advertisement
Monitor Module
M210E
• ADM loop technology with
System Sensor/200 protocol
• One input with line-monitoring for wire breakage and short circuit
• Status LED
• Setting of module address via decadic rotary switches
• Mounting in module box or by means of mounting base
Description
The addressable Monitor Module M210E serves for the line-monitored integration of contact detectors, such as manual call points, sprinkler system contacts or supervising contacts, into the bidirectional communication on the ADM loop with System Sensor/200 protocol.
A status LED indicates the condition of the monitor module. Separate terminals enable the operation of the module with or without the integrated dual-isolator.
Accessories for mounting on a wall, on a plate or on a
DIN rail are available.
Speciļ¬ cations
Operating voltage
Current consumption
Ambient temperature
Dimensions L × W × H
Colour
Weight
Approval
Order number
Order name
Supply through loop voltage approx. 510µA (quiescent)
-20°C to +60°C
93 × 94 × 23 (mm) cream
110g
VdS G202140
249100
Monitor Module 1xSurv.In/Anal./200/SS M210E
Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
A
M210E_DBL_LST_EN_0804.PDF • PAGE 1
Surface Mounting Box
Dimensions L × W × H
Order number
Order name
Base for Mounting Plate
Order number
Order name
Base for Carrier Rail
Order number
Order name
132 × 137 × 48 (mm)
249108
Surface Mounting Box for M200/SS M200SMB
249109
Base for Mounting Plate for M200/SS M200E-PMB
249110
Base for Carrier Rail for M200/SS M200E-DIN