Conventional Zone Module

M512ME

• ADM loop technology with

System Sensor/200 protocol

• Integration of conventional and special detectors into the ADM loop

• Output for resetting of detectors

• Setting of module address via decadic rotary switches

Description

The addressable Conventional Zone Module M512ME serves for the integration of conventional detectors,

detectors for intrinsically safe areas and special detectors into an ADM loop with System Sensor/200 protocol. The conventional zone module provides an output for resetting special detectors.

The address of the module is easily selected by means of two integrated decadic rotary switches. The Surface

Mounting Box SMB500 is required for mounting the module.

The module must be powered by an external supply.

Speciļ¬ cations

Operating voltage

Current consumption from loop

Ambient temperature

Dimensions L × W × H (without mounting plate)

Weight

Approval

Order number

Order name

Surface Mounting Box

Dimensions W × H × D

Colour

Weight

Order number

Order name

18 – 32VDC

300µA (quiescent)

-10°C to +60°C

70 × 70 × 32 (mm)

142g

VdS G297009

249045

Conventional Zone Module/Anal./500/SS M512ME

125 × 124 × 55 (mm) cream

155g

249004

Surface Mounting Box for M500/SS SMB500

Building Safety. Building Security.

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED