TECHNICAL MANUAL

AIR COOLED WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS

06617645-02

TEV LTD, ARMYTAGE ROAD, BRIGHOUSE, WEST YORKSHIRE, HD6 1QF. TEL: + 44 (0) 1484 405630 FAX: +44 (0) 1484 405620

EMAIL: [email protected] WEB: www.quartz.co.uk

INDEX

Page

QLAC LS cooling capacities and compressor input power

QLAC /HP/LS heating capacities and compressor input power

12

17

QLAC K1 – K2 Water pumps - available static pressure 20

Correction tables 23

/ 24

Location and minimum technical clearances 25

Start up and device

28

2 06617645-02

EC DECLARATION OF CONFORMITY

Herewith TEV Ltd declare that the air conditioning equipment designated below is in accordance with the essential requirements of current EC Directives.

This declaration is based on the design and construction of the equipment in the form brought onto the market by TEV Ltd.

If alterations are made to the machinery without prior consultation with TEV Ltd. this declaration becomes invalid.

Relevant EC Council Directives: Machinery Directive (98/37/EC)

EMC Directive (89/336/EEC in the versions 93/68/EEC)

Low Voltage Directive (73/23/EEC in the version 93/68/EEC)

Directive PED (97/23/EC)

Applied harmonised standards:

Basis of self attestation:

EN 292-1:1991, EN 292-2:1991, EN 294:1992, EN 349:1993, EN 55014-1:2000,

EN 55014-2:1997, EN 60335-1:2002, EN 60335-2-40:2003, EN 61000-3:1995

BS EN ISO 9001:2000 BSI registered firm certificate no. FM671

EG KONFORMITÄTSERKLÄRUNG

Hiermit erklärt TEV Ltd, daß die unten angegebenen Klimageräte in Übereinstimmung mit den Gesundheits - und

Sicherheitsbestimmungen der gültigen EG-Direktiven stehen.

Diese Erklärung bezieht sich auf die Konzeption und die Konstruktion der Geräte, die von TEV Ltd. auf den Markt gebracht werden.

Wenn Veränderungen an den Geräten ohne vorherige Absprache mit TEV Ltd. gemacht werden, so wird diese Erklärung ungültig.

Relevante EG Richtlinien: Maschinen - Richtlinien (Version 98/37/EWG)

EMV Direktive: (89/336/EWG/EEC in den Versionen 93/68/EWG)

Niederspannungsrichtlinie: (73/23/EWG/EEC in der Version 93/68/EWG)

Richtlinien PED (97/23/EC)

Angewandte Standard

Normen: EN 292-1:1991, EN 292-2:1991, EN 294:1992, EN 349:1993, EN 55014-1:2000,

EN 55014-2:1997, EN 60335-1:2002, EN 60335-2-40:2003, EN 61000-3:1995

Bestätigungsgrundlage: BS EN ISO 9001:2000 Zertifikat Nr. FM 671

Model Name:

Nom du modèle:

Nombre del Modelo:

Serial Number:

Numéro de série:

Numéro de Serie:

Machinebeschrijving:

Modellname:

Serienummer:

Serienummer:

Model Part Number: Modellnummer:

Référence du modèle: Número de la Parte del Modelo:

Artikelnummer:

"responsible person":

Signature d' TEV Ltd Le responsable: persoon bij TEV Ltd.:

Unterschrift von TEV Ltd.

"verantwortliche Person":

Firma de TEV Ltd. designado como

"persona responsable":

Position of Signatory:

Fonction du signataire:

Cargo del firmante:

Functie van gemachtigde

Position desUnterschreibenden:

(A C HAMMERSLEY)

MANUFACTURING DIRECTOR

DIRECTEUR DE FABRICATION

DIRECTOR FABRICACIÓN

PRODUKTIE COÖRDINATOR

PRODUKTIONS DIREKTOR

3 06617645-02

TECHNICAL FEATURES

Frame

All QLAC unit enclosures are manufactured from hot-galvanised sheet steel, painted with polyurethane powder enamel and stoved at 180°C to provide a durable, corrosion resistant finish. The frame is selfsupporting with removable panels. All screws and rivets are made from stainless steel. The paint colour is

RAL 7035.

Refrigerant circuit

Refrigerant is R407C. The refrigerant circuit is assembled using quality brand components and in accordance with ISO 97/23 concerning welding procedures. Model sizes 140 and upwards have multiple refrigerant circuits. Each refrigerant circuit is totally independent of the other. Failure of one circuit does not influence the other circuit. The refrigerant circuit includes:

Liquid line manual shut-off valve

Sight glass

Filter drier

Thermal expansion valve with external equalizer

Electronic expansion valve with control to optimise efficiency in part load conditions (option)

Reversing valve (heat pump version only)

Non return valve (for heat pump version only)

Liquid receiver (for heat pump version only)

Schraeder valves for maintenance and control

Pressure safety device (according to PED requirements)

Compressors

Scroll compressors are used, each fitted with a crankcase heater and provided with thermal overload protection via a klixon embedded in the motor winding. Compressors are mounted in a separate chamber in order to be separated from the air stream and to enable maintenance to be performed whilst the unit is still operating. The crankcase heater is always powered when the compressors are in stand-by. All compressors are in tandem configuration. This creates higher efficiencies uring part load conditions compared to units with independant refrigeration circuits per compressor.

Condensers

Condensers are made of copper tubes and aluminium fins. The diameter of the copper tubes is 3/8” and the thickness of the aluminium fins is 0.1 mm. Tubes are mechanically expanded into the aluminium fins to maximise heat transfer. The geometry of these condensers guarantees a low air side pressure drop and allows the use of slow running (and low noise) fans. The condensers can be protected by a metallic filter

(option).

Fans

Fans are axial type with aerofoil blades. They are statically and dynamically balanced and supplied complete with safety fan guard that complies with the requirements of EN 294. They are mounted on the unit frame using rubber anti-vibration mounts. The electric motors are 6 pole (approx. 900 rpm) in the low noise version and 8 pole (approx. 750 rpm) in the extra low noise version. The fans are directly driven and are fitted with integral overload protection. Motors have moisture protection to IP 54.

4 06617645-02

5

Evaporators

The plate evaporators are made of 316 stainless steel, braze-welded. Unit sizes 040 to size 130 have a single water side circuit. From unit size 140 upwards, the circuits are double “cross flow” type. The use of these types of evaporator allows a significant reduction of the refrigerant charge for the unit compared to traditional shell-in-tube evaporators and increases the efficiency of the refrigerant cycle during part load operation. The evaporators are factory insulated with flexible close-cell insulation and can be fitted with an antifreeze heater (optional). Each evaporator is provided with a temperature sensor as antifreeze protection.

Hydraulic circuit (K versions only)

QLAC chillers can be supplied with an optional built in hydraulic kit that includes:

Water tank: various capacities (depending on the size of the unit), factory insulated with flexible close-cell material and ready for installation of an antifreeze kit (option). The water tank is installed on the supplied water side (7°C) in order to minimize fluctuations in the water temperature caused by cycling of the compressors. By installing on the supply side, the supply water temperature can be maintained for some time after the compressors turn off, a situation that cannot be achieved if the water tank is installed on the return water side (12°C).

Water pump: centrifugal type, is available in single (K1) or double configuration (K2). In the K2 version, one pump is running and one pump is in stand-by. The change over can be manual (by a manual switch installed in the electric box) or automatically controlled by the microprocessor (option). The expansion vessel, safety valve and manual valves with fittings are sited in the hydraulic circuit.

Electrics enclosure

Access to the electrics enclosure is achieved by switching the mains isolator to "OFF" and removing the front cover.The electrics conform to electromagnetic compatibility norms CEE 73/23 and 89/336. Moisture protection is IP55.

All QLAC units have installed, as standard, a compressor sequence relay, which disables compressor operation if the power supply phase sequence is incorrect (scroll compressors can be damaged if they operate in reverse). The following components are also installed as standard:

Mains switch,

Compressor fuses

Magnetic-thermal switches (MCB's) for protection of pumps and fans

Control circuit automatic breakers

Compressor contactors Fan contactors, pump contactors.

The terminal board is supplied with volt free contacts for remote ON-OFF, Heat / Cool change over (heat pumps only) and general alarms.

Microprocessors

QLAC units are supplied with microprocessor controls as standard. The specific controller used depends upon the unit size, number of features and use of optional features e.g. electronic expansion valves.The microprocessor controls the following basic functions: regulation of the water temperature antifreeze protection compressor timing compressor automatic starting sequence alarm reset volt free contact for remote common alarm alarms and leds.

Any microprocessor can, on request, be connected to a BMS system for remote control and management.

Typically, solutions can be found for MODBUS, LONWORKS, BACNET or TREND protocols.

Control and protection devices

All units are supplied with the following control and protection devices:

Return water temperature sensor, installed on the return water line from the plant (12°C)

Antifreeze protection sensor installed on the outlet water temperature (7°C)

High pressure switch with manual reset

Low pressure switch with automatic reset

High pressure safety valve

Compressor thermal overload protection

Fan thermal overload protection

Flow switch. (std versions supplied loose, K versions factory fitted)

06617645-02

OTHER VERSIONS

The following versions all incorporate energy efficiency features that make a valuable contribution to enabling compliance with the European Energy Performance of Buildings Directive and the 2006 amendments to Part L of the UK Building Regulations.

Heat pump version (HP)

Heat pump versions are provided with a 4-way reversing valve and can produce hot water up to 45-50°C.

They are always supplied with a second thermostatic valve and a liquid receiver to optimise the efficiency of the refrigerant cycle in heating and in cooling. The microprocessor is set for automatic defrost (for operation in severe ambient conditions) and for Heat/Cool change over by digital input.

Free cooling version (FC)

The Free Cooling option is a system designed to give important energy savings, when the cooling system is operating continuously and when ambients are low. Free cooling units use low temperature ambient air to cool down the water in the system. In some situations, chilled water can be produced without any mechanical refrigeration (compressors) with consequent large reduction of power consumption. The Free

Cooling system comprises:

Free cooling coil: Heat exchanger made of copper tubes and aluminium fins, with bleed valves.

Microprocessor control: The “heart” of the system; it allows correct control of all parameters, leading to high efficiencies over a range of ambient conditions.

3 way valve: An ON/OFF 3 way valve that opens/closes the free cooling circuit, depending on the signal coming from the microprocessor control.

Head pressure control: Maintains the correct condensing pressure in the refrigerant circuit when ambient temperatures are low. In Free Cooling systems, this effect is achieved by partially closing refrigerant circuits in the condensing coil with solenoid valves: this reduces the heat transfer capacity and maintains a suitable condensing pressure.

Heat Recovery Version

A version that includes heat recovery by the addition of a de-superheater heat exchanger located between the compressor and condenser, is also available. This de-superheater can be fitted to both chiller and heat pump versions, however, in the heat pump it must be used only when in cooling mode. In heating mode the water circuit must be isolated. The de-superheater is capable of generating 50°C hot water for domestic use

(washing etc) and can recover up to 25% of the energy removed in cooling by this manner. Such units make a valuable contribution to energy efficiency.

6 06617645-02

WATER CHILLERS AND HEAT PUMPS

QLAC / LS (Low noise version)

TECHNICAL DATA

040 045 050 060 070 080 090 110 MOD.

Cooling capacity

Compressor input power

Water flow rate

Water pressure drop

Heating capacity

Compressor input power

Water flow rate

Water pressure drop kW kW l/h

37 45,0 52,0 58,0 64,0 78,0 90,0 104,0

12,6 15,1 17,2 19,3 21,5 25,8 29,9 33,9

6490 7910 9290 10320 11520 13590 15650 18400

KPa 26,2 32,4 31,5 23,3 30,1 30,4 27,6 26,5 kW kW

38,5

12,9

47,0 55,0 62,0 68,0 83,0 95,0 107,0

15,2 17,3 19,5 21,7 26,4 30,3 34,2 l/h 6630 8085 9460 10665 11695 14275 16340 18400 kPa 28,5 33,8 32,6 24,8 31,0 33,5 30,0 26,5

Total input current (K version)

Total peak current

Maximum input current

Power suppy

A 32,4 36 37,4 40,1 42,8 52,6 62,0 67,5

A 121,4 148,4 154,4 194,4 194,0 235,4 265,1 275,1

A

V/Ph/Hz

39,4 45,4 49,4 54,4 59,4 69,4 81,1 91,1

400/3/50

Airflow m³/h 18000

Fans n° x kW 2 x 0,37 2 x 0,37 2 x 0,69 2 x 0,69 2 x 0,69 2 x 0,69 3 x 0,69 3 x 0,69

Compressors type Scroll n° 2 2 2 2 2 2 2 2 n° 1 1 1 1 1 1 1 1 n° 2 2 2 2 2 2 2 2

Sound power level

(1)

Sound pressure level (2)

Water pump (option)

Water pump input current kW

A

1,1

2,9

1,1 1,1 1,1 1,1 1,5 1,5 2,2

2,9 2,9 2,9 2,9 4,3 4,3 5,3

Water tank capacity (option)

Length

Width

Height

Weight (Standard configuration) kPa 165 160 141 125 110 150 130 150 l 180 180 300 300 300 300 530 530 l 18 18 18 18 18 18 18 18 mm 1870 1870 2608 2608 2608 2608 3608 3608 mm 850 850 1105 1105 1105 1105 1105 1105 mm 1406 1406 1759 1759 1759 1759 1759 1759

Weight (with hydraulic kit) kg 730 750 880 895 930 980 1280 1360

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

7 06617645-02

MOD.

WATER CHILLERS AND HEAT PUMPS

QLAC / LS (Low noise version)

TECHNICAL DATA

120 130 140 160 190 210 240 260

Compressor input power

Water flow rate

Water pressure drop

Compressor input power

Water flow rate

Water pressure drop kW 115,5 128 142 156 181 206,1 232 256 kW 38 42,1 47,3 51,7 59,7 67,8 76 84,2 l/h 20640 22190 24600 27180 31990 36290 41450 45240 kPa 29,4 30,0 30,8 36,0 39,6 42,7 49,0 51,2 kW 120 132 150 165 189 217 242 267 kW 38,5 42,9 48,1 52,8 60,6 68,4 77,1 85,8 l/h 20640 22700 25800 28380 32510 37320 41620 45920 kPa 29,4 31,3 33,8 39,2 40,9 45,1 49,4 52,7

Total input current (K version)

Maximum input current

Power supply

A

V/Ph/Hz

102,1 113,1 119,9 138,3 167,6 185,6 211,6 233,6

400/3/50

Airflow m°/h 55800

Fans n° x kW 3 x 0,69 3 x 0,69 4 x 0,69 4 x 0,69 3 x 2,0 3 x 2,0 4 x 2,0 4 x 2,0

Compressors type Scroll n° 2 2 4 4 4 4 4 4 n° 1 1 2 2 2 2 2 2 n° 2 2 4 4 4 4 4 4

Sound power level

(1)

Sound pressure level (2)

Water pump (option)

Water pump input current

Water tank capacity (option)

Length

Width

Height

Weight (Standard configuration) kW

A

2,2

5,3

2,2 2,2 3,0 3,0 3,0 4,0 4,0

5,3 5,3 8,5 8,5 8,5 9,9 9,9 kPa 120 130 105 180 140 110 170 155 l 530 530 530 670 670 670 670 670 l 18 18 18 18 18 18 18 18 mm 3608 3608 4108 4108 4708 4708 4708 4708 mm 1105 1105 1105 1105 1105 1105 1105 1105 mm 1759 1759 2179 2179 2262 2262 2262 2262 kg 1200 1230 1650 1700 1960 2050 2160 2480 kg 1410 1440 1860 2000 2260 2350 2460 2780

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

8 06617645-02

WATER CHILLERS AND HEAT PUMPS

QLAC / LS (Low noise version)

TECHNICAL DATA

MOD. 300 320 380 430 500

Compressor input power

Water flow rate

Water pressure drop

Free cooling capacity

Water flow rate

Water pressure drop

Total input current (K version)

Total peak current

Maximum input current

Power supply kW 290 321 383 432 481 l/h 49880 55200 65800 74300 82700 kPa 34 39 32 38 44 kW 185 185 235 245 240 kW 12 12 16 16 16 l/h 49880 55200 65800 74300 82700 kPa 107 121 113 121 141

A

A

A

V/Ph/Hz

262,6 287,2 362 393,5 425

400/3/50

Fans

Compressors n° x kW 6x2 6x2 8x2 8x2 8x2 type Scroll n° 4 4 6 6 6 n° 2 2 2 2 2 n° 4 4 6 6 6

Sound power level

(1)

Sound pressure level (2)

Water pump (option)

Pump available pressure (option)

Water tank capacity (option)

Expansion vessel (option)

Length

Width

Height kW 4 5,5 7,5 7,5 7,5 kPa 160 172 210 190 160 l l 670 670 670 670 670

25 25 50 50 50 mm 4108 4108 4708 4708 4708 mm 2201 2201 2201 2201 2201 mm 2262 2262 2262 2262 2262 kg 2750 2800 3100 3150 3210 Weight (Standard configuration)

Weight (with hydraulic kit) kg 3150 3220 3550 3610 3690

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Free cooling: ambient air temperature 2 °C; water inlet temperature 15°C, glycol 20%, nominal waterflow, compressors switched off

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

9 06617645-02

WATER CHILLERS AND HEAT PUMPS

QLAC / XL (Extra Low noise version)

TECHNICAL DATA

040 045 050 060 070 080 090 110 MOD.

Cooling capacity

Compressor input power

Water flow rate

Water pressure drop kW kW l/h

KPa

### ###

52 58 64 78 90 104

9290 10320 11520 13590 15650 18400

Heating capacity

Compressor input power

Water flow rate

Water pressure drop

Sound power level

(1)

Sound pressure level

(2) kW kW l/h kPa

55,0 62,0 68,0 83,0 95,0 107,0

9460 10665 11695 14275 16340 18400

Total input current (K version)

Total peak current

Maximum input current

Power suppy

A

A

A

V/Ph/Hz

37,4 40,1 42,8 52,6 62 67,5

154,4 194,4 194 235,4 265,1 275,1

49,4 54,4 59,4 69,4 81,1 91,1

400/3/50

Airflow m³/h 24000

Fans

Compressors n° x kW 2 x 1.23 2 x 1.23 2 x 1.23 2 x 1.23 3 x 1.23 3 x 1.23

type Scroll n° 2 2 2 2 2 2 n° 1 1 1 1 1 1 n° 2 2 2 2 2 2 dB(A) 76 76 78 78 79,5 dB(A) 48 48 50 50 51,5 kW Water pump (option)

Pump available pressure (option)

Water tank capacity (option) kPa l

141 125 110 150 130 150

300 300 300 300 530 530 l 18 18 18 18 18 18

Length

Width

Height

Weight (Standard configuration) mm mm

2608 2608 2608 2608 3608 3608

1105 1105 1105 1105 1105 1105 mm 1842 1842 1842 1842 1842 1842 kg 710 725 760 810 1070

Weight (with hydraulic kit) kg 880 895 930 980 1280 1360

# # # XL Models in these sizes are available as a special unit. Contact QUARTZ technical department for details.

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

10 06617645-02

WATER CHILLERS AND HEAT PUMPS

QLAC / XL (Extra Low noise version)

TECHNICAL DATA

120 130 140 160 190 210 240 260 MOD.

Compressor input power

Water flow rate

Water pressure drop

Compressor input power

Water flow rate

Water pressure drop

Length

Width kW 38 42,1 47,3 51,7 59,7 67,8 l/h 20640 22190 24600 27180 31990 36290 kPa 29,4 30,0 30,8 36,0 39,6 42,7 kW 120 132 150 165 189 217 kW 38,5 42,9 48,1 52,8 60,6 68,4 l/h 20640 22700 25800 28380 32510 37320 kPa 29,4 31,3 33,8 39,2 40,9 45,1

Total input current (K version)

Total peak current

Maximum input current

Power supply

A

A

A

V/Ph/Hz

76,4 85,5 96,3 104,7 126,6 144

322,1

102,1 113,1 119,9 138,3 167,6 185,6

400/3/50

Airflow m°/h 62000

Fans n° x kW 3 x 1.23 3 x 1.23 3 x 1.23 3 x 1.23 4 x 1,25 4 x 1,25

Compressors

Sound power level

(1)

Sound pressure level (2) type Scroll n° 2 2 4 4 4 4 n° 1 1 2 2 2 2 n° 2 2 4 4 4 4 dB(A) dB(A)

Water pump (option)

Pump available pressure (option)

Water tank capacity (option) kW kPa

2,2 2,2 2,2 3,0 3,0 3,0

120 130 105 180 140 110 l 530 530 530 670 670 670 l 18 18 18 18 18 18 mm 3608 3608 4108 4108 4708 4708

Weight (Standard configuration) mm 1105 1105 1105 1105 1105 1105

2262 2262 2262 2262 kg 1200 1230 1650 1700 1960 2050

Weight (with hydraulic kit) kg 1410 1440 1860 2000 2260 2350

# # # XL Models in these sizes are available as a special unit. Contact QUARTZ technical department for details.

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

11 06617645-02

MOD.

040

045

050

060

QLAC / LS (LOW NOISE VERSION)

COOLING CAPACITIES AND COMPRESSOR INPUT POWER

TU (°C)

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

PF (kW) PA (kW)

20 25

TA (°C)

30 35 40 45 20 25

TA (°C)

30 35 40 45

26,64 24,98 23,36 21,79 --- --- 9,39 10,50 11,71 13,02 --- ---

29,27 27,48 25,74 24,04 --- --- 9,36 10,50 11,76 13,13 --- ---

32,07 30,15 28,28 26,44 --- --- 9,32 10,48 11,77 13,21 --- ---

35,05 33,00 30,98 29,00 --- --- 9,28 10,44 11,77 13,25 --- ---

38,23 36,02 33,85 31,73 29,65 --- 9,24 10,41 11,75 13,27 14,94 ---

41,60 39,24 36,91 34,63 32,39 --- 9,21 10,36 11,72 13,26 14,98 ---

40,17 35,31 32,95 9,19 10,33 11,68 13,24 15,00 16,93

48,97 46,28 43,62 40,99 38,41 35,87 9,19 10,30 11,64 13,21 14,99 16,97

52,99 50,12 47,28 44,48 41,71 38,98 9,21 10,28 11,60 13,17 14,97 16,98

57,24 54,19 51,16 48,17 45,21 42,29 9,26 10,28 11,57 13,13 14,93 16,97

61,74 58,50 55,27 52,08 48,92 45,80 9,34 10,30 11,56 13,09 14,90 16,95

33,41 31,45 29,48 27,48 --- --- 11,23 12,52 13,96 15,56 --- ---

36,45 34,36 32,24 30,11 --- --- 11,22 12,53 13,99 15,60 --- ---

39,69 37,45 35,19 32,90 --- --- 11,21 12,53 14,01 15,64 --- ---

43,13 40,75 38,33 35,89 --- --- 11,19 12,53 14,02 15,67 --- ---

46,80 44,25 41,67 39,06 36,42 --- 11,18 12,52 14,02 15,69 17,54 ---

50,69 47,98 45,23 42,44 39,63 --- 11,16 12,51 14,03 15,71 17,58 ---

49,01 43,04 40,00 11,14 12,50 14,02 15,72 17,61 19,70

59,21 56,14 53,02 49,86 46,66 43,43 11,12 12,48 14,02 15,73 17,63 19,74

63,85 60,59 57,27 53,91 50,51 47,07 11,09 12,47 14,01 15,73 17,65 19,78

68,77 65,30 61,78 58,21 54,60 50,95 11,07 12,45 14,00 15,73 17,66 19,80

73,96 70,28 66,55 62,77 58,94 55,06 11,05 12,43 13,98 15,73 17,67 19,83

39,58 37,29 34,94 32,53 --- --- 12,52 13,96 15,50 17,15 --- ---

43,08 40,64 38,14 35,57 --- --- 12,50 13,98 15,58 17,30 --- ---

46,80 44,21 41,54 38,82 --- --- 12,47 13,98 15,63 17,41 --- ---

50,76 48,00 45,17 42,27 --- --- 12,43 13,97 15,66 17,49 --- ---

54,98 52,04 49,03 45,95 42,79 --- 12,38 13,94 15,66 17,54 19,58 ---

59,45 56,33 53,13 49,86 46,50 --- 12,34 13,90 15,64 17,57 19,66 ---

57,49 50,46 46,82 12,29 13,85 15,62 17,57 19,71 22,03

69,22 65,71 62,12 58,43 54,66 50,80 12,25 13,81 15,58 17,56 19,74 22,11

74,55 70,83 67,02 63,11 59,12 55,04 12,22 13,77 15,54 17,53 19,74 22,17

80,19 76,25 72,21 68,08 63,85 59,53 12,21 13,73 15,50 17,50 19,74 22,20

86,14 81,97 77,70 73,34 68,87 64,31 12,22 13,70 15,46 17,46 19,71 22,21

44,18 41,55 38,86 36,12 --- --- 14,46 16,14 17,97 19,95 --- ---

48,09 45,29 42,42 39,49 --- --- 14,47 16,18 18,07 20,12 --- ---

52,26 49,27 46,22 43,09 --- --- 14,46 16,20 18,13 20,25 --- ---

56,69 53,51 50,26 46,93 --- --- 14,45 16,21 18,18 20,35 --- ---

61,41 58,02 54,56 51,02 47,40 --- 14,43 16,21 18,21 20,42 22,85 ---

66,42 62,82 59,14 55,37 51,52 --- 14,42 16,20 18,22 20,47 22,95 ---

64,00 55,91 51,74 14,40 16,18 18,21 20,49 23,02 25,78

77,37 73,31 69,16 64,91 60,58 56,15 14,40 16,17 18,21 20,51 23,07 25,88

83,34 79,04 74,63 70,13 65,54 60,85 14,41 16,16 18,20 20,51 23,10 25,96

89,66 85,10 80,43 75,67 70,80 65,84 14,44 16,17 18,19 20,50 23,11 26,01

96,34 91,51 86,57 81,53 76,39 71,14 14,50 16,19 18,19 20,50 23,12 26,04

TU: Outlet water temperature (°C)

TA: Ambient temperature (°C)

PA: Compressors input power (kW)

PF: Cooling capacity (kW)

12 06617645-02

MOD.

070

080

090

110

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

-5

-3

-1

1

3

5

9

11

13

15

QLAC / LS (LOW NOISE VERSION)

COOLING CAPACITIES AND COMPRESSOR INPUT POWER

TU (°C)

PF (kW)

TA (°C)

PA (kW)

TA (°C)

20 25 30 35 40 45 20 25 30 35 40 45

49,33 46,44 43,48 40,47 --- --- 15,63 17,47 19,51 21,77 --- ---

53,68 50,59 47,43 44,21 --- --- 15,65 17,51 19,60 21,92 --- ---

58,31 55,01 51,64 48,21 --- --- 15,66 17,54 19,66 22,03 --- ---

63,23 59,72 56,13 52,47 --- --- 15,66 17,56 19,71 22,12 --- ---

68,47 64,73 60,91 57,00 53,02 --- 15,67 17,57 19,74 22,18 24,90 ---

74,04 70,06 65,99 61,83 57,59 --- 15,69 17,58 19,76 22,23 24,99 ---

71,39 62,46 57,87 15,72 17,59 19,77 22,26 25,05 28,15

86,21 81,72 77,12 72,43 67,64 62,76 15,76 17,62 19,79 22,28 25,10 28,24

92,85 88,08 83,20 78,22 73,14 67,97 15,83 17,65 19,81 22,30 25,14 28,31

99,87 94,81 89,64 84,37 78,99 73,50 15,92 17,70 19,84 22,32 25,16 28,36

107,3 101,9 96,46 90,88 85,18 79,38 16,05 17,78 19,88 22,35 25,19 28,40

58,51 55,07 51,54 47,94 --- --- 19,61 21,99 24,54 27,22 --- ---

63,71 60,03 56,27 52,42 --- --- 19,57 22,02 24,67 27,51 --- ---

69,24 65,32 61,31 57,21 --- --- 19,52 22,00 24,75 27,71 --- ---

75,12 70,95 66,68 62,30 --- --- 19,46 21,96 24,76 27,83 --- ---

81,38 76,94 72,39 67,73 62,97 --- 19,40 21,90 24,75 27,89 31,30 ---

88,03 83,30 78,46 73,50 68,44 --- 19,37 21,84 24,70 27,90 31,42 ---

84,91 74,26 68,76 19,37 21,79 24,64 27,88 31,47 35,37

102,5 97,22 91,75 86,16 80,45 74,61 19,41 21,76 24,58 27,83 31,47 35,47

110,5 104,8 99,02 93,08 87,02 80,84 19,52 21,77 24,54 27,77 31,45 35,51

118,8 112,8 106,7 100,4 94,00 87,45 19,70 21,83 24,52 27,72 31,40 35,51

127,7 121,3 114,8 108,2 101,4 94,47 19,97 21,96 24,54 27,68 31,34 35,48

67,32 63,10 58,71 54,16 --- --- 22,38 25,09 28,16 31,62 --- ---

73,37 68,89 64,23 59,41 --- --- 22,41 25,14 28,23 31,73 --- ---

79,80 75,05 70,12 65,01 --- --- 22,44 25,18 28,30 31,83 --- ---

86,64 81,61 76,39 70,98 --- --- 22,46 25,21 28,34 31,90 --- ---

93,92 88,59 83,06 77,33 71,41 --- 22,50 25,24 28,39 31,97 36,01 ---

101,6 96,00 90,15 84,10 77,84 --- 22,54 25,27 28,43 32,02 36,09 ---

97,69 84,68 77,87 22,59 25,31 28,46 32,07 36,15 40,75

118,5 112,2 105,6 98,92 91,95 84,76 22,66 25,37 28,51 32,11 36,21 40,84

127,6 121,0 114,1 107,0 99,67 92,10 22,75 25,43 28,56 32,16 36,27 40,91

137,4 130,3 123,1 115,6 107,8 99,88 22,86 25,51 28,62 32,21 36,32 40,97

147,6 140,2 132,6 124,7 116,5 108,1 23,00 25,61 28,70 32,28 36,38 41,04

78,60 73,67 68,49 63,05 --- --- 24,07 26,92 30,28 34,24 --- ---

85,65 80,44 74,96 69,23 --- --- 24,17 27,00 30,31 34,21 --- ---

93,15 87,65 81,87 75,82 --- --- 24,28 27,10 30,38 34,23 --- ---

101,1 95,32 89,22 82,84 --- --- 24,39 27,21 30,47 34,28 --- ---

109,5 103,4 97,04 90,32 83,31 --- 24,50 27,33 30,59 34,36 38,76 ---

118,5 112,1 105,3 98,27 90,89 --- 24,61 27,46 30,71 34,47 38,83 ---

114,1 98,96 90,90 24,69 27,58 30,85 34,60 38,92 43,93

138,1 131,0 123,5 115,6 107,5 99,06 24,76 27,70 30,99 34,74 39,05 44,01

148,8 141,3 133,4 125,2 116,6 107,7 24,81 27,80 31,13 34,90 39,20 44,13

160,1 152,2 143,9 135,2 126,2 116,9 24,82 27,88 31,26 35,05 39,36 44,28

172,0 163,7 154,9 145,9 136,4 126,6 24,80 27,94 31,38 35,21 39,53 44,44

TU: Outlet water temperature (°C)

TA: Ambient temperature (°C)

PA: Compressors input power (kW)

PF: Cooling capacity (kW)

QLAC / LS (LOW NOISE VERSION)

13 06617645-02

MOD.

120

130

140

160

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

9

11

13

15

-5

-3

-1

1

3

5

COOLING CAPACITIES AND COMPRESSOR INPUT POWER

TU (°C)

-5

-3

-1

1

3

5

9

11

13

15

PF (kW) PA (kW)

20 25

TA (°C)

30 35 40 45 20 25

TA (°C)

30 35 40 45

88,37 82,32 76,09 69,68 --- --- 27,64 31,00 34,96 39,62 --- ---

96,55 90,15 83,54 76,75 --- --- 27,75 31,07 34,98 39,56 --- ---

105,2 98,48 91,49 84,29 --- --- 27,87 31,15 35,02 39,54 --- ---

114,5 107,3 99,94 92,33 --- --- 28,00 31,26 35,08 39,55 --- ---

124,3 116,7 108,9 100,8 92,62 --- 28,14 31,38 35,17 39,58 44,72 ---

134,8 126,8 118,5 109,9 101,2 --- 28,28 31,51 35,27 39,65 44,73 ---

128,6 110,4 100,9 28,43 31,66 35,39 39,73 44,76 50,57

157,7 148,7 139,4 129,9 120,2 110,2 28,58 31,81 35,53 39,84 44,82 50,57

170,1 160,6 150,9 140,8 130,5 120,0 28,72 31,96 35,67 39,96 44,91 50,60

183,3 173,3 163,0 152,4 141,5 130,4 28,86 32,11 35,83 40,10 45,01 50,66

197,2 186,6 175,8 164,6 153,2 141,5 29,00 32,26 35,98 40,25 45,14 50,75

95,43 88,46 81,36 74,17 --- --- 31,38 35,29 39,89 45,26 --- ---

104,5 97,10 89,57 81,92 --- --- 31,48 35,34 39,88 45,17 --- ---

114,1 106,3 98,31 90,19 --- --- 31,61 35,41 39,88 45,11 --- ---

124,4 116,1 107,6 99,00 --- --- 31,74 35,50 39,92 45,08 --- ---

135,4 126,5 117,5 108,3 99,10 --- 31,90 35,61 39,97 45,06 50,98 ---

147,0 137,6 128,0 118,3 108,5 --- 32,08 35,73 40,04 45,07 50,91 ---

139,2 118,5 107,9 32,27 35,88 40,13 45,11 50,88 57,52

172,5 161,9 151,1 140,2 129,2 118,0 32,48 36,05 40,25 45,16 50,87 57,44

186,3 175,1 163,8 152,2 140,5 128,6 32,70 36,23 40,39 45,24 50,88 57,38

201,0 189,2 177,1 164,9 152,5 140,0 32,95 36,44 40,55 45,35 50,92 57,34

216,5 204,0 191,3 178,4 165,3 152,0 33,21 36,66 40,73 45,47 50,98 57,34

105,5 99,32 92,90 86,35 --- --- 35,77 40,04 44,70 49,71 --- ---

114,9 108,2 101,4 94,42 --- --- 35,76 40,13 44,94 50,16 --- ---

124,9 117,7 110,4 103,0 --- --- 35,71 40,15 45,09 50,50 --- ---

135,5 127,9 120,1 112,1 --- --- 35,66 40,14 45,17 50,72 --- ---

146,8 138,7 130,4 121,9 113,2 --- 35,62 40,09 45,19 50,86 57,07 ---

158,7 150,1 141,3 132,3 123,1 --- 35,59 40,04 45,17 50,93 57,29 ---

152,9 133,5 123,6 35,62 40,01 45,13 50,94 57,42 64,51

185,0 175,2 165,3 155,1 144,7 134,1 35,70 40,00 45,08 50,93 57,48 64,71

199,2 188,9 178,3 167,5 156,5 145,3 35,86 40,03 45,06 50,89 57,50 64,84

214,4 203,4 192,2 180,8 169,1 157,2 36,12 40,14 45,06 50,86 57,48 64,90

230,3 218,7 206,9 194,8 182,4 169,8 36,49 40,32 45,12 50,84 57,46 64,92

115,9 109,1 102,1 95,01 --- --- 39,22 43,97 49,07 54,44 --- ---

126,2 118,9 111,5 103,9 --- --- 39,15 44,03 49,35 55,02 --- ---

137,2 129,4 121,5 113,3 --- --- 39,04 44,00 49,49 55,41 --- ---

148,9 140,6 132,1 123,4 --- --- 38,91 43,92 49,53 55,66 --- ---

161,3 152,4 143,4 134,2 124,8 --- 38,80 43,80 49,49 55,78 62,61 ---

174,4 165,1 155,5 145,6 135,6 --- 38,73 43,68 49,40 55,81 62,83 ---

168,2 147,1 136,2 38,73 43,58 49,28 55,76 62,93 70,73

203,2 192,6 181,8 170,7 159,4 147,8 38,83 43,53 49,16 55,66 62,95 70,93

218,9 207,7 196,2 184,4 172,4 160,2 39,04 43,55 49,07 55,55 62,89 71,02

235,5 223,6 211,4 199,0 186,3 173,3 39,40 43,66 49,04 55,44 62,79 71,02

253,1 240,5 227,6 214,4 200,9 187,2 39,93 43,91 49,08 55,36 62,69 70,97

TU: Outlet water temperature (°C)

TA: Ambient temperature (°C)

PA: Compressors input power (kW)

PF: Cooling capacity (kW)

QLAC / LS (LOW NOISE VERSION)

14 06617645-02

COOLING CAPACITIES AND COMPRESSOR INPUT POWER

260

210

240

QLAC / LS (LOW NOISE VERSION)

15 06617645-02

COOLING CAPACITIES AND COMPRESSOR INPUT POWER

PF (kW) PA (kW)

TU (°C) TA (°C) TA (°C) MOD.

20 25 30 35 40 20 25 30 35 40

300

320

380

430

500

1

3

5

9

11

13

15

1

3

5

9

11

13

15

1

3

5

9

11

13

15

1

3

5

9

11

13

15

1

3

5

9

11

13

15

275.9 258.8 240.9 221.8 201.4 65.7 73.2 81.8 91.8 103.3

299.9 281.7 262.8 242.7 221.4 66.1 73.5 82.1 92.0 103.5

325.5 306.1 286.0 264.9 242.5 66.5 73.8 82.3 92.2 103.6

310.7 264.9 67.0 74.2 82.7 92.4 103.8

381.7 359.7 337.0 313.4 288.6 67.6 74.7 83.0 92.7 103.9

412.6 389.0 364.8 339.8 313.7 68.2 75.2 83.4 93.0 104.1

445.4 420.2 394.5 367.9 340.3 68.9 75.8 83.9 93.3 104.4

480.3 453.4 425.9 397.8 368.6 69.7 76.4 84.4 93.7 104.6

304.3 286.5 267.4 246.3 222.8 71.3 79.7 89.1 99.8 112.0

330.8 311.9 291.8 269.9 245.7 71.7 80.0 89.4 100.1 112.3

359.1 338.9 317.7 294.8 269.7 72.2 80.3 89.7 100.4 112.6

345.1 294.9 72.7 80.7 90.0 100.6 112.8

421.6 398.4 374.3 348.9 321.6 73.4 81.2 90.3 100.9 113.0

456.1 431.1 405.4 378.5 349.8 74.1 81.7 90.7 101.2 113.3

493.0 466.0 438.5 409.9 379.7 74.9 82.4 91.2 101.5 113.5

532.3 503.3 473.8 443.4 411.5 75.9 83.1 91.7 101.9 113.8

371.3 346.7 321.5 295.9 269.9 90.0 100.0 111.8 125.7 142.0

403.6 377.4 350.6 323.4 295.7 90.6 100.5 112.2 125.9 142.0

437.8 410.0 381.6 352.6 323.1 91.3 101.0 112.6 126.1 142.0

414.4 352.3 92.0 101.6 113.0 126.4 142.1

512.8 481.4 449.3 416.7 383.4 92.8 102.3 113.5 126.8 142.3

553.6 520.3 486.4 451.7 416.4 93.6 103.0 114.1 127.2 142.5

596.9 561.6 525.6 488.9 451.5 94.5 103.8 114.8 127.7 142.8

642.5 605.2 567.1 528.2 488.6 95.4 104.6 115.5 128.3 143.2

413.9 388.2 361.3 332.7 302.1 98.5 109.7 122.7 137.7 155.0

449.9 422.6 394.2 364.1 332.1 99.1 110.2 123.1 138.0 155.2

488.2 459.2 429.0 397.4 363.8 99.8 110.8 123.5 138.3 155.4

466.1 397.4 100.6 11.4 124.0 138.7 155.6

572.6 539.5 505.4 470.0 432.9 101.4 112.0 124.5 139.1 155.9

618.9 583.5 547.3 509.7 470.6 102.4 112.8 125.1 139.5 156.2

668.2 630.3 591.7 551.9 510.5 103.4 113.7 125.8 140.0 156.6

720.5 680.0 638.9 596.6 552.9 104.6 114.6 126.5 140.6 157.0

456.4 429.8 401.1 369.5 334.3 107.0 119.5 133.6 149.7 168.0

496.2 467.9 437.7 404.9 368.5 107.6 120.0 134.1 150.1 168.4

538.6 508.4 476.5 442.1 404.5 108.3 120.5 134.5 150.5 168.8

517.7 442.4 109.1 121.1 135.0 150.9 169.2

632.4 597.6 561.5 523.4 482.4 110.0 121.8 135.5 151.3 169.6

684.2 646.7 608.1 567.8 524.7 111.1 122.6 136.1 151.8 169.9

739.5 699.1 657.8 614.9 569.6 112.4 123.5 136.8 152.3 170.3

798.5 754.9 710.7 665.1 617.2 113.8 124.6 137.6 152.9 170.7

TU: Evaporator Outlet water temperature (°C)

TA: Ambient temperature (°C)

PA: Compressors input power (kW)

PF: Cooling capacity (kW)

QLAC / HP / LS (LOW NOISE VERSION)

16 06617645-02

HEATING CAPACITIES AND COMPRESSOR INPUT POWER

MOD.

040

045

050

060

070

080

090

110

PC (kW) PA (kW)

TA (°C) TU (°C) TU (°C)

30 35 40 45 50 55 30 35 40 45 50 55

-5 25,1

0 30,3

5 36,2 35,6 35,1 --- --- --- 9,2 10,3 11,5 --- --- ---

--- ---

10

15

43,0 42,2 41,5 41,0 40,7 --- 9,1 10,2 11,5 12,9 14,5 ---

51,1 49,8 48,8 48,0 47,5 --- 9,0 10,1 11,4 12,9 14,6 ---

20 60,5 58,8 57,3 56,1 55,2 54,5 9,0 10,0 11,3 12,9 14,6 16,6

-5 32,1

0 37,9

5 44,8 44,1 43,5 --- --- --- 11,0 12,3 13,7 --- --- ---

--- ---

10

15

52,8 51,8 50,9 50,2 49,6 --- 11,0 12,3 13,7 15,3 17,1 ---

62,1 60,8 59,5 58,4 57,4 --- 10,9 12,2 13,7 15,4 17,2 ---

20 73,0 71,2 69,5 67,9 66,5 65,2 10,9 12,2 13,7 15,4 17,2 19,3

-5 37,3

0 44,2

5 52,1 51,2 50,4 --- --- --- 12,5 14,0 15,6 --- --- ---

--- ---

10

15

61,2 60,1 59,0 58,0 57,0 --- 12,5 14,0 15,6 17,5 19,4 ---

71,8 70,2 68,8 67,4 66,2 --- 12,3 13,9 15,6 17,6 19,7 ---

20 84,1 82,0 80,1 78,3 76,6 75,0 12,2 13,8 15,6 17,5 19,7 22,1

-5 42,3

0 50,0

5

10

15

59,0 58,0 57,1 --- --- --- 14,0 15,6 17,4 --- --- ---

--- ---

69,3 68,0 66,7 65,6 64,6 --- 14,0 15,7 17,6 19,6 21,9 ---

81,4 79,5 77,8 76,3 74,9 --- 13,9 15,6 17,6 19,8 22,2 ---

20 95,5 93,0 90,7 88,6 86,7 84,9 13,9 15,6 17,6 19,8 22,3 25,0

-5 46,7

0 55,2

5 65,1 64,0 63,1 --- --- --- 15,5 17,3 19,3 --- --- ---

10

15

20

-5 56,3

--- ---

76,6 75,0 73,7 72,5 71,5 --- 15,5 17,3 19,5 21,8 24,4 ---

90,0 87,8 85,9 84,2 82,7 --- 15,5 17,4 19,5 22,0 24,7 ---

0 66,8

5 78,6 77,5 76,5 --- --- --- 18,7 21,0 23,5 --- --- ---

--- ---

10

15

92,3 90,7 89,2 88,0 86,8 --- 18,6 20,9 23,6 26,5 29,7 ---

20

-5 64,7

0 76,5

5 90,4 88,8 87,4 --- --- --- 21,4 24,0 26,9 --- --- ---

--- ---

10

15

20

-5 73,4 --- --- --- --- --- --- --- --- ---

0 86,7

5

--- ---

10

15

20

TU: Outlet water temperature (°C)

TA: Ambient temperature dry bulb (°C)

PA: Compressors input power (kW)

PH: Heating capacity (kW)

17 06617645-02

MOD.

120

130

140

160

190

210

240

260

QLAC / HP / LS (LOW NOISE VERSION)

HEATING CAPACITIES AND COMPRESSOR INPUT POWER

TA (°C)

PC (kW)

TU (°C)

30 35 40 45 50 55

-5 82,2

30

0 97,9

5 116,6

10

15

20

-5 89,5

0 107,3

5 128,2

10

15

20

-5 102,1

0 120,8

5 142,2

10

15

20

-5 112,0

0 132,6

5 156,1

10

15

20

-5 129,4

0 153,1

5 180,7

10

15

20

-5 149,4

0 176,9

5 209,6

10

15

20

-5 165,3

0 197,1

5 234,8

10

15

20

-5 181,2

0 217,3

5 259,9 247,4

10

15

20

35

PA (kW)

TU (°C)

40 45 50 55

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

--- ---

TU: Outlet water temperature (°C)

TA: Ambient temperature dry bulb (°C)

PA: Compressors input power (kW)

PH: Heating capacity (kW)

18 06617645-02

30

20

50

40

70

60

80

A B

10

5000 10000

A: QLAC 040-045

B: QLAC 050

C: QLAC 060-070

D: QLAC 080

15000

EVAPORATOR PRESSURE DROPS

80

C

D

20000

50

40

30

70

60

20

10

15000 20000

E: QLAC 090

F: QLAC 110

G: QLAC 120

H: QLAC 130

E

F

25000

G

H

30000

80

70

60

50

40

30

20

I L M N O

P

60

50

40

30

20

Q R

S

T

U

10

25000 30000 35000 40000 45000 50000

I: QLAC 140

L: QLAC 160

M: QLAC 190

N: QLAC 210

O: QLAC 240

P: QLAC 260

19

10

40000 50000 60000 70000 80000 90000

Q: QLAC 300

R: QLAC 320

S: QLAC 380

T: QLAC 430

U: QLAC 500

06617645-02

WATER PUMPS AVAILABLE STATIC PRESSURE

240

220

200

180

160

140

120

100

80

60

5000

A

B

10000 15000

A: QLAC 040,045,050,060,070

B: QLAC 080, 090

20000

100

80

60

40

15000

220

200

180

160

C

140

120

D

20000

C: QLAC 110, 120

D: QLAC 130, 140

25000 30000

180

160

140

240

220 E

200 F

220

200

180

G

160

140

120

100

80

20000 25000 30000 35000 40000 45000 50000

E: QLAC 160,190,210

F: QLAC 240, 260

20

120

100

50000 60000

H

70000

G: QLAC 300, 320

H: QLAC 380, 430, 500

80000 90000

06617645-02

3

2,5

2

1,5

7°C

5°C

12°C

10°C

1

0,5

FREE COOLING CAPACITY

Return water temperature 15°C

0

-20 -15 -10 -5

Ambient air temperature (°C)

0 5 10

Mod .

Nominal Free cooling capacity

Mod .

Nominal Free cooling capacity kW

040

---

120

72

045

---

130

72

050

43

140

94

060

43

160

94

070

43

190

110

080

45

210

115

090

70

240

135

110

72

260

135 kW

Mod . 300 320 380 430 500

Nominal Free cooling capacity kW 185 185 235 245 240

The nominal Free Cooling capacity is obtained when all compressors are OFF, the return water temperature from the system is 15°C and the ambient temperature is 2°C. to calculate the free cooling capacity in different conditions please refer to the above diagram. To obtain free cooling duty multiply the nominal Free

Cooling capacity by the CFC factor obtained.

21 06617645-02

1,4

1,3

1,2

PARTIAL HEAT RECOVERY CAPACITY

Mod.

Partial heat recovery nominal capacity kW

040

9,5

045

12,8

050

13,0

060

15,0

070

15,3

080

18,5

090

21,5

110

24,8 l/h 1635 2200 2240 2580 2630 3190 3700 4270 kPa 10 14 11 15 16 18 11 15

Mod.

Partial recovery

120 130 140 160 190 210 240 260 kW 27,5 30,0 34,0 37,0 43,0 49,0 55,0 61,5 l/h 4730 5160 5850 6360 7400 8430 9460 10570

Mod.

Partial heat recovery nominal capacity kPa 13 18 18 25 11 15 19 25 kW

300

69,0

320

76,0

380 430

91,5 102,8

500

114 l/h 11850 13000 15750 17700 19600 kPa 20 25 25 29 35

The nominal value refers to an ambient temperature 35°C and outlet water temperature 50°C (Dt 5°C).

1,5

1,1

1

0,9

Ambient temperature 40°C

Ambient temperature 35°C

Ambient temperature 30°C

Ambient temperature 25°C

Ambient temperature 20°C

0,8

40 41 42 43 44 45 46 47 48 49 50

Outlet water temperature °C

The heat recovery capacity in different conditions can be obtained multiplying the nominal capacity (See above), by the correction factor indicated in the table.

Warning Partial heat recovery can only work in cooling mode. In the heat pump version it is necessary to isolate the heat recovery circuit when in heating mode to prevent damage.

Failure to comply with this will invalidate the warranty.

22 06617645-02

COMPRESSORS CAPACITY STEP CONTROLS

Water temp.

CORRECTION TABLE

Glycol

Operation with glycol

WFCF PDCF

7

3

-2

-5

10% 1,012 1,125

20% 1,048 1,32

35% 1,109 1,62

10% 0,870 0,85

20% 0,875 0,92

35% 0,925 1,13

10% 0,710 0,64

20% 0,730 0,85

35% 0,770 1,05

10% --- ---

20% 0,600 0,56

35% 0,625 0,7

WFCF = Water flow correction factor PDCF = Pressure drop correction factor

The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without glycol. The water flow rate correction factor is calculated in order to maintain the same temperature difference as that which would be obtained without glycol. The pressure drop correction factor takes into account the different flow rate obtained from the application of the flow rate correction factor.

When the new flow rate is determind the capacity can be calculated using the formula Q=4.19m

ΔT, where Q is the duty in kw, m is the flow rate in kg/s and

ΔT is the fluid temperature difference.

CORRECTION TABLES Different DT

Water temperature

3 5 8 difference

CCCP 0,99 1 1,02

IPCF 0,99 1 1,01

CCCP = Cooling capacity correction factor IPCF = Input power correction factor

CORRECTION TABLES Different Fouling factors

Fouling factor 0,00005 0,0001 0,0002

CCCP 1 0,98 0,94

CCCP = Cooling capacity correction factor IPCF = Input power correction factor

23 06617645-02

Model

Power line fuses

ELECTRICAL DATA

A

040 045 050 060 070 080 090 110

Power line cable section

Model

Power line fuses mm²

A

10 10 16 16 25 25 25 35

120 130 140 160 190 210 240 260

160 200 200 200 250 250 350 400

Power line cable section mm²

040/LS

045/LS

050/LS

060/LS

070/LS

080/LS

090/LS

110/LS

120/LS

130/LS

140/LS

160/LS

190/LS

210/LS

240/LS

260/LS

300/LS

320/LS

380/LS

430/LS

500/LS

Power supply

Auxiliary circuit

Model

V/~/Hz 400 / 3 / 50

V/~/Hz 230 / 1 / 50

Control board

Fans power supply

V/~/Hz 24 / 1 / 50

V/~/Hz 400 / 3 / 50

Electrical data varies depending on specification. Always refer to the wiring diagram supplied in the unit.

SOUND LEVELS LOW NOISE VERSION

Octave bands (Hz) Lw Lp

63 125 250 500 1K 2K 4K 8K dB dB dB dB dB dB dB dB dB(A)

90.1 91.3 75.2 73.3 72.6 67.2 63.8 54.7 90.9 77.0 49

90.1 91.3 75.2 73.3 72.6 67.2 63.8 54.7 90.9 77.0 49

92.1 83.3 77.2 75.7 74.6 69.2 65.8 56.7 92.9 79.0 51

92.1 83.3 77.2 75.7 74.6 69.2 65.8 56.7 92.9 79.0 51

93.1 84.3 78.2 76.7 75.6 70.2 66.8 57.7 93.9 80.0 52

93.1 84.3 78.2 76.7 75.6 70.2 66.8 57.7 93.9 80.0 52

95.1 86.3 80.2 78.7 77.6 72.2 68.8 59.7 95.9 82.0 54

95.6 86.8 80.7 79.2 78.1 72.7 69.3 60.2 96.4 82.5 54.5

96.0 87.2 81.1 79.6 78.5 73.1 69.7 60.6 96.8 82.9 54.9

96.2 87.4 81.3 79.8 78.7 73.3 69.9 60.8 97.0 83.1 55.1

96.6 87.8 81.7 80.2 79.1 73.7 70.3 61.2 97.4 83.5 55.5

97.1 88.3 82.2 80.7 79.6 74.2 70.8 61.7 98.0 84.0 56

99.1 90.3 84.2 82.7 81.6 76.2 72.8 63.7 99.9 86.0 58

99.1 90.3 84.2 82.7 81.6 76.2 72.8 63.7 99.9 86.0 58

102.1 93.3 87.2 85.7 84.6 79.2 75.8 66.7 102.9 89.0 61

102.1 93.3 87.2 85.7 84.6 79.2 75.8 66.7 102.9 89.0 61

103.1 94.3 88.2 86.7 85.6 80.2 76.8 67.7 103.9 90.0 62

103.1 94.3 88.2 86.7 85.6 80.2 76.8 67.7 103.9 90.0 62

104.1 95.3 89.2 87.7 86.6 81.2 77.8 68.7 104.9 91.0 63

104.1 95.3 89.2 87.7 86.6 81.2 77.8 68.7 104.9 91.0 63

104.1 95.3 89.2 87.7 86.6 81.2 77.8 68.7 104.9 91.0 63

Model

SOUND LEVELS EXTRA LOW NOISE VERSION

Octave bands (Hz) Lw Lp

63 125 250 500 1K 2K 4K 8K dB dB dB dB dB dB dB dB dB(A)

--- --- --- --- --- --- --- --- --- --- --- 040/XL

045/XL

050/XL

060/XL

070/XL

080/XL

090/XL

110/XL

120/XL

130/XL

140/XL

160/XL

190/XL

210/XL

240/XL

260/XL

--- --- --- --- --- --- --- --- --- --- ---

89.1 80.3 74.2 72.7 71.6 66.2 62.2 53.7 89.9 76.0 48

89.1 80.3 74.2 72.7 71.6 66.2 62.2 53.7 89.9 76.0 48

91.1 82.3 76.2 74.7 73.6 68.2 64.8 55.7 91.9 78.0 50

91.1 82.3 76.2 74.7 73.6 68.2 64.8 55.7 91.9 78.0 50

92.6 83.8 77.7 76.2 75.1 69.7 66.3 57.2 93.4 79.5 51.5

93.0 84.2 78.1 76.6 75.5 70.1 66.7 57.6 93.8 79.9 51.9

93.2 84.4 78.3 76.8 75.7 70.3 66.9 57.8 94.0 80.1 52.1

93.6 84.8 78.7 77.2 76.1 70.7 67.3 58.2 94.4 80.5 52.5

94.1 85.3 79.2 77.7 76.6 71.2 67.8 58.7 95.0 81.0 53

94.4 85.6 79.5 78.0 76.9 71.5 68.1 59.0 95.3 81.3 53.3

97.1 88.3 82.2 80.7 79.6 74.2 70.8 61.7 98.0 84.0 58

97.1 88.3 82.2 80.7 79.6 74.2 70.8 61.7 98.0 84.0 58

--- --- --- --- --- --- --- --- --- --- ---

--- --- --- --- --- --- --- --- --- --- ---

300/XL

320/XL

380/XL

430/XL

--- --- --- --- --- --- --- --- --- --- ---

--- --- --- --- --- --- --- --- --- --- ---

--- --- --- --- --- --- --- --- --- --- ---

--- --- --- --- --- --- --- --- --- --- ---

500/XL --- --- --- --- --- --- --- --- --- --- ---

--- (not availble)

Lw – Sound power level according to ISO 3746.

Lp – Sound pressure level measured at 10 mt from the unit in free field conditions direction factor Q = 2 according to ISO 3746.

24 06617645-02

Installation Instructions – General

- When installing or servicing the unit, you must follow the instructions given in this manual and on labels attached to the unit.

- As the chiller is charged with refrigerant under pressure and unauthorised access to the electrical components provides a shock hazard, any work performed on the unit must be by suitably trained

personnel only.

- Failure to observe the instructions provided in this manual, or any modification of the unit without explicit previous authorisation, will invalidate the warranty.

Attention: before servicing the unit ensure that the electric supply is disconnected.

Inspection

After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition; any eventual damage must be reported to the carrier and be recorded on the Delivery Note before it is signed.

TEV Ltd must be informed, within 8 days, of the extent of the damage. The customer should prepare a written statement of any severe damage: digital photos of any damage is useful.

Lifting and site handling

When unloading the unit, care must be taken to prevent damage to the refrigerant circuit, condensing coils or unit casing.

When using a crane, pass bars through the base frame lifting holes (marked with yellow arrows) and attach the cable or chains to these bars. Ensure that they are clamped firmly. Protect the sides of the chiller with boarding or material of a similar nature.

Forklift forks must be inserted in the base pallet: care must be taken to prevent them hitting the base or panels. Keep the unit horizontal to avoid damage to the internal components.

IMPORTANT: be sure that the method of lifting does not allow the unit to slip from chains or slings,

turn over or slide from lifting devices.

Unpacking

When unpacking, be careful not to damage the unit. The packing is made up of different materials: wood, cardboard, polythene etc. We recommend that they are sent to a re-cycling centre in order to reduce their environmental impact.

LOCATION AND MINIMUM CLEARANCES

QLAC units are designed for external installation. Any overhang or cover above the unit should be avoided as this can cause air re-circulation. It is advisable to create a firm base for the unit, with a size similar to unit foot-print. Normal unit vibration levels are very low: it is good practice, however, to fit a rigid rubber interface between base and unit frame. Where desirable, fit anti-vibration mounts (spring or rubber), to keep vibration to a minimum. For future maintenance, these clearances are recommended:-

Mod.

040

045

050

060

070

080

090

110

120

130

140

160

190

210

240

260

300

320

380

430

A B C D E

1000 800 800 800 3000

1000 800 800 800 3000

1500 800 800 800 3000

1500 800 800 800 3000

1500 800 800 800 3000

1500 800 800 800 3000

1500 1000 1000 1000 3000

1500 1000 1000 1000 3000

1500 1000 1000 1000 3000

1500 1000 1000 1000 3000

1500 1000 1000 1000 4000

1500 1000 1000 1000 4000

2000 1000 1000 1000 4000

2000 1000 1000 1000 4000

2000 1000 1000 1000 4000

2000 1000 1000 1000 4000

2000 1000 2000 2000 5000

2000 1000 2000 2000 5000

2000 1000 2000 2000 5000

2000 1000 2000 2000 5000

500 2000 1000 2000 2000 5000

Warning: The unit should be installed such that there is suitable access for maintenance and/or

repair.

25 06617645-02

E

A

B

C

D

HYDRAULIC CONNECTIONS

Unit water pipe-work must be installed in accordance with national and local regulations. Pipes can be steel, galvanized steel, copper or PVC. Pipes have to be designed depending on the nominal water flow and the hydraulic pressure drops of the system. All pipes must be insulated with closed-cell material of adequate thickness. The chiller must be connected to the pipework using flexible joints. Piping should include:

Temperature and pressure gauges for maintenance or servicing operations.

Manual shut-off valves to separate the unit from the hydraulic circuit.

Metallic supply water filter to be sited at the inlet pipe, with a mesh not larger than 1 mm.

Vent valves, expansion tank with water filling, discharge valve.

The water inlet must correspond with the connection labelled ”USER WATER INLET”, otherwise the evaporator may freeze.

You must fit a metallic filter with a mesh not larger than 1 mm at the ‘USER WATER INLET’ connection. If the flow switch is altered or the water filter is not fitted, the warranty will be invalidated. All units are supplied with flow switch, on ‘K’ versions it is factory installed, on standard versions it is supplied loose. The flow switch MUST be installed on the water outlet pipe. Please refer to the wiring diagram for the flow switch electrical connections

LAC

Standard

LAC / K

Water tank

Flexible connection

Ball shut-off valve

Vent valve

System filling group

F

G

H

I

Water strainer

Water pump

Expansion vessel

Safety valve

26 06617645-02

(QLAC / FC FREE COOLING VERSION)

FREE COOLING SYSTEMS MUST ALWAYS BE FILLED WITH GLYCOL SOLUTION

The free cooling versions can operate in 3 different operating modes. The free-cooling coil is installed in series with the water chiller evaporator; the 3 way valve controls the water flow through the coil. When the ambient temperature is lower than the return water temperature, the microprocessor allows the water flow to pass through the free-cooling coil first, then through the evaporator.

Cooling mode (Summer operation) Ambient temperature is higher than the return water temperature. In this case, the ambient conditions are not suitable to allow Free Cooling operation; the 3 way valve is closed and the water flows to the evaporator, where it is cooled. The compressors, fans, and the water pump are activated; the unit operates like a normal liquid cooler.

Free cooling mode (Winter operation) Ambient temperature is much lower than the return water temperature. In this case, the ambient conditions are suitable to allow Free Cooling operation; the 3 way valve opens and the water flows into the free cooling coil, where the ambient conditions are sufficient to give the total required load. In this case the pump and the fans are in operation, while the compressors are stopped. In this case, the free cooling system works in substitution of the water chiller.

Cooling mode + Free cooling (Mid-season operation) Ambient temperature is lower than the return water temperature. In this case, the ambient conditions are suitable to allow Free Cooling operation; the 3 way valve opens and water flow passes into the free cooling coil although the ambient conditions are not sufficiently low to give the total required load. The microprocessor control activates the compressors (pump and fans are already in operation) to satisfy the required load. In this case the free cooling system works in conjunction with the water chiller. In these circumstances the head pressure control device is activated.

CONDENSING PRESSURE CONTROL (optional)

If unit operation below 20°C is expected, a condensing pressure control must be fitted in the unit. This device will allow unit operation under low ambient temperature, by reducing condenser air flow and obtaining acceptable operating parameters. This device modulates the fan speed in proportion to the condensing pressure measured by the pressure transducer.

This device is factory pre-set. The values must never be modified.

OPERATIONAL LIMITS

Evaporator water flow rate

The nominal water flow rates are based on a delta T (W in

- W out

) of 5 °C. The maximum flow rate allowed is that achieved with a delta T of 3 °C: higher values may cause too high pressure drop. The minimum water flow rate allowed is that achieved with a delta T of 8 °C. Insufficient values cause too low evaporating temperatures, tripping safety devices which stop the unit.

Chilled water temperature (summer operation)

The minimum temperature allowed at the evaporator outlet is 5 °C. To work below this limit, the unit requires modification - please contact TEV Ltd. The maximum temperature allowed at the evaporator inlet is

20 °C.

Hot water temperature (winter operation)

Once the system is at temperature, the water temperature at the condenser inlet should not be less than 23

°C: lower values could cause incorrect working operation of the compressor and compressor failure may occur. The maximum water temperature at the condenser outlet should not exceed 48 °C: higher values will cause safety devices to trip and stop operation.

Ambient air temperature

The units are designed and manufactured to operate, in cooling, with ambient air temperature between 20°C to 42 °C If a fan speed control is installed then the minimum ambient air temperature is -10°C. In winter operation (heat pump cycle) operates from -5°C to 20°C.

27 06617645-02

ELECTRICAL CONNECTIONS

Disconnect the electrical supply before undertaking any work on the unit.

All electrical work must be undertaken by suitably qualified personnel .

The electrical supply must match the nominal electrical data (voltage, phase, frequency) shown on the label in the front panel of the unit. Power connections must be made in accordance to the wiring diagram enclosed with the unit and in accordance current local and national regulations. Power cable and line protection must be sized according to the specification stated on the wiring diagram enclosed with the unit.

The variation in line voltage must not be more than ±5% of the nominal value, whilst the voltage imbalance between phases must not exceed 2%. If those tolerances are likely to be exceeded, please contact TEV

Ltd., as further protection devices are required.

Electrical supply must be as described, otherwise warranty will be invalid.

START UP

Before start-up

- Check that all power cables are connected in the correct sequence and that all terminals are tight.

- The voltage measured at the R Y B phase clamps must be 400 V ± 5% (or the value given on the rating plate for special voltages). If the voltage is incorrect, do not proceed.

- Check for any refrigerant leaks using a leak detector. Should a leak be found do not proceed. All leaks must be rectified and the unit re-charged by trained personnel.

- Check that the crankcase heaters are energised.

Crankcase heaters must be energised at least 12 hours before start up by switching on the unit at the main switch.

- Verify that heaters are working correctly. After a short warm up period, the compressor crankcase must be warm to the touch and must have a temperature at least 10K higher than ambient temperature.

- Check that all hydraulic connections have been made correctly and that all information given on the unit's labels have been observed.

- The system must be filled with water and bled to eliminate any air.

Caution: before starting the unit up, check that all cover panels are correctly located and securely

fastened.

Start up

Please refer to the microprocessor manual enclosed with the unit.

If the unit fails to start:

• Check that the control thermostat is set to the correct value.

Do not modify any internal wiring, otherwise warranty will be invalidated.

Controls during unit operation

• Check the rotation of the fans. If the rotation is incorrect, disconnect the main switch and change over any two phases of the incoming main supply to reverse motor rotation:

• Check that water temperature at evaporator inlet is near to the set point of the control thermostat.

• For “K” version units (units with pumps and storage tank) if the motor driven pump is noisy, slowly close the discharge shut-off valve until normal working conditions are restored.

This trouble may occur when system pressure drop is significantly different from pump available pressure.

28 06617645-02

Refrigerant charge checking

• A few minutes after start up, working on cooling operating mode, check that condensing temperature, is approximately 15 °C higher than condenser inlet air temperature. Also check that the evaporation temperature is about 5 °C lower than the evaporator outlet temperature.

• When the unit has stabilised, check that the sight glass core shows green: if the core is yellow, moisture is present in the circuit. In this case it is necessary to dehydrate the circuit (qualified personnel only). Check at the sight glass that there are no continuous vapour bubbles present. If so, additional refrigerant charge may be required. (A few vapour bubbles are acceptable).

• Check that refrigerant superheat on the evaporator is about 5-7 °C

• Check if refrigerant sub-cooling on the condenser is about 5-7 °C.

Unit switch OFF

Please refer to the microprocessor manual enclosed with the unit.

Caution: For temporary stops (night time, weekend etc.) never switch off the unit by opening the mains switch: this should only be used to disconnect the unit from the power supply when current is not passing through it, i.e. when the unit is in ‘OFF’ mode. Additionally, with no supply to the crankcase heater, the compressor could be seriously damaged at unit start up.

Control devices - factory settings

CAPACITY STEPS

CONTROL DEVICE

CONTROL AND SAFETY DEVICE SETTINGS

Control thermostat (cooling)

Control thermostat (heating)

°C

°C

2 4

Set-point Differential Set point Differential

10 2 9 3

42 2 43 3

Safety devices - factory settings

CONTROL DEVICE

Anti-freeze thermostat

Electric heater thermostat

High pressure switch

Low pressure switch

End defrosting pressure

Defrosting set-point

Water safety valve (Optional)

°C

°C bar bar bar bar bar

SET POINT DIFFERENTIAL RESET TYPE

6 -- --

29 06617645-02

MAINTENANCE AND PERIODIC CHECKS

All maintenance and service operations MUST BE CARRIED OUT BY TRAINED PERSONNEL.

Disconnect the electrical supply before undertaking any work on the unit. (Any servicing performed when the supply is connected will need a suitable risk assessment).

The compressor casing and discharge line of the compressor are usually hot. Care should be taken when working in this area. Aluminium coil fins are very sharp and can cause serious wounds. Care should be taken when working in this area. After any servicing operation ensure that all covers are replaced and fastened with their locking screws.

It is strongly recommended that regular maintenance checks are performed to maintain correct operation of the unit:-

Every three months:

- Check that safety and control devices work correctly as previously described.

- Check all the terminals on the electric board and on the compressor are tight. Periodic cleaning of the terminals of the contactors should be done: if any damage is found, please replace the contactors.

- Verify refrigerant charge by checking the sight glass.

- Check that there is no oil leakage from the compressor.

- Check that there is no water leakage from the hydraulic system.

- If the unit is to be stopped for a long period, the unit hydraulic circuit, including all internal pipework and heat exchanger, should be emptied. This operation is compulsory if, during a seasonal shutdown, the ambient temperature is expected to go below the freezing point of the fluid in the hydraulic circuit (typical seasonal operation).

- Check hydraulic circuit water level.

- Check the flow switch operation .

- Check the compressor crankcase heater power supply and operation.

- Check defrosting procedure.

- Clean drain pan and pipeline.

- Clean mesh on water strainers.

- Clean the finned coils metallic filters with compressed air. This should be in the opposite direction of the normal air flow. If filters become fully clogged, clean them with a water jet.

Every six months:

- Check the colour of the sight glass core (green = no moisture, yellow = moisture present).

If it is yellow, the refrigerant circuit should be dehydrated and the refrigerant filter/drier changed.

- Check the unit noise level.

- Check mounting of fan blades and their balancing, check the tension and the wear of the belt.

REFRIGERANT CIRCUIT REPAIR

If the refrigerant circuits need to be evacuated,, all the refrigerant must be recovered using suitable

equipment. The system must be charged with nitrogen, using a gas bottle with a pressure reducing valve, until 15 bar pressure is reached. Search for leaks with a bubble leak finder. If bubbles appear, discharge the circuit before repairing by brazing with a suitable braze alloy. Never use oxygen instead of nitrogen:

explosions may occur.

30 06617645-02

Environmental Protection

European legislation regarding the use of ozone depleting substances forbids the release of refrigerants to the atmosphere. They must be reclaimed and returned to the vendor, or to authorised re-cyclers at the end of their operating life.

R407C refrigerant is deemed to be a controlled substance and is therefore subject to this legislation.

Particular care is required during servicing operations in order to prevent refrigerant loss.

De-commissioning

When the unit reaches the end of its service life and requires removal or replacement, the following operations are recommended:-

- the unit refrigerant must be reclaimed by trained personnel and returned to an authorised re-cycling centre

- compressor lubricating oil should be recovered and sent to an authorised re-cycling centre

- the unit frame, coil, heat exchanger etc, should be dismantled and subdivided into material type; bear in mind that copper and aluminium are present in substantial quantities in the unit.

These operations aid material recovery and recycling processes, reducing environmental impact.

31 06617645-02

DIMENSIONS

32 06617645-02

33 06617645-02

34 06617645-02

35 06617645-02

36 06617645-02

37 06617645-02

38 06617645-02

39 06617645-02

40 06617645-02

41 06617645-02

TEV LTD, ARMYTAGE ROAD, BRIGHOUSE, WEST YORKSHIRE, HD6 1QF. TEL: + 44 (0) 1484 405630 FAX: +44 (0) 1484 405620

EMAIL: [email protected] WEB: www.quartz.co.uk