen from one to another.
(3) Termination of jog operation
To end the jog operation, switch power off once or press the "MODE" button to switch to the next screen and then hold down the "SET" button for 2 or more seconds.
7 - 17
7. DISPLAY AND OPERATION
7.8.3 Positioning operation
POINT
The MR Configurator (servo configuration software) is required to perform positioning operation.
Positioning operation can be performed once when there is no command from the external command device.
(1) Operation
Connect EMG-SG, LSP-SG and LSN-SG to start positioning operation and connect VDD-COM to use the internal power supply.
Pressing the "Forward" or "Reverse" button on the MR Configurator (servo configuration software) starts the servo motor, which will then stop after moving the preset travel distance. You can change the operation conditions on the MR Configurator (servo configuration software). The initial conditions and setting ranges for operation are listed below.
Item Initial setting Setting range
Travel distance [pulse]
Speed [r/min]
Acceleration/deceleration time constant [ms]
10000
200
1000
0 to 9999999
0 to instantaneous permissible speed
0 to 50000
How to use the keys is explained below.
Key Description
"Forward"
"Reverse"
Press to start positioning operation CCW.
Press to start positioning operation CW.
"Pause"
Press during operation to make a temporary stop. Pressing the
"Pause" button again erases the remaining distance.
To resume operation, press the button that was pressed to start the operation.
If the communication cable is disconnected during positioning operation, the servo motor will come to a sudden stop.
(2) Status display
You can monitor the status display even during positioning operation.
7 - 18
7. DISPLAY AND OPERATION
7.8.4 Motor-less operation
Without connecting the servo motor, you can provide output signals or monitor the status display as if the servo motor is running in response to external input signals. This operation can be used to check the sequence of a host programmable controller or the like.
(1) Operation
After turning off the signal across SON-SG, choose motor-less operation. After that, perform external operation as in ordinary operation.
(2) Status display
You can confirm the servo status during motor-less operation.
Pressing the "MODE" button in the motor-less operation-ready status calls the status display screen.
With this screen being shown, perform motor-less operation. Every time you press the "MODE" button, the next status display screen appears, and on completion of a screen cycle, pressing that button returns to the motor-less operation-ready status screen. For full information of the status display, refer to section 7.2. In the test operation mode, you cannot use the "UP" and "DOWN" buttons to change the status display screen from one to another.
(3) Termination of motor-less operation
To terminate the motor-less operation, switch power off.
7 - 19
7. DISPLAY AND OPERATION
MEMO
7 - 20
8. GENERAL GAIN ADJUSTMENT
8. GENERAL GAIN ADJUSTMENT
8.1 Different adjustment methods
8.1.1 Adjustment on a single servo amplifier
The gain adjustment in this section can be made on a single servo amplifier. For gain adjustment, first execute auto tuning mode 1. If you are not satisfied with the results, execute auto tuning mode 2, manual mode 1 and manual mode 2 in this order.
(1) Gain adjustment mode explanation
Gain adjustment mode
Parameter No. 3 setting
Estimation of load inertia moment ratio
Automatically set parameters
Manually set parameters
Auto tuning mode 1
(initial value)
Auto tuning mode 2 020
PG1 (parameter No. 7)
GD2 (parameter No. 34)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG1 (parameter No. 7)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
VG2 (parameter No. 37)
VIC (parameter No. 38)
Response level setting of parameter No. 3
GD2 (parameter No. 34)
Response level setting of parameter No. 3
Manual mode 1
Manual mode 2
030
040
Fixed to parameter No.
34 value
PG2 (parameter No. 35)
VG1 (parameter No. 36)
PG1 (parameter No. 7)
GD2 (parameter No. 34)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG1 (parameter No. 7)
GD2 (parameter No. 34)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
VG2 (parameter No. 37)
VIC (parameter No. 38)
Interpolation mode
GD2 (parameter No. 34)
PG2 (parameter No. 35)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG1 (parameter No. 7)
VG1 (parameter No. 36)
8 - 1
8. GENERAL GAIN ADJUSTMENT
(2) Adjustment sequence and mode usage
START
Yes
Interpolation
made for 2 or more axes?
No
Auto tuning mode 1
Operation
OK?
No
Auto tuning mode 2
Operation
Yes
No
Interpolation mode
Operation
OK?
Yes
Usage
Used when you want to match the position gain
(PG1) between 2 or more axes. Normally not used for other purposes.
Allows adjustment by merely changing the response level setting.
First use this mode to make adjustment.
Used when the conditions of auto tuning mode 1 are not met and the load inertia moment ratio could not be estimated properly, for example.
Yes
OK?
No
Manual mode 1
Operation
This mode permits adjustment easily with three gains if you were not satisfied with auto tuning results.
Yes
OK?
No
Manual mode 2
You can adjust all gains manually when you want to do fast settling or the like.
END
8.1.2 Adjustment using MR Configurator (servo configuration software)
This section gives the functions and adjustment that may be performed by using the servo amplifier with the MR Configurator (servo configuration software) which operates on a personal computer.
Function Description
Machine analyzer
Gain search
With the machine and servo motor coupled, the characteristic of the mechanical system can be measured by giving a random vibration command from the personal computer to the servo and measuring the machine response.
Executing gain search under to-and-fro positioning command measures settling characteristic while simultaneously changing gains, and automatically searches for gains which make settling time shortest.
Adjustment
You can grasp the machine resonance frequency and determine the notch frequency of the machine resonance suppression filter.
You can automatically set the optimum gains in response to the machine characteristic. This simple adjustment is suitable for a machine which has large machine resonance and does not require much settling time.
You can automatically set gains which make positioning settling time shortest.
Machine simulation
Response at positioning settling of a machine can be simulated from machine analyzer results on personal computer.
You can optimize gain adjustment and command pattern on personal computer.
8 - 2
8. GENERAL GAIN ADJUSTMENT
8.2 Auto tuning
8.2.1 Auto tuning mode
The servo amplifier has a real-time auto tuning function which estimates the machine characteristic (load inertia moment ratio) in real time and automatically sets the optimum gains according to that value. This function permits ease of gain adjustment of the servo amplifier.
(1) Auto tuning mode 1
The servo amplifier is factory-set to the auto tuning mode 1.
In this mode, the load inertia moment ratio of a machine is always estimated to set the optimum gains automatically.
The following parameters are automatically adjusted in the auto tuning mode 1.
Parameter No.
7
34
35
36
37
Abbreviation
PG1
GD2
PG2
VG1
VG2
Name
Position control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 1
Speed control gain 2
POINT
The auto tuning mode 1 may not be performed properly if the following conditions are not satisfied.
Time to reach 2000r/min is the acceleration/deceleration time constant of 5s or less.
Speed is 150r/min or higher.
The ratio of load inertia moment to motor inertia moment is not more than
100 times.
The acceleration/deceleration torque is 10% or more of the rated torque.
Under operating conditions which will impose sudden disturbance torque during acceleration/deceleration or on a machine which is extremely loose, auto tuning may not function properly, either. In such cases, use the auto tuning mode 2 or manual mode 1,2 to make gain adjustment.
(2) Auto tuning mode 2
Use the auto tuning mode 2 when proper gain adjustment cannot be made by auto tuning mode 1.
Since the load inertia moment ratio is not estimated in this mode, set the value of a correct load inertia moment ratio (parameter No. 34).
The following parameters are automatically adjusted in the auto tuning mode 2.
Parameter No.
7
35
36
37
Abbreviation
PG1
PG2
VG1
VG2
Position control gain 1
Position control gain 2
Speed control gain 1
Speed control gain 2
Name
8 - 3
8. GENERAL GAIN ADJUSTMENT
8.2.2 Auto tuning mode operation
The block diagram of real-time auto tuning is shown below.
Command
Automatic setting
Control gains
PG1,VG1
PG2,VG2,VIC
Servo motor
Load inertia moment
Encoder
Current control
Current feedback
Gain table
Set 0 or 1 to turn on.
Real-time auto tuning section
Switch
Load inertia moment ratio estimation section
Position/speed feedback
Speed feedback
Parameter No. 3
Parameter No. 34
Load inertia moment ratio estimation value
First digit
Third digit
Response level setting
Auto tuning selection
When a servo motor is accelerated/decelerated, the load inertia moment ratio estimation section always estimates the load inertia moment ratio from the current and speed of the servo motor. The results of estimation are written to parameter No. 34 (load inertia moment ratio). These results can be confirmed on the status display screen of the servo amplifier display section.
If the value of the load inertia moment ratio is already known or if estimation cannot be made properly, chose the "auto tuning mode 2" (parameter No.3: 2 ) to stop the estimation of the load inertia moment ratio (Switch in above diagram turned off), and set the load inertia moment ratio (parameter No.
34) manually.
From the preset load inertia moment ratio (parameter No. 34) value and response level (The first digit of parameter No. 3), the optimum control gains are automatically set on the basis of the internal gain tale.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 60 minutes since poweron. At power-on, auto tuning is performed with the value of each control gain saved in the EEP-ROM being used as an initial value.
POINT
If sudden disturbance torque is imposed during operation, the estimation of the inertia moment ratio may malfunction temporarily. In such a case, choose the
"auto tuning mode 2" (parameter No. 3: 2 ) and set the correct load inertia moment ratio in parameter No. 34.
When any of the auto tuning mode 1, auto tuning mode 2 and manual mode 1 settings is changed to the manual mode 2 setting, the current control gains and load inertia moment ratio estimation value are saved in the EEP-ROM.
8 - 4
8. GENERAL GAIN ADJUSTMENT
8.2.3 Adjustment procedure by auto tuning
Since auto tuning is made valid before shipment from the factory, simply running the servo motor automatically sets the optimum gains that match the machine. Merely changing the response level setting value as required completes the adjustment. The adjustment procedure is as follows.
Auto tuning adjustment
Acceleration/deceleration repeated
Yes
Load inertia moment ratio estimation value stable?
No
Auto tuning conditions not satisfied.
(Estimation of load inertia moment ratio is difficult)
No
Yes
Choose the auto tuning mode 2
(parameter No.3 : 2 ) and set the load inertia moment ratio
(parameter No.34) manually.
Adjust response level setting so that desired response is achieved on vibration-free level.
Acceleration/deceleration repeated
Requested performance satisfied?
Yes
END
No
To manual mode
8 - 5
8. GENERAL GAIN ADJUSTMENT
8.2.4 Response level setting in auto tuning mode
Set the response (The first digit of parameter No.3) of the whole servo system. As the response level setting is increased, the track ability and settling time for a command decreases, but a too high response level will generate vibration. Hence, make setting until desired response is obtained within the vibrationfree range.
If the response level setting cannot be increased up to the desired response because of machine resonance beyond 100Hz, adaptive vibration suppression control (parameter No. 63) or machine resonance suppression filter (parameter No. 61 62) may be used to suppress machine resonance. Suppressing machine resonance may allow the response level setting to increase. Refer to section 9.3 for adaptive vibration suppression control and section 9.2 for machine resonance suppression filter.
Parameter No. 3
Response level setting
Machine rigidity
Response level setting
Auto tuning selection
Machine characteristic
Machine resonance
Guideline of corresponding machine frequency guideline
4
C
Large conveyor
30Hz
160Hz
Arm robot
Precision working machine
General machine tool conveyor
Inserter
Mounter
Bonder
8 - 6
8. GENERAL GAIN ADJUSTMENT
8.3 Manual mode 1 (simple manual adjustment)
If you are not satisfied with the adjustment of auto tuning, you can make simple manual adjustment with three parameters.
8.3.1 Operation of manual mode 1
In this mode, setting the three gains of position control gain 1 (PG1), speed control gain 2 (VG2) and speed integral compensation (VIC) automatically sets the other gains to the optimum values according to these gains.
User setting
PG1
VG2
VIC
GD2
Automatic setting
PG2
VG1
Therefore, you can adjust the model adaptive control system in the same image as the general PI control system (position gain, speed gain, speed integral time constant). Here, the position gain corresponds to
PG1, the speed gain to VG2 and the speed integral time constant to VIC. When making gain adjustment in this mode, set the load inertia moment ratio (parameter No. 34) correctly.
8.3.2 Adjustment by manual mode 1
POINT
If machine resonance occurs, adaptive vibration suppression control
(parameter No. 63) or machine resonance suppression filter (parameter No.
61 62) may be used to suppress machine resonance. (Refer to section 9.2, 9.3.)
(1) For speed control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No. Abbreviation
7
34
37
PG1
GD2
VG2
Name
Position control gain 1
Ratio of load inertia moment to servo motor inertia moment
Speed control gain 2
(b) Adjustment procedure
Step Operation
1
2
3
4
5
Set an estimated value to the ratio of load inertia moment to servo motor inertia moment (parameter No. 34).
Increase the speed control gain 2 (parameter No. 37) within the vibration- and unusual noise-free range, and return slightly if vibration takes place.
Decrease the speed integral compensation (parameter No. 38) within the vibration-free range, and return slightly if vibration takes place.
If the gains cannot be increased due to mechanical system resonance or the like and the desired response cannot be achieved, response may be increased by suppressing resonance with adaptive vibration suppression control or machine resonance suppression filter and then executing steps 2 and 3.
While checking the settling characteristic and rotational status, fineadjust each gain.
Description
Increase the speed control gain.
Decrease the time constant of the speed integral compensation.
Suppression of machine resonance.
Refer to section 9.2, 9.3.
Fine adjustment
8 - 7
8. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Speed control gain 2 (parameter No. 37)
This parameter determines the response level of the speed control loop. Increasing this value enhances response but a too high value will make the mechanical system liable to vibrate. The actual response frequency of the speed loop is as indicated in the following expression.
Speed loop response frequency(Hz)
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment) 2
2) Speed integral compensation (VIC: parameter No. 38)
To eliminate stationary deviation against a command, the speed control loop is under proportional integral control. For the speed integral compensation, set the time constant of this integral control. Increasing the setting lowers the response level. However, if the load inertia moment ratio is large or the mechanical system has any vibratory element, the mechanical system is liable to vibrate unless the setting is increased to some degree. The guideline is as indicated in the following expression.
Speed integral compensation setting(ms) Speed control gain 2 setting/
2000 to 3000
(1 ratio of load inertia moment to
servo motor inertia moment setting 0.1)
(2) For position control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No. Abbreviation
7
34
37
PG1
GD2
VG2
Name
Position control gain 1
Ratio of load inertia moment to servo motor inertia moment
Speed control gain 2
(b) Adjustment procedure
Step Operation
1
2
3
4
Set an estimated value to the ratio of load inertia moment to servo motor inertia moment (parameter No. 34).
Set a slightly smaller value to the position control gain 1 (parameter
No. 7).
Increase the speed control gain 2 (parameter No. 37) within the vibration- and unusual noise-free range, and return slightly if vibration takes place.
Decrease the speed integral compensation (parameter No. 38) within the vibration-free range, and return slightly if vibration takes place.
Description
Increase the speed control gain.
Decrease the time constant of the speed integral compensation.
5
6
7
Increase the position control gain 1 (parameter No. 7).
If the gains cannot be increased due to mechanical system resonance or the like and the desired response cannot be achieved, response may be increased by suppressing resonance with adaptive vibration suppression control or machine resonance suppression filter and then executing steps 3 to 5.
While checking the settling characteristic and rotational status, fineadjust each gain.
Increase the position control gain.
Suppression of machine resonance.
Refer to section 9.2, 9.3.
Fine adjustment
8 - 8
8. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Position control gain 1 (parameter No. 7)
This parameter determines the response level of the position control loop. Increasing position control gain 1 improves track ability to a position command but a too high value will make overshooting liable to occur at the time of settling.
Position control gain 1 guideline
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment)
(
1
to
1
5
)
2) Speed control gain 2 (VG2: parameter No. 37)
This parameter determines the response level of the speed control loop. Increasing this value enhances response but a too high value will make the mechanical system liable to vibrate. The actual response frequency of the speed loop is as indicated in the following expression.
Speed loop response frequency(Hz)
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment) 22
3) Speed integral compensation (parameter No. 38)
To eliminate stationary deviation against a command, the speed control loop is under proportional integral control. For the speed integral compensation, set the time constant of this integral control. Increasing the setting lowers the response level. However, if the load inertia moment ratio is large or the mechanical system has any vibratory element, the mechanical system is liable to vibrate unless the setting is increased to some degree. The guideline is as indicated in the following expression.
Speed integral compensation setting(ms)
2000 to 3000
Speed control gain 2 setting/ (1 ratio of load inertia moment to
servo motor inertia moment 2 setting 0.1)
8 - 9
8. GENERAL GAIN ADJUSTMENT
8.4 Interpolation mode
The interpolation mode is used to match the position control gains of the axes when performing the interpolation operation of servo motors of two or more axes for an X-Y table or the like. In this mode, the position control gain 2 and speed control gain 2 which determine command track ability are set manually and the other parameter for gain adjustment are set automatically.
(1) Parameter
(a) Automatically adjusted parameters
The following parameters are automatically adjusted by auto tuning.
Parameter No.
34
35
37
Abbreviation
GD2
PG2
VG2
Name
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
(b) Manually adjusted parameters
The following parameters are adjustable manually.
Parameter No.
7
36
(2) Adjustment procedure
Abbreviation
PG1
VG1
Position control gain 1
Speed control gain 1
Name
Step Operation Description
1
2
6
7
Set 15Hz (parameter No. 3: 010 ) as the machine resonance frequency of response in the auto tuning mode 1.
Select the auto tuning mode 1.
During operation, increase the response level setting (parameter No. 2), and Adjustment in auto tuning mode return the setting if vibration occurs. 1.
3
Check the values of position control gain 1 (parameter No. 7) and speed control gain 1 (parameter No. 36).
Check the upper setting limits.
4 interpolation
5
Set the position control gain 1 of all the axes to be interpolated to the same value. At that time, adjust to the setting value of the axis, which has the Set position control gain 1. smallest position control gain 1.
Using the speed control gain 1 value checked in step 3 as the guideline of the upper limit, look at the rotation status and set in speed control gain 1 the value three or more times greater than the position control gain 1 setting.
Set speed control gain 1.
Looking at the interpolation characteristic and rotation status, fine-adjust the gains and response level setting.
Fine adjustment.
(3) Adjustment description
(a) Position control gain 1 (parameter No.7)
This parameter determines the response level of the position control loop. Increasing position control gain 1 improves track ability to a position command but a too high value will make overshooting liable to occur at the time of settling. The droop pulse value is determined by the following expression.
Droop pulse value (pulse)
Rotation speed (r/min) 131,072(pulse)
Position control gain 1 setting
(b) Speed control gain 1 (parameter No. 36)
Set the response level of the speed loop of the model. Make setting using the following expression as a guideline.
Speed control gain 1 setting Position control gain 1 setting 3
8 - 10
8. GENERAL GAIN ADJUSTMENT
8.5 Differences in auto tuning between MELSERVO-J2 and MELSERVO-J2-Super
8.5.1 Response level setting
To meet higher response demands, the MELSERVO-J2-Super series has been changed in response level setting range from the MELSERVO-J2 series. The following table lists comparison of the response level setting.
Parameter No. 3
Response level setting
MELSERVO-J2 series
Response level setting Machine resonance frequency
MELSERVO-J2-Super series
Response level setting Machine resonance frequency guideline
1 15Hz
1 20Hz 2 20Hz
3 25Hz
4 30Hz
5 35Hz
2 40Hz 6 45Hz
7 55Hz
3 60Hz 8
4 80Hz 9
70Hz
85Hz
5 100Hz A 105Hz
B 130Hz
C 160Hz
D 200Hz
E 240Hz
F 300Hz
Note that because of a slight difference in gain adjustment pattern, response may not be the same if the resonance frequency is set to the same value.
8.5.2 Auto tuning selection
The MELSERVO-J2-Super series has an addition of the load inertia moment ratio fixing mode. It also has the addition of the manual mode 1 which permits manual adjustment with three parameters.
Parameter No. 3
Auto tuning selection
Gain adjustment mode
Interpolation mode
Auto tuning mode 1
Auto tuning
Auto tuning invalid
Auto tuning mode 2
Manual mode 1
Manual mode 2
Auto tuning selection
MELSERVO-J2 series MELSERVO-J2-Super series
0
1
0
1
2
2
3
4
Remarks
Position control gain 1 is fixed.
Ordinary auto tuning
Estimation of load inertia moment ratio stopped.
Response level setting valid.
Simple manual adjustment
Manual adjustment of all gains
8 - 11
8. GENERAL GAIN ADJUSTMENT
MEMO
8 - 12
9. SPECIAL ADJUSTMENT FUNCTIONS
9. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The functions given in this chapter need not be used generally. Use them if you are not satisfied with the machine status after making adjustment in the methods in chapter 8.
If a mechanical system has a natural resonance point, increasing the servo system response may cause the mechanical system to produce resonance (vibration or unusual noise) at that resonance frequency.
Using the machine resonance suppression filter and adaptive vibration suppression control functions can suppress the resonance of the mechanical system.
9.1 Function block diagram
Speed control
00
Parameter
No.61
0
Parameter
No.63
00
Parameter
No.62
Low-pass filter
0
Parameter
No.63
Current command
Servo motor
Machine resonance suppression filter 1 except
Adaptive vibration suppression control 1
00 or 2
Machine resonance suppression filter 2 except 00
1
Encoder
9.2 Machine resonance suppression filter
(1) Function
The machine resonance suppression filter is a filter function (notch filter) which decreases the gain of the specific frequency to suppress the resonance of the mechanical system. You can set the gain decreasing frequency (notch frequency) and gain decreasing depth.
Machine resonance point
Mechanical system response
Frequency
Notch depth
Notch frequency
Frequency
9 - 1
9. SPECIAL ADJUSTMENT FUNCTIONS
You can use the machine resonance suppression filter 1 (parameter No. 61) and machine resonance suppression filter 2 (parameter No. 62) to suppress the vibration of two resonance frequencies. Note that if adaptive vibration suppression control is made valid, the machine resonance suppression filter
1 (parameter No. 61) is made invalid.
Machine resonance point
Mechanical system response
Frequency
Notch depth
Frequency
Parameter No. 61 Parameter No. 62
POINT
The machine resonance suppression filter is a delay factor for the servo system. Hence, vibration may increase if you set a wrong resonance frequency or a too deep notch.
(2) Parameters
(a) Machine resonance suppression filter 1 (parameter No. 61)
Set the notch frequency and notch depth of the machine resonance suppression filter 1 (parameter
No. 61)
When you have made adaptive vibration suppression control selection (parameter No. 63) "valid" or
"held", make the machine resonance suppression filter 1 invalid (parameter No. 61: 0000).
Parameter No. 61
0
Notch frequency
Setting value
04
05
06
07
00
01
02
03
Invalid
4500
2250
1500
1125
900
750
642.9
Frequency
Setting value
Frequency
0C
0D
0E
0F
08
09
0A
0B
562.5
500
450
409.1
375
346.2
321.4
300
Setting value
Frequency
14
15
16
17
10
11
12
13
281.3
264.7
250
236.8
225
214.3
204.5
195.7
Setting value
1C
1D
1E
1F
18
19
1A
1B
Frequency
187.5
180
173.1
166.7
160.1
155.2
150
145.2
Notch depth
Setting value
0
1
2
3
Depth (Gain)
Deep ( 40dB)
( 14dB)
( 8dB)
Shallow( 4dB)
9 - 2
9. SPECIAL ADJUSTMENT FUNCTIONS
POINT
If the frequency of machine resonance is unknown, decrease the notch frequency from higher to lower ones in order. The optimum notch frequency is set at the point where vibration is minimal.
A deeper notch has a higher effect on machine resonance suppression but increases a phase delay and may increase vibration.
The machine characteristic can be grasped beforehand by the machine analyzer on the MR Configurator (servo configuration software). This allows the required notch frequency and depth to be determined.
Resonance may occur if parameter No. 61 62 is used to select a close notch frequency and set a deep notch.
(b) Machine resonance suppression filter 2 (parameter No. 62)
The setting method of machine resonance suppression filter 2 (parameter No. 62) is the same as that of machine resonance suppression filter 1 (parameter No. 61). However, the machine resonance suppression filter 2 can be set independently of whether adaptive vibration suppression control is valid or invalid.
9.3 Adaptive vibration suppression control
(1) Function
Adaptive vibration suppression control is a function in which the servo amplifier detects machine resonance and sets the filter characteristics automatically to suppress mechanical system vibration.
Since the filter characteristics (frequency, depth) are set automatically, you need not be conscious of the resonance frequency of a mechanical system. Also, while adaptive vibration suppression control is valid, the servo amplifier always detects machine resonance, and if the resonance frequency changes, it changes the filter characteristics in response to that frequency.
Machine resonance point Machine resonance point
Mechanical system response
Mechanical system response
Frequency Frequency
Notch depth
Notch depth
Notch frequency
Frequency
Notch frequency
Frequency
When machine resonance is large and frequency is low When machine resonance is small and frequency is high
POINT
The machine resonance frequency which adaptive vibration suppression control can respond to is about 150 to 500Hz. Adaptive vibration suppression control has no effect on the resonance frequency outside this range. Use the machine resonance suppression filter for the machine resonance of such frequency.
Adaptive vibration suppression control may provide no effect on a mechanical system which has complex resonance characteristics or which has too large resonance.
Under operating conditions in which sudden disturbance torque is imposed during operation, the detection of the resonance frequency may malfunction temporarily, causing machine vibration. In such a case, set adaptive vibration suppression control to be "held" (parameter No. 63: 2 ) to fix the characteristics of the adaptive vibration suppression control filter.
9 - 3
9. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
The operation of adaptive vibration suppression control selection (parameter No.63).
Parameter No. 63
Adaptive vibration suppression control selection
Choosing "valid" or "held" in adaptive vibration suppression control selection makes the machine resonance suppression filter 1 (parameter No. 61) invalid.
0: Invalid
1: Valid
Machine resonance frequency is always detected to generate the filter in response to resonance, suppressing machine vibration.
2: Held
Filter characteristics generated so far is held, and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
Set the sensitivity of detecting machine resonance.
0: Normal
1: Large sensitivity
POINT
Adaptive vibration suppression control is factory-set to be invalid
(parameter No. 63: 0000).
The filter characteristics generated are saved in the EEP-ROM every 60 minutes since power-on. At next power-on, vibration suppression control is performed with this data saved in the EEP-ROM being used as an initial value.
Setting the adaptive vibration suppression control sensitivity can change the sensitivity of detecting machine resonance. Setting of "large sensitivity" detects smaller machine resonance and generates a filter to suppress machine vibration. However, since a phase delay will also increase, the response of the servo system may not increase.
9 - 4
9. SPECIAL ADJUSTMENT FUNCTIONS
9.4 Low-pass filter
(1) Function
When a ballscrew or the like is used, resonance of high frequency may occur as the response of the servo system is increased. To prevent this, the low-pass filter is factory-set to be valid for a torque command. The filter frequency of this low-pass filter is automatically adjusted to the value in the following expression.
Filter frequency(Hz)
2
Speed control gain 2 setting 10
(1 Ratio of load inertia moment to servo motor inertia moment setting 0.1)
(2) Parameter
Set the operation of the low-pass filter (parameter No. 63.)
Parameter No. 63
Low-pass filter selection
0: Valid (automatic adjustment) initial value
1: Invalid
9.5 Gain changing function
POINT
In a mechanical system where rigidity is extremely high and resonance is difficult to occur, setting the low-pass filter to be "invalid" may increase the servo system response to shorten the settling time.
This function can change the gains. You can change between gains during rotation and gains during stop or can use an external signal to change gains during operation.
9.5.1 Applications
This function is used when.
(1) You want to increase the gains during servo lock but decrease the gains to reduce noise during rotation.
(2) You want to increase the gains during settling to shorten the stop settling time.
(3) You want to change the gains using an external signal to ensure stability of the servo system since the load inertia moment ratio varies greatly during a stop (e.g. a large load is mounted on a carrier).
9 - 5
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5.2 Function block diagram
The valid control gains PG2, VG2, VIC and GD2 of the actual loop are changed according to the conditions selected by gain changing selection CDP (parameter No. 68) and gain changing condition CDS (parameter
No. 69).
CDP
Parameter No.68
External signal
CDP
Command pulse frequency
Droop pulses
Model speed
Changing
Comparator
CDS
Parameter No.69
GD2
Parameter No.34
GD2
Parameter No.64
PG2
Parameter No.35
PG2 PG2B
100
VG2
Parameter No.37
VG2 VG2B
100
VIC
Parameter No.38
VIC VICB
100
Valid
GD2 value
Valid
PG2 value
Valid
VG2 value
Valid
VIC value
9 - 6
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5.3 Parameters
When using the gain changing function, always set " 4 " in parameter No.3 (auto tuning) to choose the manual mode of the gain adjustment modes. The gain changing function cannot be used in the auto tuning mode.
Parameter
No.
7
Abbreviation
Name Unit
PG1 Position control gain 1 rad/s
Description
Position and speed gains of a model used to set the response
35
68
69
70
PG2 Position control gain 2
CDP Gain changing selection
CDS Gain changing condition
CDT Gain changing time constant
0.1 times rad/s
Control parameters before changing rad/s
0.1 times
%
%
% kpps pulse r/min
Used to set the ratio of load inertia moment to servo motor inertia moment after changing.
Used to set the ratio (%) of the after-changing position control gain 2 to position control gain 2.
Used to set the ratio (%) of the after-changing speed control gain 2 to speed control gain 2.
Used to set the ratio (%) of the after-changing speed integral compensation to speed integral compensation.
Used to select the changing condition.
Used to set the changing condition values. ms
You can set the filter time constant for a gain change at changing.
9 - 7
9. SPECIAL ADJUSTMENT FUNCTIONS
(1) Parameters No. 7, 34 to 38
These parameters are the same as in ordinary manual adjustment. Gain changing allows the values of ratio of load inertia moment to servo motor inertia moment, position control gain 2, speed control gain
2 and speed integral compensation to be changed.
(2) Ratio of load inertia moment to servo motor inertia moment 2 (GD2B: parameter No. 64)
Set the ratio of load inertia moment to servo motor inertia moment after changing. If the load inertia moment ratio does not change, set it to the same value as ratio of load inertia moment to servo motor inertia moment (parameter No. 34).
(3) Position control gain 2 changing ratio (parameter No. 65), speed control gain 2 changing ratio (parameter
No. 66), speed integral compensation changing ratio (parameter No. 67)
Set the values of after-changing position control gain 2, speed control gain 2 and speed integral compensation in ratio (%). 100% setting means no gain change.
For example, at the setting of position control gain 2 100, speed control gain 2 2000, speed integral compensation 20 and position control gain 2 changing ratio 180%, speed control gain 2 changing ratio 150% and speed integral compensation changing ratio 80%, the after-changing values are as follows.
Position control gain 2 Position control gain 2 Position control gain 2 changing ratio /100 180rad/s
Speed control gain 2 Speed control gain 2 Speed control gain 2 changing ratio /100 3000rad/s
Speed integral compensation Speed integral compensation Speed integral compensation changing ratio /100 16ms
(4) Gain changing selection (parameter No. 68)
Used to set the gain changing condition. Choose the changing condition in the first digit. If you set "1" here, you can use the gain changing (CDP) external input signal for gain changing. The gain changing signal (CDP) can be assigned to the pins using the MR Configurator (servo configuration software).
Parameter No. 68
Gain changing selection
Gains are changed in accordance with the settings of
parameters No. 64 to 67 under any of the following conditions.
0: Invalid
1: Gain changing (CDP) input is ON
2: Command frequency is equal to higher than parameter No. 69 setting
3: Droop pulse value is equal to higher than parameter No. 69 setting
4: Servo motor speed is equal to higher than parameter No. 69 setting
(5) Gain changing condition (parameter No. 69)
When you selected "command frequency", "droop pulses" or "servo motor speed" in gain changing selection (parameter No.68), set the gain changing level.
The setting unit is as follows.
Gain changing condition Unit
Command frequency
Droop pulses kpps pulse
Servo motor speed r/min
(6) Gain changing time constant (parameter No. 70)
You can set the primary delay filter to each gain at gain changing. This parameter is used to suppress shock given to the machine if the gain difference is large at gain changing, for example.
9 - 8
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5.4 Gain changing operation
This operation will be described by way of setting examples.
(1) When you choose changing by external input
(a) Setting
Parameter No.
7
36
Abbreviation
PG1
VG1
Name
Position control gain 1
Speed control gain 1
35
37
PG2
VG2
Position control gain 2
Speed control gain 2
Setting
100
1000
120
3000
Unit rad/s rad/s rad/s rad/s
70 %
133 %
Gain changing selection
Gain changing time constant
250 %
0001
(Changed by ON/OFF of pin CN1A-8)
100 ms
68
70
(b) Changing operation
Gain changing
(CDP)
CDP
CDT
OFF
ON
After-changing gain
OFF
Change of each gain
Position control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
Before-changing gain
4.0
120
3000
20
CDT 100ms
100
1000
10.0 4.0
84 120
4000 3000
50 20
9 - 9
9. SPECIAL ADJUSTMENT FUNCTIONS
(2) When you choose changing by droop pulses
(a) Setting
Parameter No.
7
36
Abbreviation
PG1
VG1
Name
Position control gain 1
Speed control gain 1
35
37
38
PG2
VG2
VIC
Position control gain 2
Speed control gain 2
Speed integral compensation
Setting
100
1000
120
3000
20
Unit rad/s rad/s rad/s rad/s ms
68
69
70
(b) Changing operation
CDP
CDS
CDT
Command pulse
Gain changing selection
Gain changing condition
Gain changing time constant
70 %
133 %
250 %
0003
(Changed by droop pulses)
50
100 pulse ms
Droop pulses
Droop pulses [pulses] 0
CDS
CDS
After-changing gain
Change of each gain
Before-changing gain
CDT 100ms
Position control gain 1
Speed control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
4.0
120
3000
20
100
1000
10.0 4.0 10.0
84 120 84
4000 3000 4000
50 20 50
9 - 10
10. INSPECTION
10. INSPECTION
WARNING
Before starting maintenance and/or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Any person who is involved in inspection should be fully competent to do the work.
Otherwise, you may get an electric shock. For repair and parts replacement, contact your safes representative.
POINT
Do not test the servo amplifier with a megger (measure insulation resistance), or it may become faulty.
Do not disassemble and/or repair the equipment on customer side.
(1) Inspection
It is recommended to make the following checks periodically.
(a) Check for loose terminal block screws. Retighten any loose screws.
(b) Check the cables and the like for scratches and cracks. Perform periodic inspection according to operating conditions.
(2) Life
The following parts must be changed periodically as listed below. If any part is found faulty, it must be changed immediately even when it has not yet reached the end of its life, which depends on the operating method and environmental conditions. For parts replacement, please contact your sales representative.
Part name Life guideline
Smoothing capacitor
Servo amplifier
Relay
Cooling fan
Absolute position battery
10 years
Number of power-on and number of forced stop times : 100,000 times
10,000 to 30,000hours (2 to 3 years)
Refer to section 4.5
(a) Smoothing capacitor
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly depends on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of continuous operation in normal air-conditioned environment.
(b) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of their life when the cumulative number of power-on and forced stop times is 100,000, which depends on the power supply capacity.
(c) Servo amplifier cooling fan
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore, the cooling fan must be changed in a few years of continuous operation as a guideline.
It must also be changed if unusual noise or vibration is found during inspection.
10 - 1
10. INSPECTION
MEMO
10 - 2
11. TROUBLESHOOTING
11. TROUBLESHOOTING
11.1 Trouble at start-up
CAUTION
Excessive adjustment or change of parameter setting must not be made as it will make operation instable.
POINT
Using the MR Configurator (servo configuration software), you can refer to unrotated servo motor reasons, etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
No. Start-up sequence Fault Investigation Possible cause Reference
LED is not lit.
LED flickers.
Not improved if connectors
CN1A, CN1B, CN2 and CN3 are disconnected.
Improved when connectors
CN1A and CN1B are disconnected.
Improved when connector
CN2 is disconnected.
1. Power supply voltage fault
2. Servo amplifier is faulty.
Power supply of CNP1 cabling is shorted.
1. Power supply of encoder cabling is shorted.
2. Encoder is faulty.
Improved when connector
CN3 is disconnected.
Power supply of CN3 cabling is shorted.
Refer to section 11.2 and remove cause. Alarm occurs.
2 Switch servo-on Alarm occurs. signal. Servo motor shaft is not servo-locked
(is free).
Refer to section 11.2 and remove cause.
1. Check the display to see if the servo amplifier is ready to operate.
2. Check the external I/O signal indication to see if
1. Servo-on signal is not input.
(Wiring mistake)
2. 24VDC power is not supplied to COM. the servo-on (SON) signal is ON.
Section 11.2
Section 11.2
Section 7.3.2
4 Cyclic operation
Rotation ripples
(speed fluctuations) are large at low speed.
Make gain adjustment in the following procedure.
1. Increase the auto tuning response level.
2. Repeat acceleration and deceleration several times to complete auto tuning.
Gain adjustment fault
Large load inertia moment causes the servo motor shaft to oscillate side to side.
If the servo motor may be run with safety, repeat acceleration and deceleration several times to complete auto tuning.
Position shift occurs Confirm the cumulative command pulses, cumulative feedback pulses and actual servo motor position.
Gain adjustment fault
Pulse counting error, etc. due to noise.
Chapter 7
Chapter 7
11 - 1
11. TROUBLESHOOTING
11.2 When alarm or warning has occurred
POINT
Configure up a circuit which will detect the trouble (ALM) signal and turn off the servo-on (SON) signal at occurrence of an alarm.
11.2.1 Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or warning has occurred, refer to section 11.2.2 or 11.2.3 and take the appropriate action.
Set "1 " in parameter No. 59 to output the alarm code in ON/OFF status across the corresponding pin and SG. Warnings (AL.90 to AL.E9) have no alarm codes. Any alarm code is output at occurrence of the corresponding alarm. In the normal status, the signals available before alarm code setting (CN1B-19,
CN1A-18, CN1A-19) are output.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the alarm deactivation column.
(Note 2) Alarm code
Display CN1B-19 pin
CN1A-18 pin
CN1A-19 pin
Name
AL.10 0 1 0
AL.12 0 0 0
AL.13 0 0 0 error
AL.15 0 0 0
AL.16 1 1 0
2
Encoder
AL.17 0 0 0
AL.19 0 0 0 error
Memory
AL.1A 1 1 0
AL.20 1
AL.24 1
1
0
0
0
2
Main circuit error
AL.25 1 1 0
AL.30 0 0 1
AL.31 1 0 1 error
Overspeed
AL.32 1 0 0
AL.33 0 0 1
AL.35 1 0 1 Command pulse frequency error
AL.37 0 0 0
AL.39 0 0 0 error
Program
AL.45 0 1 1 Main circuit device overheat
AL.46 0 1 1 Servo motor overheat
AL.50 0 1 1
AL.51 0 1 1
AL.52 1 0 1
2
Error
AL.63
AL.64
AL.8A
AL.8E
1
1
0
0
0
0
0
0
1
1
0
0
Home position return incomplete
Home position setting error
Serial communication time-out error
Serial communication error
88888 0 0 0
AL.92 Open battery cable warning
Alarm deactivation
Power
OFF ON
Press
"SET" on current alarm screen.
Alarm reset
(RES) signal
(Note 1) (Note 1) (Note 1)
(Note 1) (Note 1) (Note 1)
(Note 1) (Note 1) (Note 1)
(Note 1) (Note 1) (Note 1)
(Note 1) (Note 1) (Note 1) regenerative automatically.
AL.E3 Absolute position counter warning
AL.E9 Main circuit off warning
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. 0: Pin-SG off (open)
1: Pin-SG on (short)
11 - 2
11. TROUBLESHOOTING
11.2.2 Remedies for alarms
When any alarm has occurred, eliminate its cause, ensure safety, then reset the alarm, and restart operation. Otherwise, injury may occur.
CAUTION If an absolute position erase alarm (AL.25) occurred, always make home position setting again. Otherwise, misoperation may occur.
As soon as an alarm occurs, turn off Servo-on (SON) and power off.
POINT
When any of the following alarms has occurred, always remove its cause and allow about 30 minutes for cooling before resuming operation. If operation is resumed by switching control circuit power off, then on to reset the alarm, the servo amplifier and servo motor may become faulty.
Regenerative error (AL.30)
Overload 1 (AL.50)
Overload 2 (AL.51)
The alarm can be deactivated by switching power off, then on press the
"SET" button on the current alarm screen or by turning on the reset (RES).
For details, refer to section 11.2.1.
When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the servo motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The optional MR Configurator (servo configuration software) may be used to refer to the cause.
Display Name Definition Cause Action
1. Power supply voltage is low. voltage dropped. 2. There was an instantaneous
MR-J2S- CL: control power failure of 60ms or
160VAC or less longer.
MR-J2S- CL1:
83VAC or less
3. Shortage of power supply capacity caused the power supply voltage to drop at start, etc.
4. Power was restored after the bus voltage had dropped to 200VDC.
(Main circuit power switched on within 5s after it had switched off.)
5. Faulty parts in the servo amplifier
Review the power supply.
Change the servo amplifier.
Checking method
Alarm (AL.10) occurs if power is switched on after disconnection of all cables but the control circuit power supply cables.
AL.12 Memory error 1 RAM, memory fault Faulty parts in the servo amplifier
Checking method
Alarm (any of AL.12 and 13) occurs if power is switched on after disconnection of all cables but the control circuit power supply cables.
Change the servo amplifier.
11 - 3
11. TROUBLESHOOTING
Display Name Definition
AL.15 Memory error 2 EEP-ROM fault
Cause
1. Faulty parts in the servo amplifier
Action
Change the servo amplifier.
Checking method
Alarm (AL.15) occurs if power is switched on after disconnection of all cables but the control circuit power supply cables.
2. The number of write times to EEP-
ROM exceeded 100,000. error Communication error occurred
1. Encode connector (CN2) disconnected. between encoder
2. Encoder fault and servo amplifier. 3. Encoder cable faulty
(wire breakage or short)
AL.17 Board error CPU/parts fault Faulty parts in the servo amplifier
Checking method
Alarm (AL.17) occurs if power is switched on after disconnection of all cable but the control circuit power supply cable.
The output terminals U, V, W of
2. The wiring of U, V, W is disconnected or not connected. the servo amplifier and the input terminals U, V, W of the servo motor are not connected.
AL.19 Memory error 3 ROM memory fault Faulty parts in the servo amplifier
Checking method
Alarm (AL.19) occurs if power is switched on after disconnection of all cable but the control circuit power supply cable.
Connect correctly.
Change the servo motor.
Repair or change the cable.
Change the servo amplifier.
Correctly connect the output terminals U,
V, W of the servo amplifier and the input terminals U, V, W of the servo motor.
Change the servo amplifier.
AL.1A Motor combination error
Wrong combination of servo amplifier and servo motor.
Wrong combination of servo amplifier and servo motor connected.
AL.20 Encoder error 2 Communication error occurred
1. Encoder connector (CN2) disconnected. between encoder 2. Encoder fault and servo amplifier. 3. Encoder cable faulty
(wire breakage or shorted)
Use correct combination.
Connect correctly.
Change the servo motor.
Repair or change the cable.
Encoder detected acceleration error.
4. Excessive acceleration is occurred due to oscillation and others.
1. Decrease the speed control gain 2.
2. Decrease the auto tuning response level.
11 - 4
11. TROUBLESHOOTING
Display Name error
Definition
Cause
Action
Ground fault occurred at the servo
1. Power input wires and servo motor output wires are in contact at main
Connect correctly. motor outputs (U,V circuit terminal block (TE1). and W phases) of the 2. Sheathes of servo motor power servo amplifier. cables deteriorated, resulting in ground fault.
Change the cable.
3. Main circuit of servo amplifier failed.
Change the servo amplifier.
AL.25 Absolute position erase
AL.30 Regenerative error
Checking method
AL.24 occurs if the servo is switched on after disconnecting the U, V, W power cables from the servo amplifier.
Absolute position data in error
1. Reduced voltage of super capacitor in encoder
2. Battery voltage low
3. Battery cable or battery is faulty.
After leaving the alarm occurring for a few minutes, switch power off, then on again.
Always make home position setting again.
Change battery.
Always make home position setting again.
Power was switched on for the first time in the absolute position detection system.
4. Super capacitor of the absolute position encoder is not charged
After leaving the alarm occurring for a few minutes, switch power off, then on again.
Always make home position setting again.
Permissible regenerative power of the built-in regenerative resistor
1. Wrong setting of parameter No. 0 Set correctly.
2. Built-in regenerative resistor or regenerative option is not connected.
Connect correctly or regenerative 3. High-duty operation or continuous 1. Reduce the frequency of positioning. option is exceeded. regenerative operation caused the 2. Use the regenerative option of larger permissible regenerative power of the regenerative option to be exceeded. capacity.
3. Reduce the load.
Checking method
Call the status display and check the regenerative load ratio.
4. Power supply voltage is abnormal.
MR-J2S- CL:260VAC or more
MR-J2S- CL1:135VAC or more
5. Built-in regenerative resistor or regenerative option faulty.
Regenerative 6. Regenerative transistor faulty. transistor fault
Checking method
1) The regenerative option has
overheated abnormally.
2) The alarm occurs even after
removal of the built-in
regenerative resistor or
regenerative option.
Review power supply
Change servo amplifier or regenerative option.
Change the servo amplifier.
11 - 5
11. TROUBLESHOOTING
Display Name
AL.31 Overspeed
Definition
Speed has exceeded the instantaneous permissible speed.
Cause
1. Input command pulse frequency exceeded the permissible instantaneous speed frequency.
2. Small acceleration/deceleration time constant caused overshoot to be large.
3. Servo system is instable to cause overshoot.
AL.32 Overcurrent
4. Electronic gear ratio is large
(parameters No. 4, 5)
5. Encoder faulty.
Current that flew is higher than the permissible current of the servo amplifier. (If the alarm (AL.32) occurs again when turning
ON the servo after
1. Short occurred in servo amplifier output phases U, V and W.
2. Transistor (IPM) of the servo amplifier faulty.
Checking method
Alarm (AL.32) occurs if power is switched on after U,V and W are disconnected.
resetting the alarm by turning OFF/ON the power when the alarm (AL.32) first
3. Ground fault occurred in servo amplifier output phases U, V and
W. occurred, the transistor (IPM,
IGBT) of the servo amplifier may be at
4. External noise caused the overcurrent detection circuit to misoperate. fault. In the case, do not repeat to turn
OFF/ON the power.
Check the transistor with the checking method of “Cause
2”.)
Action
Set command pulses correctly.
Increase acceleration/deceleration time constant.
1. Re-set servo gain to proper value.
2. If servo gain cannot be set to proper value.
1) Reduce load inertia moment ratio; or
2) Reexamine acceleration/ deceleration time constant.
Set correctly.
Change the servo motor.
Correct the wiring.
Change the servo amplifier.
Correct the wiring.
Take noise suppression measures.
11 - 6
11. TROUBLESHOOTING
Display Name Definition voltage exceeded
400VDC.
Cause Action
1. Regenerative option is not used.
3. Lead of built-in regenerative resistor or regenerative option is open or disconnected.
Use the regenerative option.
2. Though the regenerative option is used, the parameter No. 0 setting is
Make correct setting.
" 0 (not used)".
1. Change lead.
2. Connect correctly. frequency error
Input pulse frequency of the command pulse is too high.
AL.37 Parameter error
4. Regenerative transistor faulty.
5. Wire breakage of built-in regenerative resistor or regenerative option
6. Capacity of built-in regenerative resistor or regenerative option is insufficient.
7. Power supply voltage high.
8. The jumper across BUE-SD of the
FR-BU2 brake unit is removed.
1. Pulse frequency of the manual pulse generator is too high.
2. Noise entered the pulses of the manual pulse generator.
3. Manual pulse generator failure
Parameter setting is 1. Servo amplifier fault caused the wrong. parameter setting to be rewritten.
2. Regenerative option not used with servo amplifier was selected in parameter No.0.
3. Value outside setting range has been set in some parameter.
4. Value outside setting range has been set in electronic gear.
5. Opposite sign has been set in software limit increasing side
(parameters No. 46, 47). Similarly, opposite sign has been set in software limit decreasing side
(parameters No. 48, 49).
6. Opposite sign has been set in position range output address increasing side (parameters No. 50,
51). Similarly, opposite sign has been set in position range output address decreasing side
(parameters No. 52, 53).
7. The number of write times to EEP-
ROM exceeded 100,000 due to parameter write, program write, etc.
Change servo amplifier
1. For wire breakage of built-in regenerative resistor, change servo amplifier.
2. For wire breakage of regenerative option, change regenerative option.
Add regenerative option or increase capacity.
Review the power supply.
Fit the jumper across BUE-SD.
Change the pulse frequency to a proper value.
Take action against noise.
Change the manual pulse generator.
Change the servo amplifier.
Set parameter No.0 correctly.
Set the parameter correctly.
Set parameters No. 4, 5 correctly.
Set parameters No. 46 to 49 correctly.
Set parameters No. 50 to 53 correctly.
Change the servo amplifier.
11 - 7
11. TROUBLESHOOTING
Display Name Definition abnormal
Cause
1. Servo amplifier fault caused the program data to be rewritten.
2. Command argument is out of the setting range.
3. The number of write times to EEP-
ROM exceeded 100,000 due to parameter write, program write, etc.
Action
Change the servo amplifier.
Programming correctly.
Change the servo amplifier. device overheat
Main circuit device overheat overheat
AL.50 Overload 1
Servo motor temperature rise actuated the thermal sensor.
Load exceeded overload protection characteristic of servo amplifier.
1. Servo amplifier faulty.
2. The power supply was turned on and off continuously by overloaded status.
3. Air cooling fan of servo amplifier stops.
1. Ambient temperature of servo motor is over 40 (104 ).
2. Servo motor is overloaded.
Change the servo amplifier.
The drive method is reviewed.
1. Exchange the cooling fan or the servo amplifier.
2. Reduce ambient temperature.
Review environment so that ambient temperature is 0 to 40 (32 to 104 ).
1. Reduce load.
2. Review operation pattern.
3. Use servo motor that provides larger output.
3. Thermal sensor in encoder is faulty. Change servo motor.
1. Servo amplifier is used in excess of its continuous output current.
1. Reduce load.
2. Review operation pattern.
3. Use servo motor that provides larger output.
2. Servo system is instable and hunting.
1. Repeat acceleration/ deceleration to execute auto tuning.
2. Change auto tuning response setting.
3. Set auto tuning to OFF and make gain adjustment manually.
3. Machine struck something. 1. Review operation pattern.
2. Install limit switches.
Connect correctly. 4. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's input terminals U, V, W.
5. Encoder faulty. Change the servo motor.
Checking method
When the servo motor shaft is rotated with the servo off, the cumulative feedback pulses do not vary in proportion to the rotary angle of the shaft but the indication skips or returns midway.
11 - 8
11. TROUBLESHOOTING
Display Name Definition Cause Action
Machine collision or the like caused max.
1. Machine struck something.
For the time of the alarm occurrence, refer to the section
13.1.
2. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's input terminals U, V, W.
1. Review operation pattern.
2. Install limit switches.
Connect correctly.
3. Servo system is instable and hunting.
4. Encoder faulty.
Checking method
When the servo motor shaft is rotated with the servo off, the cumulative feedback pulses do not vary in proportion to the rotary angle of the shaft but the indication skips or returns midway.
1. Repeat acceleration/deceleration to execute auto tuning.
2. Change auto tuning response setting.
3. Set auto tuning to OFF and make gain adjustment manually.
Change the servo motor. between the model position and the actual servo motor position exceeds 2.5 rotations. (Refer to the function block diagram in section
1.1.1)
1. Acceleration/deceleration time constant is too small.
2. Internal torque limit 1 (parameter
No.28) is too small.
Increase the acceleration/deceleration time constant.
Increase the torque limit value.
3. Motor cannot be started due to torque shortage caused by power supply voltage drop.
4. Position control gain 1 (parameter
No.7) value is small.
1. Review the power supply capacity.
2. Use servo motor which provides larger output.
Increase set value and adjust to ensure proper operation.
5. Servo motor shaft was rotated by external force.
6. Machine struck something.
7. Encoder faulty
8. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's input terminals U, V, W.
1. When torque is limited, increase the limit value.
2. Reduce load.
3. Use servo motor that provides larger output.
1. Review operation pattern.
2. Install limit switches.
Change the servo motor.
Connect correctly.
11 - 9
11. TROUBLESHOOTING
Display Name
AL.63 Home return incomplete
Definition Cause system.
1. Positioning
1. Positioning operation was performed without home position return. operation was performed without
2. Home position return speed could not be decreased to creep speed. home position return.
2. Home position return ended abnormally.
3. Limit switch was actuated during home position return starting at other than position beyond dog.
Action
1. Perform home position return.
2. Review home position return speed/creep speed/moving distance after proximity dog. setting error
In absolute position detection system.
1. Positioning operation was
1. Positioning operation was performed without home position setting.
2. Home position setting speed could performed without home position not be decreased to creep speed.
3. Limit switch was actuated during setting.
2. Home position home position setting starting at other than position beyond dog. setting ended abnormally. setting could not be made.
1. Droop pulses remaining are greater than the in-position range setting.
1. Perform home position setting.
2. Review home position setting speed/creep speed/moving distance after proximity dog.
Remove the cause of droop pulse occurrence
2. Command pulse entered after clearing of droop pulses.
Do not enter command pulse after clearing of droop pulses.
AL.8A Serial RS-232C or RS-422 communication communication time-out error stopped for longer than the time set in parameter No.23.
2. Communication cycle longer than parameter No. 23 setting.
3. Wrong protocol.
AL.8E Serial Serial communication communication error
1. Communication cable fault
(Open cable or short circuit) error occurred between servo amplifier and
2. Communication device (e.g. personal computer) faulty communication device (e.g. personal computer).
88888 Watchdog
3. Creep speed high.
1. Communication cable breakage.
CPU, parts faulty Fault of parts in servo amplifier
Reduce creep speed.
Repair or change communication cable
Set correct value in parameter.
Correct protocol.
Repair or change the cable.
Change the communication device (e.g. personal computer).
Change servo amplifier.
Checking method
Alarm (88888) occurs if power is switched on after disconnection of all cables but the control circuit power supply cables.
11 - 10
11. TROUBLESHOOTING
11.2.3 Remedies for warnings
CAUTION
If an absolute position counter warning (AL.E3) occurred, always make home position setting again. Otherwise, misoperation may occur.
POINT
When any of the following alarms has occurred, do not resume operation by switching power of the servo amplifier OFF/ON repeatedly. The servo amplifier and servo motor may become faulty. If the power of the servo amplifier is switched OFF/ON during the alarms, allow more than 30 minutes for cooling before resuming operation.
Excessive regenerative warning (AL.E0)
Overload warning 1 (AL.E1)
If AL.E6 occurs, the servo off status is established. If any other warning occurs, operation can be continued but an alarm may take place or proper operation may not be performed. Use the optional MR
Configurator (servo configuration software) to refer to the cause of warning.
Display Name Definition Cause Action cable warning
Absolute position detection system battery voltage is low.
AL.97 Program operation disable
Program was started in a program operation disable status. warning
Software limit set in parameter is reached.
1. Battery cable is open.
After a program change, the program was started without the servo amplifier being powered off/on.
1. Software limit was set within actual operation range.
2. Program of position data in excess of software limit was executed.
Repair cable or changed.
2. Battery voltage supplied from the servo amplifier to the encoder fell to about
Change battery.
3.2V or less.
(Detected with the encoder)
Power off/on the servo amplifier.
Set parameter No. 48 to 51 correctly.
Set program correctly.
3. Software limit was reached during JOG Perform operation within operation or manual pulse generator operation. software limit range.
Change the battery. AL.9F Battery warning Voltage of battery for absolute position detection system reduced.
Battery voltage fell to 3.2V or less.
(Detected with the servo amplifier)
AL.E0 Excessive regenerative warning
AL.E1 Overload warning
There is a possibility that Regenerative power increased to 85% or regenerative power may exceed permissible more of permissible regenerative power of built-in regenerative resistor or regenerative option. regenerative power of built-in regenerative resistor or regenerative option.
Checking method
Call the status display and check regenerative load ratio.
1. Reduce frequency of positioning.
2. Change regenerative option for the one with larger capacity.
3. Reduce load.
There is a possibility that Load increased to 85% or more of overload Refer to AL.50, AL.51. overload alarm 1 or 2 may occur. alarm 1 or 2 occurrence level.
Cause, checking method
Refer to AL.50,51.
11 - 11
11. TROUBLESHOOTING
Display Name Definition
AL.E3 Absolute position Absolute position encoder 1. Noise entered the encoder. counter warning pulses faulty.
2. Encoder faulty.
The multi-revolution counter value of the absolute position encoder exceeded the maximum revolution range.
3. The movement amount from the home position exceeded a 32767 rotation or
37268 rotation in succession.
AL.E6 Servo forced stop EMG-SG are open. warning
Cause
External forced stop was made valid.
(EMG-SG opened.)
AL.E9 Main circuit off warning
Servo was switched on with main circuit power off.
11.3 MR-DP60 external digital display error
Action
Take noise suppression measures.
Change servo motor.
Make home position setting again.
Ensure safety and deactivate forced stop.
Switch on main circuit power.
When MR-DP60 external digital display detects an error, the following alarms are displayed. The alarms are displayed only on the MR-DP60, but not on the servo amplifier display.
Display Name Definition Cause Action
AL. CPU CPU error
AL. C0 Communication error
CPU error Faulty parts in the MR-D60. Exchange the MR-D60.
Communication error occurred between MR-DP60 and MR-J2S-CL.
1. CN3 connector disconnected. Connect correctly.
2. Wire breakage of the cable. Repair or exchange the cable.
11 - 12
12. OUTLINE DIMENSION DRAWINGS
12. OUTLINE DIMENSION DRAWINGS
12.1 Servo amplifiers
(1) MR-J2S-10CL to MR-J2S-60CL
MR-J2S-10CL1 to MR-J2S-40CL1
Approx.70 (2.76)
6 ( 0.24) mounting hole B
A
MITSUBISHI
OPEN
C
N
1
A
E
N
C
C
N
2
L1 L2 L3
(Note)
C
N
3
U V W
C
N
1
B
6
(0.24)
PE terminal
135 (5.32)
Rating plate
TE1
[Unit: mm]
([Unit: in])
Terminal layout
(Terminal cover open)
MITSUBISHI
OPEN
C
N
2
E
N
C
C
N
1
A
C
N
3
C
N
1
B
TE2
4(0.16)
Servo amplifier
Variable dimensions Mass
MR-J2S-10CL (1)
MR-J2S-20CL (1)
MR-J2S-40CL (1)
MR-J2S-60CL
50 (1.97)
70 (2.76)
6 (0.24)
22 (0.87)
0.7 (1.54)
1.1 (2.43)
Note. This data applies to the 3-phase 200 to 230VAC and 1-phase 230VAC power supply models.
Terminal signal layout
TE1
For 3-phase 200 to 230VAC and 1-phase 230VAC For 1-phase 100 to 120VAC
L
1
U
L
2
L
3
V W
L
1
U V
L
2
W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
PE terminals
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
TE2
Front
D C P L
21
L
11
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 1
12. OUTLINE DIMENSION DRAWINGS
(2) MR-J2S-70CL MR-J2S-100CL
6 ( 0.24) mounting hole
70(2.76)
22
(0.87)
MITSUBISHI
Approx.70(2.76)
OPEN
C
N
1
A
C
N
2
E
N
C
L1 L2 L3
C
N
3
C
N
1
B
U V W
22
(0.87)
6(0.24)
42
(1.65)
PE terminal
6(0.24)
190(7.48)
Rating plate
TE2 TE1
Servo amplifier
MR-J2S-70CL
MR-J2S-100CL
Mass
[kg] ([lb])
1.7 (3.75)
Terminal signal layout
TE1
L
1
U
L
V
2
L
3
W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
Front
D C P L
21
L
11
N
PE terminals
Mounting Screw
Screw Size:M5
Tightening torque:3.24[N m](28.676 [lb in])
6(0.24)
[Unit: mm]
([Unit: in])
Terminal layout
(Terminal cover open)
MITSUBISHI
OPEN
C
N
2
E
N
C
C
N
1
A
C
N
1
B
C
N
3
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 2
12. OUTLINE DIMENSION DRAWINGS
(3) MR-J2S-200CL MR-J2S-350CL
6 ( 0.24) mounting hole
6
(0.24)
90(3.54)
78(3.07)
MITSUBISHI
Approx.70(2.76) 195(7.68)
[Unit: mm]
([Unit: in])
Terminal layout
MITSUBISHI
TE2
TE1
PE terminal
Cooling fan wind direction
Servo amplifier
MR-J2S-200CL
MR-J2S-350CL
Mass
[kg] ([lb])
2.0 (4.41)
Terminal signal layout
TE1
L
1
L
2
L
3
U V W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
L
11
L
21
D P C N
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
PE terminals
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
12 - 3
12. OUTLINE DIMENSION DRAWINGS
(4) MR-J2S-500CL
2- 6( 0.24) mounting hole
(0.24)
6
130(5.12)
118(4.65)
(0.24)
6
Approx.70
(2.76)
OPEN
MITSUBISHI
OPEN
C
N
C
N
N
2
N
3
N.P.
6(0.24)
[Unit: mm]
([Unit: in])
200(7.87)
(0.19) 5
TE1
Terminal layout
MITSUBISHI
OPEN
C
N
C
N
1
N
2
N
3
TE2
N.P.
Cooling fan Cooling fan
Cooling fan wind direction
Servo amplifier
Mass
[kg] ([lb])
TE1
L
1
C
P
L
2
L
3
V
W
N
U
Terminal signal layout
PE terminals
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6[lb in])
Built-in regenerative resistor lead terminal fixing screw
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6[lb in])
TE2
L
11
L
21
Terminal screw : M3.5
Tightening torque : 0.8 [N m](7[lb in])
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
12 - 4
12. OUTLINE DIMENSION DRAWINGS
(5) MR-J2S-700CL
2- 6( 0.24) mounting hole
(0.39)
10
180(7.09)
160(6.23)
Approx.70
10 (2.76)
(0.39)
200(7.87)
138(5.43) 62
(2.44)
MITSUBISHI
OPEN
C
N
1
A
C
2
C
N
3
C
N
1
B
6(0.24)
OPEN
[Unit: mm]
([Unit: in])
Terminal layout
MITSUBISHI
OPEN
C
N
1
A
C
2
C
N
1
B
C
N
3
TE2
Cooling fan
TE1
6 (0.24)
Cooling fan wind direction
Servo amplifier
Mass
[kg] ([lb])
TE1
Terminal signal layout
PE terminals
L
1
L
2
L
3
C P N U V W
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6[lb in])
Built-in regenerative resistor lead terminal fixing screw
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6[lb in]) TE2
L
11
L
21
Terminal screw : M3.5
Tightening torque : 0.8 [N m](7[lb in])
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
12 - 5
12. OUTLINE DIMENSION DRAWINGS
12.2 Connectors
(1) Servo amplifier side
<3M >
(a) Soldered type
Model
Connector : 10120-3000PE
Shell kit : 10320-52F0-008
[Unit: mm]
([Unit: in])
12.0(0.47)
22.0 (0.87)
14.0
(0.55)
Logo, etc. are indicated here.
33.3 (1.31)
12.7(0.50)
(b) Threaded type
Model
Connector : 10120-3000PE
Shell kit : 10320-52A0-008
Note. This is not available as option
and should be user-prepared.
22.0
(0.87)
14.0
(0.55)
12.0
(0.47)
[Unit: mm]
([Unit: in])
27.4
(1.08)
33.3
(1.31)
12.7
(0.50)
(c) Insulation displacement type
Model
Connector : 10120-6000EL
Shell kit : 10320-3210-000
6.7
( 0.26)
[Unit: mm]
([Unit: in])
20.9 (0.82)
2- 0.5 (0.02)
Logo, etc. are indicated here.
29.7 (1.17)
12 - 6
12. OUTLINE DIMENSION DRAWINGS
(2) Communication cable connector
<JAE>
[Unit: mm]
([Unit: in])
B
A
Fitting fixing screw G
Type
DE-C1-J6-S6
E (max. diameter of cable used)
F
C
D
A
1
34.5 (1.36)
B
1
C
0.25
D
1
19 (0.75) 24.99 (0.98) 33 (1.30)
E
6 (0.24)
F reference
18 (0.71)
G
#4-40
12 - 7
12. OUTLINE DIMENSION DRAWINGS
MEMO
12 - 8
13. CHARACTERISTICS
13. CHARACTERISTICS
13.1 Overload protection characteristics
An electronic thermal relay is built in the servo amplifier to protect the servo motor and servo amplifier from overloads. Overload 1 alarm (AL.50) occurs if overload operation performed is above the electronic thermal relay protection curve shown in any of Figs 13.1. Overload 2 alarm (AL.51) occurs if the maximum current flew continuously for several seconds due to machine collision, etc. Use the equipment on the left-hand side area of the continuous or broken line in the graph.
In a machine like the one for vertical lift application where unbalanced torque will be produced, it is recommended to use the machine so that the unbalanced torque is 70% or less of the rated torque.
1000 1000
During rotation
During rotation
100
100
During stop
10 10
During stop
1
1
0.1
0 50 100 150 200
(Note) Load ratio [%]
250
10000 a. MR-J2S-10CL to MR-J2S-100CL
300
0.1
0 50 100 150 200
(Note) Load ratio [%]
250 b. MR-J2S-200CL to MR-J2S-350CL
300
1000
During rotation
100
During servo lock
10
1
0 50 100 150 200
(Note) Load ratio [%]
250 300 c. MR-J2S-500CL MR-J2S-700CL
Note. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor stop status (servo lock status) or in a 30r/min or less low-speed operation status, the servo amplifier may fail even when the electronic thermal relay protection is not activated.
Fig 13.1 Electronic thermal relay protection characteristics
13 - 1
13. CHARACTERISTICS
13.2 Power supply equipment capacity and generated loss
(1) Amount of heat generated by the servo amplifier
Table 12.1 indicates servo amplifier's power supply capacities and losses generated under rated load.
For thermal design of an enclosure, use the values in Table 13.1 in consideration for the worst operating conditions. The actual amount of generated heat will be intermediate between values at rated torque and servo-off according to the duty used during operation. When the servo motor is run at less than the maximum speed, the power supply capacity will be smaller than the value in the table, but the servo amplifier's generated heat will not change.
Table 13.1 Power supply capacity and generated heat per servo amplifier at rated output
Servo amplifier
MR-J2S-10CL(1)
MR-J2S-20CL(1)
MR-J2S-40CL(1)
MR-J2S-60CL
MR-J2S-70CL
MR-J2S-100CL
MR-J2S-200CL
MR-J2S-350CL
MR-J2S-500CL
MR-J2S-700CL
Servo motor
(Note 1)
Power supply
(Note 2)
Servo amplifier-generated heat[W] capacity[kVA] At rated torque With servo off
Area required for heat dissipation
[m 2 ] [ft 2 ]
HC-KFS053 13 0.3
HC-MFS053 13 0.3
25
25
15
15
0.5
0.5
5.4
5.4
HC-UFS13 0.3 25 15 0.5 5.4
HC-KFS23 0.5 25 15 0.5 5.4
HC-MFS23 0.5 25 15 0.5 5.4
HC-UFS23 0.5 25 15 0.5 5.4
HC-KFS43 0.9 35 15 0.7 7.5
HC-MFS43 0.9 35 15 0.7 7.5
HC-UFS43 0.9 35 15 0.7 7.5
HC-SFS52 1.0 40 15 0.8 8.6
HC-SFS53 1.0 40 15 0.8 8.6
HC-LFS52 1.0 40 15 0.8 8.6
HC-KFS73 1.3 50 15 1.0 10.8
HC-MFS73 1.3 50 15 1.0 10.8
HC-UFS72 73 1.3 50 15 1.0 10.8
HC-SFS81 1.5 50 15 1.0 10.8
HC-SFS102 103 1.7 50 15 1.0 10.8
HC-LFS102 1.7 50 15 1.0 10.8
HC-SFS121 2.1 90 20 1.8 19.4
HC-SFS201 3.5 90 20 1.8 19.4
HC-SFS152 153 2.5 90 20 1.8 19.4
HC-SFS202 203 3.5 90 20 1.8 19.4
HC-RFS103 1.8 50 15 1.0 10.8
HC-RFS153 2.5 90 20 1.8 19.4
HC-UFS152 2.5 90 20 1.8 19.4
HC-LFS152 2.5 90 20 1.8 19.4
HC-SFS301 4.8 120 20 2.7 29.1
HC-SFS352 353 5.5 130 20 2.7 29.1
HC-RFS203 3.5 90 20 1.8 19.4
HC-UFS202 3.5 90 20 1.8 19.4
HC-LFS202 3.5 90 20 1.8 19.4
HC-SFS502 7.5 195 25 3.9 42.0
HC-RFS353 5.5 135 25 2.7 29.1
HC-RFS503 7.5 195 25 3.9 42.0
HC-UFS352 5.5 195 25 3.9 42.0
HC-UFS502 7.5 195 25 3.9 42.0
HC-LFS302 4.5 120 25 2.4 25.8
HA-LFS502 7.5 195 25 3.9 42.0
HC-SFS702 10.0 300 25 6.0 64.6
HA-LFS702 10.6 300 25 6.0 64.6
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value assumes that the power factor improving reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the regenerative option, refer to section 14.1.1.
13 - 2
13. CHARACTERISTICS
(2) Heat dissipation area for enclosed servo amplifier
The enclosed control box (hereafter called the control box) which will contain the servo amplifier should be designed to ensure that its temperature rise is within 10 ( 50 ) at the ambient temperature of 40 (104 ). (With a 5 (41 ) safety margin, the system should operate within a maximum 55 (131 ) limit.) The necessary enclosure heat dissipation area can be calculated by
Equation 13.1.
P
A K T
............................................................................................................................................. (13.1) where, A : Heat dissipation area [m 2
]
P : Loss generated in the control box [W]
T : Difference between internal and ambient temperatures [ ]
K : Heat dissipation coefficient [5 to 6]
When calculating the heat dissipation area with Equation 13.1, assume that P is the sum of all losses generated in the enclosure. Refer to Table 13.1 for heat generated by the servo amplifier. "A" indicates the effective area for heat dissipation, but if the enclosure is directly installed on an insulated wall, that extra amount must be added to the enclosure's surface area.
The required heat dissipation area will vary wit the conditions in the enclosure. If convection in the enclosure is poor and heat builds up, effective heat dissipation will not be possible. Therefore, arrangement of the equipment in the enclosure and the use of a cooling fan should be considered.
Table 13.1 lists the enclosure dissipation area for each servo amplifier when the servo amplifier is operated at the ambient temperature of 40 (104 ) under rated load.
(Outside)
(Inside)
Air flow
Fig. 13.2 Temperature distribution in enclosure
When air flows along the outer wall of the enclosure, effective heat exchange will be possible, because the temperature slope inside and outside the enclosure will be steeper.
13 - 3
13. CHARACTERISTICS
13.3 Dynamic brake characteristics
13.3.1 Dynamic brake operation
(1) Calculation of coasting distance
Fig. 13.3 shows the pattern in which the servo motor comes to a stop when the dynamic brake is operated. Use Equation 13.2 to calculate an approximate coasting distance to a stop. The dynamic brake time constant varies with the servo motor and machine operation speeds. (Refer to (2) in this section.)
Forced stop (EMG)
ON
OFF
Time constant
Machine speed
V
0 t e
Time t e
L max
V
0
60 t e 1
J
L
J
M
Fig. 13.3 Dynamic brake operation diagram
....................................................................................................................... (13.2)
L max
: Maximum coasting distance .................................................................................................[mm][in]
V
0
: Machine rapid feed rate ........................................................................................ [mm/min][in/min]
J
M
J
L
: Servo motor inertial moment................................................................................. [kg cm
: Load inertia moment converted into equivalent value on servo motor shaft
2 ][oz in 2 ]
................................................................................................................................. [kg cm 2 ][oz in 2 ]
: Brake time constant ........................................................................................................................ [s]
: Delay time of control section........................................................................................................... [s]
(There is internal relay delay time of about 30ms.)
(2) Dynamic brake time constant
The following shows necessary dynamic brake time constant for the equations (13.2).
16
14
12
10
8
6
4
2
0
0
053
73
23
43 13
500 1000 1500 2000 2500 3000
Speed [r/min]
0.02
0.018
0.016
0.014
0.012
0.01
0.008
0.006
0.004
0.002
0
0
23
053
73
43
13
500 1000 1500 2000 2500 3000
Speed [r/min] a. HC-KFS series b. HC-MFS series
13 - 4
13. CHARACTERISTICS
0.04
0.035
0.03
0.025
0.02
0.015
0.01
0.005
0
0
121
201
301
81
50 500
Speed [r/min]
0.12
c. HC-SFS1000r/min series
1000
0.1
0.08
203
53
0.06
0.04
353
0.02
103
0
0
153
50 500 1000 1500 2000 2500 3000
Speed [r/min] e. HC-SFS3000r/min series
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
0
72
152
352
502
202
500 1000 1500 2000
Speed [r/min] g. HC-UFS 2000r/min series
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0
0
302
500 1000 1500 2000
Speed [r/min] i. HC-LFS series
13 - 5
0.045
0.04
0.035
0.03
0.025
0.02
0.015
0.01
0.005
0
0
352202
702
502
52
102
152
500 1000 1500 2000
Speed [r/min]
0.018
0.016
0.014
0.012
0.01
0.008
0.006
0.004
0.002
0
0 d. HC-SFS2000r/min series
353
103
153
503
203
500 1000 1500 2000 2500 3000
Speed [r/min] f. HC-RFS series
0.07
0.06
0.05
0.04
0.03
0.02
0.01
73
13
23
43
0
0 50 500 10001500200025003000
Speed [r/min] h. HC-UFS3000r/min series
13. CHARACTERISTICS
13.3.2 The dynamic brake at the load inertia moment
Use the dynamic brake under the load inertia moment ratio indicated in the following table. If the load inertia moment is higher than this value, the built-in dynamic brake may burn. If there is a possibility that the load inertia moment may exceed the value, contact Mitsubishi.
Servo amplifier Load inertia moment ratio [times]
MR-J2S-10CL to MR-J2S-200CL
MR-J2S-10CL1 to MR-J2S-40CL1
30
MR-J2S-350CL 16
MR-J2S-500CL MR-J2S-700CL 15
13.4 Encoder cable flexing life
The flexing life of the cables is shown below. This graph calculated values. Since they are not guaranteed values, provide a little allowance for these values.
1 10 8
5 10 7 a
1 10 7
5 10 6
1 10 6
5 10 5
1 10 5
5 10 4
1 10 4
5 10 3 b
1 10 3
4 7 10 20 40 70 100
Flexing radius [mm]
200 a : Long flexing-life encoder cable
MR-JCCBL M-H
MR-JHSCBL M-H
MR-ENCBL M-H b : Standard encoder cable
MR-JCCBL M-L
MR-JHSCBL M-L
13 - 6
13. CHARACTERISTICS
13.5 Inrush Currents at Power-On of Main Circuit and Control Circuit
The following table indicates the inrush currents (reference value) that will flow when the maximum permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
1m.
Servo Amplifier
MR-J2S-10CL 20CL
MR-J2S-40CL 60CL
MR-J2S-70CL 100CL
MR-J2S-200CL 350CL
Inrush Currents (A
0-p
)
Main circuit power supply (L
1
, L
2
, L
3
) Control circuit power supply (L
11
, L
21
)
30A
(Attenuated to approx. 5A in 10ms)
30A
(Attenuated to approx. 5A in 10ms)
54A
(Attenuated to approx. 12A in 10ms)
120A
(Attenuated to approx. 12A in 20ms)
70 to 100A
(Attenuated to approx. 0A in 0.5 to 1ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
MR-J2S-500CL
44A
(Attenuated to approx. 20A in 20ms)
MR-J2S-700CL
88A
(Attenuated to approx. 20A in 20ms)
MR-J2S-10CL1 20CL1 59A (Attenuated to approx. 5A in 4ms)
30A
(Attenuated to approx. 0A in several ms)
100 to 130A
MR-J2S-40CL1 72A (Attenuated to approx. 5A in 4ms) (Attenuated to approx. 0A in 0.5 to 1ms)
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic contactors. (Refer to section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped by an inrush current.
13 - 7
13. CHARACTERISTICS
MEMO
13 - 8
14. OPTIONS AND AUXILIARY EQUIPMENT
14. OPTIONS AND AUXILIARY EQUIPMENT
WARNING
Before connecting any option or peripheral equipment, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
CAUTION
14.1 Options
Use the specified auxiliary equipment and options. Unspecified ones may lead to a fault or fire.
14.1.1 Regenerative options
CAUTION
The specified combinations of regenerative options and servo amplifiers may only be used. Otherwise, a fire may occur.
(1) Combination and regenerative power
The power values in the table are resistor-generated powers and not rated powers.
Regenerative power[W]
Servo amplifier Built-in regenerative resistor
MR-RB032
[40 ]
MR-RB12
[40 ]
MR-RB32
[40 ]
MR-RB30
[13 ]
(Note)
MR-RB50
[13 ]
(1) 30
MR-RB31
[6.7 ]
(Note)
MR-RB51
[6.7 ]
Note. Always install a cooling fan.
14 - 1
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection of the regenerative option
(a) Simple selection method
In horizontal motion applications, select the regenerative option as described below. When the servo motor is run without load in the regenerative mode from the running speed to a stop, the permissible duty is as indicated in section 5.1 of the separately available Servo Motor Instruction
Manual.
For the servo motor with a load, the permissible duty changes according to the inertia moment of the load and can be calculated by the following formula.
Permissible duty
Permissible duty for servo motor with no load (value indication Section 5.1 in Servo Motor Instruction Manual)
(m 1) ratedspeed running speed
2
[times/min] where m load inertia moment/servo motor inertia moment
From the permissible duty, find whether the regenerative option is required or not.
Permissible duty number of positioning times [times/min]
Select the regenerative option out of the combinations in (1) in this section.
(b) To make selection according to regenerative energy
Use the following method when regeneration occurs continuously in vertical motion applications or when it is desired to make an in-depth selection of the regenerative option. a. Regenerative energy calculation
Use the following table to calculate the regenerative energy. tf(1 cycle)
N0
Up
M
Firiction torque
T
F
( )
1)
T psa1 t1
(Driving)
2)
T psd1 t2
4)
Down
T psa2 t3
Time t4
T psd2
8)
5)
T
U
6)
3)
(Regenerative) 7)
( )
Formulas for calculating torque and energy in operation
Regenerative power Torque applied to servo motor [N m] Energy
1)
2)
3)
4), 8)
5)
6)
T
1
T
2
T 3
T
4
T
5
T
6
(J
L
J
M
) N 0
9.55 10
4
T
U
T
F
(J
L
J
M
) N
0
9.55 10
4
T
U
(J
L
J
M
) N
0
9.55 10
4
T
U
T
F
1
T psa1
1
T psd1
1
T psa2
T
U
T
F
T U T F
T
U
T
F
E
1
E
2
E
3
E
4
0.1047
2
N
0
T
3
T psd1
0 (N0 regeneration)
E
5
E
6
0.1047
2
N
0
T
1
T psa1
0.1047 N
0
T
2 t
1
0.1047
2
0.1047 N
0
N
0
T
5
T psa2
T
6 t
3
7) T
7
(J
L
J
M
)
9.55 10 4
N
0
1
T psd2
T
U
T
F
E
7
0.1047
2
N
0
T
7
T psd2
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative energies.
14 - 2
14. OPTIONS AND AUXILIARY EQUIPMENT b. Losses of servo motor and servo amplifier in regenerative mode
The following table lists the efficiencies and other data of the servo motor and servo amplifier in the regenerative mode.
Servo amplifier Inverse efficiency[%]
MR-J2S-10CL 55
MR-J2S-10A1 55
MR-J2S-20CL 70
MR-J2S-20A1 70
MR-J2S-40CL 85
MR-J2S-40A1 85
Capacitor charging[J]
9
4
9
4
11
12
MR-J2S-60CL 85
MR-J2S-70CL 80
MR-J2S-100CL 80
MR-J2S-200CL 85
MR-J2S-350CL 85
MR-J2S-500CL 90
11
18
18
40
40
45
MR-J2S-700CL 90 70
Inverse efficiency ( ) :Efficiency including some efficiencies of the servo motor and servo amplifier when rated (regenerative) torque is generated at rated speed. Since the efficiency varies with the speed and generated torque, allow for about 10%.
Capacitor charging (Ec) :Energy charged into the electrolytic capacitor in the servo amplifier.
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J] Es Ec
Calculate the power consumption of the regenerative option on the basis of single-cycle operation period tf [s] to select the necessary regenerative option.
PR [W] ER/tf
(3) Connection of the regenerative option
Set parameter No.0 according to the option to be used.
Parameter No.0
Selection of regenerative
0: Not used.
(However, this is irrelevant to the MR-J2S-10CL, as it does
not include the built-in regenerative resistor.)
1: FR-RC, FR-BU2
2: MR-RB032
3: MR-RB12
4: MR-RB32
5: MR-RB30
6: MR-RB50(Cooling fan is required)
8: MR-RB31
9: MR-RB51(Cooling fan is required)
14 - 3
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Connection of the regenerative option
POINT
When using the MR-RB50 and MR-RB51, cooling by a cooling fan is required. Please obtain a cooling fan at your discretion.
The regenerative option will cause a temperature rise of 100 degrees relative to the ambient temperature. Fully examine heat dissipation, installation position, used cables, etc. before installing the option. For wiring, use flame-resistant cables and keep them clear of the regenerative option body.
Always use twisted cables of max. 5m(16.4ft) length for connection with the servo amplifier.
(a) MR-J2S-350CL or less
Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 are disconnected when the regenerative option overheats abnormally.
Servo amplifier
Always remove the lead from across P-D.
D
Regenerative option
P
P
C
C
G3
(Note 2)
G4
5m (16.4 ft) max.
Cooling fan(Note 1)
Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (92 92, minimum air flow: 1.0m
3 ).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
For the MR-RB50 install the cooling fan as shown.
Top
Cooling fan Terminal block
[Unit : mm(in)]
Cooling fan installation screw hole dimensions
2-M3 screw hole
(for cooling fan installation)
Depth 10 or less
(Screw hole already machined)
Thermal relay
Bottom
82.5
(3.25)
40 (1.58)
Vertical installation
Horizontal installation Installation surface
14 - 4
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J2S-500CL MR-J2S-700CL
Always remove the wiring (across P-C) of the servo amplifier built-in regenerative resistor and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option overheats abnormally.
Servo amplifier
Always remove wiring (across P-C) of servo amplifier built-in regenerative resistor.
Regenerative option
P
P
C
C
G3
(Note 2)
G4
5m(16.4ft) or less
Cooling fan(Note 1)
Note 1. When using the MR-RB50 MR-RB51, forcibly cool it with a cooling fan (92 92, minimum air flow: 1.0m
3 ).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor option, remove the servo amplifier's built-in regenerative resistor terminals (across P-C), fit them back to back, and secure them to the frame with the accessory screw as shown below.
Mounting method
Accessory screw
14 - 5
14. OPTIONS AND AUXILIARY EQUIPMENT
For MR-J2S-500CL For MR-J2S-700CL
Accessory screw
Accessory screw
For the MR-RB50 MR-RB51 install the cooling fan as shown.
Top
Cooling fan Terminal block
[Unit : mm(in)]
Cooling fan installation screw hole dimensions
2-M3 screw hole
(for cooling fan installation)
Depth 10 or less
(Screw hole already machined)
Thermal relay
Bottom
82.5
(3.25)
40 (1.58)
Vertical installation
Horizontal installation Installation surface
14 - 6
14. OPTIONS AND AUXILIARY EQUIPMENT
(5) Outline drawing
(a) MR-RB032 MR-RB12
LB
LA
6 (0.24) mounting hole
MR-RB
[Unit: mm (in)]
TE1
G3
G4
P
C
6 (0.24)
5 (0.20)
Approx.
20
(0.79)
LC
LD
1.6 (0.06)
TE1
Terminal block
G3
G4
P
C
Terminal screw: M3
Tightening torque:
0.5 to 0.6 [N m](4 to 5 [lb in])
Mounting screw
Screw size: M5
Tightening torque:
3.2 [N m](28.32 [lb in])
Regenerative option
MR-RB032
MR-RB12
Variable dimensions Mass
LA LB LC LD [kg] [lb]
30
(1.18)
40
(1.58)
15
(0.59)
15
(0.59)
119
(4.69)
169
(6.69)
99
(3.9)
149
(5.87)
0.5 1.1
1.1 2.4
(b) MR-RB32 MR-RB30 MR-RB31
[Unit: mm (in)]
Terminal block
P
C
G3
G4
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [Ib in])
10
(0.39)
7 (0.28)
90 (3.54)
100 (3.94)
17
(0.67)
318 (12.52)
335 (13.19)
Mounting screw
Screw: M6
Tightening torque: 5.4 [N m] (47.79 [Ibi n])
Regenerative
Mass [kg] (Ib) option
MR-RB30
(6.4)
MR-RB32
14 - 7
14. OPTIONS AND AUXILIARY EQUIPMENT
(c) MR-RB50 MR-RB51
Cooling fan mounting screw (2-M3 screw)
On opposite side
49
(1.93)
82.5
(3.25)
7 14 slot
Wind blows in the arrow direction
[Unit: mm (in)]
Terminal block
P
C
G3
G4
Terminal screw: M4
Tightening torque: 1.2 [N m]
(10.6 [Ib in])
Mounting screw
Screw: M6
Tightening torque: 5.4 [N m]
(47.79 [Ib in])
Regenerative option
MR-RB50
MR-RB51
Mass [kg] (Ib)
5.6 (12.3)
2.3
(0.09)
200 (7.87)
217 (8.54)
17
(0.67)
12
(0.47)
7 (0.28)
108 (4.25)
120 (4.73)
Approx.30 (1.18)
8 (0.32)
14.1.2 FR-BU2 brake unit
POINT
Use a 200V class brake unit and a resistor unit with a 200V class servo amplifier. Combination of different voltage class units and servo amplifier cannot be used.
Install a brake unit and a resistor unit on a flat surface vertically. When the unit is installed horizontally or diagonally, the heat dissipation effect diminishes.
Temperature of the resistor unit case rises to higher than 100 . Keep cables and flammable materials away from the case.
Ambient temperature condition of the brake unit is between 10 (14 ) and 50 (122 ). Note that the condition is different from the ambient temperature condition of the servo amplifier (between 0 (32 ) and
55 (131 )).
Configure the circuit to shut down the power-supply with the alarm output of the brake unit and resistor unit under abnormal condition.
Use the brake unit with a combination indicated in this section (1).
For executing a continuous regenerative operation, use FR-RC power regeneration converter.
Brake unit and regenerative options (Regenerative resistor) cannot be used simultaneously.
Connect the brake unit to the bus of the servo amplifier. As compared to the MR-RB regenerative option, the brake unit can return larger power. Use the brake unit when the regenerative option cannot provide sufficient regenerative capability.
When using the brake unit, set the parameter No.0 of the servo amplifier to " 01 ".
When using the brake unit, always refer to the FR-BU2-(H) Brake Unit Instruction Manual.
14 - 8
14. OPTIONS AND AUXILIARY EQUIPMENT
(1) Selection
Use a combination of servo amplifier, brake unit and resistor unit listed below.
Number of Permissible Total
Brake unit Resistor unit connected units continuous power [kW] resistance
[ ]
Applicable servo amplifier
(2) Brake unit parameter setting
Normally, when using the FR-BU2, changing parameters is not necessary. Whether a parameter can be changed or not is listed below.
Parameter Change possible/
No. Name impossible
Remarks
0 Brake mode switchover
1 Monitor display data selection
Impossible Do not change the parameter.
Possible Refer to the FR-BU2-(H) Brake Unit
Instruction Manual.
Impossible Do not change the parameter. 2 Input terminal function selection 1
3 Input terminal function selection 2
77 Parameter write selection carrying-over times
14 - 9
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Connection example
POINT
Connecting PR terminal of the brake unit to P terminal of the servo amplifier results in brake unit malfunction. Always connect the PR terminal of the brake unit to the PR terminal of the resistor unit.
ALM
RA1
EMG OFF ON
MC
MC
SK
(Note 1)
Power supply
NFB MC
L
1
L
2
L
3
L
11
L
21
Servo amplifier
CN1B
(Note 9) EMG
10
3
13
18
SG
VDD
COM
ALM
D
P
(Note 7)
N
C
(Note 6)
P
PR
FR-BR
(Note 4) TH1
TH2
FR-BU2
PR
P/
N/
(Note 3)
MSG
SD
A
B
BUE
SD
(Note 8)
C
(Note 5)
(Note 2)
Note 1. For power supply specifications, refer to section 1.2.
2. For the servo amplifier of 5k and 7kW, always disconnect the lead of built-in regenerative resistor, which is connected to the P and C terminals.
3. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and brake unit malfunction.
4. Contact rating: 1b contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
5. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
6. For the servo amplifier of 3.5kW, always disconnect the wiring between P and D terminals.
7. Do not connect more than one cable to each P to N terminals of the servo amplifier.
8. Always connect between BUE and SD terminals (Factory-wired).
9. In the device setting, assign the forced stop (EMG) to any pin (Refer to section 6.6).
14 - 10
14. OPTIONS AND AUXILIARY EQUIPMENT
(a) Precautions for wiring
The cables between the servo amplifier and the brake unit, and between the resistor unit and the brake unit should be as short as possible. Always twist the cable longer than 5m (twist five times or more per one meter). Even when the cable is twisted, the cable should be less than 10m. Using cables longer than 5m without twisting or twisted cables longer than 10m, may result in the brake unit malfunction.
Servo amplifier Servo amplifier
Brake unit Resistor unit Brake unit Resistor unit
P
N
P
N
P
PR
P
PR
P
N
Twist P
N
P
PR
Twist P
PR
5m or less 5m or less 10m or less 10m or less
(b) Cables
1) Cables for the brake unit
For the brake unit, HIV cable (600V grade heat-resistant PVC insulated wire) is recommended. a) Main circuit terminal
N/ P/ PR
Terminal block
Brake unit
Main circuit terminal screw size
Crimping terminal
N/ , P/ ,
PR,
Tightening torque
[N m]
([Ib in])
FR-BU2-15K M4 5.5-4 1.5(13.3)
FR-BU2-30K M5 5.5-5 2.5(22.1)
Cable size
N/ , P/ , PR,
HIV cables, etc. [mm 2 ]
AWG
3.5 12
5.5 10
14 - 11
14. OPTIONS AND AUXILIARY EQUIPMENT b) Control circuit terminal
POINT
Undertightening can cause a cable disconnection or malfunction.
Overtightening can cause a short circuit or malfunction due to damage to the screw or the brake unit.
A B C
PC BUE SD
RES
Jumper
SD MSG MSG SD SD
Sheath
Core
6mm
Terminal block
Wire the stripped cable after twisting to prevent the cable from becoming loose. In addition, do not solder it.
Screw size: M3
Tightening torque: 0.5N m to 0.6N m
Cable size: 0.3mm
2 to 0.75 mm 2
Screw driver: Small flat-blade screwdriver
(Tip thickness: 0.4mm/Tip width 2.5mm)
(c) Crimping terminals for P and N terminals of servo amplifier
POINT
Always use recommended crimping terminals or equivalent since some crimping terminals cannot be installed depending on the size.
Servo amplifier Brake unit
Number of connected units
Crimping terminal Applicable tool
MR-J2S-350CL FR-BU2-15K 1
MR-J2S-500CL
FR-BU2-15K 1
FR-BU2-30K 1
MR-J2S-700CL FR-BU2-30K 1
Manufacturer
Terminal
14 - 12
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Outline dimension drawings
(a) FR-BU2 brake unit
FR-BU2-15K
5 hole
(Screw size: M4)
[Unit: mm]
Rating plate
6 56
68
5
6
FR-BU2-30K
2- 5 hole
(Screw size: M4)
18.5
52
132.5
62
4
6 96
108
5
6
Rating plate
18.5
52
129.5
59
5
14 - 13
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) FR-BR resistor unit
2 C
(Note)
Control circuit terminal
Main circuit terminal
Approx. 35
C
W1 1
C
Approx. 35
(Note)
[Unit: mm]
W 5
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Resistor W W1 H H1 H2 H3 D D1 C
Approximate mass
[kg]([Ib])
FR-BR-15K 170 100 450 410 20 432 220 3.2 6 15(33.1)
FR-BR-30K 340 270 600 560 20 582 220 4 10 30(66.1)
14.1.3 Power regeneration converter
When using the power regeneration converter, set "01 " in parameter No. 0.
(1) Selection
The converters can continuously return 75% of the nominal regenerative power. They are applied to the servo amplifiers of the MR-J2S-500CL and MR-J2S-700CL.
Power regeneration converter
Nominal regenerative power (kW)
Servo amplifier
500
300
200
100
50
30
20
0 50 75 100
Nominal regenerative power (%)
150
14 - 14
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
Servo amplifier
L
11
L
21
NFB
Power factor improving reactor
MC FR-BAL
(Note 3)
Power supply
L
1
L
2
L
3
SG
EMG
SON
VDD
COM
ALM
RA2
FR-RC
B C
RA2
(Note 2)
N/
N P C
P/
5m(16.4ft) or less
Ready
RDY
SE
EMG
RDY output
A
B
C
R/L
1
S/L
2
T/L
3
Alarm output
RX
R
SX
S
(Note)
Phase detection terminals
TX
T
Power regeneration converter
FR-RC
Operation ready
OFF
ON
MC MC
SK
B
C
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed, the FR-RC will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative resistor connected to P terminal and C terminal.
3. Refer to section 1.2 for the power supply specification.
14 - 15
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outside dimensions of the power regeneration converters
2- D hole
Mounting foot (removable)
Mounting foot movable
Rating plate
Front cover
Display panel window
Cooling fan
[Unit : mm(in)]
AA
A
D F
K
C
Heat generation area outside mounting dimension
Power regeneration converter
Approx.
A AA B BA C D E EE K F mass [kg(Ib)]
FR-RC-15K
270
(10.630)
200
(7.874)
Approx.AA
450
(17.717)
432
(17.008)
(2- D hole)
195
(7.677)
10
(0.394)
10
(0.394)
8
(0.315)
3.2
(0.126)
87
(3.425)
19
(41.888)
FR-RC-30K
340
(13.386)
270
(10.630)
600
(23.622)
582
(22.913)
195
(7.677)
10
(0.394)
10
(0.394)
8
(0.315)
3.2
(0.126)
90
(3.543)
31
(68.343)
(4) Mounting hole machining dimensions
When the power regeneration converter is fitted to a totally enclosed type box, mount the heat generating area of the converter outside the box to provide heat generation measures. At this time, the mounting hole having the following dimensions is machined in the box.
[Unit : mm(in)]
(Mounting hole)
FR-RC-15K
FR-RC-30K
260 412
(10.236) (16.220)
10
(0.394)
330 562
(12.992) (22.126)
200
(7.874)
432
(17.009)
10
(0.394)
270 582
(10.630) (22.913) a
14 - 16
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.4 Cables and connectors
(1) Cable make-up
The following cables are used for connection with the servo motor and other models. Those indicated by broken lines in the figure are not options.
Servo amplifier
9)
Operation panel
CN1A CN1B
Personal computer
CN2 CN3
14)
Controller
13)
10) 12)
11)
10)
11) To U, V, W,
19) 20)
1) 2)
HC-KFS
HC-MFS
HC-UFS 3000 r/min
15) 16) 17) 18)
3) 4) 5)
6)
7) 8)
HC-SFS
HC-RFS
HC-UFS 2000r/min
14 - 17
14. OPTIONS AND AUXILIARY EQUIPMENT
No. Product cable
6) Encoder connector set
Model
Refer to (2) in this section.
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent) encoder cable cable encoder cable
5) IP65-compliant encoder cable
MR-JCCBL M-H
Refer to (2) in this section.
Refer to (2) in this section.
MR-JHSCBL M-H
Refer to (2) in this section.
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
MR-ENCBL M-H
Refer to (2) in this section.
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
MR-J2CNM Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Description Application
1-172161-9 Standard
Connector pin : 170359-1
(Tyco Electronics or equivalent) flexing life
IP20
Cable clamp : MTI-0002
(Toa Electric Industry)
Connector: D/MS3106B20-29S
Cable clamp: D/MS3057-12A
(DDK)
Long flexing life
IP20
Standard flexing life
IP20
Long flexing life
Connector
: D/MS3106A20-29S (D190) life
Cable clamp: CE3057-12A-3-D
Back shell: CE02-20BS-S-D
(DDK)
Housing : 1-172161-9
(Tyco Electronics or equivalent)
Cable clamp: MTI-0002
(Toa Electric Industry)
Long flexing
IP65
IP67
Not oilresistant.
IP20
7) Encoder connector set
8) Encoder connector set
MR-J2CNS
MR-ENCNS
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: D/MS3106B20-29S
Cable clamp: D/MS3057-12A
(DDK)
IP20
Connector: D/MS3106A20-29S
(D190)
Cable clamp: CE3057-12A-3-D
Back shell: CE02-20BS-S-D
(DDK)
IP65
IP67
14 - 18
14. OPTIONS AND AUXILIARY EQUIPMENT
No. Product connector set
10) Junction terminal block cable
Model
MR-J2TBL M
Refer to section14.1.5.
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: HIF3BA-20D-2.54R
(Hirose Electric)
Description Application
Qty: 2 each
Connector: 10120-6000EL For junction
Shell kit: 10320-3210-000
(3M or equivalent) terminal block connection
11) Junction terminal block
MR-TB20 Refer to section 14.1.5.
MR-J2HBUS M
Refer to section14.1.6.
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
For maintenance junction card connection
13) Maintenance junction card
14) Communication cable
MR-J2CN3TM Refer to section 14.1.6.
MR-CPCATCBL3M Connector: 10120-6000EL
Refer to (3) in this section.
Shell kit: 10320-3210-000
(3M or equivalent)
Connector: DE-9SF-N
Case: DE-C1-J6-S6
(JAE)
For connection with PC-ATcompatible personal computer
15) Power supply connector set
16) Power supply connector set
17) Power supply connector set set
19) Power supply connector set
20) Power supply connector set
MR-PWCNS1
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNS2
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNS3
Refer to the Servo
Motor Instruction
Manual.
MR-BKCN
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNK1
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNK2
Connector: CE05-6A22-23SD-D-BSS
Cable clamp:CE3057-12A-2-D
(DDK)
Connector: CE05-6A24-10SD-D-BSS
Cable clamp: CE3057-16A-2-D
(DDK)
Plug: CE05-6A32-17SD-D-BSS
Cable clamp: CE3057-20A-1-D
(DDK)
Plug: D/MS3106A10SL-4S (D190) (DDK)
Cable connector: YS010-5-8 (Daiwa Dengyo)
Plug: 5559-04P-210
Terminal: 5558PBT3L (For AWG16)(6 pcs.)
(molex)
Plug: 5559-06P-210
Terminal: 5558PBT3L (For AWG16)(8 pcs.)
(molex)
Must be used to comply with the EN
Standard.
IP65 IP67
EN
Standardcompliant
IP65 IP67
IP20
For motor with brake
IP20
14 - 19
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Encoder cable
CAUTION
If you have fabricated the encoder cable, connect it correctly.
Otherwise, misoperation or explosion may occur.
POINT
The encoder cable is not oil resistant.
Refer to section 14.4 for the flexing life of the encoder cable.
When the encoder cable is used, the sum of the resistance values of the cable used for P5 and the cable used for LG should be within 2.4 .
When soldering the wire to the connector pin, insulate and protect the connection portion using heat-shrinkable tubing.
Generally use the encoder cable available as our options. If the required length is not found in the options, fabricate the cable on the customer side.
(a) MR-JCCBL M-L MR-JCCBL M-H
These encoder cables are used with the HC-KFS HC-MFS HC-UFS3000r/min series servo motors.
1) Model explanation
Model: MR-JCCBL M-
Symbol
L
H
Specifications
Standard flexing life
Long flexing life
Symbol (Note) Cable length [m(ft)]
30
40
50
2
5
10
20
2 (6.56)
5 (16.4)
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
Note: MR-JCCBL M-H has
no 40m(131.2ft) and 50m(164.0ft) sizes.
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.3.1.
Servo amplifier
Encoder cable supplied to servo motor
Encoder connector
Encoder cable
(option or fabricated)
Servo motor
Encoder connector
172161-9 (Tyco Electronics)
CN2
50m(164.0ft) max.
30cm
(0.98ft)
Encoder
1 2 3
MR MRR BAT
4 5 6
MD MDR
7
P5
8 9
LG SHD
14 - 20
14. OPTIONS AND AUXILIARY EQUIPMENT
P5
LG
P5
LG
P5
LG
MR-JCCBL2M-L
MR-JCCBL5M-L
MR-JCCBL2M-H
MR-JCCBL5M-H
Servo amplifier side Encoder side
19
11
20
12
18
2
7
Servo amplifier side
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
MR-JCCBL10M-L to
MR-JCCBL30M-L
Encoder side
7
Servo amplifier side
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
MR-JCCBL10M-H to
MR-JCCBL50M-H
Encoder side
7
MR
MRR
MD
MDR 16
BAT
LG
9
1
7
17
6
8
1
2
4
5
3
MR
MRR
MD
MDR 16
BAT
LG
9
1
7
17
6
8
1
2
4
5
3
MR
MRR
MD
MDR 16
BAT
LG
9
1
7
17
6
8
1
2
4
5
3
(Note) (Note) (Note)
SD Plate 9 SD Plate 9 SD Plate 9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
When fabricating an encoder cable, use the recommended wires given in section 14.2.1 and the MR-
J2CNM connector set for encoder cable fabrication, and fabricate an encoder cable as shown in the following wiring diagram. Referring to this wiring diagram, you can fabricate an encoder cable of up to
50m(164.0ft) length including the length of the encoder cable supplied to the servo motor.
When the encoder cable is to be fabricated by the customer, the wiring of MD and MDR is not required.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according to the servo motor installation environment.
For use of AWG22
Servo amplifier side
(3M)
Encoder side
7 P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
MR
MRR
7
17
8
1
2
BAT
LG
9
1
3
(Note)
SD Plate 9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
14 - 21
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-JHSCBL M-L MR-JHSCBL M-H MR-ENCBL M-H
These encoder cables are used with the HC-SFS HC-RFS HC-UFS2000r/min series servo motors.
1) Model explanation
Model: MR-JHSCBL M-
Symbol
L
H
Specifications
Standard flexing life
Long flexing life
Symbol
30
40
50
2
5
10
20
Cable length [m(ft)]
2 (6.56)
5 (16.4)
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
Note: MR-JHSCBL M-L has
no 40(131.2) and 50m(164.0ft) sizes.
Model: MR-ENCBL M-H
Symbol
2
5
10
20
30
40
50
Long flexing life
Cable length [m(ft)]
2 (6.56)
5 (16.4)
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.3.1.
Servo amplifier
Encoder cable
Encoder connector
Servo motor
(Optional or fabricated)
Encoder connector
CN2
50m(164.0ft) max.
Encoder
L
K
J
H
M
T
S
N
A B
P
G
R
C
D
E
F
Pin Signal
A
B
C
MD
MDR
MR
D MRR
E
F BAT
G LG
H
J
Pin Signal
R
S
T
K
L
M
N SHD
P
LG
P5
14 - 22
14. OPTIONS AND AUXILIARY EQUIPMENT
Servo amplifier side
P5
LG
P5
LG
MR
MRR
P5
LG
BAT
LG
SD
7
17
18
2
19
11
20
12
9
1
MR-JHSCBL2M-L
MR-JHSCBL5M-L
MR-JHSCBL2M-H
MR-JHSCBL5M-H
MR-ENCBL2M-H
MR-ENCBL5M-H
Encoder side
S
F
G
Plate
(Note1)
N
(Note2) Use of AWG24
(Less than 10m(32.8ft))
R
C
D
MR-JHSCBL10M-L
Servo amplifier side to
MR-JHSCBL30M-L
MR-JHSCBL10M-H to
MR-JHSCBL50M-H
MR-ENCBL10M-H to
MR-ENCBL50M-H
Encoder side Servo amplifier side Encoder side
P5
LG
P5
LG
P5
LG
MR
MRR
Note1: This wiring is required for use in the absolute
position detection system. This wiring is not
needed for use in the incremental system.
2: AWG28 can be used for 5m(16.4ft) or less.
SD
19
11
20
12
18
2
7
17
S
R
C
D
BAT
LG
9
1
F
G
Plate
(Note1)
N
Use of AWG22
(10m(32.8ft) to 50m(164.0ft))
P5
LG
P5
LG
P5
LG
MR
MRR
BAT
LG
SD
19
11
20
12
18
2
7
17
9
1
S
R
C
D
F
G
(Note1)
Plate N
Use of AWG24
(10m(32.8ft) to 50m(164.0ft))
When fabricating an encoder cable, use the recommended wires given in section 14.2.1 and the MR-
J2CNS connector set for encoder cable fabrication, and fabricate an encoder cable in accordance with the optional encoder cable wiring diagram given in this section. You can fabricate an encoder cable of up to 50m(164.0ft) length.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according to the servo motor installation environment.
14 - 23
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Communication cable
POINT
This cable may not be used with some personal computers. After fully examining the signals of the RS-232C connector, refer to this section and fabricate the cable.
(a) Model definition
Model : MR-CPCATCBL3M
Cable length 3[m](10[ft])
(b) Connection diagram
MR-CPCATCBL3M
Personal computer side
TXD
RXD
GND
RTS
CTS
DSR
DTR
7
8
6
4
3
2
5
D-SUB9 pins
Servo amplifier side
Plate
2
1
12
11
FG
RXD
LG
TXD
LG
Half-pitch 20 pins
When fabricating the cable, refer to the connection diagram in this section.
The following must be observed in fabrication.
1) Always use a shielded, multi-core cable and connect the shield with FG securely.
2) The optional communication cable is 3m(10ft) long. When the cable is fabricated, its maximum length is 15m (49ft) in offices of good environment with minimal noise.
14 - 24
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.5 Junction terminal block (MR-TB20)
POINT
When using the junction terminal block, you cannot use SG of CN1A-20 and CN1B-20. Use SG of CN1A-4 and CN1B-4.
(1) How to use the junction terminal block
Always use the junction terminal block (MR-TB20) with the junction terminal block cable (MR-J2TBL
M) as a set. A connection example is shown below.
Servo amplifier
Cable clamp
(AERSBAN- ESET)
Junction terminal block
MR-TB20
CN1A or
CN1B
Junction terminal block cable
(MR-J2TBL M)
Ground the junction terminal block cable on the junction terminal block side with the standard accessory cable clamp fitting (AERSBAN- ESET). For the use of the cable clamp fitting, refer to section 13.2.6, (2)(c).
(2) Terminal labels
The junction terminal block does not include the terminal block labels which indicate the signal layouts for MR-J2S-CL. Cut off the terminal block label in Appendix 2 at the dotted line and fold it up at the centerline for use.
1) For CN1A
LG PP COM OPC PG SON
2) For CN1B
LG VDD DIO ST1 PI2 P15R COM RST LSN RD
NP P15R DOG SG NG ZP SD VC OUT1 PED PI1 SG TLA DI1 LSP ALM SD
(3) Outline drawing
126(4.96)
117(4.61)
[Unit: mm]
([Unit: in.])
B1 B10
10 11 12
A1
13 14
A10
MITSUBISHI
MR-TB20
15 16 17 18 19
Terminal block No.
0 1 2 3
4
5 6 7 8 9 2- 4.5(0.18)
Terminal screw: M3.5
Applicable cable: Max. 2mm 2
(Crimping terminal width: 7.2mm (0.283 in) max.)
14 - 25
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Junction terminal block cable (MR-J2TBL M)
Model : MR-J2TBL M
Symbol
05
1
Cable length[m(ft)]
0.5 (1.64)
1 (3.28)
Junction terminal block side connector (Hirose Electric)
HIF3BA-20D-2.54R (connector)
Terminal block label
For CN1A For CN1B
LG
NP
PP
P15R
LG
VC
VDD
DOG
COM
SG
OUT1
DI0
PED
ST1
PI1
PI2
OPC
NG
PG
ZP
SON
SD
SG
P15R
TLA
COM
DI1
RST
LSP
LSN
ALM
RD
SD
Junction terminal block terminal No.
16
6
17
7
14
4
15
5
18
8
19
9
12
2
13
3
10
0
11
1
Pin
No.
B7
A7
B8
A8
B5
A5
B6
A6
B3
A3
B4
A4
B1
A1
B2
A2
B9
A9
B10
A10
Servo amplifier side (CN1A CN1B) connector (3M)
10120-6000EL (connector)
10320-3210-000 (shell kit)
Pin
No.
13
14
15
16
9
10
11
12
17
18
19
20
Plate
7
8
5
6
3
4
1
2
14 - 26
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.6 Maintenance junction card (MR-J2CN3TM)
(1) Usage
The maintenance junction card (MR-J2CN3TM) is designed for use when a personal computer and analog monitor are used at the same time.
Servo amplifier
Bus cable
MR-J2HBUS M
Maintenance junction card (MR-J2CN3TM)
Communication cable
CN3B
CN3 CN3A
CN3C
A1 A2 A3 A4 B4 B3 B2 B1 B5 B6 A5 A6
VDD COM EM1 DI MBR EMGO SG PE LG LG MO1 MO2
Not used.
Analog monitor 2
Analog monitor 1
(2) Connection diagram
B5
TE1
B6
A5
A6
LG
LG
MO1
MO2
CN3A
14
15
16
17
9
10
11
12
13
18
19
20
LG
RXD
LG
MO1
3
4
1
2
5
6
MO3
8
SDP
TRE
LG
TXD
LG
MO2
Shell
CN3B
14
15
16
17
9
10
11
12
13
18
19
20
7
8
5
6
3
4
1
2
Shell
CN3C
14
15
16
17
9
10
11
12
13
18
19
20
7
8
5
6
3
4
1
2
1
10
13
14
15
19
20
3
4
5
Shell
A1
A2
A3
A4
B4
B3
B2
B1
VDD
COM
EM1
DI
MBR
EMGO
SG
PE
Not used.
14 - 27
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawing
CN3A CN3B CN3C
2- 5.3(0.21)(mounting hole)
[Unit: mm]
([Unit: in])
A1
B1
TE1
88(3.47)
100(3.94)
(4) Bus cable (MR-J2HBUS M)
Model: MR-J2HBUS M
A6
B6
Symbol
05
1
5
Cable length [m(ft)]
0.5 (1.64)
1 (3.28)
5 (16.4)
MR-J2HBUS05M
MR-J2HBUS1M
MR-J2HBUS5M
10120-6000EL (connector)
10320-3210-000 (shell kit)
10120-6000EL (connector)
10320-3210-000 (shell kit)
16
7
17
8
14
5
15
6
18
9
19
10
20
1
11
2
12
3
13
4
Plate
16
7
17
8
14
5
15
6
18
9
19
10
20
12
3
13
4
1
11
2
Plate
3(0.12)
41.5(1.63)
Mass: 110g(0.24Ib)
14 - 28
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.7 External digital display (MR-DP60)
The data equivalent to the servo amplifier status display can be displayed on the MR-DP60.
When using the MR-DP60, set " 1 4" in parameter No. 16.
The items that appear at the time of power-on can be selected in parameter No.18.
(1) Specifications
Item Specifications
Display
Power supply
Communication
Permissible voltage fluctuation
Current consumption
Interface
Baud rate
Bit length
Red seven-segment LED, signed, six digits
Single-phase, 85 to 253VAC, 50/60Hz
Within 200mA
Conforms to RS-422
4800bps, asynchronous
Start bit 1, date bit 8, parity bit 1, stop bit 1
Communication commands
Operating temperature / humidity range
Storage temperature range
(2) Connection example
Commands dedicated to MELSERVO
0 to 60 (32 to 140 ),
90%RH or less, non-condensing
5 to 70 (23 to 158 )
NFB MC
(Note)
Power supply
L
1
L
2
L
3
L
11
L
21
Servo amplifier
External digital display
MR-DP60
L
1
L
2
CN3
5
15
9
19
1
Plate
RDP
RDN
SDP
SDN
LG
SD
TXD
TXD
RXD
RXD
LG
Note. Refer to section 1.2 for the power supply specification.
(3) Terminal arrangement
TB2
L
1
L 2
Signal Description
L
1
L
2
100 to 230VAC power input
Ground
RXD Inverse receive signal input TB1
TXD TXD RXDRXD P5 LG output
Note. The 5VDC output is designed for the internal control circuit and used to make a voltage check, etc. Do not use this terminal to supply a voltage to the other equipment.
14 - 29
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Mounting
2- 5 (0.20)
Front mounting
Square hole
141(5.55)
150(5.91)
2- 5 (0.20)
[Unit: mm (in)]
Inside mounting
Square hole
95(3.74)
150(5.91)
(5) Outline dimension drawing
[Unit: mm (in)]
TB2
7.5
(0.30)
MITSUBISHI
150(5.91)
165(6.50)
TB1
MR-DP60
7.5
(0.30) 2- 4.5 (0.18) mounting hole
2- 6.5 (0.26), depth 1 (0.04)
14 - 30
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.8 Manual pulse generator (MR-HDP01)
(1) Specifications
Item Specifications
Power supply
Interface
Pulse signal form
Current consumption 60mA max.
Output current max. 20mA for open collector output
A-phase and B-phase signals with 90°phase difference
Pulse resolution
Max. speed
Operating temperature range
100pulse / rev
Instantaneous max. 600r/min, ordinary 200r/min
10 to 60 (14 to 140 )
Storage temperature range 30 to 80 ( 22 to 176 )
(2) Connection example
Use an external power supply to supply power to the manual pulse generator.
Servo amplifier
VDD
CN1B
3
Manual pulse generator
MR-HDP01
SV
A
OV
B
OPC
PP
SG
NP
CN1A
11
3
10
2
External power supply
+5
GND
SD Plate
(3) Terminal arrangement
+5 to
12V 0V A B
Signal name
5 to 12V
Description
Power input
14 - 31
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Mounting
Panel cutting 3- 4.8(0.189) equally divided
2.
44
1)
6
2(
72(2.
835)
[Unit: mm(in)]
(5) Outline dimension drawing
3.6(0.142)
Packing t2.0
[Unit: mm(in)]
3-M4 stud L10
P.C.D.72 equally divided
5V to
12V 0V A B
16 20
(0.63)(0.787)
27.0
0.5
(1.063
0.02)
8.89
(0.35)
M3 6 may only be used.
7.6(0.299)
14.1.9 Battery (MR-BAT, A6BAT)
POINT
The revision (Edition 44) of the Dangerous Goods Rule of the
International Air Transport Association (IATA) went into effect on
January 1, 2003 and was enforced immediately. In this rule, "provisions of the lithium and lithium ion batteries" were revised to tighten the restrictions on the air transportation of batteries. However, since this battery is non-dangerous goods (non-Class 9), air transportation of 24 or less batteries is outside the range of the restrictions. Air transportation of more than 24 batteries requires packing compliant with the Packing
Standard 903. When a self-certificate is necessary for battery safety tests, contact our branch or representative. For more information, consult our branch or representative. (As of September, 2007).
Use the battery to build an absolute position detection system.
+
-
14 - 32
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2 Auxiliary equipment
Always use the devices indicated in this section or equivalent. To comply with the EN Standard or UL/C-
UL (CSA) Standard, use the products which conform to the corresponding standard.
14.2.1 Recommended wires
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
1) Main circuit power supply lead 3) Motor power supply lead
Servo amplifier Servo motor
Power supply
L
1
L
2
L
3
U
V
W
U
V
W Motor
6) Power regeneration
converter lead
2) Control power supply lead
L
11
L
21
5) Electromagnetic
brake lead
Power regeneration converter
Regenerative option
N B1
B2
Electromagnetic brake
C
P
Encoder
4) Regenerative option lead
Encoder cable (refer to section 14.1.4)
The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the wiring distance is 30m(98.4ft) max. If the wiring distance is over 30m(98.4ft), choose the wire size in consideration of voltage drop.
The alphabets (a, b, c) in the table correspond to the crimping terminals (Table 14.2) used to wire the servo amplifier. For connection with the terminal block TE2 of the MR-J2S-100CL or less, refer to section 3.11.
The servo motor side connection method depends on the type and capacity of the servo motor. Refer to section 3.8.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60 (140 ) or more for wiring.
Servo amplifier
Table 14.1 Recommended wires
(Note 1) Wires [mm
2
]
1) L
1
L
2
L
3
2)
21
U V W
MR-J2S-10CL (1)
MR-J2S-20CL (1)
MR-J2S-40CL (1)
MR-J2S-60CL
MR-J2S-70CL
MR-J2S-100CL
MR-J2S-200CL
2 (AWG14) : a
1.25 (AWG16) : a
MR-J2S-350CL
MR-J2S-500CL
MR-J2S-700CL
3.5 (AWG12) : b
5.5 (AWG10) : b
8 (AWG8) : c
1.25 (AWG16) 2 (AWG14) : a
3.5 (AWG12) : b
(Note 2)
5.5 (AWG10) : b
5.5 (AWG10) : b
8 (AWG8) : c
Note 1. For the crimping terminals and applicable tools, refer to table 14.2.
2. 3.5mm
2 for use of the HC-RFS203 servo motor.
14 - 33
2 (AWG14) : a
3.5(AW12) : c
1.25 (AWG16)
14. OPTIONS AND AUXILIARY EQUIPMENT
Use wires 6) of the following sizes with the power regeneration converter (FR-RC).
Model Wires[mm 2 ]
FR-RC-15K 14(AWG6)
Table 14.2 Recommended crimping terminals
Symbol
Servo amplifier side crimping terminals
Crimping terminal Applicable tool Manufacturer a 32959 b EVD5.5-4 YNT-1210S
Body YF-1 E-4 Japan Solderless
Terminal
Die DH-111 DH-121
(2) Wires for cables
When fabricating a cable, use the wire models given in the following table or equivalent.
Table 14.3 Wires for option cables
Encoder cable
Communication cable
Bus cable
MR-JCCBL M-L
MR-JCCBL M-H
MR-JHSCBL M-L
MR-JHSCBL M-H
MR-ENCBL M-H
MR-J2HBUS M
2 to 10
(6.56 to 32.8)
20 30
(65.6 98.4)
2 5
(6.56 16.4)
10 to 50
(32.8 to 164)
2 5
(6.56 16.4)
10 to 30
(32.8 to 98.4)
2 5
(6.56 16.4)
10 to 50
(32.8 to 164)
2 5
(6.56 16.4)
10 to 50
(32.8 to 164)
0.5 to 5
(1.64 to 16.4)
Core size
[mm 2 ]
0.08
0.3
0.2
0.2
0.08
0.3
0.2
0.2
0.2
0.2
0.08
Number of Cores
Structure
[Wires/mm]
Characteristics of one core
Conductor resistance[ /mm]
Insulation coating
ODd[mm] (Note 1)
12
(6 pairs)
12
(6 pairs)
12
(6 pairs)
14
(7 pairs)
8
(4 pairs)
12
(6 pairs)
8
(4 pairs)
12
(6 pairs)
8
(4 pairs)
12
(6 pairs)
6
7/0.127 222
12/0.18 62
40/0.08 105
40/0.08 105
7/0.127 222
12/0.18 62
40/0.08 105
40/0.08 105
40/0.08 105
40/0.08 105
7/0.127 222
0.38
1.2
0.88
0.88
0.38
1.2
0.88
0.88
0.88
0.88
0.38
(Note 3)
Finishing
OD [mm]
Wire model
6pair (BLACK)
6pair (BLACK)
A14B2343 6P
A14B0238 7P
4pair (BLACK)
6pair (BLACK)
A14B2339 4P
A14B2343 6P
A14B2339 4P
A14B2343 6P
3pair (BLACK)
20
(10 pairs)
7/0.127 222 0.38
10pair (CREAM)
Note 1. d is as shown below. d
Conductor Insulation sheath
2. Purchased from Toa Electric Industry
3. Standard OD. Max. OD is about 10% greater.
14 - 34
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.2 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse instead of the no-fuse breaker, use the one having the specifications given in this section.
Servo amplifier No-fuse breaker
Fuse
Class Current [A] Voltage [V]
MR-J2S-10CL (1) 30 frame 5A
MR-J2S-20CL 30
K5 frame
10
10
MR-J2S-40CL 20CL1
MR-J2S-60CL 40CL1
MR-J2S-70CL
30 frame 10A
30 frame 15A
30 frame 15A
K5
K5
K5
15
20
20
250AC
MR-J2S-100CL
MR-J2S-200CL
MR-J2S-350CL
30 frame 15A
30 frame 20A
30 frame 30A
K5
K5
K5
25
40
70
MR-J2S-500CL 50 frame 50A
MR-J2S-700CL 100
K5 frame
125
150
14.2.3 Power factor improving reactors
Magnetic contactor
S-N10
S-N18
S-N20
S-N35
S-N50
The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be slightly lower than 90%.
[Unit : mm]
([Unit : in.])
NFB
MC
R
FR-BAL
X
Servo amplifier
MR-J2S- CL
L
1
3-phase
200 to 230VAC
S Y
L
2
T Z
L
3
W
D1
Installation screw
NFB MC
R
FR-BAL
X
Servo amplifier
MR-J2S- CL
L
1
RX S Y T Z
(Note)
1-phase
230VAC
S Y
L
2
C W1
T Z
L
3
1-phase
100 to120VAC
NFB
MC
R
FR-BAL
X
Servo amplifier
MR-J2S- CL1
L
1
S Y
L
2
T Z
Note. Connect a 1-phase 230VAC power supply to L
1
/L
2
and keep L
3
open.
Servo amplifier Model
Dimensions [mm (in) ] Mounting
W W1 H D D1 C
MR-J2S-
10CL(1)/20CL
FR-BAL-0.4K 135 (5.31) 120 (4.72) 115 (4.53) 59 (2.32) 45
0
-2.5
(1.77
0
-0.098
) 7.5 (0.29)
MR-J2S-40CL/20CL1
FR-BAL-
0.75K
135 (5.31) 120 (4.72) 115 (4.53) 69 (2.72) 57 (2.24
0
-0.098
) 7.5 (0.29)
MR-J2S-60CL/ 70CL/
40CL1
MR-J2S-100CL
FR-BAL-1.5K 160 (6.30) 145 (5.71) 140 (5.51) 71 (2.79) 55 0
-2.5
(2.17
0
-0.098
) 7.5 (0.29)
MR-J2S-200CL
MR-J2S-350CL
MR-J2S-500CL
MR-J2S-700CL
FR-BAL-2.2K 160 (6.30) 145 (5.71) 140 (5.51) 91 (3.58) 75 0
-2.5
(2.95
0
-0.098
) 7.5 (0.29)
FR-BAL-3.7K 220 (8.66) 200 (7.87) 192 (7.56) 90 (3.54) 70 0
-2.5
(2.76
0
-0.098
) 10 (0.39)
FR-BAL-7.5K 220 (8.66) 200 (7.87) 194 (7.64) 120 (4.72) 100
0
-2.5
(3.94
0
-0.098
) 10 (0.39)
FR-BAL-11K 280 (11.02) 255 (10.04) 220 (8.66) 135 (5.31) 100 0
-2.5
(3.94
FR-BAL-15K 295 (11.61) 270 (10.62) 275 (10.83) 133 (5.24) 110
0
-2.5
(4.33
0
-0.098
0
-0.098
) 12.5 (0.49)
) 12.5 (0.49)
M5
M5
14 - 35
Terminal screw size
M4
M5
Mass
[kg (lb)]
8.5 (18.74)
14.5 (32.0)
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.4 Relays
The following relays should be used with the interfaces.
Relay used for input signals (interface DI-1) signals To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY
Relay used for digital output signals (interface DO-1) Small relay with 12VDC or 24VDC of 40mA or less
(Ex.) Omron : type MY
14.2.5 Surge absorbers
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
Insulate the wiring as shown in the diagram.
Maximum rating
Permissible circuit voltage
Surge immunity
Energy immunity
Rated power
Maximum limit voltage
Static capacity
(reference value)
Varistor voltage rating (range) V1mA
[J] [W] [A] [V] [pF] [V]
220
(198 to 242)
Note. 1 time 8 20 s
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)
13.5 (0.53) 4.7 1.0 (0.19 0.04)
0.8 (0.03)
Vinyl tube
Crimping terminal for M4 screw
14 - 36
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.6 Noise reduction techniques
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and those radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier is an electronic device which handles small signals, the following general noise reduction techniques are required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle them together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal transmission, and connect the shield to the SD terminal.
Ground the servo amplifier, servo motor, etc. together at one point (refer to section 3.10).
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many relays which make a large amount of noise) near the servo amplifier and the servo amplifier may malfunction, the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and other equipment against large exogenous noise and lightning surge, attaching a varistor to the power input section of the equipment is recommended.
14 - 37
14. OPTIONS AND AUXILIARY EQUIPMENT
(c) Techniques for noises radiated by the servo amplifier that cause peripheral devices to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected to the servo amplifier and its main circuits (input and output circuits), those induced electromagnetically or statically by the signal cables of the peripheral devices located near the main circuit cables, and those transmitted through the power supply cables.
Noises produced by servo amplifier
Noises transmitted in the air
Noise radiated directly from servo amplifier
Route 1)
Noise radiated from the power supply cable
Route 2)
Magnetic induction noise
Static induction noise
Noises transmitted through electric channels
Noise radiated from servo motor cable
Routes 4) and 5)
Route 6)
Noise transmitted through power supply cable
Noise sneaking from grounding cable due to leakage current
Route 3)
Route 7)
Route 8)
5)
Instrument
7)
Receiver
7) 7)
2)
3)
1)
Servo amplifier
4)
6)
2)
Sensor
power
supply
Sensor
8)
3)
Servo motor M
14 - 38
14. OPTIONS AND AUXILIARY EQUIPMENT
Noise transmission route
1) 2) 3)
4) 5) 6)
7)
Suppression techniques
When measuring instruments, receivers, sensors, etc. which handle weak signals and may malfunction due to noise and/or their signal cables are contained in a control box together with the servo amplifier or run near the servo amplifier, such devices may malfunction due to noises transmitted through the air. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo amplifier.
3. Avoid laying the power lines (Input cables of the servo amplifier) and signal cables side by side or bundling them together.
4. Insert a line noise filter to the I/O cables or a radio noise filter on the input line.
5. Use shielded wires for signal and power cables or put cables in separate metal conduits.
When the power lines and the signal cables are laid side by side or bundled together, magnetic induction noise and static induction noise will be transmitted through the signal cables and malfunction may occur. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo amplifier.
3. Avoid laying the power lines (Input cables of the servo amplifier) and signal cables side by side or bundling them together.
4. Use shielded wires for signal and power cables or put the cables in separate metal conduits.
When the power supply of peripheral devices is connected to the power supply of the servo amplifier system, noises produced by the servo amplifier may be transmitted back through the power supply cable and the devices may malfunction. The following techniques are required.
1. Insert the radio noise filter (FR-BIF) on the power cables (Input cables) of the servo amplifier.
2. Insert the line noise filter (FR-BSF01 FR-BLF) on the power cables of the servo amplifier.
8)
When the cables of peripheral devices are connected to the servo amplifier to make a closed loop circuit, leakage current may flow to malfunction the peripheral devices. If so, malfunction may be prevented by disconnecting the grounding cable of the peripheral device.
(2) Noise reduction products
(a) Data line filter
Noise can be prevented by installing a data line filter onto the encoder cable, etc.
For example, the ZCAT3035-1330 of TDK and the ESD-SR-25 of NEC Tokin make are available as data line filters.
As a reference example, the impedance specifications of the ZCAT3035-1330 (TDK) are indicated below.
This impedances are reference values and not guaranteed values.
[Unit: mm]([Unit: in.])
Impedance[ ]
39 1(1.54 0.04)
34 1
(1.34 0.04)
Loop for fixing the cable band
10 to 100MHz 100 to 500MHz
80 150
TDK
Product name Lot number
Outline drawing (ZCAT3035-1330)
14 - 39
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge suppressor
The recommended surge suppressor for installation to an AC relay, AC valve, AC electromagnetic brake or the like near the servo amplifier is shown below. Use this product or equivalent.
MC
Relay
Surge suppressor
Surge suppressor
Rated voltage
AC[V]
Surge suppressor This distance should be short
(within 20cm(0.79 in.)).
(Ex.) 972A.2003 50411
(Matsuo Electric Co., Ltd. 200VAC rating)
Outline drawing [Unit: mm] ([Unit: in.])
Vinyl sheath
18 1.5
(0.71 0.06)
Blue vinyl cord Red vinyl cord
6(0.24) Across
T-C 1000(1 to 5s)
10(0.39)or less 10(0.39)or less
4(0.16)
10 3
(0.39
0.12) 200(7.87) or more
15 1(0.59 0.04)
48 1.5
(1.89 0.06)
200(7.87) or more
10 3
(0.39
0.15)
31(1.22)
Note that a diode should be installed to a DC relay, DC valve or the like.
Maximum voltage: Not less than 4 times the drive voltage of the relay or the like
Maximum current: Not less than twice the drive current of the relay or the like
RA
Diode
(c) Cable clamp fitting (AERSBAN - SET)
Generally, the earth of the shielded cable may only be connected to the connector's SD terminal.
However, the effect can be increased by directly connecting the cable to an earth plate as shown below.
Install the earth plate near the servo amplifier for the encoder cable. Peel part of the cable sheath to expose the external conductor, and press that part against the earth plate with the cable clamp.
If the cable is thin, clamp several cables in a bunch.
The clamp comes as a set with the earth plate.
Strip the cable sheath of the clamped area. cutter cable
Cable clamp
(A,B)
Cable
Earth plate
External conductor
Clamp section diagram
14 - 40
14. OPTIONS AND AUXILIARY EQUIPMENT
Outline drawing
Earth plate
2- 5(0.20) hole installation hole
17.5(0.69)
[Unit: mm]
([Unit: in.])
Clamp section diagram
L or less 10(0.39)
0 0.
(Note)M4 screw
6
(0.24) 35(1.38)
22(0.87)
Note: Screw hole for grounding. Connect it to the earth plate of the control box.
AERSBAN-DSET
AERSBAN-ESET
100
(3.94)
70
(2.76)
86
(3.39)
56
(2.20)
30
(1.18) clamp A: 2pcs. clamp B: 1pc.
A
B
70
(2.76)
45
(1.77)
14 - 41
14. OPTIONS AND AUXILIARY EQUIPMENT
(d) Line noise filter (FR-BLF, FR-BSF01)
This filter is effective in suppressing noises radiated from the power supply side and output side of the servo amplifier and also in suppressing high-frequency leakage current (zero-phase current) especially within 0.5MHz to 5MHz band.
Connection diagram
Use the line noise filters for wires of the main power supply
(L
1
L
2
L
3
) and of the motor power supply (U V W). Pass each of the 3-phase wires through the line noise filter an equal number of times in the same direction. For the main power supply, the effect of the filter rises as the number of passes increases, but generally four passes would be appropriate. For the motor power supply, passes must be four times or less. Do not pass the grounding (earth) wire through the filter, or the effect of the filter will drop. Wind the wires by passing through the filter to satisfy the required number of passes as shown in
Example 1. If the wires are too thick to wind, use two or more filters to have the required number of passes as shown in
Example 2. Place the line noise filters as close to the servo amplifier as possible for their best performance.
Example 1
NFB MC
Servo amplifier
Outline drawing [Unit: mm] ([Unit: in.])
FR-BSF01(for MR-J2S-200CL or less)
Approx.110 (4.33)
95 0.5 (3.74 0.02)
Approx.65 (2.56)
33 (1.30)
2- 5(0.20)
Power supply
FR-BLF(MR-J2S-350CL or more)
Example 2
L
1
L
2
Line noise
L
3 filter
(Number of turns: 4)
NFB MC
Servo amplifier
7(0.28)
130(5.12)
85(3.35)
Power supply
L
1
Line noise filter
L
2
L
3
Two filters are used
(Total number of turns: 4)
160(6.30)
180(7.09)
(e) Radio noise filter (FR-BIF)...for the input side only
This filter is effective in suppressing noises radiated from the power supply side of the servo amplifier especially in 10MHz and lower radio frequency bands. The FR-BIF is designed for the input only.
Connection diagram
Make the connection cables as short as possible.
Grounding is always required.
When using the FR-BIF with a single-phase wire, always insulate the wires that are not used for wiring.
NFB MC Servo amplifier
Power supply
L
1
L
2
L
3
Outline drawing (Unit: mm) ([Unit: in.])
Leakage current: 4mA
Red White Blue Green
29 (1.14)
5 (0.20) hole
Radio noise filter FR-BIF
58 (2.28) 29 (1.14)
44 (1.73)
7 (0.28)
14 - 42
14. OPTIONS AND AUXILIARY EQUIPMENT
(f) Varistors for input power supply (Recommended)
Varistors are effective to prevent exogenous noise and lightning surge from entering the servo amplifier. When using a varistor, connect it between each phase of the input power supply of the equipment. For varistors, the TND20V-431K and TND20V-471K, manufactured by NIPPON
CHEMI-CON, are recommended. For detailed specification and usage of the varistors, refer to the manufacturer catalog.
Varistor
Permissible circuit voltage
Maximum rating
Surge current immunity
Energy immunity
Rated pulse power
Maximum limit voltage
Static capacity
(reference value)
AC[V rms
] DC[V] 8/20 s[A] 2ms[J] [W] [A] [V] [pF]
Varistor voltage rating (range)
V1mA
[V]
195
1.0 100
775
1300 430(387 to 473)
1200 470(423 to 517)
D T Model
D
Max.
H
Max.
T
Max.
E
1.0
(Note)L min. d
0.05
[Unit: mm]
W
1.0
TND20V-471K 6.6 3.5
Note. For special purpose items for lead length (L), contact the manufacturer.
W
d
E
14 - 43
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.7 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier, servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as possible (about 30cm (11.8 in)) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(14.1)
K: Constant considering the harmonic contents
Cable
Leakage current breaker
K products
NV Noise filter
Servo amplifier
Cable
M
Models provided with harmonic and surge reduction techniques
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
1
Ig1 Ign Iga Ig2 Igm
General models
BV-C1
NFB
NV-L
3
Ig1: Leakage current on the electric channel from the leakage current breaker to the input terminals of the servo amplifier (Found from Fig. 14.1.)
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo motor (Found from Fig. 14.1.)
Ign: Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Iga: Leakage current of the servo amplifier (Found from Table 14.5.)
Igm: Leakage current of the servo motor (Found from Table 14.4.)
120
Table 14.4 Servo motor's leakage current
100 example (Igm)
80
Servo motor output [kW]
Leakage current [mA]
Table 14.5 Servo amplifier's
leakage current
example (Iga)
Servo amplifier capacity [kW]
Leakage current [mA]
60
40
0.05 to 0.5
0.6 to 1.0
1.2 to 2.2
0.1
0.1
0.2
0.1 to 0.6
0.7 to 3.5
0.1
0.15
5 7 2
[mA]
20 3 to 3.5 0.3
5 0.5
0
2 3.5
5.5
8 1422 38 80 150
30 60 100
Cable size[mm 2 ]
Fig. 14.1 Leakage current example
(Ig1, Ig2) for CV cable run
in metal conduit
Servo amplifier
Rated sensitivity current of leakage circuit breaker [mA]
MR-J2S-10C L to MR-J2S-350C L
MR-J2S-10C L 1 to MR-J2S-40C L 1
15
MR-J2S-500C L 30
MR-J2S-700C L 50
14 - 44
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions.
2mm 2 5m(196.85inch) 2mm 2 5m(196.85inch)
NV
Servo amplifier
MR-J2S-40CL
M
Servo motor
HC-MFS43
Ig1 Iga Ig2 Igm
Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (14.1) from the diagram.
Ig1 20
5
1000
0.1 [mA]
Ig2 20
5
1000
0.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (14.1).
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/ SW/CW/HW series.
14 - 45
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.8 EMC filter
For compliance with the EMC Directive of the EN Standard, it is recommended to use the following filter.
Some EMC filters are large in leakage current.
(1) Combination with the servo amplifier
Servo amplifier
Recommended filter
Model Leakage current [mA]
Mass [kg]([lb])
MR-J2S-10CL to MR-J2S-100CL
MR-J2S-10CL1 to MR-J2S-40CL1
SF1252 38
MR-J2S-200CL MR-J2S-350CL SF1253
MR-J2S-500CL (Note) HF-3040A-TM
57
1.5
(1.65)
1.37
5.5 (12.13)
MR-J2S-700CL (Note) HF-3050A-TM 1.5 6.7 (14.77)
Note. Soshin Electric. A surge protector is separately required to use any of these EMC filters. (Refer to the EMC Installation
Guidelines.)
(2) Connection example
EMC filter
(SOSHIN Electric Co., Ltd)
(Note 1)
Power supply
NFB
EMC filter
(SF1252, SF1253)
LINE LOAD
L
1
L
1
L
2
L
3
L
L
2
3
(Note 2)
MC
Servo amplifier
L
1
L
2
(Note 1)
Power supply
L
3
L
11
L
21
NFB
1
2
3 6
E
4
5
MC
Servo amplifier
L
1
L
2
L
3
L
11
L
21
1
2
3
Surge protector 1
(RAV-781BYZ-2)
(OKAYA Electric Industries
Co., Ltd.)
1 2 3
Surge protector 2
(RAV-781BXZ-4)
(OKAYA Electric Industries Co., Ltd.)
Note 1. For 1-phase 230VAC power supply, connect the power supply to L
1
,L
2
and leave L
3
open.
There is no L
3
for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
2. Connect when the power supply has earth.
14 - 46
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawing
(a) EMC filter
SF1252
149.5(5.886)
L1
L2
L3
6.0(0.236)
LINE
(input side)
SF1253
209.5(8.248)
L1
L2
L3
[Unit: mm(in)]
6.0(0.236)
LINE
(input side)
L1'
L2'
L3'
LOAD
(output side)
8.5
(0.335)
42.0
(1.654)
16.0(0.63)
HF3040-TM HF3050A-TM
6-K
3-L 3-L
L1'
L2'
L3'
LOAD
(output side)
8.5
(0.335)
23.0(0.906)
49.0
(1.929)
M
C 1
B 2
A 5
C 1
H 2
J 2
Model
HF3040A-TM
HF3050A-TM
Dimensions [mm(in)]
A B C D E F G H J K L M
260
(10.23)
290
(11.42)
210
(8.27)
240
(9.45)
85
(3.35)
100
(3.94)
155
(6.10)
190
(7.48)
140
(5.51)
175
(6.89)
125
(4.92)
160
(6.30)
44
(1.73)
44
(1.73)
140
(5.51)
170
(5.51)
70
(2.76)
100
(3.94)
R3.25, length 8
M5 M4
M6 M4
14 - 47
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge protector
RAV-781BYZ-2
4.2 0.2
[Unit: mm]
1) 2)
Black Black
3)
Black
30 0
UL-1015AWG16
1 2 3
4.2 0.2
41 1.0
RAV-781BXZ-4 [Unit: mm]
1) 2) 3) 4)
30 0
UL-1015AWG16
1 2 3
41 1.0
14 - 48
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.9 Setting potentiometers for analog inputs
The following variable resistors are available for use with analog inputs.
(1) Single-revolution type
WA2WYA2SEBK2K (Japan Resistor make)
Rated power Resistance
Resistance tolerance
Dielectric strength
(for 1 minute)
Insulation resistance
2W 2k
Connection diagram Outline dimension drawing
[Unit: mm (in)]
Mechanical rotary angle
300 5
Rotary torque
10 to 100g-cm or less
Panel hole machining diagram
[Unit: mm (in)]
20 (0.79) 25 (0.98)
10 (0.39)
30 (1.18)
2.8 (0.11)
2.5 (0.10)
3.6 (0.14) hole
1.6 (0.06)
10 (0.37) hole
1 2 3
M9 0.75 (0.03)
.9
8)
R2
5
(0
3- 1.54 (0.56) hole
3
(0.08)
Connection diagram
1 3
1 30
2
30 3
(2) Multi-revolution type
Position meter: RRS10M202 (Japan Resistor make)
Analog dial: 23M (Japan Resistor make)
Rated power Resistance
1W 2k
Resistance tolerance
Dielectric strength
(for 1 minute)
A.C
Insulation resistance
Mechanical rotary angle
3600
10
0
Panel hole machining diagram
Rotary torque
100g-cm or less
[Unit: mm (in)]
Panel thickness: 2 to 6 (0.08 to 0.24)
2
CW
9 (0.35) hole
2.1 (0.08) hole
Outline dimension drawing
RRS10 M202
2) 1)
3)
M9 0.75 (0.03)
2)
[Unit: mm (in)]
30
1)
3)
23M
15 (0.59)
[Unit: mm (in)]
12.5 (0.49)
L
7.5
(0.3)
1.2
(0.05)
23 (0.91)
12 (0.47) 6 (0.24)
20.5
(0.81)
14 - 49
14. OPTIONS AND AUXILIARY EQUIPMENT
MEMO
14 - 50
15. COMMUNICATION FUNCTIONS
15. COMMUNICATION FUNCTIONS
This servo amplifier has the RS-422 and RS-232C serial communication functions. These functions can be used to perform servo operation, parameter changing, monitor function, etc.
However, the RS-422 and RS-232C communication functions cannot be used together. Select between RS-
422 and RS-232C with parameter No.16. (Refer to section 15.2.2.)
15.1 Configuration
15.1.1 RS-422 configuration
(1) Outline
Up to 32 axes of servo amplifiers from stations 0 to 31 can be operated on the same bus.
Servo amplifier
MITSUBISHI
Servo amplifier
MITSUBISHI
Servo amplifier
MITSUBISHI
Controller such as personal computer
CHARGE
To CN3
CHARGE
To CN3
RS-232C/
RS-422 converter
Axis 1 (Station 0) Axis 2 (Station 1)
Unavailable as option.
To be prepared by customer.
RS-422
(2) Cable connection diagram
Wire as shown below.
(Note 3) 30m (98.4ft) or less
(Note 1)
Axis 1 servo amplifier
CN3 connector
Plate SD
9
19
SDP
SDN
5
15
10
11
1
RDP
RDN
TRE
LG
LG
(Note 1)
Axis 2 servo amplifier
CN3 connector
Plate
9
19
5
15
10
11
1
SD
SDP
SDN
RDP
RDN
TRE
LG
LG
RS-422 output unit
RDP
RDN
SDP
SDN
GND
GND
Note 1. Connector set MR-J2CN1 (3M)
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
2. In the last axis, connect TRE and RDN.
3. 30m (98.4ft) or less in environment of little noise.
15 - 1
CHARGE
To CN3
Axis 32 (Station 31)
(Note 1)
Axis 32 (last axis) servo amplifier
CN3 connector
Plate
9
19
5
15
10
11
1
SD
SDP
SDN
RDP
RDN
TRE (Note 2)
LG
LG
15. COMMUNICATION FUNCTIONS
15.1.2 RS-232C configuration
(1) Outline
A single axis of servo amplifier is operated.
Servo amplifier
MITSUBISHI
CHARGE To CN3
RS-232C
Controller such as personal computer
(2) Cable connection diagram
Wire as shown below. The communication cable for connection with the personal computer (MR-
CPCATCBL3M) is available. (Refer to section 14.1.4.)
Personal computer connector D-SUB9 (socket)
(Note 2) 15m (49.2ft) or less
(Note 1)
Servo amplifier
CN3 connector
TXD 3
Plate
2
1
12
11
FG
RXD
GND
TXD
GND
RXD
GND
RTS
CTS
DSR
DTR
2
5
7
8
6
4
Note 1. Connector set MR-J2CN1 (3M)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
2. 15m (49.2ft) or less in environment of little noise. However, this distance should be 3m (9.84ft) or less for use at
38400bps or more baud rate.
15 - 2
15. COMMUNICATION FUNCTIONS
15.2 Communication specifications
15.2.1 Communication overview
This servo amplifier is designed to send a reply on receipt of an instruction. The device which gives this instruction (e.g. personal computer) is called a master station and the device which sends a reply in response to the instruction (servo amplifier) is called a slave station. When fetching data successively, the master station repeatedly commands the slave station to send data.
Item Description
Baud rate
Transfer code
9600/19200/38400/57600 asynchronous system
Start bit
Data bit
: 1 bit
: 8 bits
Parity bit : 1 bit (even)
Stop bit : 1 bit
Transfer protocol Character system, half-duplex communication system
(LSB) (MSB)
Start
0 1 2 3 4 5 6 7 Parity Stop
Next start
Data
1 frame (11bits)
15 - 3
15. COMMUNICATION FUNCTIONS
15.2.2 Parameter setting
When the RS-422/RS-232C communication function is used to operate the servo, set the communication specifications of the servo amplifier in the corresponding parameters.
After setting the values of these parameters, they are made valid by switching power off once, then on again.
(1) Serial communication baud rate
Choose the communication speed. Match this value to the communication speed of the sending end
(master station).
Parameter No. 16
Communication baud rate
0: 9600[bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
(2) Serial communication selection
Select the RS-422 or RS-232C communication standard. RS-422 and RS-232C cannot be used together.
Parameter No. 16
Serial communication standard selection
0: RS-232C used
1: RS-422 used
(3) Serial communication response delay time
Set the time from when the servo amplifier (slave station) receives communication data to when it sends back data. Set "0" to send back data in less than 800 s or "1" to send back data in 800 s or more.
Parameter No. 16
Serial communication response delay time
0: Invalid
1: Valid, reply sent in 800 s or more
(4) Station number setting
Set the station number of the servo amplifier in parameter No. 15. The setting range is stations 0 to
31.
(5) Protocol station number selection
When communication is made without setting station numbers to servo amplifiers, choose "no station numbers" in parameter No. 57. The communication protocol will be free of station numbers.
Parameter No. 57
Protocol station number selection
0: With station numbers
1: No station numbers
15 - 4
15. COMMUNICATION FUNCTIONS
15.3 Protocol
POINT
Whether station number setting will be made or not must be selected if the RS-232C communication function is used. Note that choosing "no station numbers" in parameter No. 57 will make the communication protocol free of station numbers.
Since up to 32 axes may be connected to the bus, add a station number or group to the command, data
No., etc. to determine the destination servo amplifier of data communication. Set the station number to each servo amplifier using the parameter and set the group to each station using the communication command. Transmission data is valid for the servo amplifier of the specified station number or group.
When "*" is set as the station number added to the transmission data, the transmission data is made valid for all servo amplifiers connected. However, when return data is required from the servo amplifier in response to the transmission data, set "0" to the station number of the servo amplifier which must provide the return data.
(1) Transmission of data from the controller to the servo
Controller side
(Master station)
S
O
H
S
T
X
Data
No.
Data*
E
T
X
Check sum
10 frames (data)
Station number or group
Servo side
(Slave station)
Station number or group
S
T
X
E
T
X
Check sum
6 frames
Positive response: Error code A
Negative response: Error code other than A
(2) Transmission of data request from the controller to the servo
10 frames
Controller side
(Master station)
S
O
H
S
T
X
Data
No.
E
T
X
Check sum
Station number or group
Servo side
(Slave station)
Station number or group
S
T
X
Data*
6 frames (data)
E
T
X
Check sum
15 - 5
15. COMMUNICATION FUNCTIONS
(3) Recovery of communication status by time-out
Controller side
(Master station)
E
O
T
EOT causes the servo to return to the receive neutral status.
Servo side
(Slave station)
(4) Data frames
The data length depends on the command. or Data
4 frames
Data
8 frames or 12 frames or 16 frames
15 - 6
15. COMMUNICATION FUNCTIONS
15.4 Character codes
(1) Control codes
Code name
Hexadecimal
(ASCII code)
SOH
STX
ETX
01H
02H
03H
EOT 04H
(2) Codes for data
ASCII codes are used.
Description start of head start of text end of text end of transmission
Personal computer terminal key operation
(General) ctrl A ctrl B ctrl C ctrl D b
8 b
7 b
6 b
5
0 0 0 0 0 0 0 0
0 0 0 0 1 1 1 1
0 0 1 1 0 0 1 1
0 1 0 1 0 1 0 1 b
8
to b
5 b
4
b
3
b
2
b
1
R
C
0 1 2 3 4 5 6 7
0 0 0 0 0 NUL DLE Space 0 @ P ` p
0 0 0 1 1 SOH DC
1
! 1
0 0 1 0 2 STX DC
2
“ 2
0 0 1 1 3 ETX DC
3
# 3
0 1 0 0 4
0 1 0 1 5
0 1 1 0 6
0 1 1 1 7
1 0 0 0 8
1 0 0 1 9
1 0 1 0 10
1 0 1 1 11
1 1 0 0 12 , L l |
1 1 0 1 13
1 1 1 0 14 . N ^ n
_
1 1 1 1 15
(3) Station numbers
You may set 32 station numbers from station 0 to station 31 and the ASCII unit codes are used to specify the stations.
Station number
ASCII code
Station number
ASCII code
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 A B C D E F
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
G H I J K L M N O P Q R S T U V
For example, "30H" is transmitted in hexadecimal for the station number of "0" (axis 1).
(4) Group
Group
ASCII code a b c d e f
For example, "61H" is transmitted in hexadecimal for group a.
15 - 7
15. COMMUNICATION FUNCTIONS
15.5 Error codes
Error codes are used in the following cases and an error code of single-code length is transmitted.
On receipt of data from the master station, the slave station sends the error code corresponding to that data to the master station.
The error code sent in upper case indicates that the servo is normal and the one in lower case indicates that an alarm occurred.
Error code
Servo normal Servo alarm
[A]
[B]
[C]
[a]
[b]
[c]
Error name Description
Normal operation Data transmitted was processed properly.
Parity error Parity error occurred in the transmitted data.
Checksum error Checksum error occurred in the transmitted data.
Remarks
Positive response
Negative response
15.6 Checksum
The checksum is a ASCII-coded hexadecimal representing the lower two digits of the sum of ASCII-coded hexadecimal numbers up to ETX, with the exception of the first control code (STX or SOH).
Station number (Example) or group
S E
T [0] [A] [1] [2] [5] [F] T [5] [2]
X X
02H 30H 41H 31H 32H 35H 46H 03H
STX or
SOH
ETX Check
30H 41H 31H 32H 35H 46H 03H
152H
Checksum range
Lower 2 digits 52 is sent after conversion into ASCII code [5][2].
15 - 8
15. COMMUNICATION FUNCTIONS
15.7 Time-out operation
The master station transmits EOT when the slave station does not start reply operation (STX is not received) 300[ms] after the master station has ended communication operation. 100[ms] after that, the master station retransmits the message. Time-out occurs if the slave station does not answer after the master station has performed the above operation three times. (Communication error)
100ms 100ms 100ms
300ms 300ms 300ms 300ms
*Time-out
Controller
(Master station)
E
O
T
E
O
T
E
O
T
Servo
(Slave station)
15.8 Retry operation
When a fault occurs in communication between the master and slave stations, the error code in the response data from the slave station is a negative response code ([B] to [F], [b] to [f]). In this case, the master station retransmits the message which was sent at the occurrence of the fault (Retry operation). A communication error occurs if the above operation is repeated and results in the error three or more consecutive times.
*Communication error
Controller
(Master station)
Servo
(Slave station)
S
T
X
S
T
X
S
T
X
Station number or group
Station number or group
Station number or group
Similarly, when the master station detects a fault (e.g. checksum, parity) in the response data from the slave station, the master station retransmits the message which was sent at the occurrence of the fault. A communication error occurs if the retry operation is performed three times.
15 - 9
15. COMMUNICATION FUNCTIONS
15.9 Initialization
After the slave station is switched on, it cannot reply to communication until the internal initialization processing terminates. Hence, at power-on, ordinary communication should be started after.
(1) 1s or more time has elapsed after the slave station is switched on; and
(2) Making sure that normal communication can be made by reading the parameter or other data which does not pose any safety problems.
15.10 Communication procedure example
The following example reads the set value of parameter No.2 "function selection 1" from the servo amplifier of station 0.
Data item Value Description
Station number 0 Servo amplifier station 0
Data No. 02 Parameter No.2
Axis No. Command Data No.
Start
Data make-up
Checksum calculation and addition
Addition of SOH to make up transmission data
Data [0] 0 5 STX 0 2 ETX
ETX
Checksum 30H 30H 35H 02H 30H 32H 03H FCH
Transmission data SOH 0 0 5 STX 0 2 ETX F C 46H 43H
Master station slave station
Data transmission
Data receive
Master station slave station
No
Is there receive data?
Yes
No
300ms elapsed?
Yes
No
Yes
3 consecutive times?
Other than error code
[A] [a]?
No
Yes
Receive data analysis
Error processing
End
Error processing
No
3 consecutive times?
Yes
100ms after EOT transmission
Master station slave station
15 - 10
15. COMMUNICATION FUNCTIONS
15.11 Command and data No. list
POINT
If the command/data No. is the same, its data may be different from the interface and drive units and other servo amplifiers.
15.11.1 Read commands
(1) Status display (Command [0][1])
Command Data No.
[1][2]
[1][2]
Description
[8][0] Output device statuses
[C][0] External output pin statuses
Display item
[0][1] [8][2]
[0][1] [8][3]
[0][1] [8][4]
[0][1] [8][5]
[0][1] [8][6]
[0][1] [8][7]
[0][1] [8][8]
[0][1] [8][9]
[0][1] [8][A]
[0][1]
[0][1]
[8][B]
[8][C]
[0][1] [8][D]
[0][1] [8][E]
[0][1] [8][F]
[0][1] [9][0]
[0][1] [9][1]
(2) Parameter (Command [0][5])
Command remaining distance
Cumulative feedback pulses
Override
Regenerative load ratio
Effective load ratio
Peak load ratio
Within one-revolution position
Load inertia moment ratio
Bus voltage
Description
[0][5]
[0][0] to
[5][A]
Current value of each parameter
The decimal equivalent of the data No. value (hexadecimal) corresponds to the parameter number.
(3) External I/O signals (Command [1][2])
Description
[1][2]
[1][2]
[0][0] Input device statuses
[4][0] External input pin statuses
Frame length
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
8
8
8
8
8
8
15 - 11
15. COMMUNICATION FUNCTIONS
(4) Alarm history (Command [3][3])
Command Data No. Description
[3][3]
[3][3]
[3][3]
[3][3]
[1][0]
[1][1]
[1][2]
[1][3]
Alarm number in alarm history
[3][3] [1][4]
[3][3] [1][5]
[3][3]
[3][3]
[2][0]
[2][1]
Alarm occurrence time in alarm history
[3][3]
[3][3]
[3][3]
[2][2]
[2][3]
[2][4]
[3][3] [2][5]
(5) Current alarm (Command [0][2] [3][5])
Description
Alarm occurrence sequence
Most recent alarm
First alarm in past
Second alarm in past
Third alarm in past
Fourth alarm in past
Fifth alarm in past
Most recent alarm
First alarm in past
Second alarm in past
Third alarm in past
Fourth alarm in past
Fifth alarm in past
[0][2] [0][0] Current alarm number
Command Data No. Description Status display item
Frame length
8
8
4
4
4
4
4
4
8
8
8
8
[3][5] [8][2] occurrence
[3][5] [8][3]
[3][5] [8][4]
[3][5] [8][5]
[3][5] [8][6]
[3][5] [8][7]
[3][5] [8][8]
[3][5] [8][9]
[3][5] [8][A]
[3][5]
[3][5]
[8][B]
[8][C]
[3][5] [8][D]
[3][5] [8][E]
[3][5] [8][F]
[3][5] [9][0]
[3][5] [9][1]
Command remaining distance
Cumulative feedback pulses
Servo speed
Override
Regenerative load ratio
Effective load ratio
Peak load ratio
Within one-revolution position
Load inertia moment ratio
Bus voltage
4
Frame length
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
15 - 12
15. COMMUNICATION FUNCTIONS
(6) Current position latch data (Command [6][C])
Description
(7) General-purpose register (Rx) value (Command [6][D])
Description
[6][D]
[6][D]
[6][D]
[0][1] The value of the general-purpose register (R1)
[0][2] The value of the general-purpose register (R2)
[0][3] The value of the general-purpose register (R3)
[6][D] [0][4] The value of the general-purpose register (R4)
(8) General-purpose register (Dx) value (Command [6][E])
Description
[6][E]
[6][E]
[6][E]
[0][1] The value of the general-purpose register (D1)
[0][2] The value of the general-purpose register (D2)
[0][3] The value of the general-purpose register (D3)
[6][E] [0][4] The value of the general-purpose register (D4)
(9) Group setting (Command [1][F])
Description
(10) Software version (Command [0][2])
Description
8
8
8
8
4
8
8
8
8
8
16
15 - 13
15. COMMUNICATION FUNCTIONS
15.11.2 Write commands
(1) Status display (Command [8][1])
Command Data No. Description
(2) Parameter (Command [8][4])
Command Data No. Description
[8][4]
[0][0] to
[5][A]
Each parameter write
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the parameter number.
(3) External I/O signal (Command [9][2])
Command Data No. Description
Setting range Frame length
1EA5 4
Setting range Frame length
Depends on the parameter. 8
Setting range Frame length
Refer to section 15.12.5
8
(4) Alarm history (Command [8][2])
Command Data No.
(5) Current alarm (Command [8][2])
Command Data No.
Description
Description
(6) General-purpose register (Rx) value (Command [B][9])
Command Data No. Description
[B][9]
[B][9]
[B][9]
[0][1] The value of the general-purpose register (R1)
[0][2] The value of the general-purpose register (R2)
[0][3] The value of the general-purpose register (R3)
[B][9] [0][4] The value of the general-purpose register (R4)
(7) General-purpose register (Dx) value (Command [B][A])
Command Data No.
[B][A]
[B][A]
[B][A]
[B][A]
[0][1]
[0][2]
[0][3]
[0][4]
Description
The value of the general-purpose register (D1)
The value of the general-purpose register (D2)
The value of the general-purpose register (D3)
The value of the general-purpose register (D4)
Setting range Frame length
1EA5 4
Setting range Frame length
1EA5 4
Setting range Frame length
Depends on the used instruction.
4
Setting range Frame length
Depends on the used instruction.
4
15 - 14
15. COMMUNICATION FUNCTIONS
(8) External input signal disable (Command [9][0])
Command Data No. Description
Turns off the input devices, external analog input signals
[9][0] [0][3]
LSN, independently of the external ON/OFF statuses.
Disables all output devices (DO).
Enables the disabled input devices (DI), external analog
[9][0] [1][0]
EMG, LSP and LSN.
[9][0] [1][3] Enables the disabled output devices (DO).
(9) Operation mode selection (Command [8][B])
Command Data No. Description
Operation mode changing
0000: Exit from test operation mode
Setting range Frame length
1EA5 4
1EA5 4
1EA5 4
1EA5 4
Setting range Frame length
0000 to 0004 4
0003: Motor-less operation
0004: Output signal (DO) forced output
(10) Data for test operation mode (Command [9][2] [A][0])
Command Data No. Description
Command Data No. Description
Setting range Frame length
Refer to section 15.12.7
Refer to section 15.12.9
8
8
Setting range Frame length
0000 to 7FFF
00000000 to
7FFFFFFF
4
8
1EA5 4
80000000 to
7FFFFFFF
8
1EA5 4
(11) Group setting (Command [9][F])
Command Data No.
[9][F] [0][0] Setting of group
Description Setting range Frame length a to f 4
15 - 15
15. COMMUNICATION FUNCTIONS
15.12 Detailed explanations of commands
15.12.1 Data processing
When the master station transmits a command data No. or a command data No. data to a slave station, the servo amplifier returns a reply or data according to the purpose.
When numerical values are represented in these send data and receive data, they are represented in decimal, hexadecimal, etc.
Therefore, data must be processed according to the application.
Since whether data must be processed or not and how to process data depend on the monitoring, parameters, etc., follow the detailed explanation of the corresponding command.
The following methods are how to process send and receive data when reading and writing data.
(1) Processing the read data
When the display type is 0, the eight-character data is converted from hexadecimal to decimal and a decimal point is placed according to the decimal point position information.
When the display type is 1, the eight-character data is used unchanged.
The following example indicates how to process the receive data "003000000929" given to show.
The receive data is as follows.
0 0 3 0 0 0 0 0 0 9 2 9
Data 32-bits length (hexadecimal representation)
(Data conversion is required as indicated in the display type)
Display type
0: Data must be converted into decimal.
1: Data is used unchanged in hexadecimal.
Decimal point position
0: No decimal point
1: First least significant digit (normally not used)
2: Second least significant digit
3: Third least significant digit
4: Forth least significant digit
5: Fifth least significant digit
6: Sixth least significant digit
Since the display type is "0" in this case, the hexadecimal data is converted into decimal.
00000929H 2345
As the decimal point position is "3", a decimal point is placed in the third least significant digit.
Hence, "23.45" is displayed.
15 - 16
15. COMMUNICATION FUNCTIONS
(2) Writing the processed data
When the data to be written is handled as decimal, the decimal point position must be specified. If it is not specified, the data cannot be written. When the data is handled as hexadecimal, specify "0" as the decimal point position.
The data to be sent is the following value.
0
Data is transferred in hexadecimal.
Decimal point position
0: No decimal point
1: First least significant digit
2: Second least significant digit
3: Third least significant digit
4: Forth least significant digit
5: Fifth least significant digit
By way of example, here is described how to process the set data when a value of "15.5" is sent. Since the decimal point position is the second digit, the decimal point position data is "2". As the data to be sent is hexadecimal, the decimal data is converted into hexadecimal.
155 9B
Hence, "0200009B" is transmitted.
15 - 17
15. COMMUNICATION FUNCTIONS
15.12.2 Status display
(1) Status display data read
When the master station transmits the data No. to the slave station, the slave station sends back the data value and data processing information.
(a) Transmission
Transmit command [0][1] and the data No. corresponding to the status display item to be read.
Refer to section 15.11.1.
(b) Reply
The slave station sends back the status display data requested.
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
(2) Status display data clear
The cumulative feedback pulse data of the status display is cleared. Send this command immediately after reading the status display item. The data of the status display item transmitted is cleared to zero.
Command Data Data
[8][1] [0][0] 1EA5
For example, after sending command [0][1] and data No. [8][0] and receiving the status display data, send command [8][1], data No. [0][0] and data [1EA5] to clear the cumulative feedback pulse value to zero.
15 - 18
15. COMMUNICATION FUNCTIONS
15.12.3 Parameter
(1) Parameter read
Read the parameter setting.
(a) Transmission
Transmit command [0][5] and the data No. corresponding to the parameter No.
Data No. definition Command Data No.
[0][5]
[0][0] to
[5][A]
Corresponds to the parameter No.
(b) Reply
The slave station sends back the data and processing information of the requested parameter No.
Data is transferred in hexadecimal.
0
Decimal point position
0: No decimal point
1: Lower first digit
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Parameter write type
0: Valid after write
1: Valid when power is switched on again after write
Read enable/disable
0: Read enable
1: Read disable
Enable/disable information changes according to the setting of parameter No.19 "parameter write inhibit". When the enable/disable setting is read disable, ignore the parameter data part and process it as unreadable.
15 - 19
15. COMMUNICATION FUNCTIONS
(2) Parameter write
POINT
If setting values need to be changed with a high frequency (i.e. one time or more per one hour), write the setting values to the RAM, not the EEP-
ROM. The EEP-ROM has a limitation in the number of write times and exceeding this limitation causes the servo amplifier to malfunction. Note that the number of write times to the EEP-ROM is limited to approximately 100, 000.
Write the parameter setting.
Write the value within the setting range. Refer to section 5.1 for the setting range.
Transmit command [8][4], the data No., and the set data.
The data number is represented in hexadecimal. The decimal value converted from the data number value corresponds to the parameter number. Refer to (1) (a) in this section.
When the data to be written is handled as decimal, the decimal point position must be specified. If it is not specified, data cannot be written. When the data is handled as hexadecimal, specify 0 as the decimal point position.
Write the data after making sure that it is within the upper/lower limit value range given in section
5.1.2. Read the parameter data to be written, confirm the decimal point position, and create transmission data to prevent error occurrence. On completion of write, read the same parameter data to verify that data has been written correctly.
Command
[8][4]
Data No.
[0][0] to
[5][A]
See below.
Set data
Data is transferred in hexadecimal.
Decimal point position
0: No decimal point
1: Lower first digit
2: Lower second digit
3: Lower third digit
4: Lower forth digit
5: Lower fifth digit
Write mode
0: Write to EEP-ROM
3: Write to RAM
When the parameter data is changed frequently through communication, set "3" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour), do not write it to the EEP-ROM.
15 - 20
15. COMMUNICATION FUNCTIONS
15.12.4 External I/O signal statuses
(1) Reading of input device statuses
Read the statuses of the input devices.
(a) Transmission
Transmit command [1][2] and data No. [0][0].
[1][2] [0][0]
(b) Reply
The slave station sends back the statuses of the input pins. b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master station as hexadecimal data.
0 Servo-on (SON) 12 Reverse rotation start (ST2) 24 Temporary stop/restart (STP)
1 Forward rotation stroke limit (LSP) 13
2 Reverse rotation stroke limit (LSN) 14
3 External torque limit selection (TL) 15
4 Internal torque limit selection (TL2) 16 Forced stop (EMG)
5 Proportion control selection (PC) 17 Automatic/manual selection (MD0)
25
26
Manual pulse generator multiplication 1 (TP0)
Manual pulse generator multiplication 2 (TP1)
27 Gain switch (CDP)
6 Reset (RES) 18 Proximity dog (DOG) 28
7
8
9
19 Program No. selection 1 (DI0)
20 Program No. selection 2 (DI1)
21 Program No. selection 3 (DI2)
29 Program input 1 (PI1)
30 Program input 2 (PI2)
31 Program input 3 (PI3)
10 Current position latch input (LPS) 22 Program No. selection 4 (DI3)
11 Forward rotation start (ST1) 23 Override selection (OVR)
(2) External input pin status read
Read the ON/OFF statuses of the external output pins.
(a) Transmission
Transmit command [1][2] and data No. [4][0].
[1][2] [4][0]
(b) Reply
The ON/OFF statuses of the input pins are sent back. b31 b1 b0
1:ON
0:OFF bit
Command of each bit is transmitted to the master station as hexadecimal data.
External input pin
0 CN1B-16
1 CN1B-17
2 CN1B-15
3 CN1B-5
4 CN1B-14 bit External input pin
5 CN1A-8
6 CN1B-7
7 CN1B-8
8 CN1B-9
9 CN1A-19
15 - 21
15. COMMUNICATION FUNCTIONS
(3) Read of the statuses of input devices switched on through communication
Read the ON/OFF statuses of the input devices switched on through communication.
(a) Transmission
Transmit command [1][2] and data No. [6][0].
[1][2] [6][0]
(b) Reply
The slave station sends back the statuses of the input pins. b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master station as hexadecimal data.
0 Servo-on (SON) 12 Reverse rotation start (ST2)
1 Forward rotation stroke limit (LSP) 13
2 Reverse rotation stroke limit (LSN) 14
3 External torque limit selection (TL) 15
4 Internal torque limit selection (TL2) 16 Forced stop (EMG)
5 Proportion control selection (PC)
6 Reset (RES)
7
8
9
17 Automatic/manual selection (MD0)
18 Proximity dog (DOG)
19 Program No. selection 1 (DI0)
20 Program No. selection 2 (DI1)
21 Program No. selection 3 (DI2)
24 Temporary stop/restart (STP)
25
26
Manual pulse generator multiplication 1 (TP0)
Manual pulse generator multiplication 2 (TP1)
27 Gain switch (CDP)
28
29 Program input 1 (PI1)
30 Program input 2 (PI2)
31 Program input 3 (PI3)
10 Current position latch input (LPS) 22 Program No. selection 4 (DI3)
11 Forward rotation start (ST1) 23 Override selection (OVR)
(4) External output pin status read
Read the ON/OFF statuses of the external output pins.
(a) Transmission
Transmit command [1][2] and data No. [C][0].
[1][2] [C][0]
(b) Reply
The slave station sends back the ON/OFF statuses of the output pins. b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master station as hexadecimal data.
bit External output pin
0 CN1A-19
1 CN1A-18
2 CN1B-19
3 CN1B-6
4 CN1B-4 bit External output pin
5 CN1B-18
6 CN1A-14
15 - 22
15. COMMUNICATION FUNCTIONS
(5) Read of the statuses of output devices
Read the ON/OFF statuses of the output devices.
(a) Transmission
Transmit command [1][2] and data No. [8][0].
[1][2] [8][0]
(b) Reply
The slave station sends back the statuses of the output devices. b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master station as hexadecimal data.
0 Ready (RD)
1
2
3 Limiting torque (TLC)
4
5
6
7 Warning (WNG)
8 Trouble (ALM)
9
15.12.5 Input devices ON/OFF
10 Electromagnetic brake (MBR)
11 Dynamic brake interlock (DBR)
12
13
14
15 Battery warning (BWNG)
16
17
Home position return completion
(ZP)
18 Position range (POT)
19 Temporary stop (PUS)
20 Program output 1 (OUT1)
21 Program output 2 (OUT2)
22 Program output 3 (OUT3)
23 SYNC Synchronous output (SOUT)
24 Movement complete (PED)
25
26
27
28
POINT
The ON/OFF states of all devices in the servo amplifier are the states of the data received last. Hence, when there is a device which must be kept
ON, send data which turns that device ON every time.
Each input device can be switched on/off. However, when the device to be switched off exists in the external input signal, also switch off that input signal.
Send command [9][2], data No. [6][0] and data. b31
Command Data No. Set data
[9][2] [6][0] below. b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the slave station as hexadecimal data.
0 Servo-on (SON) 12 Reverse rotation start (ST2)
1 Forward rotation stroke limit (LSP) 13
2 Reverse rotation stroke limit (LSN) 14
3 External torque limit selection (TL) 15
4 Internal torque limit selection (TL2) 16 Forced stop (EMG)
5 Proportion control selection (PC)
24 Temporary stop/restart (STP)
25
Manual pulse generator multiplication 1 (TP0)
26
Manual pulse generator multiplication 2 (TP1)
17 Automatic/manual selection (MD0) 27 Gain switch (CDP)
6 Reset (RES)
7
8
9
18 Proximity dog (DOG)
19 Program No. selection 1 (DI0)
20 Program No. selection 2 (DI1)
21 Program No. selection 3 (DI2)
28
29 Program input 1 (PI1)
30 Program input 2 (PI2)
31 Program input 3 (PI3)
10 Current position latch input (LPS) 22 Program No. selection 4 (DI3)
11 Forward rotation start (ST1) 23 Override selection (OVR)
15 - 23
15. COMMUNICATION FUNCTIONS
15.12.6 Disable/enable of I/O devices (DIO)
Inputs can be disabled independently of the I/O devices ON/OFF. When inputs are disabled, the input signals (devices) are recognized as follows. Among the input devices, EMG, LSP and LSN cannot be disabled.
Signal Status
Input devices (DI)
External analog input signals
OFF
0V
Pulse train inputs None
(1) Disabling/enabling the input devices (DI), external analog input signals and pulse train inputs with the exception of EMG, LSP and LSN.
Transmit the following communication commands.
(a) Disable
Data
[9][0] [0][0] 1EA5
(b) Enable
Data
[9][0] [1][0] 1EA5
(2) Disabling/enabling the output devices (DO).
Transmit the following communication commands.
(a) Disable
Data
[9][0] [0][3] 1EA5
(b) Enable
Data
[9][0] [1][3] 1EA5
15 - 24
15. COMMUNICATION FUNCTIONS
15.12.7 Input devices ON/OFF (test operation)
Each input devices can be turned on/off for test operation. when the device to be switched off exists in the external input signal, also switch off that input signal.
Send command [9] [2], data No. [0] [0] and data.
Command Data No. Set data b31 b1 b0
1: ON
0: OFF
Command of each bit is transmitted to the slave station as hexadecimal data.
0 Servo-on (SON) 12 Reverse rotation start (ST2)
1 Forward rotation stroke limit (LSP) 13
2 Reverse rotation stroke limit (LSN) 14
24 Temporary stop/restart (STP)
25
Manual pulse generator multiplication 1 (TP0)
3 External torque limit selection (TL) 15
4 Internal torque limit selection (TL2) 16 Forced stop (EMG)
5 Proportion control selection (PC) 17 Automatic/manual selection (MD0)
26
Manual pulse generator multiplication 2 (TP1)
27 Gain switch (CDP)
6 Reset (RES)
7
18 Proximity dog (DOG)
19 Program No. selection 1 (DI0)
28
29 Program input 1 (PI1)
8
9
20 Program No. selection 2 (DI1)
21 Program No. selection 3 (DI2)
10 Current position latch input (LPS) 22 Program No. selection 4 (DI3)
11 Forward rotation start (ST1) 23 Override selection (OVR)
30 Program input 2 (PI2)
31 Program input 3 (PI3)
15 - 25
15. COMMUNICATION FUNCTIONS
15.12.8 Test operation mode
(1) Instructions for test operation mode
The test operation mode must be executed in the following procedure. If communication is interrupted for longer than 0.5s during test operation, the servo amplifier causes the motor to be decelerated to a stop and servo-locked. To prevent this, continue communication without a break, e.g. monitor the status display.
(a) Execution of test operation
1) Turn off all input devices.
2) Disable the input devices.
Data
[9][0] [0][0] 1EA5
3) Choose the test operation mode.
Command
[8][B]
Data No.
[0][0]
Transmission data
0000
[8][B] [0][0]
[8][B] [0][0]
[8][B] [0][0]
[8][B] [0][0]
Selection of test operation mode
Test operation mode cancel
4) Set the data needed for test operation.
5) Start.
6) Continue communication using the status display or other command.
(b) Termination of test operation
To terminate the test operation mode, complete the corresponding operation and.
1) Clear the test operation acceleration/deceleration time constant.
[A][0] [1][2]
Data
1EA5
2) Cancel the test operation mode.
[8][B] [0][0]
Data
0000
3) Enable the disabled input devices.
Data
[9][0] [1][0] 1EA5
15 - 26
15. COMMUNICATION FUNCTIONS
(2) Jog operation
Transmit the following communication commands.
(a) Setting of jog operation data
Speed
Acceleration/deceleration time constant
[A][0] [1][0]
Data
Write the speed [r/min] in hexadecimal.
(b) Start
Turn on the input devices SON LSP LSN and ST1/ST2 by using command [9][2] data No.
[0][0].
Forward rotation start
Reverse rotation start
[9][2]
[9][2]
[0][0]
[0][0]
Stop [9][2] [0][0]
(3) Positioning operation
Transmit the following communication commands.
(a) Setting of positioning operation data
Data
00000807: Turns on SON LSP LSN and ST1.
00001007: Turns on SON LSP LSN and ST2.
00000007: Turns on SON LSP and LSN.
[A][0] [1][0]
Data
Write the speed [r/min] in hexadecimal. Speed
Acceleration/deceleration time constant
Moving distance [A][0] [1][3] Write the moving distance [pulse] in hexadecimal.
(b) Input of servo-on stroke end
Turn on the input devices SON LSP and LSN by using command [9][2] data No. [0][0].
Data
[9][2] [0][0] 00000001: Turns on SON. Servo-on
Servo OFF
Stroke end ON
Servo-on
Stroke end ON
[9][2] [0][0] 00000006: Turns off SON and turns on LSP LSN.
15 - 27
15. COMMUNICATION FUNCTIONS
(c) Start of positioning operation
Transmit the speed and acceleration/deceleration time constant, turn on the servo-on (SON) and forward/reverse rotation stroke end (LSP LSN), and then send the moving distance to start positioning operation. After that, positioning operation will start every time the moving distance is transmitted. To start opposite rotation, send the moving distance of a negative value.
When the servo-on (SON) and forward/reverse rotation stroke end (LSP LSN) are off, the transmission of the moving distance is invalid. Therefore, positioning operation will not start if the servo-on (SON) and forward/reverse rotation stroke end (LSP LSN) are turned on after the setting of the moving distance.
(d) Temporary stop
A temporary stop can be made during positioning operation.
[A][0] [1][5]
Data
1EA5
Retransmit the same communication commands as at the start time to resume operation.
To stop positioning operation after a temporary stop, retransmit the temporary stop communication command. The remaining moving distance is then cleared.
15 - 28
15. COMMUNICATION FUNCTIONS
15.12.9 Output signal pin ON/OFF output signal (DO) forced output
In the test operation mode, the output signal pins can be turned on/off independently of the servo status.
Using command [9][0], disable the output signals in advance.
(1) Choosing DO forced output in test operation mode
Transmit command [8][B] data No. [0][0] data "0004" to choose DO forced output.
0 0 0 4
Selection of test operation mode
4: DO forced output (output signal forced output)
(2) External output signal ON/OFF
Transmit the following communication commands.
Command Data No. Setting data b31
Command of each bit is sent to the slave station in hexadecimal.
b1 b0
1: ON
0: OFF bit External output pin bit External output pin bit External output pin bit
CN1A-19 8
CN1A-18 9
External output pin
CN1B-6 11
CN1B-4 20
15 - 29
15. COMMUNICATION FUNCTIONS
15.12.10 Alarm history
(1) Alarm No. read
Read the alarm No. which occurred in the past. The alarm numbers and occurrence times of No.0 (last alarm) to No.5 (sixth alarm in the past) are read.
(a) Transmission
Send command [3][3] and data No. [1][0] to [1][5]. Refer to section 15.11.1.
(b) Reply
The alarm No. corresponding to the data No. is provided.
0 0
Alarm No. is transferred in decimal.
For example, "0032" means AL.32 and "00FF" AL._ (no alarm).
(2) Alarm occurrence time read
Read the occurrence time of alarm which occurred in the past.
The alarm occurrence time corresponding to the data No. is provided in terms of the total time beginning with operation start, with the minute unit omitted.
(a) Transmission
Send command [3][3] and data No. [2][0] to [2][5].
Refer to section 15.11.1.
(b) Reply
The alarm occurrence time is transferred in decimal.
Hexadecimal must be converted into decimal.
For example, data [0][1][F][5] indicates that the alarm occurred 501 hours after start of operation.
(3) Alarm history clear
Erase the alarm history.
Send command [8][2] and data No. [2][0].
Command Data Data
[8][2] [2][0] 1EA5
15 - 30
15. COMMUNICATION FUNCTIONS
15.12.11 Current alarm
(1) Current alarm read
Read the alarm No. which is occurring currently.
(a) Transmission
Send command [0][2] and data No. [0][0].
[0][2] [0][0]
(b) Reply
The slave station sends back the alarm currently occurring.
0 0
Alarm No. is transferred in decimal.
For example, "0032" means AL.32 and "00FF" AL._ (no alarm).
(2) Read of the status display at alarm occurrence
Read the status display data at alarm occurrence. When the data No. corresponding to the status display item is transmitted, the data value and data processing information are sent back.
(a) Transmission
Send command [3][5] and any of data No. [8][0] to [8][E] corresponding to the status display item to be read. Refer to section 15.11.1.
(b) Reply
The slave station sends back the requested status display data at alarm occurrence.
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Conversion into decimal required
1: Used unchanged in hexadecimal
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
(3) Current alarm clear
As by the entry of the Reset (RES), reset the servo amplifier alarm to make the servo amplifier ready to operate. After removing the cause of the alarm, reset the alarm with no command entered.
(a) Transmission
Command Data Data
[8][2] [0][0] 1EA5
15 - 31
15. COMMUNICATION FUNCTIONS
15.12.12 Current position latch data
Read the current position latch data. When the data No. is transmitted, the data value and data processing information are sent back.
(1) Transmission
Send command [6][C] and data No. [0][1] to be read.
(2) Reply
The slave station sends back. (Current position latch data.)
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Conversion into decimal required
1: Used unchanged in hexadecimal
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
15 - 32
15. COMMUNICATION FUNCTIONS
15.12.13 General-purpose register
(1) General-purpose register (Rx) read
Read the general-purpose register (Rx) value stored in the EEP-ROM.
(a) Transmission
Transmit command [6][D] and any of data No. [0][1] to [0][4] corresponding to the general-purpose register (Rx) to be read. Refer to section 15.11.1.
(b) Reply
The slave station sends back the position data of the requested the value of the general-purpose register (Rx).
The alarm occurrence time is transferred in decimal.
Hexadecimal must be converted into decimal.
(2) General-purpose register (Dx) read
Read the general-purpose register (Dx) value stored in the RAM.
(a) Transmission
Transmit command [6][E] and any of data No. [0][1] to [0][4] corresponding to the general-purpose register (Dx) to be read. Refer to section 15.11.1.
(b) Reply
The slave station sends back the position data of the requested the value of the general-purpose register (Dx).
The alarm occurrence time is transferred in decimal.
Hexadecimal must be converted into decimal.
15 - 33
15. COMMUNICATION FUNCTIONS
(3) General-purpose register (Rx) write
Write the value of the general-purpose register (Rx).
Write the value within the setting range. Refer to section 4.2.2 (1) for the setting range.
Transmit command [B][9], the data No., and setting value. Data to be written is hexadecimal.
Data is transferred in hexadecimal.
Decimal point position
0: No decimal point
1: Lower first digit
2: Lower second digit
3: Lower third digit
4: Lower forth digit
5: Lower fifth digit
Write mode
0: Write to EEP-ROM
3: Write to RAM
When the parameter data is changed frequently through communication, set "3" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour), do not write it to the EEP-ROM.
(4) General-purpose register (Dx) write
Write the value of the general-purpose register (Dx) to the RAM.
Write the value within the setting range. Refer to section 4.2.2 (1) for the setting range.
Transmit command [B][A], the data No., and setting value. Data to be written is hexadecimal.
Data is transferred in hexadecimal.
15 - 34
15. COMMUNICATION FUNCTIONS
15.12.14 Servo amplifier group designation
With group setting made to the slave stations, data can be transmitted simultaneously to two or more slave stations set as a group through RS-422 communication.
(1) Group setting write
Write the group designation value to the slave station.
(a) Transmission
Transmit command [9][F], data No. [0][0] and data.
Command Data Data
0 0
Group designation
0: No group designation
1: Group a
2: Group b
3: Group c
4: Group d
5: Group e
6: Group f
Response command enable
Set whether data can be sent back or not in
response to the read command of the master station.
0: Response disable
Data cannot be set back.
1: Response enable
Data can be set back.
(2) Group setting read
Read the set group designation value from the slave station.
(a) Transmission
Transmit command [1][F] and data No. [0][0].
[1][F] [0][0]
(b) Reply
The slave station sends back the group setting requested.
0 0
Group designation
0: No group designation
1: Group a
2: Group b
3: Group c
4: Group d
5: Group e
6: Group f
Response command enable
0: Response disable
1: Response enable
15 - 35
15. COMMUNICATION FUNCTIONS
15.12.15 Software version
Reads the software version of the servo amplifier.
(a) Transmission
Send command [0] [2] and data No. [7] [0].
[0][2] [7][0]
(b) Reply
The slave station returns the software version requested.
Space Software version (15 digits)
15 - 36
APPENDIX
App 1. Status indication block diagram
Current cont
Current po
App - 1
APPENDIX
App 2. Junction terminal block (MR-TB20) terminal block labels
19
18
17
16
15
14
13
12
11
10
For CN1A
9
19
8
18
7
17
6
16
5
15
4
14
3
13
2
12
1
11
0
10
9
8
7
6
5
4
3
2
1
0
10
11
12
13
14
15
16
17
18
19
For CN1B
9
19
8
18
7
17
6
16
5
15
4
14
3
13
2
12
1
11
0
10
6
5
4
3
8
7
9
1
0
2
App - 2
APPENDIX
App 3. Combination of servo amplifier and servo motor
The servo amplifier software versions compatible with the servo motors are indicated in the parentheses.
The servo amplifiers whose software versions are not indicated can be used regardless of the versions.
Servo amplifier Servo amplifier
Servo motor Servo motor
(Software version) (Software version)
HC-KFS053
HC-KFS13
MR-J2S-10CL
MR-J2S-10CL 1
MR-J2S-10CL
MR-J2S-10CL 1
HC-KFS23
HC-KFS43
MR-J2S-20CL
MR-J2S-20CL 1
MR-J2S-40CL
MR-J2S-40CL 1
HC-KFS73 MR-J2S-70CL
HC-MFS053
MR-J2S-10CL
MR-J2S-10CL 1
HC-RFS103 MR-J2S-200CL
HC-RFS153 MR-J2S-200CL
HC-RFS203 MR-J2S-350CL
HC-RFS353 MR-J2S-500CL
HC-RFS503 MR-J2S-500CL
HC-UFS72 MR-J2S-70CL
HC-UFS152 MR-J2S-200CL
HC-UFS202 MR-J2S-350CL
HC-UFS352 MR-J2S-500CL
HC-UFS502 MR-J2S-500CL
HC-UFS13
MR-J2S-10CL
MR-J2S-10CL1
HC-MFS13
HC-MFS23
MR-J2S-10CL
MR-J2S-10CL 1
MR-J2S-20CL
MR-J2S-20CL 1
HC-MFS43
MR-J2S-40CL
MR-J2S-40CL1
HC-MFS73 MR-J2S-70CL
HC-SFS81 MR-J2S-100CL
HC-SFS121 MR-J2S-200CL
HC-SFS201 MR-J2S-200CL
HC-SFS301 MR-J2S-350CL
HC-SFS52 MR-J2S-60CL
HC-SFS102 MR-J2S-100CL
HC-UFS23
HC-UFS43
MR-J2S-20CL
MR-J2S-20CL1
MR-J2S-40CL
MR-J2S-40CL1
HC-UFS73 MR-J2S-70CL
HC-LFS52 MR-J2S-60CL
HC-LFS102 MR-J2S-100CL
HC-LFS152 MR-J2S-200CL
HC-LFS202 MR-J2S-350CL
HC-LFS302 MR-J2S-500CL
HA-LFS502 MR-J2S-500CL
HA-LFS702 MR-J2S-700CL
HC-SFS152 MR-J2S-200CL
HC-SFS202 MR-J2S-200CL
HC-SFS352 MR-J2S-350CL
HC-SFS502 MR-J2S-500CL
HC-SFS702 MR-J2S-700CL
HC-SFS53 MR-J2S-60CL
HC-SFS103 MR-J2S-100CL
HC-SFS153 MR-J2S-200CL
HC-SFS203 MR-J2S-200CL
HC-SFS353 MR-J2S-350CL
App - 3
APPENDIX
App 4. Change of connector sets to the RoHS compatible products
Connector sets (options) in the following table are changed to the RoHS compatible products after
September, 2006 shipment.
Please accept that the current products might be mixed with RoHS compatible products based on availability.
Model Current Product RoHS Compatible Product
MR-J2CNM
MR-J2CN1
MR-J2CNS
MR-ENCNS
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
Encoder connector (DDK)
MS3057-12A (Cable clump)
MS3106B20-29S (Straight plug)
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
MS3106A20-29S (D190) (Plug, DDK)
CE3057-12A-3 (D265) (Cable clump, DDK)
CE02-20BS-S (Back shell, DDK)
CE05-6A22-23SD-B-BSS (Connector and back shell)
CE3057-12A-2 (D265) (Cable clump)
CE05-6A24-24SD-B-BSS (Connector and back shell)
CE3057-16A-2 (D265) (Cable clump)
CE05-6A32-17SD-B-BSS (Connector and back shell)
CE3057-20A-1 (D265) (Cable clump)
MS3106A10SL-4S (D190) (Plug, DDK)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
Encoder connector (DDK)
D/MS3057-12A (Cable clump)
D/MS3106B20-29S (Straight plug)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
D/MS3106A20-29S (D190) (Plug, DDK)
CE3057-12A-3-D (Cable clump, DDK)
CE02-20BS-S-D (Back shell, DDK)
Power supply connector (DDK)
CE05-6A22-23SD-D-BSS (Connector and back shell)
CE3057-12A-2-D (Cable clump)
Power supply connector (DDK)
CE05-6A24-10SD-B-BSS (Connector and back shell)
CE3057-16A-2-D (Cable clump)
Power supply connector (DDK)
CE05-6A32-17SD-D-BSS (Connector and back shell)
CE3057-20A-1-D (Cable clump)
Electromagnetic brake connector
D/MS3106A10SL-4S (D190) (Plug, DDK)
App - 4
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Data *Manual Number Revision
Jan., 2003 SH(NA)030034-A First edition
Jan., 2004 SH(NA)030034-B Changing “Servo configuration Software” to “MR Configurator (Servo configuration Software)”.
Safety Instructions 1. To prevent electric shock, note the following: Addition
3. To prevent injury, note the following: Addition
4. Additional instructions
(2) Reexamination
(4) Reexamination
(5) Reexamination of the circuit diagram for electromagnetic brake operation.
(6) Reexamination
COMPLIANCE WITH EC DIRECTIVES
(3) Changing “IEC664” to “IEC60664-1” in the sentences.
(4) Changing “IEC664” to “IEC60664-1” in the sentences.
Section 1.1.1
Section 1.2
Section 1.7
Section 3.1
Section 3.8.3 (2)
Section 3.9
Section 3.9 (3) (a)
Section 4.1.2
Section 4.4.3 (2)
Section 4.4.4 (2)
Section 4.4.5 (2)
Section 4.4.6 (2)
Section 4.4.7 (2)
Section 4.4.8 (2)
Section 4.4.9 (2)
Section 5.1.2 (2)
Section 5.2.1 (1) (a)
Section 6.2 (1)
Section 6.7.2
Section 6.7.5
Section 13.5
Section 14.1.1 (3)
Section 14.1.1 (4)
Section 14.1.1 (5)
Section 14.1.3 (2)
Section 14.1.7
Section 14.1.9
Partial modification made to the wiring diagram.
Addition of inrush current.
Changing “programming” to “program”.
Addition of notes (3), (4).
Addition of Note (12) to the connection example.
Addition of CE05-2A32-17PD-B.
Reexamination of the circuit diagram for electromagnetic brake operation.
Reexamination of the timing charts.
Reexamination of the instructions.
Reexamination
Reexamination
Reexamination
Reexamination
Reexamination
Reexamination
Reexamination
Parameter No. 0: Reexamination of the regenerative option selection.
Parameter No.63: Reexamination of the low-pass filter selection.
Modification made to the CDV value: “1250”.
Modification made to the description relevant to
Windows trademark.
Addition of sentences to POINT
Addition of POINT
Reexamination
Reexamination of the regenerative option selection.
Reexamination
Reexamination of Outline drawing.
Partial change made to the connection example.
Reexamination
Addition of POINT
Print Data *Manual Number Revision
Jan., 2004 SH(NA)030034-B Section 14.2.8 (3) Partial change made to the EMC filter HF3040-
TM/HF3050-TM outline drawings.
Mar., 2005 SH(NA)-030034-C COMPLIANCE WITH EC DIRECTIVES:
"1. WHAT ARE EC DIRECTIVES?" Sentence reexamination
Section 1.1.1 (1) MR-J2S-350CL Reexamination of words and note in the figure.
Section 1.1.1 (2)
Section 1.4 (2)
Addition of the function block diagram for MR-J2S-
500CL, 700CL.
Reexamination of words in the figure.
Reexamination of CAUTION sentence.
Section 3.1
Section 3.2
Section 3.3.1 (1)
Section 3.3.2 (2)
Section 3.5
Section 3.7.3 (1)
Section 3.8.3 (1)
Section 3.9
Section 3.11
Section 4.4.2 (3)
Section 4.4.4 (2)
Section 4.4.5 (2)
Section 4.4.7 (2)
Partial reexamination of "Standard connection example".
Internal connection diagram of servo amplifier
Deletion of PG, NG Figure reexamination
Signal arrangement Deletion of PG, NG
(b) Sentence reexamination
Input signal Deletion of PG, NG
Addition of CAUTION sentence, Sentence
Reexamination
(3) Sentence reexamination
1) Sentence addition
Changing of AMP name.
Sentence Reexamination (3) (d), (e) Figure change
POINT addition (1) Sentence Reexamination
Addition of "ST2" to the timing chart.
Addition of "ST2" to the timing chart.
Addition of "ST2" to the timing chart.
Addition of "ST2" to the timing chart.
Section 4.4.8 (2)
Section 4.4.9 (2)
Section 4.5
Section 5.1.2 (2)
Section 6.2 (1)
Section 9.4 (1)
Section 11.2.2
Addition of "ST2" to the timing chart.
Addition of "ST2" to the timing chart.
Addition of CAUTION sentence, Sentence
Reexamination
(5) Reexamination of WARNING sentence.
No. 55 Reexamination of words in the figure.
Sentence Reexamination
Sentence Reexamination
Addition and reexamination of CAUTION sentence.
AL. 17, AL. 19 Sentence addition, reexamination
AL. 33 Sentence addition
AL. 46 Sentence reexamination
Section 11.2.3
Section 12.1 (1) to (5)
Section 13.1
Section 13.3
Section 14.1.1 (2)
Section 14.1.1 (4)
Section 14.1.1 (4) (a)
Section 14.1.1 (4) (b)
Section 14.1.1 (5) (c)
Section 14.1.2 (2)
Section 14.1.3 (2)
CAUTION addition
AL. E3 Sentence addition
Specification addition of mounting screw.
Changing of CAUTION sentence.
Addition of HC-LFS series graph. b. Figure addition
POINT addition
Sentence reexamination
Sentence reexamination
Partial changing of figure.
Note change
Sentence reexamination Addition of Note 2
Print Data *Manual Number
Mar., 2005 SH(NA)-030034-C Section 14.1.4 (1)
Section 14.1.6 (3)
Section 14.2.1 (1)
Section 14.2.3
Section 14.2.6 (2)
Section 14.2.8 (2)
Section 15.11.1 (5)
App 2
App 5
Jan., 2006 SH(NA)-030034-D Safety Instructions
Section 1.1.1
Section 1.4 (2)
Section 1.6.1
Section 1.7
Chapter 2
Section 3.6.2 (2)
Section 3.6.2 (3) (b)
Section 3.8.3
Section 3.9
Section 3.9 (d)
Section 3.11.1
Section 4.1.2 (2) (b)
Section 4.2.3 (1) (c)
Section 5.1.2 (2)
Section 5.2.4
Section 5.2.4 (2)
Section 6.7
Section 6.7.1
Section 6.7.2
Section 6.7.3
Section 11.2.3
Section 12.1
Section 14.2.6 (2)
Jul., 2006 SH(NA)-030034-E Safety Instructions
Section 1.6.2
Chapter 3
Section 3.7.2
Section 3.7.3 (3)
Section 3.8.2
Section 5.1.2 (2)
Section 5.2.1
Section 12.2 (1) (b)
Section 14.1.1 (2)
Revision
Sentence reexamination (2)
2) Sentence reexamination
Figure addition
Table 14.2 Sentence reexamination
Addition of MR-J2S- CL.
Changing of values.
Changing of company name.
(d) Sentence reexamination
(e) Connection diagram change
Sentence reexamination
Sentence reexamination in the current alarm chart.
Addition of "Combination of servo amplifier and servo motor".
Reexamination of words.
Reexamination of date and telephone No.
4. (2) Sentence addition
(4) Sentence addition
Correction of error in writing
Note reexamination
Correction of instructions
Note reexamination
CAUTION addition
Correction of error in writing
2) Addition of descriptions
Change of signal expression
Addition of CAUTION sentence
Change of “Servo motor speed” range
Addition of descriptions
Sentence change
Table correction
Note addition of parameter No. 17, No. 30
Sentence change
Note addition
CAUTION correction
POINT correction
POINT correction
POINT correction
POINT addition
Correction of error in writing
(d) Change of outline drawing
4. Additional instructions (2) Figure change
Correction of words in CAUTION
Addition of CAUTION sentence
Addition of sentence in Table
CAUTION addition
CAUTION addition
Correction of description for parameter No.1
Correction of POINT sentence
Correction of error in dimensions
Correction of formula in Table
Print Data *Manual Number
Jul., 2006 SH(NA)-030034-E Section 14.1.7 (2)
Section 15.12.3 (2)
Sep., 2007 SH(NA)-030034-F Sefety Instructions
Section 1.1.1
Section 1.7
Chapter 2
Chapter 3
Section 3.6.2 (2)
Section 3.6.2 (6)
Section 4.5(5)
Chapter 10
Section 11.2.2
Section 11.3
Chapter 14
Section 14.1.2
Section 14.1.4
Section 14.2.6 (2) (d)
Appendix 4
Revision
Correction of signal name for CN3-1 pin
Correction of POINT sentence
1,2. Sentence change
Note reexamination
Note reexamination
WARNING reexamination
WARNING reexamination
Note addition
Note addition
WARNING reexamination
WARNING reexamination
AL.20 Cause addition
AL.32 Cause sentence addition
AL.33 Cause 8,9 addition
Addition of MR-DP60 external digital display error
WARNING reexamination
Change of "brake unit" to "FR-BU2"
Change of connector models to be compatible with RoHS
Sentence change
Addition
MODEL
MODEL
CODE
SH (NA) 030034-F (0709) MEE Printed in Japan
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
Specifications subject to change without notice.
General-Purpose AC Servo
J2-Super
Series
Program Compatible
MODEL
MR-J2S- CL
SERVO AMPLIFIER
INSTRUCTION MANUAL
F
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project