Fire Alarm Systems | D9124 Addressable Fire Alarm Control Panel (FACP)

D9124 Addressable Fire Alarm Control

Panel (FACP)

24 VDC, 4 A power for initiation circuits and NACs;

12 VDC, 1.4 A power for system accessories

Up to eight supervised or 32 unsupervised remote annunciators

One-man Fire Test Mode

Schedules (Skeds function) service reminder for local systems

Low battery, AC power supply, and battery lead supervision

Dual phone line monitor

The D9124 FACP controls complex alarm systems used in schools, universities, manufacturing plants, and health care facilities. Program it for fire, fire supervisory, intrusion, or access control applications. Program it locally using the

D5200CE hand-held programmer or remotely using RPS over telephone lines or local-area or wide-area networks

(LAN or WAN).

The D9124 FACP is a modular assembly, installed in a red steel enclosure, which can be surface- or flush-mounted.

The enclosure has keyed controller access making it suitable for installation in public access areas.

Functions

Alarm Verification

The alarm verification feature reduces potential false alarms by requiring a reset and a second alarm signal from the device before the control panel raises an alarm condition.

Auxiliary and Standby Power

The 4 A, 24 VDC power supply charges the standby batteries and powers auxiliary devices. The power supply responds to low battery or battery disconnect conditions with a

Trouble LED and a Trouble Relay for sounders or lights.

Five system power trouble conditions are selected by DIP switches. They can be individually linked to a central station, or grouped to activate a trouble relay, allowing a single supervised address to monitor the power supply.

A pair of 12 V batteries provides standby power. Two additional batteries provide standby power for initiating devices and notification appliances. All four batteries are housed within the panel enclosure.

Note Batteries are not included in the D9124 and must be purchased separately.

Central Station Communication

Events can be communicated to a central station by the digital communicator or by adding an optional Ethernet interface module. The optional Bosch D6500 or D6600

NetCom Receiver and Modem IIIa 2 reporting format provide individual point reporting to monitoring facilities.

The D5500 Remote Programming Software (RPS) allows the following to be controlled from a central station:

• Resetting notification appliances

Activating or deactivating remote annunciation

Activating or deactivating relays

Supervising battery condition

• Setting point status and armed status

Enabling or disabling reporting functions

Shunting reporting points during servicing

www.boschsecurity.com

2 | D9124 Addressable Fire Alarm Control Panel (FACP)

Event Log Storage, Viewing, and Printing

The D9124's memory log stores time, date, point, and user

ID for up to 1000 events. Programming options allow restricting specific event reports to the central station receiver. A programming option allows the log to record certain functions entered at command centers.

Display the 1000 events in memory at the fire system controller(s) or retrieve them with a single phone call by a central station using Bosch RPS version 3.7.025 or higher.

The D9131A Parallel Printer Interface Module allows an onsite parallel printer to print events as they are stored in the log: recording time, date, account number, event, point ID, point text, and if the message was transmitted to a receiver.

Inputs

The D9124 Control Panel is a 127-point addressable system that is expandable to 246 addressable points. The control panel receives information from alarm initiating points through integrated devices over a two-wire multiplex zone expansion system. Each addressable point accommodates both normally-open and normally-closed devices with endof-line (EOL) resistor supervision. Each point is programmable for fire, fire supervisory, intrusion, or access control applications.

Outputs

System notification appliance capacity can be extended beyond the two supervised circuits by adding D8129 Octorelay Modules. Up to 128 relay outputs can be operated through the controller or the central station, or they can be programmed for automatic operations.

Notification appliances can be programmed for steady, pulsed, California March Time, or Temporal Code 3 patterns. Temporal Code 3 patterns can be synchronized using the appropriate synchronization modules.

Notification Appliance Circuits (NACs)

The D9124 FACP has two supervised, on-board NACs with individual circuit silencing.

User Interface

A D1256 Fire Alarm keypad is visible and accessible behind a locked, clear sliding panel located on the enclosure door.

It displays programmable text identifying specific initiating and supervisory devices. It also provides point annunciation, signal silence, trouble silence, detector reset, and annunciator reset. The sliding panel lock is keyed to match the Bosch manual pull stations for resetting the system.

Also available as options are:

D1255R Security/Fire Keypad

D1257 Remote Fire Alarm Annunciator

• D1260 Keypad

Certifications and Approvals

Region

USA

Hong Kong

Certification

UL AMCX: Central Station Alarm Units

(UL1610, UL1635), APAW: Police Station

Alarm Units (UL365, UL464), UOJZ:

Control Units, System (UL864)

FM

CSFM 7165-1615: 113 and 7170-1615:

144 July 2008

NYC-MEA 12-92-E, Vol. IV 12-92-E, Vol. IV

12-92-E, Vol. X11 12-92-E, Vol. 12

HKFSD

Installation/Configuration Notes

Compatible Products

The following products are compatible with the D9124

FACP:

Category

Batteries and

Power Supply

Products

Product ID Product Description

BATB-40 Battery box

Detectors

Keypads and

Annunciators

BATB-80

D126

D1218

D7038

D285

D285TH

D298M

D298S

FMM-462

D603

D604

D605

D720B/R

Battery box

12 V, 7 Ah standby battery

12 V, 18 Ah standby battery

Power supply address circuit module

Photoelectric smoke head

Photoelectric smoke head with heat

Zonex smoke master base

Zonex smoke single base

Manual station

Rate-of-rise heat detector head

Fixed (135°F) heat detector head

Fixed (190°F) heat detector head

Security and fire keypads

Modules

D1255B/R Security and fire keypads

D1256 Fire command center

D1257 Remote fire alarm annunciator

D1260

D125B

D129

D130

D136

D192C

D192E

ATM keypad

Powered loop interface module

(Dual, Class B)

Initiation circuit module

(Dual, Class A)

Relay module

Plug-in relay

Bell supervision module

Bell supervision module

D9124 Addressable Fire Alarm Control Panel (FACP) | 3

Category

Programming

Products

Product ID Product Description

D192G Bell supervision module

D8125 POPEX module

D8125MUX Zonex to dual multiplex interface

D8128D

D8129

OctoPOPIT module

Octo-relay module

D8130

D9127U

D9127T

D9131A

DX4020

D5200CE

Release module

POPIT module (no tamper)

POPIT module (tamper)

Parallel printer interface module

Ethernet interface module

Handheld programmer

RPS

RPS-LITE

RPS-INTL

Remote Programming Software

Remote Programming Software

Remote Programming Software

Parts Included

The D9124 Addressable Control Panel is shipped in three boxes. One box contains:

Quant.

Component

1 D9412GLTB Control Panel (less terminal blocks)

Another box contains:

Quant.

Component

1 D9101 Enclosure Assembly with Door

The third box contains a D9100 Accessory Module Carrier that includes the following:

Quant.

Component

1

1

2

1

D192C Indicating Circuit Supervision Modules

D928 Dual Phone Line Switcher

D8125 POPEX Module (additional optional)

D9142LC 24 VDC Power Supply

The third box also contains:

1

1

2

2

Quant.

Component

1

1

1

1

D1256 Fire Alarm Keypad

D1601 Transformer

Wiring Harness

Wiring Harness for the D8125 POPEX Module

560 Ω Resistors (for D192C Modules)

D161 Dual Modular Telephone Cords

D162 Dual Modular Telephone Cord

Literature pack

Technical Specifications

Environmental Considerations

Relative Humidity: Up to 85%; non-condensing

Temperature (operating): +32°F to +122°F (0°C to +50°C)

Inputs

Sensor Circuits: Up to two 8125 POPEX modules,

119 addresses per module

Sensor Circuit Protection: Power limited to 4 A; short circuit, reverse polarity, thermal overload and current overload protection on-board

Sensor Loop Technology: Four-wire addressable circuits

Mechanical Properties

Color:

Material:

Dimensions (H x W x D)

Enclosure Box:

Red

16-gauge (1.5 mm) steel

Removable Door:

36.1 in. x 22.1 in. x 3.2 in.

(92 cm x 56 cm x 8.1 cm)

37.1 in. x 23.3 in. x 1.1 in.

(94 cm x 59 cm x 2.8 cm)

Outputs

Off-board relays:

On-board NACs:

Power Requirements

Up to 16 optional D8129 Relay Modules (eight relay outputs per module)

Two; 1.8 A maximum per circuit

Current (operating)

Alarm + sensor load:

Idle:

Power (auxiliary):

Power (primary):

874 mA

412 mA

24 VDC nominal at 1.8 A

120 VAC, 60 Hz, 360 VA

Ordering Information

D9124 Addressable Fire Alarm Control

Panel (FACP)

Up to eight supervised or 32 unsupervised remote annunciators

Accessories

D113 Battery Lead Supervision Module

Supervises wiring connections for two 12 V batteries connected to the same set of charging terminals.

D122 Dual Battery Harness

Harness with circuit breaker. Connects two batteries to a compatible control panel.

D135A Low‑battery Disconnect Module

Disconnects the control panel from the battery when the battery level drops to 9.5 VDC.

D9124

D113

D122

D135A

www.boschsecurity.com

4 | D9124 Addressable Fire Alarm Control Panel (FACP)

Ordering Information

D127 Reversing Relay Module

Reports two separate alarm conditions to the central station.

D136 Plug‑In Relay

Maximum rating is 1 A at 24 VDC or 2 A at

12 VDC. Available individually (D136) or in a package of 25 (D136‑25).

D138 Mounting Bracket, Right Angle

Used to mount accessory modules in D8103,

D8108A, and D8109 enclosures.

D127

D136

D138

Americas:

Bosch Security Systems, Inc.

130 Perinton Parkway

Fairport, New York, 14450, USA

Phone: +1 800 289 0096

Fax: +1 585 223 9180 [email protected]

www.boschsecurity.us

Europe, Middle East, Africa:

Bosch Security Systems B.V.

P.O. Box 80002

5600 JB Eindhoven, The Netherlands

Phone: + 31 40 2577 284

Fax: +31 40 2577 330 [email protected]

www.boschsecurity.com

© Bosch Security Systems Inc. 2010 | Data subject to change without notice

T1113332363 | Cur: en-US, V5, 4 Jul 2010

Asia-Pacific: Represented by

Robert Bosch (SEA) Pte Ltd, Security Systems

11 Bishan Street 21

Singapore 573943

Phone: +65 6258 5511

Fax: +65 6571 2698 [email protected]

www.boschsecurity.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement