Viessmann VITOCELL-V 100 Installation Instructions Manual


Add to my manuals
24 Pages

advertisement

Viessmann VITOCELL-V 100 Installation Instructions Manual | Manualzz

Installation Instructions

Vitocell 100

CVA Series

Enameled indirect-fired domestic hot water storage tank

42 to 120 USG / 160 to 450 ltr capacity

VITOCELL-V 100

42 to 79 USG / 160 to 300 ltr capacity

120 USG / 450 ltr capacity

IN BOILER APPLICATIONS:

CAUTION

THE HEAT TRANSFER

MEDIUM MUST BE WATER

OR OTHER NON-TOXIC

FLUID HAVING A TOXICITY

RATING OR CLASS OF 1,

AS LISTED IN CLINICAL

TOXICOLOGY OF

COMMERCIAL PRODUCTS,

5TH EDITION.

THE PRESSURE OF THE

HEAT TRANSFER MEDIUM

MUST BE LIMITED TO A

MAXIMUM OF

30 PSIG BY AN APPROVED

SAFETY OR RELIEF VALVE

(SEE PAGE 2).

IMPORTANT

Read and save these instructions for future reference.

5167 519 v2.2

02/2009

2

Safety, Installation and Warranty Requirements

Safety, Installation and Warranty Requirements

Please ensure that this manual is read and understood before commencing installation. Failure to comply with the issues listed below and details printed in this manual can cause product/property damage , severe personal injury , and/or loss of life . Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).

H Licensed professional heating contractor

The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.

H Advice to owner

Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.

" Please see section entitled “Important

Regulatory and

Installation

Requirements”.

H Product documentation

Read all applicable documentation before commencing installation. Store documentation near product in a readily accessible location for reference in the future by service personnel.

H Warranty

Information contained in this and related product documentation must be read and followed.

Failure to do so renders warranty null and void.

" For a listing of applicable literature, please see section entitled “Important

Regulatory and

Installation Requirements”.

IN SOLAR

APPLICATIONS:

CAUTION

THE HEAT TRANSFER

MEDIUM MUST BE EITHER

POTABLE WATER OR

CONTAIN ONLY

SUBSTANCES WHICH ARE

RECOGNIZED AS SAFE BY

THE U.S. FOOD AND DRUG

ADMINISTRATION.

THE PRESSURE OF THE

HEAT TRANSFER MEDIUM

MUST BE MAINTAINED

LESS THAN THE NORMAL

MINIMUM OPERATING

PRESSURE OF THE

POTABLE WATER SYSTEM.

Safety

General Information

Set-up

Connections

Additional Information

Page

Important Regulatory and Installation Requirements

. . . . .

4

About these Instructions

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Product Information

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Tank Set-up

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Recommended installation clearances for service access

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Minimum clearances to combustibles

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

6

6

Multiple Tank Set-up

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

Orientation and Dimensions

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

Installation of Inspection Opening Cover

. . . . . . . . . . . . . . . . . . . . . . . . . . .

8

DHW Tank Installation (42 to 79 USG /

160 to 300 ltr)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DHW temperature sensor installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Aquastat installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature sensor installation for solar operation

. . . . . . .

Checking anode connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

9

10

10

11

DHW Tank Installation (120 USG / 450 ltr)

. . . . . . . . . . . . . . . . . . . . . .

Installation of thermal insulation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DHW temperature sensor installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Aquastat installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature sensor installation for solar operation

. . . . . . .

Checking anode connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

12

13

13

14

15

Boiler Water/Solar Loop Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Individual DHW tank

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Multiple DHW tanks

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

16

18

Domestic Hot Water Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19

Recirculation Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21

Contents

Pressure Drop Information

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22

Post Installation ...

Start-up information

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service binder

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

23

23

3

Safety

Important Regulatory and Installation Requirements

Codes

The installation of indirect-fired hot water storage tanks might be governed by individual local rules and regulations for this type of product, which must be observed. Always use latest editions of codes.

Mechanical room

Ensure the mechanical room complies with the requirements of the technical data manual.

The tank must be installed in a mechanical room which is never subject to freezing temperatures.

If not in use and danger of freezing exists in the mechanical room, ensure water in tank is drained.

WARNING

If the heating system itself is to be filled with Glycol or any other antifreeze, the system fill must be of non-toxic or food grade antifreeze. In any circumstance, a non-toxic fluid must be used. Ensure a copy of the

Material Safety Data Sheet (MSDS) is supplied to the operator/ultimate owner of the system.

Working on the equipment

The installation, adjustment, service, and maintenance of this equipment must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water heating systems. There are no user serviceable parts on this equipment.

Ensure main power supply to equipment, the heating system, and all external controls has been deactivated .

Close main oil or gas supply valve . Take precautions in all instances to avoid accidental activation of power during service work.

Technical literature

Literature applicable to all aspects of the Vitocell:

- Technical Data Manual

- Installation Instructions

- Start-up/Service Instructions

- Operating Instructions and User’s Information Manual

Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed.

This product must be installed observing not only the necessary product literature (see list below), but also all local, provincial/state plumbing and building codes, as they apply to this product and all periphery equipment.

For information regarding other

Viessmann System Technology componentry, please reference documentation of the respective product.

We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.

The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, temperature controls, etc.

Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact

Viessmann for additional copies.

4

General Information

About These Instructions

Take note of all symbols and notations intended to draw attention to potential hazards or important product information.

These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.

WARNING

Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.

CAUTION

Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.

IMPORTANT

Warnings draw your attention to the presence of potential hazards or important product information.

Cautions draw your attention to the presence of potential hazards or important product information.

Helpful hints for installation, operation or maintenance which pertain to the product.

This symbol indicates that additional, pertinent information is to be found in column three.

This symbol indicates that other instructions must be referenced.

Product Information

42 to 120 USG / 160 to 450 ltr capacity

Enameled indirect-fired domestic hot water storage tank with one heat exchanger coil for use with hot water heating boilers.

5

Set-up

Tank Set-up

Fig 1.

Leveling bolt

H For narrow passageways, remove upper and lower portion of crating and carry DHW tank to its installation location by means of crating boards mounted on the tank.

min. ¾” / 20 mm max. 1½” / 35 mm

H Position tank carefully and remove wood crating.

H Locate tank(s) on flooring or foundation capable of supporting the weight of the tank(s) filled with water.

H The tank does not require a special foundation and can be placed directly on the floor. If, for cleanliness purposes, the tank is to be kept off the floor, a foundation for each tank or tank battery can be used.

H Level tank using leveling bolts on tank frame.

Recommended installation clearances for service access

Storage capacity

Rear

Sides

Top

Front

USG ltr inches mm

May be reduced if rear pipe connections can be reached with less clearance inches mm inches mm inches mm

42

160

18

460

12

300

53

200

18

460

12

300

79

300

18

460

12

300

120

450

18

460

12

300

36

900

24

600

36

900

48

1200

48

1200

24

600

24

600

24

600

Minimum clearances to combustibles

Storage capacity

All sides

Floor

USG ltr inches mm

42

160

53

200

0

0

0

0

Combustibles

79

300

0

0

120

450

0

0

6

Set-up

Multiple Tank Set-up

Y Y

Domestic hot water supply and T&P valve connection

Recirculation tapping

Boiler/solar water supply

Operating aquastat

Boiler/solar water return

Domestic cold water

Drain

Air vent

Fig 2.

Installing multiple tanks in a battery only for 79 and 120 USG / 300 and 450 ltr capacity

Two tanks, each with 79 USG / 300 ltr content, or up to four tanks , each with 120

USG / 450 ltr content , may be installed side-by-side.

The tank battery is controlled via one DHW tank aquastat making control of individual tanks within the tank battery impossible.

If control of individual tanks within a battery is necessary, two alternatives exist.

Either a 4-tank battery needs to be separated into smaller batteries i.e. two batteries each consisting of two tanks (one DHW tank aquastat controls each battery), or all tanks should be installed individually i.e. individual tank set-up (one

DHW tank aquastat controls each tank).

Y Y

1.

Install aquastat in the boiler water supply of the last tank receiving the boiler water of the tank battery (see illustration).

2.

Install domestic cold and hot water header lines (see illustration).

3.

Install boiler/solar water supply and return header lines (see illustration).

4.

Make final cold and hot water connections.

IMPORTANT

Both the boiler/solar supply/return header and the domestic hot/cold water header must be installed in a reverse return method. This ensures uniform heating of all tanks in the battery. Header sizes for batteries up to four 79 to 120 USG / 300 to

450 ltr tanks are printed on page 8.

5.

Insulate header piping lines.

CAUTION

In commercial installations, we recommend the installation of an additional high limit aquastat in the main discharge pipe of domestic hot water from the tank battery into the system, and to wire this additional high limit aquastat in series with the operating aquastat.

7

Orientation and Dimensions

Storage capacity

Number of tanks

Layout

USG ltr

42 and 53

160 and 200

1

Connections (individual tank)

Heating water supply / return

Domestic cold / hot water

Recirculation tapping

∅ ”

∅ ”

∅ ”

1

3 /

4

3 /

4

79

300

1 2 1

120

450

2 3 4

1

1

1

2

1 1 /

4

1

1 1 /

1

4

1

2

1 1 /

4

1

2

1 1 /

2

1

Ground terminal

Domestic hot water supply and

T&P valve connection

Recirculation tapping

Aquastat well / sensor well

Boiler water supply / solar supply

Boiler water return / solar return

Domestic cold water supply

2 1 /

2

2

1

Fig 3.

DHW tank connections

(42 to 79 USG / 160 to 300 ltr)

Fig 4.

DHW tank connections

(120 USG / 450 ltr)

Installation of Inspection Opening Cover

1.

only for 42 to 79 USG / 160 to 300 ltr capacity

1.

Insert insulation blanket.

2.

Secure plastic cover with supplied mounting bolts.

2.

8

Fig 5.

Connections

DHW Tank Installation (42 to 79 USG / 160 to 300 ltr)

DHW temperature sensor installation

2.

1.

7.

Fig 6.

Sensor installation

3.

4.

6.

5.

1.

Mount sensor on the outside of the sensor spring-clip (not in the center groove) so that it is flush with the front of the sensor spring-clip.

2.

Snap sensor cabling into plastic clip of sensor mounting equipment.

CAUTION

Never wrap sensor with any type of tape or insulation.

3.

Completely insert sensor mounting hardware along with sensor into sensor well.

4.

Remove top panel and insulation blanket.

5.

Remove cap from thermometer opening.

6.

Slide thermometer sensor cable through thermometer opening in the panel and insert thermometer.

7.

Completely insert sensor into metal clip on flange.

8.

For applications with Vitotronic 100 control, use supplied plastic clip and two screws to secure Honeywell bulb capillary. For applications with the

Vitotronic 200 or 300 control option, use supplied plastic clip and two screws to secure sensor cable to the tank sheet metal.

9.

For Solar Domestic Hot Water with

Vitosolic 200, SCU124 or SCU 224, use supplied plastic clip and two screws to secure sensor cable to the tank sheet metal.

9

Connections

DHW Tank Installation (42 to 79 USG / 160 to 300 ltr)

(continued)

Aquastat installation

Fig 7.

Aquastat installation

Where a Vitotronic 100 and a

Viessmann Power/Pump Control Module

(accessory) is utilized to control DHW production:

1.

Insert the extended capillary of the aquastat (supplied with Viessmann

Power/Pump Control Module, not illustrated) fully and completely into sensor well. Mount aquastat inconspicuously on tank panelling.

Follow instructions in Fig 6. with regard to sensor and spring clip installation.

The aquastat is to be mounted remote from the tank well as follows:

2.

Align sensor bulb with spring clip.

3.

Slide assembly into well.

4.

The retention spring clip must press the bulb properly to ensure surface contact with the well.

Temperature sensor installation for solar operation

The temperature sensor for solar operation is included in the solar control unit package.

1.

For solar operation, install the sensor well into the brass elbow and connect the assembly to the heating return line (solar return).

The brass elbow with sensor well is available as an accessory,

Part No. 7175 213.

1.

2.

Insert the temperature sensor until it bottoms out inside the sensor well.

1.

IMPORTANT

Never wrap insulating tape around the sensor.

2.

Fig. 8.

Installation of temperature sensor for solar operation

10

Connections

DHW Tank Installation (42 to 79 USG / 160 to 300 ltr)

(continued)

Checking anode connections

Magnesium anode

Grounding wire

Ensure the grounding wire is properly secured to the magnesium anode.

Fig 9.

11

Connections

DHW Tank Installation (120 USG / 450 ltr)

Installation of thermal insulation

1.

Slide bottom thermal insulation blanket underneath the DHW tank (if not already installed).

CAUTION

The thermal insulation must not come into contact with open flames.

Exercise caution when welding and soldering in the vicinty of the tank.

1.

Fig 10.

4.

2.

6.

5.

3.

2.

Push thermal insulation jacket at the front onto the flange and sensor well.

3.

Hook enclosure strips of the thermal insulation jacket into each other.

4.

Guide the thermometer sensor cable through the opening provided and push in the thermometer.

5.

Insert the sensor until it bottoms out inside sensor well, and secure with the spring clip.

6.

Push insulation plugs into the appropriate openings as shown.

Fig 11.

Installation of thermal insulation

12

Connections

DHW Tank Installation (120 USG / 450 ltr)

(continued)

DHW temperature sensor installation

1.

2.

Fig 12.

Sensor installation

Aquastat installation

3.

1.

Mount sensor on the outside of the sensor spring-clip (not in the center groove) so that it is flush with the front of the sensor spring-clip.

2.

Snap sensor cabling into plastic clip of sensor mounting equipment.

CAUTION

Never wrap sensor with any type of tape or insulation.

3.

Completely insert sensor mounting equipment along with sensor into sensor well.

4.

For applications with Vitotronic 100 control, use supplied plastic clip and two screws to secure Honeywell bulb capillary. For applications with the

Vitotronic 200 or 300 control option, use supplied plastic clip and two screws to secure sensor cable to the tank sheet metal.

Fig 13.

Aquastat installation

Where a Vitotronic 100 and a

Viessmann Power/Pump Control Module

(accessory) is utilized to control DHW production:

1.

Insert the extended capillary of the aquastat (supplied with Viessmann

Power/Pump Control Module, not illustrated) fully into sensor well.

Mount aquastat inconspicuously on tank panelling. Follow instructions in

Fig 12. with regard to sensor and spring clip installation.

The aquastat is to be mounted remote from the tank well as follows:

2.

Align sensor bulb with spring clip.

3.

Slide assembly into well.

4.

The retention spring clip must press the bulb properly to ensure surface contact with the well.

13

Connections

DHW Tank Installation (120 USG / 450 ltr)

(continued)

Temperature sensor installation for solar operation

The temperature sensor for solar operation is included in the solar control unit package.

3.

1.

For solar operation, install the sensor well into the brass elbow and connect the assembly to the heating return line (solar return).

The brass elbow with sensor well is available as an accessory,

Part No. 7219 729.

2.

Insert the temperature sensor until it bottoms out inside the sensor well.

IMPORTANT

Never wrap insulating tape around the sensor.

1.

2.

Fig. 14.

Temperature sensor installation for solar operation

14

Connections

DHW Tank Installation (120 USG / 450 ltr)

(continued)

Checking anode connections

3.

2.

1.

Ensure the grounding wire is properly secured to the magnesium anode.

2.

Install top insulation as shown.

3.

Attach Viessmann name plate to top panel.

Magnesium anode

Grounding wire

A

B

1.

Fig 15.

15

Connections

Boiler Water/Solar Loop Connections

WARNING

The operating aquastat and any secondary high limit aquastat of the tank must be set such that the DHW temperature inside the tank never exceeds 210°F / 99°C.

DANGER

Domestic hot water temperatures over 125°F / 52°C can cause severe burns instantly or death from scalds.

Children, disabled and elderly are at highest risk of being scalded.

Feel water before bathing or showering.

Temperature limiting valves are available and must be used where domestic hot water storage tank temperatures exceed 140°F / 60°C.

Individual DHW tank

H Maximum working pressure on the heat exchanger side of up to

150 psig / 10 bar

H Maximum working pressure on DHW side of up to 150 psig / 10 bar

H Maximum supply temperature on the heat exchanger side of up to

230ºF / 110ºC

H Maximum DHW supply temperature of up to 150ºF / 65.6ºC

Fig 16.

Recommended piping of an individual tank

Hot water heating boiler

Recirculation pump

Spring-loaded flow check valve

Boiler water supply

DHW tank temperature sensor well / aquastat well

Vitocell 100

Boiler water return

WARNING

Install tempering valve(s) to protect against scalding.

IMPORTANT

This is a simplified conceptual drawing only! Piping and necessary componentry must be field verified. Proper installation and functionality in the field are the responsibility of the heating contractor.

1.

Pipe together boiler and tank as illustrated. Connections must be accessible for service (use factory supplied adaptors). Viessmann flexible piping of stainless steel

(accessory) may be used.

2.

For:

- boiler water supply temperatures above 203°F / 95°C and

- 92 and 120 USG / 300 and 450 ltr tanks:

Remove plastic supply and return grommets (grommets are left-threaded).

3.

Pipe supply line with an incline and install componentry as follows:

H flow check valve, to stop gravity circulation of hot water back to the boiler when the boiler temperature is lower than the actual tank temp.

H automatic air vent, at the high point from the boiler supply to the tank heat exchanger

H drain valve, on the boiler return piping from the tank heat exchanger coil

H isolation valve, on the boiler supply and boiler return piping to the tank coil.

16

Connections

Boiler Water/Solar Loop Connections

(continued)

Individual DHW tank (continued)

Supply

D

4.

Install DHW tank temperature sensor in sensor well (see pages 9 and 13).

5.

Insulate piping.

IMPORTANT

This is a simplified conceptual drawing only! Piping and necessary componentry must be field verified. Proper installation and functionality in the field are the responsibility of the heating contractor.

IMPORTANT

Use Loctite 55 on all threaded steel nipples on tank.

H

DCW

Fig 17.

Recommended piping for solar applications

A Collector

B Safety valve

C Solar-Divicon

D Solar control

E Diaphragm expansion vessel

F Vitocell 100

G High limit safety cut-out

H Brass elbow c/w sensor well

17

Connections

Boiler Water/Solar Loop Connections

(continued)

Multiple DHW tanks

Y

Battery of DHW tanks

Sensor/Operating aquastat well

Boiler water return / solar return

Boiler water supply / solar supply

Fig 18.

Recommended piping of multiple tanks

IMPORTANT

Y

Use Loctite 55 on all threaded steel nipples on tank.

IMPORTANT

The circulation pump is activated by the operating aquastat or by the control system installed. The operating aquastat should be mounted on the tank which receives the boiler water supply last.

Viessmann recommends the installation of an additional high limit aquastat in the main discharge pipe of the DHW system.

This aquastat should be wired in series with the operating aquastat and should be set approximately 9°F / 5°C higher than the operating aquastat.

Y only for 79 and 120 USG / 300 and 450 ltr capacity

Domestic cold water supply

Domestic hot water

Drain

Air vent

Secondary high limit aquastat

All piping reverse return or use balancing valves.

1.

Pipe together boiler and tanks as illustrated. Connections must be accessible for service (use factory supplied adaptors).

2.

For boiler water supply temperatures over 203°F / 95°C, and for solar systems:

Remove plastic supply and return grommets (grommets are left-threaded).

3.

Pipe supply line with an incline and install componentry as follows:

H flow check valve, to stop gravity circulation of hot water back to the boiler when the boiler temperature is lower than the actual tank temperature

H automatic air vent, at the high point from the boiler supply to the tank heat exchanger

H drain valve, on the boiler return piping from the tank heat exchanger coil

H isolation valve, on the boiler supply and boiler return piping to the tank coil.

4.

Install boiler sensor in sensor well

(see page 13).

5.

Insulate piping.

WARNING

Install tempering valve(s) to protect against scalding.

18

Domestic Hot Water Connections

Connections

IMPORTANT

This is a simplified conceptual drawing only! Piping and necessary componentry must be field verified. Proper installation and functionality in the field are the responsibility of the heating contractor.

Fig 19.

Recommended domestic hot water connection

Domestic hot water supply

DHW recirculation line

DHW recirculation pump

Spring-loaded flow check valve

Discharge pipe

Temperature and pressure relief valve

Shut-off valve

Drain

Domestic cold water supply lines

Back flow preventer

Domestic cold water inlet

Precharged expansion tank

(required where back flow preventer is installed; check local plumbing codes and requirements)

1.

Pipe together boiler and tank as illustrated. Connections must be accessible for service (use factory supplied adaptors).

2.

Insulate domestic hot water supply piping.

IMPORTANT

Use Loctite 55 on all threaded steel nipples on tank.

19

Connections

Domestic Hot Water Connections

(continued)

Always ensure the use of type approved devices. Safety devices include the following components:

IMPORTANT

Use Loctite 55 on all threaded steel nipples on tank.

H Isolation valves

H Drain valve

It is tested under ANSI Z21.22 Code for

Relief Valves and Automatic Gas

Shut-off Devices for Hot Water Supply

Systems. The relief temperature is set at 210°F / 99°C. The valve has a male threaded inlet and female threaded outlet, both ¾” sizes.

Proper installation of the T&P valve shall include all of the following:

H Pressure reducing valve

H where required by local jurisdiction

Drinking water filter where required by local jurisdiction

H Back flow preventer

Where backflow preventers are required, a domestic water expansion tank installation is required in the cold water inlet piping before the cold water enters the tank. The back flow device must be installed according to the manufacturer’s installation instructions. Observe local codes and regulations.

- The T&P valve shall be installed in the pipe connection point marked TPV in the Installation Fittings Installation

Instruction Supplement of the tank.

- The discharge line from the T&P valve shall be ¾” / 1.9 cm ∅ and run to a safe place of discharge approximately

1 ft / 30 cm above the floor, close to a floor drain.

- The discharge line must be installed in the shortest distance and pitch downward from the T&P valve and terminate plain.

H Tempering valve

A tempering valve must be field installed where storage tank

(domestic hot water temperature) exceeds local restricted temperatures or 140°F / 60°C. Check code requirements.

WARNING

The discharge line for the T&P valve must be oriented to prevent scalding of attendants.

- Do not route discharge line to the outdoors.

- Do not install any type of valve or an obstruction of any kind between the tank and the T&P valve, or between the T&P valve and the discharge line outlet.

Temperature and pressure relief valve

A temperature and pressure relief valve

(T&P valve) is supplied with the tank.

The heating contractor must install the valve on each tank in a method meeting code requirements.

If local codes require a different relief valve, consult Viessmann

Manufacturing for a substitute valve.

The tank is approved for 150 psig.

Maximum operating pressure is 150 psig.

The T&P valve supplied with the tank is manufactured by Watts Industries

(Model 40XL-8), set to 150 psig for US and Canadian installations. The valve is

ASME pressure steam rated for 998

MBH and CSA temperature steam rated for 200 MBH.

WARNING

The valve test lever must be operated at least once per year by the owner to ensure that waterways are clear. A licensed professional heating contractor shall reinspect the T&P valve at least once every three years.

Failure to inspect can result in unsafe temperature or pressure build-up, which can result in death, serious injury or substantial product/property damage.

Warranty

Our warranty for domestic hot water tanks states that the water heated must be of drinking (potable) water quality and that any water treatment equipment in use must function correctly.

Viessmann accepts no responsibility for damage howsoever caused and reserves the right to withdraw the product warranty if the product has been improperly installed or misapplied by the installer, contractor or final user.

In order to qualify for product warranty, strict adherence to the installation and service manuals must be observed. In the event that Viessmann non-approved components are utilized, Viessmann reserves the right to withdraw all expressed or implied warranties without written notice.

The water to be heated with the

Vitocell must be drinking (potable) water quality. If the tank is used to heat other media, the warranty will be null and void. Damage resulting from excessive pressure or temperature is clearly not the responsibility of

Viessmann.

The amount of chloride and sulfate acceptable to the tank is limited. In areas where high concentrations of chloride and sulfate are present in drinking water, please consult

Viessmann for directions.

20

Connections

Recirculation Connections

H Pipe domestic hot water supply piping with tank as illustrated. Connections must be accessible for service (use factory supplied adaptors).

Connection sizes are provided in section entitled Orientation and

Dimensions on page 8.

H Install recirculation pump, flow-check valve and recirculation timer (for shut-down during off-hours where feasible) on the recirculation piping side.

H Gravity circulation of the recirculation system is restricted due to the upward-curved domestic hot water discharge piping inside the tank.

H Connect tank battery to existing recirculation piping. Cap off unused recirculation connections of individual tanks.

H Saving Energy

A timer on the recirculation pump reduces the heat loss significantly in commercial applications during times when no or reduced demand for domestic hot water occurs.

Connection of a recirculation system in a multiple-tank installation for systems utilizing boilers or remote heating plants without low temperature boiler return water

Y Y Y

Drawpoints

Recirculation piping

Circulation pump

Spring-loaded flow check valve

Domestic cold water supply

Domestic hot water supply

Secondary high limit aquastat

Air vent Fig 20.

Connection of a recirculation system in a multiple-tank installation for remote heating plants with low temperature boiler return water limit and/or for multiple recirculation lines

Y Y Y

Fig 21.

Drawpoints

Recirculation piping

Circulation pump

Spring-loaded flow check valve

Domestic cold water supply

Domestic hot water supply

Secondary high limit aquastat

Air vent

21

Additional Information

Pressure Drop Information

Pressure drop on heating water side (primary circuit) Pressure drop on domestic hot water side

(secondary circuit)

200

160

120

500

400

300

80 200

40 100

32 80

24 60

20 50

16 40

12 30

8 20

40

32

24

20

16

12

100

80

60

50

40

30

8 20

4 10

3.2

8

2.4

6

2 5

1.6

4

1.2

3

0.8

2 4

3.2

2.4

2

1.6

10

8

6

5

4

Flow rate ltr/h

GPM

0.4

1

8 10 13 17

2.2

2.6

3.5

4.4

Flow rate

33

8.8

50 67 83 100 ltr/min

13 18 22 26 GPM

42 USG / 160 ltr and 53 USG / 200 ltr storage capacity

79 USG / 300 ltr storage capacity

120 USG / 450 ltr storage capacity

22

Post Installation...

Start-up information

Service binder

Additional Information

Start-up/Service Instructions

Vitocell-V 100

1.

File all Parts Lists, Operating and

Service Instructions, and Installation

Instructions in the Service Binder.

2.

Install a protective hanging case near the boiler and store the Service

Binder in this location.

For a listing of applicable Viessmann literature, please see Important

Regulatory and Installation

Requirements on page 4.

23

Viessmann Manufacturing Company (U.S.) Inc.

45 Access Road

Warwick, Rhode Island

1-800-288-0667

02886

USA

Fax (401) 732-0590 www.viessmann-us.com

[email protected]

24

Viessmann Manufacturing Company Inc.

750 McMurray Road

Waterloo, Ontario

1-800-387-7373

N2V 2G5

Canada

Fax (519) 885-0887 www.viessmann.ca

[email protected]

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement