Emerson NetSure 722 Bulk Output Power System Brochures and Data Sheets


Add to my manuals

advertisement

Emerson NetSure 722 Bulk Output Power System Brochures and Data Sheets | Manualzz

DC Power for

Business-Critical Continuity ™

eSure

Rectifier

R48-3500e

Key Features

 3500 Watt high-efficiency rectifier designed for -48V DC power applications

 Optimized depth – reduced footprint allows installation in short-depth racks and cabinets

 DSP (Digital Signaling

Processor) – means fewer components, optimized operation and active load sharing for increased reliability

 Compliant with global standards – delivers quality, performance and reliability no matter what the application or location demands

 High efficiency, approaching

97% – reduces power consumption for lower operating costs

 Hot pluggable – facilitates future extensions

 Wide input voltage range to operate in the most demanding environments where input voltage changes

 Wide temperature operating range (-40°C / -40°F to +75°C /

167°F) to meet the harshest climatic environment requirements

In addition to reducing power consumption and lowering operating cost, eSure ™ high-efficiency rectifiers offer superior performance and uncompromised reliability.

Description

The eSure ™ R48-3500e high-efficiency rectifier is designed to convert standard AC supply voltages into stable nominal -48V DC voltage that is adjustable to application needs. The R48-3500e is a constant power rectifier designed with the latest patented switchmode technology, using DSP (Digital Signaling Processor) functionality for efficient operation.

For a higher load capacity, rectifiers can be connected in parallel, and intelligent control can be added with the help of a separate controller.

Sure ™ Rectifier

Effi iency Curve

2012.10

1

2

eSure ™ Rectifier R48-3500e

Technical Specifications

AC Input

Input Voltage, Nominal 200 to 250 VAC

Input Voltage, Permitted Variation 85 to 300 VAC

Line Frequency

Max Input Current

45 to 65 Hz

22.5A

Power Factor

THD (Total Harmonic Distortion)

0.99

<5% from 50 to 100% of rated load

DC Output

Output Voltage, Adjustment Range -42 to -58 V DC

Output Power

Output Power,

Derated for Input Voltage

Output Current

3500W@Vout >48VDC

See diagram

73A

Output Current Limit Set Point

Efficiency

Psophometric Noise (system)

Temperature Derating

7.3 to 73A

96.5% peak

<2 mV; <32 dBrnc

See diagram

Control and Monitoring

Rectifier Alarm and Signaling

Visual Indications

Alarm and status reported via CAN bus to system controller

Green LED:

Yellow LED:

Red LED:

Flashing Red LED:

Normal Operation

Alarm

Failure

Fan Failure

Environmental

Temperature Range, Operating

Temperature Range, Storage

Relative Humidity

Altitude

EMC

Safety

Mechanics

Dimensions (H x W x D)

Weight

Other Parts

Controller Units

-40 to +75°C, -40 to +167°F

-40 to +70°C, -40 to +158°F

0 to 95%

2000 m, 6560 ft at full power

ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B,

Telcordia GR-1089-CORE class B

IEC 60950, EN 60950, UL 60950

132 x 85.3 x 287mm / 5.2 x 3.36 x 11.3 inches

3.5kg / 7.7Ibs

See separate ACU/ACU+ and SCU/SCU+ datasheets

Ordering Information

Model Number Description

1R483500E2 Rectifier 48V, 3500W

EmersonNetworkPower.com/EnergySystems (North America)

EmersonNetworkPower.eu/EnergySystems (EMEA)

© Emerson Network Power Energy Systems North America 2012.

Business-Critical Continuity ™ , Emerson Network Power ™ , the Emerson Network Power logo, Emerson ® and Consider it Solved are service marks and trademarks of Emerson Electric Co.

EnergyMaster ™ , eSure ™ , NetPerform ™ , NetReach ™ , NetSpan ™ , NetSure ® and NetXtend ™ are trademarks of Emerson Network Power Energy Systems North America.

Diagrams

120

100

80

60

40

20

0

-40

Output Power vs. Temperature at 264 ≥ Vin ≥176Vac

-20 0 20 40

Temperature (C°)

60 80 100

120

100

80

60

40

20

0

0

Output Power vs. Input Voltage and Vo > 48V at Temp <45°C

50 100 150 200

Input Voltage (VAC)

250 300 350

Output voltage vs. Output current at max. output power 3500 W

30

20

10

0

70

60

50

40

0

10 15 20 25 30 35 40 45 50 55 60 65 70 75

Output Current (A)

2012.10