Emerson NetSure 211 Series is a reliable and efficient power distribution unit designed to provide clean, stable power to your mission-critical equipment. With advanced monitoring and control capabilities, it offers real-time visibility and control over power usage, allowing you to optimize energy efficiency and ensure uninterrupted operation. Ideal for data centers, telecommunications facilities, and other demanding environments, the NetSure 211 Series ensures your equipment has the power it needs to perform at its best.
advertisement
R48-1000
DC Power for Business-Critical Continuity
™
Technical Specifications, R48-1000
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
200 to 250 V AC
85 to 300 V AC
45 to 65 Hz
6.8 A
0.99
≤ 5% for 50%-100% load
DC Output
Output Voltage, Adjustment Range
Output Power
-42 to -58 V DC
1000W@Vout >48VDC
Output Power, Derated for Input Voltage See Diagram
Output Current
Efficiency
Psophometric Noise (System)
20.83 A @ -48 VDC
>92%
≤ 1mV; ≤32dBrnc
Temperature Derating See Diagram
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
Alarm and status reported via CAN bus to system controller
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Flashing Red LED: Fan Failure
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
EMC
Safety
Mechanics
Dimensions (H×W×D)
Weight
Other parts
Controller Units
Ordering information
Product Name
-40 to +75°C, -40 to +167°F
-40 to +75°C, -40 to +167°F
0 to 95%
2000 m, 6560 ft at full power
ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B
IEC 60950, EN 60950, UL 60950
40.8×86.5×241mm (1.6×3.4×9.5 inches)
1.25 kg (2.76 lbs)
See separate ACU+ and SCU+ datasheets
Rectifier R48-1000
R48-1000 Output Power vs. Temperature at
264V ≥ Vin ≥ 176 Vac
120
100
80
60
40
20
0
-40 -20 0 20 40 60 80 100
For R48-1000 Temperature (°C)
Output Power vs. Input Voltage at Tamb<45°C
Output Power vs. Input voltage and Vo > 48V at Temp ≥45°C
120
100
80
60
40
20
0
0 50 100 150 200 250 300 350
For R48-1000 Input voltage (VAC)
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
™
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection www.emersonnetworkpower.com www.emersonnetworkpower.com/energysystems www.DCpowerefficiency.com