Nortec MH Series Installation manual
Add to my manuals
40 Pages
Nortec MH SERIES is an advanced control unit designed to provide precise humidity and temperature control in various industrial and commercial applications. With its intuitive user interface, comprehensive configuration options, and extensive monitoring capabilities, the Nortec MH SERIES empowers users to achieve optimal environmental conditions efficiently and reliably. From manufacturing facilities and data centers to healthcare and hospitality environments, the Nortec MH SERIES offers a versatile solution for humidity management.
advertisement
MH
Series
CONTROL UNIT
Installation Manual
2544831-A
PROPRIETARY NOTICE
This document and the information disclosed herein are proprietary data of
WALTER MEIER LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of
WALTER MEIER LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the NORTEC name should be taken as referring to WALTER MEIER LTD.
LIABILITY NOTICE
WALTER MEIER LTD. does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by WALTER MEIER LTD.
COPYRIGHT NOTICE
Copyright 2008, WALTER MEIER LTD. All rights reserved.
RECORD OF REVISIONS
For each revision, put the revised pages in your manual and discard the superseded pages. Write the revision number and revision date, date put in manual, and the incorporator’s initials in the applicable columns on the Record of Revisions.
Revision
Number
Revision
Date
Date Put
In Manual By
Revision
Number
Revision
Date
Date Put
In Manual By
TABLE OF CONTENTS
Subject Page
10-00 INTRODUCTION
1.
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 NOTES ON THE OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.
3.
OPERATING THE MH CONTROL UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 FUNCTION OF THE DISPLAY AND OPERATING ELEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 SWITCHING THE CONTROL UNIT ON AND OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 REMOTE OPERATING AND FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 OVERVIEW AND OPERATING OF THE MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EXPLANATION OF CONFIGURATION SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 EXPLANATION OF THE STATUS INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 EXPLANATION OF UNIT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 EXPLANATION OF ERROR HISTORY LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
10-10 CONFIGURATION
1.
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.1 UNIT SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2 MODBUS SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10-20 OPERATIONAL FUNCATIONS
1.
OPERATIONAL FUNCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.1 CARRYING OUT MANUAL DRAINING / PIPE FLUSHING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.2 RESETTING THE MAINTENANCE INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.3 RESETTING THE HOURS METER OF THE UV LAMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10-30 TROUBLESHOOTING
1.
FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.1 FAULT INDICATION 28
1.2 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.3 RESETTING THE ERROR INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
WARRANTY
THIS PAGE INTENTIONALLY LEFT BLANK
10-00
INTRODUCTION
10-00
Page 1
2008-12-03
1. INTRODUCTION
1.1 NOTES ON THE OPERATING INSTRUCTIONS
Limitation
These operating instructions are an addendum to the installation and operating instructions for the Nortec MH and describe the operating of the MH control unit, which is used with the models Nortec MHTC Flow, MHB Reflow, MHTC Reflow. These operating instructions are meant for well trained personnel being sufficiently qualified.
Safekeeping
Please safeguard these operating instructions in a safe place, where they can be immediately accessed. If the equipment changes hands, the documentation must be passed on to the new operator.
If the documentation gets lost, please contact your local Nortec representative.
Copyright protection
The present operating instructions are protected under the Copyright Act. Passing-on and reproduction of the manual (or part thereof) as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to legal prosecution and arises liability for indemnification. The manufacturer reserves the right to fully exploit commercial patent rights.
1.2 SAFETY
Every person operating the MH control unit must have read and understood the operating instructions of the MH control unit as well as the installation and operating instructions of the Nortec MH (specially the safety instructions).
Knowing and understanding the contents of the operating instructions of the MH control unit and the installation and operating instructions of the Nortec MH is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
10-00
Page 2
2008-12-03
2. OPERATING THE MH CONTROL UNIT
2.1 FUNCTION OF THE DISPLAY AND OPERATING ELEMENTS
Figure 1. Display
10-00
Page 3
2008-12-03
2.2 SWITCHING THE CONTROL UNIT ON AND OFF
NOTE: For putting the unit into operation and taking the unit out of operation please follow the procedures described in the installation and operating instructions for the
Nortec MH.
Switching the MH control unit on
The control carries out a system test, during which all the
LEDs light up and the opposite display is shown. If a failure occurs on the system test, a corresponding error message is shown in the display.
After the system test the control is in normal operation mode.
The display shows the standard operating display. Note: The contents of the standard operating display depends on the type (MHTC Flow, MHTC Reflow), the actual operating status and on the configuration of the Nortec MH and can differ from the opposite display.
Switching the MH control unit off
The display goes out. On models MHB Reflow and MHTC Reflow the drain valve opens and the water tub empties.
Note: The different hygiene functions (regular draining, flushing of the supply line, etc.) remain active also in times without humidification / cooling demand, the control unit should only be switched off for maintenance or, troubleshooting, or to disable completely operation (as in seasonal shutdown).
2.3 REMOTE OPERATING AND FAULT INDICATION
If your control is equipped with a remote indication board (accessory) the following operating status are shown remotely:
Activated remote indication relay
H1 “Error” A fault is present, further operation is not possible
Red LED lights. An error message is shown in the display
H2 “Service”
H3 “Humidification”
H4 “Unit on”
Maintenance or UV lamp
(option) replacement is due. The unit remains operational for a certain time
Unit is humidifying
Unit ready for operation
Yellow LED lights. The service warning message is shown in the display
Green LED lights
Unit switch lights
10-00
Page 4
2008-12-03
2.4 OVERVIEW AND OPERATING OF THE MENU
The operating and display is operated via the four keys located just below the display. The four status fields at the bottom of the display show the current function of the keys.
Keys
Figure 2. Menu Overview
10-00
Page 5
2008-12-03
3. EXPLANATION OF CONFIGURATION SETTINGS
3.1 EXPLANATION OF THE STATUS INFORMATION (INDICATION STATUS)
In normal operation mode the control un it is in the status level. The status level forms a loop that includes several pages holding operating information which can be accessed with the arrow keys. The various displays of the status level are shown below.
Standard operating display
The appearance of the standard operating display depends on the actual operating status and the configuration of the Nortec MH
Standard operating display with external control via the external controller.
Standby (no humidity demand) or Demand % (humidity demand present).
Standard operating display with internal control.
- Actual humidity in %rh.
- Configured humidity setpoint in %rh.
Info Page: Settings
- Software version.
- Selected control signal source.
- Configured control signal range.
- Configured Modbus address of the unit.
Info Page: Performance data
- Configure power limitation in % of the maximum output.
- Actual output unit A in kg/h.
- Actual total output in kg/h (the same as Capacity A unless a second module is connected to control unit).
.
Info Page: Operating hours
- Total operating hours of the Nortec MH.
- Remaining operating hours to the next maintenance.
10-00
Page 6
2008-12-03
Info Page: Clean Trg. 1
This page shows the current settings for the time based and externally activated forced draining/box cleaning (MHTC Reflow) or the box cleaning (MHTC Flow), respectively.
Note: Wash = draining with simultaneous box cleaning (MHTC Reflow) or box cleaning only (MHTC Flow), Drain = draining only.
– Time controlled draining/box cleaning (Timer).
– Actual time of day.
– Point in time of the next draining/cleaning cycle.
– Configured cleaning mode.
– Interval controlled draining/box cleaning (Periodic).
– Configured interval time in hours.
– Remaining time in hours up to the next draining/cleaning cycle.
– Configured cleaning mode.
– Externally controlled draining/box cleaning
(Demand).
– Actual status of the draining/cleaning demand.
– Configured cleaning mode.
– Clean Trg. 1 deactivated (can appear only with module MHTC Flow).
Info Page: Clean Trg. 2 (Note: This page is not shown with model MHTC Flow)
– Fill cycle controlled draining (Cycle).
– Number of fill cycles between cleaning/draining cycles.
– Remaining fill cycles up to the next draining.
– Cleaning mode (Wash= Draining with simultaneous box cleaning or box cleaning only, Drain= draining only).
– Conductivity controlled draining/cleaning (µSensor) --
>Option.
– Set conductivity limit value inn µS/cm.
– Actual conductivity value of the water in the tub in
µS/cm.
– Configured cleaning mode.
– Operation-dependent draining deactivated (Off).
10-00
Page 7
2008-12-03
10-00
Page 8
2008-12-03
Info Page: Box drying
This page shows the settings for box drying.
– Time controlled box drying (Timer)
– Actual time of day
– Point in time of the next drying cycle
– Interval controlled box drying (Periodic)
– Configured interval time in hours
– Remaining time in hours up to the next drying cycle
Info Page: Supply line flushing function/water quantity reduction function
– Indicates if the supply line flushing function.
– Indicates if the "Softstart" water conservation function is enabled.
Info Page: UV Module (option)
Indicates if the UV water treatment option is enabled
(Note: UV treatment requires optional components be installed).
3.2 EXPLANATION OF UNIT INFORMATION
Path: Main menu > Info > Unit Status
Press <> and <> keys, in order to select the unit information available in the list:
– System Operation Hour:
Total operating hours of the control unit (unit on) since the initial commissioning of the unit.
– Relay Humidity:
Actual status of the remote indication relay “Humidify”.
– Relay Service:
Actual status of the remote indication relay “Service”.
– Relay Error:
Actual status of the remote indication relay “Error”.
– Relay Unit On:
Actual status of the remote indication relay “Unit on”.
– Drain Valve:
Actual operating status of the drain valve.
– Inlet Valve:
Actual operating status of the inlet valve.
– Pump:
Actual operating status of the circulation pump.
– UV Lamp:
Actual operating status of the UV lamp
– Stage 1 Valve: Actual operating status of the step valve 1
– Stage 2 Valve: Actual operating status of the step valve 2
– Stage 3 Valve: Actual operating status of the step valve 3
– Pressure Sensor (MHTC Flow only):
Actual operating status of the minimum pressure switch
– Max Level Sensor (MHTC Reflow only):
Actual operating status of the minimum level sensor
– Thermal Contact (MHTC Reflow only):
Actual operating status of the thermal contact (pump motor protection)
– Extension Present:
Indication, whether or not a unit extension is present.
– Wash Demand:
Actual status of the external demand triggering a wash cycle.
Press the <Esc> key several times to quit the information list and to return to the standard operating display.
10-00
Page 9
2008-12-03
3.3 EXPLANATION OF ERROR HISTORY LIST
The last 10 faults that occurred during operation are saved in the error history list and can be reviewed.
Path: Main menu > Info > Error History
The last error that occurred is shown with:
– Current Error being viewed / Total number of errors
recorded.
– date and time of occurrence
– error code (Warning: W..., Error: E...– error message
– additional info text regarding the error
Press < Å> and <Æ> keys, in order to select further error messages in the list.
Press the <Esc> key several times to quit the error history list and to return to the standard operating display.
10-00
Page 10
2008-12-03
10-10
CONFIGURATION
10-10
Page 11
2008-12-03
1. CONFIGURATION
1.1 UNIT SETTINGS
1.1.1 Launching the unit settings menu
Path: Main menu > User > Password entry:
8808 > Settings
Press the < È> and <Ç> keys in order to select the individual settings in the settings menu.
Detailed information on the different settings are found in the following chapters sections.
10-10
Page 12
2008-12-03
1.1.2 Select dialogue language
Select “Language” in the settings menu, then press the <Set> key. In the following modification dialogue select the desired dialogue language.
After confirmation, the unit automatically switches to the selected dialogue language.
Factory setting: English
Options: French, Spanish
1.1.3 Control Settings
Select “Controls” in the settings menu, then press the <Set> key.
The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maximum number of settings available.
DESCRIPTION OF THE SETTINGS
SignalSource
Hum.Control:
Selecting the signal source.
Factory setting: Analog
Options: Analog
Modbus
Selecting the control type.
Factory setting: External
Controlsign.
Hum.Setpoint:
P-Band:
Integr.-Time:
Options: External (external continuous controller)
24VOn/Off (external On/Off humidistat)
Int. (P) (Internal P controller)
Int. (PI) (Internal PI controller)
Selecting the control signal.
NOTE: This setting is available only if control type
“External”, “Int. (P)” or “Int. (PI)” is selected.
Factory setting: 0–10V
Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–
16V, 0–20mA, 4–20mA
Setting the n ominal humidity value inn %rh.
NOTE: This setting is available only if the internal P or PI controller is activated.
Factory setting: 50 %rH
Setting range: 20...99 %rH
Setting the proportional range inn % for the internal
P/PI conntroller.
NOTE: This setting is available only if the internal P or PI controller is activated.
Factory setting: 18 %
Setting range: 1...100 %
Setting the integral time in minutes for the internal
PI controller.
NOTE: This setting is available only if the internal P or PI controller is activated.
Factory setting: 18 Minutes
Setting range: 1...60 Minutes
10-10
Page 13
2008-12-03
10-10
Page 14
2008-12-03
.
1.1.4 Setting the capacity limitation
Select “Power Limit” in the settings menu, then press the <Set> key. In the upcoming modification dialogue set the desired capacity limitation in % of the maximum capacity of the humidifier.
Factory setting: 100 %
Setting range: 30...100 %
1.1.5 Configuring the supply pipe flushing
Select “Inlet Flush” in the settings menu, then press the <Set> key.
Used to configure the unit to flush supply lines even if there is no demand signal. You can;
- enable / disable inlet flush
- set length of flush
- set time between flushes
DESCRIPTION OF THE SETTINGS
Inlet Flush Enable or disable the supply pipe flushing.
Factory setting: On
Options: On (enable)
Drain Time
Periodic Int
Setting the flushing time in seconds.
Factory setting: 60s
Setting range: 5...600s
Setting the time without demand after which the supply pipe should be flushed.
Factory setting: 12.0 h
Setting range: 0.5 ... 24.0 h
1.1.6 Setting the Cleaning Mode (MHTC Reflow only)
NOTE: The cleaning mode may only be set with the MHTC Reflow. With the cleaning mode you determine whether the humidification boxes will be washed simultaneously during a draining or operation dependent draining /cleaning cycle. This option does not appear for other models.
Select “Clean Mode” in the settings menu, then press the <Set> key. In the upcoming modification dialogue select the desired cleaning/draining mode.
Factory setting: Drain
Options: Drain (draining only)
Wash (Draining w/box cleaning)
NOTE: During operation, the washing process of the humidification boxes can lead to a temporary humidity increase.
10-10
Page 15
2008-12-03
10-10
Page 16
2008-12-03
1.1.7 Configuring the cleaning trigger 1 (Clean Trg. 1)
With the cleaning trigger 1 settings you determine whether the forced draining/cleaning (MHTC Reflow) or the box cleaning (MHTC Flow) is time or interval controlled or triggered via an external signal. The forced draining can be deactivated, however the box cleaning can be deactivated. The forced draining cannot be deactivated for the MHTC Reflow. The washing can be deactivated for either the MHTC Flow or Reflow.
Note: the forced cleaning/draining serves to empty the water tub regularly and independent of the operation time of the Nortec MH.
Select “Clean Trg. 1” in the settings menu, then press the <Set> key. The current settings for the forced draining/box cleaning appear. The available settings depend on whether the interval controlled (Periodic (factory setting), timer controlled (Timer) or external signal controlled (Demand) triggering of the forced draining/box cleaning is selected.
Interval controlled draining/box cleaning
(Periodic). With Periodic Int you can determine in which time intervals the draining/box cleaning is performed (setting range: 0.5 ...24 .0h, factory setting: 2.0h).
Time controlled draining/box cleaning
(Timer)With the parameters “time 1” to “time 4” you can define up to four times of day to start the draining/box cleaning (factory setting: no starting times defined).
Triggering the draining/box cleaning via an external signal (Demand). In order to trigger the draining/box cleaning via an external signal a potential-free contact (B4 ) must be connected to the control board of the control unit MH. Closing the contact results in a draining/box cleaning cycle.
Cleaning trigger 1 deactivated (Off)Note: this option is only available/visible for model MHTC
Flow.
1.1.8 Configuring the cleaning trigger 2 (Clean Trg. 2) (MHTC Reflow only)
Note: The cleaning trigger 2 to configure operation dependent draining appears only with the MHTC Reflow. With the cleaning trigger 2 settings you determine whether operation dependent draining is triggered depending on the fill cycles or on the conductivity of the water in the water tub (option) or whether the cleaning trigger 2 should be deactivated.
Select “Clean Trg. 2” in the settings menu, then press the <Set> key. The current settings for the operation dependent draining appear. The settings available depend on whether the operation dependent draining is deactivated
(Off, factory setting) or the fill cycle (Cycle) or the conductivity controlled (µ Sensor) triggering of the operation dependent draining is selected.
Operation dependent draining deactivated (Off)
Fill cycle controlled draining (Cycle). With the parameter “Cycle” you can determine after how many filling cycles a drain is performed (setting range: 10...10000, factory setting: 100).
Conductivity controlled draining (µ Sensor)
(Requires optional components). With the parameter “µS Limit” you can set a conductivity limit value. If during operation the conductivity value of the water in the tub reaches the set limit, a draining is performed (setting range:
10...5 000 µS, factory setting: 1000µS).
10-10
Page 17
2008-12-03
10-10
Page 18
2008-12-03
1.1.9 Configuring the humidification box drying
An occasional drying of the humidification boxes helps prevent germs and bacteria from developing in the humidification boxes. The drying process can be time triggered or, interval controlled, or it can be deactivated.
Note: During operation, the drying process of the humidification boxes can lead to a temporary humidity decrease.
Select “Box Drying” in the settings menu, then press the <Set> key. The current settings for the box drying function appear. The settings available depend on whether the box drying function is deactivated (Off, factory setting) or whether the time controlled (Timer) or the interval controlled (Periodic) triggering of the drying function is selected.
Drying function deactivated (Off ---> factory setting)
Time controlled drying (Timer)With the parameters “time 1” to “time 4 ” you can define up to four times of day to start a box drying process (factory setting: no starting times defined).
Interval controlled drying (Periodic) With the parameter “Periodic Int” you can determine inn which time intervals a box drying process is performed (setting range: 0.5 ...24 .0h, factory setting: 12.0h).
1.1.10 Configuring the Humidifier Maintenance Interval
Select “Maintenance” in the settings menu, then press the <Set> key. In the following dialogue set the desired maintenance interval time in hours. After the maintenance interval time has elapsed a maintenance message appears in the display and the yellow LED lights up. If the maintenance is not performed and the maintenance indication is not reset within a certain time (168 h) , an error message is triggered. Factory setting: 800 h
Setting range: 100... 50000 h
Note: to determine the maintenance interval time please refer to 1.3 in section 10-40 of the installation and operating instructions for the
Nortec MH.
1.1.11
Activating/deactivating the softstart function
If the mats in the humidifier boxes became dry due to a operation interruption, they need a certain time until they are again moistened with water. In order to prevent too much water flows over the humidification boxes in this phase and water droplets are carried in the air flow, the amount of water can be reduced for a fixed time with the
“Softstart” function.
Select “Softstart” in the settings menu, then press the <Set> key. In the modification dialogue you can activate or deactivate the softstart function. Factory setting: Off Options:
Off (Softstart function deactivated)
On (Softstart function activated)
10-10
Page 19
2008-12-03
1.1.12
Performing remote relay tests
With the test functions under “Remote Test” you can check the function of the relays
“Humidification”, “Service”, “Error” and “Unit on”.
Select “Remote Test” in the settings menu, then press the <Set> key.
Press the < Ç> and <È> keys in order to select the relay you want to test and press the <Set> key to activate/deactivate the corresponding relay for testing.
10-10
Page 20
2008-12-03
1.1.13
Setting the date
Select “Date” in the settings menu, then press the <Set> key. In the following dialogue set the actual date (format “tt.mm.jj”).
1.1.14
Setting the time
Select “Time” in the settings menu, then press the <Set> key. In the following dialogue set the actual time (format “hh.mm”).
1.1.15
Setting the display contrast
Select “Contrast” in the settings menu, then press the <Set> key. In the following dialogue set the desired value for the display contrast.
Factory setting: 20
Setting range: 0 (no display) ...100 (display turns black).
1.2
Modbus Settings
Select the Modbuus menu: Path: Main menu >
User > Password entry: 8808 > Modbus
The settings for the Modbuus appear.
Description of Modbus Settings
Modbus Add.: Setting the modbus address of the Nortec MH.
Factory setting: 1
Setting range: 1...247
Parity:
Timeout:
Selecting the parity bit for the data transmission.
Factory setting: None.
Options: None1, None2, Odd, Even
Setting the time out time for the data transmission.
Factory setting: 5
Seconds Setting range: 1...600 Seconds
10-10
Page 21
2008-12-03
THIS PAGE INTENTIONALLY LEFT BLANK
10-10
Page 22
2008-12-03
10-20
OPERATIONAL
FUNCTIONS
10-20
Page 23
2008-12-03
1. OPEARTIONAL FUNCTIONS
1.1 CARRYING OUT MANUAL DRAINING / PIPE FLUSHING
To carry out a manual draining (MHTC Reflow) or pipe flushing (MHTC Flow) proceed as follows:
Drain
1. Briefly press the drain key. The drain/flush dialogue appears in the display.
2. Press the <Start> key.
– Models MHTC Reflow: The drain valve opens after a delay of up to 3 minutes and the water tub empties. The yellow LED flashes.
– Model MHTC Flow: The inlet valve and the flushing valve open and the pipe is flushed. The
yellow LED flashes.
To stop the drain/flush cycle press the <Stop> key.
Note: By pressing the <Esc> key the control unit returns to the standard operating display. A drain/flush cycle in progress will be stopped automatically.
10-20
Page 24
2008-12-03
1.2 RESETTING THE MAINTENANCE INDICATION
After completing maintenance work, the maintenance indication (yellow LED lights) must be reset on the models MHTC Flow, MHB Reflow, MHTC Reflow.
Note: If the maintenance indication is not reset within 168 hours a fault is triggered and the unit stops operation.
Select the maintenance menu:
Path: Main menu > User > Password entry: 8808
> Maintenance
Select “Module A”, then press the <Set> key.
Select "Stage Reset”, then press the <Set> key.
The reset dialogue shows up in the display. Press the <Yes> key to reset the maintenance hours of the unit.
Note: Press the <Esc> or <No> key if you wish to abort the reset procedure.
To return to the standard operating display press the <Esc> key several times.
10-20
Page 25
2008-12-03
1.3 RESETTING THE HOURS METER OF THE UV LAMP
After replacing the UV lamp (option) the hours meter of the UV lamp must be reset.
Note: If the hours meter of the UV lamp is not reset within 168 hours the UV maintenance warning an error message is triggered.
Select the maintenance menu:
Path: Main menu > User > Password entry: 8808
> Maintenance
Select “Module A”, then press the <Set> key.
Select "UV lamp Rst”, then press the <Set> key.
The reset dialogue shows up in the display.
Press the <Yes> key to reset the hours meter of
the UV lamp.
Note: Press the <Esc> or <No> key if you wish to abort the reset procedure.
To return to the standard operating display press the <Esc> key several times.
10-20
Page 26
2008-12-03
10-30
TROUBLESHOOTING
10-30
Page 27
2008-12-03
1. FAULT INDICATION
1.1 FAULT INDICATION
Malfunctions during operation are indicated by a corresponding warning or error message in the display of the control unit:
Warning messages (additionally to the error message the red LED is on)
Further operation is still possible. If the cause of the malfunction disappears of its own accord, the warning message will automatically switch off. If the cause of the malfunction does not disappear even after a longer period of time, an error message is triggered.
Error message (additionally to the error message the red LED is on)
Further operation is not possible. The malfunction is stored in the error list.
By pressing the <Info> key additional information are displayed for each warning or error message.
By pressing the <Esc> key the control unit returns to the standard operating display.
10-30
Page 28
2008-12-03
--
--
--
--
--
--
--
--
Unit Module B missing
Red lights
Wrong parameter settings
Red lights
Hardware Fault (flash)
Hardware Fault (clock)
1.2 TROUBLESHOOTING
1.2.1 System Faults
Warning Error
LED Display LED Display
MH Card Missing MH Card missing (Test run possible)
Red flashes
Red lights
-- --
MH Card is Empty
Red lights
-- --
MH Card is defective
Red lights
-- --
MH Card is incompatible
Red lights
Cause Remedy
No MH Card installed on the control board.
No data stored on the MH Card
Invalid data stored on the MH Card
Install MH
Card or start test run.
Install new
MH Card.
Install new
MH Card.
The MH Card is not compatible with the hardware or the basic settings on the control board.
No response from module B. Flat ribbon cable interrupted or disconnected
120V supply cable disconnected.
Data of CPU and
MH Card do not match.
CPU on control board defective.
CPU on control board defective.
Install new
MH Card.
Modify basic settings.
Plug in flat ribbon cable, plug in 120V supply cable.
Install correct MH
Card.
Contact your
Nortec supplier.
Replace control board.
Replace control board.
10-30
Page 29
2008-12-03
1.2.2 Unit Faults
External safety chain is open
Red and green flash
Error level sensor
Red flashes
Maximum filling time exceeded (30 minutes)
Red flashes
--
Error level sensor
Red lights
Air proving interlock open.
Air flow monitor triggered
Safety humidistat triggered.
The level sensor is blocked or defective
(broken or shortcircuited).
Maximum filling time exceeded (more than 4 hours)
Red lights
Note: This error message is reset automatically as soon as the water supply functions again.
Water supply blocked/shut-off valve closed/water pressure too low. Water treatment unit (fully demineralised water) is regenerating.
Check water supply
(filter, pipes, etc.),
Check/open shutoff valve, Check water pressure.
Inlet valve blocked or defective.
Check strainer in the inlet valve, clean if necessary.
Replace inlet valve. blocked in open position or not electrically connected. Drain valve is open unless powered drain system. drain valve, connect drain valve. drain system.
If applicable, check/turn on fan.
Check fan/filter of the fan system.
Wait, if applicable, check safety humidistat
Check/clean or replace level sensor. Check level sensor with ohmmeter: If no water is in the tub, the circuit of the level sensor must be closed. If the water in the tub is on maximum
level sensor must be open.
10-30
Page 30
2008-12-03
When draining the water tub float is not open within 8 minutes
Red flashes
Conductivity of the water in the tub too high
Red flashes
When draining the water tub the float is not open within 4 hours
Red lights
Drain valve blocked/defective or clogged.
Siphon clogged.
Relay defective
(weld-shut).
Level sensor stucked or short circuited.
Backpressure in the siphon.
Conductivity of the water in the tub too high
Red lights
Conductivity after draining, restart or cleaning cycle during 10 minutes higher than the set nominal value.
Conductivity sensor defective.
Conductivity transmitter defective.
Check/clean or replace drain valve.
Clean siphon.
Replace control board.
Clean/Replace level sensor.
Install special siphon.
Increase the nominal value or enhance water quality.
Replace conductivity sensor.
Replace conductivity transmitter.
10-30
Page 31
2008-12-03
LED Display LED Display
Maintenance due Maintenance not performed and/or maintenance
indication not reset
Red flashes and yellow lights red and yellow lights
Maintenance due. Perform maintenance according to section 10-40 of the installation and operating instructions for the Nortec MH.
Then, reset the maintenance indication. performed and/or maintenance indication not reset within 168 h (1 week). maintenance according to section 10-40 of the installation and operating instructions for the Nortec MH.
Then, reset the maintenance indication.
Maximum lifespan of the
UV lamp reached red flashes and yellow lights
Maximum lifespan of the
UV lamp reached red and yellow light
Maximum lifespan of the UV lamp reached.
UV lamp not replaced or hours counter of the UV lamp not reset after replacement of the
UV lamp. Unit switches off after
168 hours.
Wrong UV lamp installed.
Replace UV lamp and clean glass tube
Replace UV lamp and clean glass tube (see
1.4.2 in section 10-40
), then reset hours counter of the UV lamp.
Install correct UV lamp.
No signal from humidity
sensor
Red flashes
No signal from humidity
sensor
Red lights
Sensor cable not connected or sensor cable interrupted.
Humidity sensor defective.
Connect/replace sensor cable.
Replace humidity sensor.
10-30
Page 32
2008-12-03
No signal from
conductivity sensor
Red flashes
No signal from
conductivity sensor
Red lights
Nortec SH2 deactivated
via Modbus
Red flashes
Modbus system failed
Red lights
Red flashes
Timeout Modbus
-- Red lights
Cleaning of humidification
boxes in progress
-- -- --
Draining of water tub in
progress
-- -- --
Sensor cable not connected or sensor cable interrupted.
Conductivity transmitter defective or wrong version
(conductivity constant).
Conductivity transmitter not configured correctly.
Conductivity sensor defective.
Connect/replace sensor cable.
Replace conductivity transmitter.
Contact your
Nortec supplier.
Replace conductivity sensor.
Nortec MH deactivated via
Modbus.
Modbus system failed.
Timeout. No activity from
Modbus
None or activate
Nortec MH via
Modbus.
Check/activate
Modbus system.
Activate Modbus system humidification boxes in progress.
None (wait). tub in progress.
10-30
Page 33
2008-12-03
Water pressure too low
(flow only)
Red flashes
Water pressure for more than
4 hours too low (flow only)
Red
Lights
Water supply blocked/shut-off valve closed/water pressure too low.
Water treatment unit (fully demineralised water) is regenerating.
Inlet valve blocked or defective.
Flushing valve leaking.
Check water supply (filter, pipes, etc.),
Check/open shut-off valve.
Check water pressure.
Check strainer in the inlet valve, clean if necessary.
Replace inlet valve.
Replace flushing valve.
1.3 RESETTING THE ERROR INDICATION
To reset the error indication: Investigate and correct cause of error. Turn control panel
ON/OFF switch to OFF.
Wait approx. 5 seconds, then turn control panel ON/OFF switch to On position.
Note: If the fault has not been eliminated, the error indication reappears after a short while.
10-30
Page 34
2008-12-03
WARRANTY
(1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
(2) THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or
90 days, whichever is longer.
(3) The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of
THE COMPANY.
(4) THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
(5) THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
(6) THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
(7) THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation.
U.S.A.
Walter Meier (Climate USA) Inc.
826 Proctor Avenue
Ogdensburg, NY 13669
TEL: 1-866-NORTEC-1
EMAIL: [email protected]
WEBSITE: www.humidity.com
CANADA
Walter Meier (Climate Canada) Ltd.
2740 Fenton Road
Ottawa, ON K1T 3T7
TEL: 1-866-NORTEC-1
FAX: (613) 822-7964
Authorized Agent:
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 6 INTRODUCTION
- 6 1.1 NOTES ON THE OPERATING INSTRUCTIONS
- 6 1.2 SAFETY
- 7 OPERATING THE MH CONTROL UNIT
- 7 2.1 FUNCTION OF THE DISPLAY AND OPERATING ELEMENTS
- 8 2.2 SWITCHING THE CONTROL UNIT ON AND OFF
- 8 2.3 REMOTE OPERATING AND FAULT INDICATION
- 9 2.4 OVERVIEW AND OPERATING OF THE MENU
- 10 EXPLANATION OF CONFIGURATION SETTINGS
- 10 3.1 EXPLANATION OF THE STATUS INFORMATION
- 13 3.2 EXPLANATION OF UNIT INFORMATION
- 14 3.3 EXPLANATION OF ERROR HISTORY LIST
- 16 CONFIGURATION
- 16 1.1 UNIT SETTINGS
- 25 1.2 MODBUS SETTINGS
- 28 OPERATIONAL FUNCATIONS
- 28 1.1 CARRYING OUT MANUAL DRAINING / PIPE FLUSHING
- 29 1.2 RESETTING THE MAINTENANCE INDICATION
- 30 1.3 RESETTING THE HOURS METER OF THE UV LAMP
- 32 FAULT INDICATION
- 33 1.2 TROUBLESHOOTING
- 38 1.3 RESETTING THE ERROR INDICATION