TRIPLETT CM650 600 Amp True RMS AC/DC Clamp Meter Use and Care Manual

Add to My manuals
15 Pages

advertisement

TRIPLETT CM650 600 Amp True RMS AC/DC Clamp Meter Use and Care Manual | Manualzz

User Manual

CM650

600A TRMS AC/DC Clamp Meter

Introduction

Congratulations on your purchase of the Triplett CM650 600A True RMS

AC/DC Clamp meter. The CM650 True RMS AC/DC Clamp meter features:

 AC/DC Current measurements up to 600A.

 Variable Frequency Drive (VFD) Voltage Measurements

Inrush Current Mode

 Temperature Measurements

 Non-contact AC voltage detection

 Auto Power OFF

Safety

International Safety Symbols

This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.

This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages may be present

Double insulation

SAFETY NOTES

Do not exceed the maximum allowable input range of any function.

When the instrument is not in use, press the ON/OFF key to turn off the meter.

Remove the battery if meter is to be stored for longer than 60 days.

CAUTIONS

Improper use of this meter can cause damage, shock, injury or death.

Read and understand this user manual before operating the meter.

Always remove the test leads before replacing the battery.

The meter itself for any damage before operating the meter. Repair or replace any damage before use.

Use great care when making measurements if the voltages are greater than 25VAC rms or 35VDC. These voltages are considered a shock hazard.

Voltage checks on electrical outlets can be difficult and misleading because of the uncertainty of connection to the recessed electrical contacts. Other means should be used to ensure that the terminals are not “live”.

Description

Meter Description

1. NCV (Non-Contact Voltage) Sensor

2. Current Clamp

3. NCV (Non-Contact Voltage) Indicator LED

4. Clamp Trigger

5. Rotary Function Switch

6. LCD Display

7. Data HOLD/Flashlight Button

8. REL/Backlight Button

9. Range Button

10. MODE and VFD Button

11. PEAK and INRUSH Button

12. Flashlight

13. Battery Cover

14. COM Input Jack (-)

15. Positive Input Jack (+)

Display Icons Description

1. REL/ ZERO Button

2. Alternating Current/Voltage

3. Direct Current/Voltage

4. Minus Sign

5. Low Battery

6. Auto Range Mode

7. INRUSH Current Mode

8. Display Hold

9. MAX/MIN Mode

10. Variable Frequency Drive (VFD) Voltage Value

11. Diode Test

12. Continuity Test

13. Auto Power Off (APO)

14. Faranheit and Celcius Units (Temperature)

15. Units of Measure Prefixes

16. Hertz (Frequency)

17. Percent (%) Duty Cycle

18. Measurement Display Digits

Operation

AC/DC Current Measurements

*NOTE: Ensure that the test leads are disconnected from the meter before making current clamp measurements.*

1. Set the Function switch to the 600A range, If the approx range of the measurement is not known, select the highest range then move to the lower ranges if necessary.

2. Press the REL button to zero the meter display.

3. Use rotary function switch to select 60A AC/DC or 600A AC/DC range.

4. Use MODE Button to select AC or DC .

5. Select AC current Test, press the INRUSH/PEAK Button to turn Inrush current test, the LCD will display “----”.

6. 6. Press the trigger to open jaw, Enclose only one conductor, For optimum results, center the conductor in the jaw.

7. 7. The clamp meter LCD will display the reading.

AC Voltage Measurements

8. Insert the black test lead into COM input jack and the red test lead into the Positive input jacks.

9. Set the function switch to the VAC position.

10. Press the MODE/VFD Button for 1 second to turn on the VFD test.

11. Press the INRUSH/PEAK Button to turn on PEAK test.

12. Connect the test leads in parallel to the circuit under test.

13. Read the voltage measurement on the LCD display.

DC Voltage Measurements

1. Insert the black test lead into COM input jack and the red test lead into the Positive input jacks.

2. Set the function switch to the VDC position.

3. Connect the test leads in parallel to the circuit under test.

4. Read the voltage measurement on the LCD display.

Resistance Measurements

1. Insert the black test lead into the COM input jack and the red test lead into the Positive input jacks.

2. Set the function switch to the ΩCAP position.

3. Touch the test probe tips across the circuit or component under test.

4. Read the resistance on the LCD display.

Continuity Measurements

1. Insert the black test lead into the COM input jack and the red test lead into the Positive input jacks.

2. Set the function switch to the “ ” position.

3. Use the MODE Button to select continuity “ ”, The display icons will change when the MODE Button is pressed.

4. Touch the test probe tips across the circuit or component under test.

5. If the resistance is <50Ω, a tone will sound.

Capacitance Measurements

WARNING : To avoid electric shock, discharge the capacitor under test before measuring.

1. Set the function switch to the ΩCAP position.

2. Insert the black test lead into the COM input jack and the red test lead into the Positive input jacks.

3. Touch the test probe tips across the part under test, If

“OL”

appears in the display, remove and discharge the component.

Read the capacitance value in the display.

4. The display will indicate the proper decimal point and value.

Frequency Measurements

1. Insert the black test lead into the COM input jack and the red test lead into the Positive input jacks.

1. Set the function switch to the VAC Hz/% Position.

2. Press MODE Button to select the Frequency ( Hz ) or Duty Cycle ( % ).

3. Touch the test probe tips across the part under test.

4. Read the value on the display.

5. The display will indicate the proper decimal point and value.

Temperature Measurements

1. Set the function switch to the TEMP position.

2. Insert the Temperature Probe into the negative COM and Positive jacks, observing polarity.

3. Touch the Temperature Probe head to the device under test, Continue to touch the part under test with the probe until the reading stabilizes.

4. Read the temperature on the display, The digital reading will indicate the proper decimal point and value.

5. Use the MODE Button to select °C or °F.

WARNING: To avoid electric shock, be sure the thermocouple probe has been removed before changing to another measurement function.

Diode Measurements

1. Insert the black test lead into the COM input jack and the red test lead into the Positive input jacks.

2.

Turn the function switch to “ ” position.

3. Use the MODE Button to select the diode function if necessary (Diode symbol will appear on the LCD when in Diode test mode)

4. Touch the test probe tips to the diode or semiconductor junction under test. Note the meter reading.

5. Reverse the test lead polarity by reversing the red and black leads, Note this reading.

6. The diode or junction can be evaluated as follows:

If one reading displays a value (Typically 0.400V to 0.900V) and the other reading displays “ OL ”, the diode is good.

 If both readings display “ OL ” the device is open.

 If both readings are very small or ‘

0

’, the device is shorted.

Non-Contact Voltage (NCV) Measurements

WARNING: Risk of Electrocution, always test the Voltage Detector on a known live circuit to verify proper operation before use.

1. Touch the probe tip to the hot conductor or insert into the hot side of the electrical outlet.

2. If AC voltage is present, the detector light will illuminate.

Note: The conductors in electrical cord sets are often twisted. For best results, rub the probe tip along a length of the cord to assure placing the tip in close proximity to the live conductor.

Note: The detector is designed with high sensitivity. Static electricity or other sources of energy may randomly trip the sensor. This is normal operation.

Function Buttons

MODE and VFD Button

• Short Press the MODE/VFD Button to toggle between modes available for the rotary switch position (V/Hz/%)

• Long Press and Hold the MODE/VFD while POWERING ON will disable the

Auto Power OFF (APO) Function

Long Press and hold MODE/VFD will engage VFD measuring mode.

HOLD and Flashlight Button

To freeze the LCD reading, press the Hold/Flashlight Button.

• While data hold is active, the “H” icon appears on the LCD.

• Press the Hold/Flashlight Button again to return to normal operation.

The LCD is equipped with backlighting for easier viewing, especially in dimly lit areas.

Press the Hold/Flashlight Button to turn the Flashlight on, Press again to turn the Flashlight off.

Range Button

Press the RANGE Button to activate the manual mode and to disable the

Autorange function, The symbol “AUTO” disappears from the upper left part of the display.

• In manual mode, press the RANGE Button to change measuring range, the relevant decimal point will change its position.

• The RANGE Button is not active in positions , ,CAP,Hz%,Temp °C °F .

• In Autorange mode, the instrument selects the most appropriate ratio for carrying out measurement.

• • If a reading is higher than the maximum measurable value, the indication

“O.L” appears on the display.

Press and hold the RANGE Button for more than 1 second to exit the manual mode and restore the Autorange mode.

PEAK/ INRUSH Button

In AC voltage test mode, Press PEAK/INRUSH Button the Peak maximum and Peak minimum values are measured.

In current test mode, Press PEAK/INRUSH Button the Inrush current values are measured.

Relative/Backlight Button

The relative measurement feature allows you to make measurements relative to a stored reference value, A reference voltage, current, Capacitance etc. can be stored and measurements made in comparison to that value, The displayed value is the difference between the reference value and the measured value.

Press the

“REL/Backlight ” Button to zero the display “ ” will appear in the display.

To exit this mode, press the

“REL/Backlight” Button again, and “ ” will disappear in the display.

• DC voltage measurement mode, Press the “ REL/Backlight”

Button to

“zero” the display.

• Press and hold the the “

REL/Backlight

” Button to turn the Backlight on, Press and hold again to turn the Backlight off.

In order to conserve battery life, the meter will automatically turn off after approximately 15minutes.

To turn the meter on again, turn the function switch to the OFF position and then to the desired function position.

To press and hold the MODE/VFD Button to turn the system on, the auto power off function will be cancelled.

Auto Power OFF (APO)

Maintenance

WARNING: To avoid electrical shock, disconnect the meter from any circuit, remove the test leads from the input terminals, and turn OFF the meter before opening the case. Do not operate the meter with an open case.

Cleaning and Storage

Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or solvents. If the meter is not to be used for 60 days or more, remove the battery and store it separately.

Battery Replacement

1. Remove the Phillips head screw that secures the rear battery door

2. Open the battery compartment.

3. Replace the 1.5V x 3 “AAA” batteries.

4. Secure the battery compartment.

Type K Temperature Probe Replacement

Note:

To use a Type K thermocouple probe that is terminated by a subminiature (Flat blade) connector, a subminiature-to-banana plug adaptor is required.

Specifications

Function Range Resolution Accuracy ±(% of

AC True RMS

Current

60.00A

600.0A

10mA

100mA

reading+digits)

±2.0% of rdg ± 8 digits

±2.5% of rdg ± 8 digits

Over rang protection: Maximum input 600A;

Accuracy specified from 5% to 100% of the measuring range;

Frequency Response:50Hz to 60Hz True RMS;

Inrush current Maximum Input: 600A;Inrush current

Sensitivity: >2A.

DC Current

Max:600A

AC True RMS

Voltage (with

VFD)

60.00A

600.0A

6.000V

60.00V

600.0V

10mA

100mA

1mV

10mV

100mV

±2.0% of rdg ± 8 digits

±2.5% of rdg ± 8 digits

±1.2% of rdg ± 5 digits

1000V 1V ±1.5% of rdg ± 5 digits

Variable frequency drive test AC voltage rang: 100V-600V.

AC voltage bandwidth: 50 to 1000Hz(Sine); 50/60(All wave).

Accuracy specified from 5% to 100%of the measuring range.

Maximum Input: 1000V ac rms. PEAK Maximum Input:1000V.

DC Voltage

Maximum Input:

1000V dc

6.000V

60.00V

600.0V

1mV

10mV

100mV

±0.9% of rdg ± 3 digits

±1.0% of rdg ± 3 digits

Resistance

1000V

600.0Ω

1V

0.1Ω

6.000kΩ 1Ω

±1.2% of rdg ± 3 digits

±1% of rdg ± 4 digits

60.00kΩ 10Ω

600.0kΩ 100Ω

6.000MΩ 1kΩ

60.00MΩ 10kΩ

±1.5% of rdg ± 2 digits

±2.0% of rdg ± 5 digits

±3% of rdg ± 8 digits

Input Protection: 300V dc or 300V ac rms.

Function

Capacitance

(Auto-Ranging)

Range

99.99nF*

999.9nF

9.999µF

99.99µF

999.9µF

Resolution Accuracy ±(% of reading+digits)

0.01nF

0.1nF

±4.5% of rdg ± 20 digits

0.001µF

0.01µF

0.1µF

±3.0% of rdg ± 5 digits

Frequency with Test

Leads (AC Voltage)

9.999mF

99.99mF

0.001mF

0.01mF ±5% of rdg ± 5 digits

Input Protection: 300Vdc or 300V ac rms.

*

< 99.99nF(No specification)

10Hz to 100kHz ±1.0% of rdg ± 5 digits

Input Protection: 1000V AC rms; Sensitivity: >15V AC rms.

±1.0% of rdg ± 5 digits Frequency (AC

Current)

Sensitivity: >20A.

45Hz to 1kHz

Duty Cycle

Temperature

20.0%~80.0% 0.1

-20 to 1000°C 0.1/1°C

±1.2% of rdg ± 10 digits

±3% of rdg ± 3°C

-4 to 1832°F 0.1/1°F ±3% of rdg ± 5°F

Sensor: Type K Thermocouple; Input Protection: 300V dc or 300V ac rms.

Function

Diode

Continuity

Testing Condition

Forward DCA is approx.1mA, open circuit

Voltage MAX. 3V

Reading

Forward voltage drop of

Diode

Test current MAX. 1.5mA Buzzer makes a long sound,

While resistance is less than(50Ω)

Input Protection: 300V dc or 300V ac rms .

General Specifications

Clamp Jaw Opening

Display

Low Battery Indication

Over-Range Indication

Measurement Rate

Temperature Sensor

Input Impedance

AC Response

ACV Bandwidth

Operating Temperature

Storage Temperature

Operating Humidity

Storage Humidity

Operating Altitude

Battery

Battery Life

Auto Power Off

Safety

1.3” (33mm) approx

6000 counts backlit LCD

“ ” is displayed

“OL” display

3 readings per second, nominal

Type K thermocouple

10MΩ(VDC and VAC)

True rms (AAC and

VAC) 2KHz

5 to 40°C (41 to 104°F)

-20 to 60°C (-4 to 140°F)

Max 80% up to 31°C(87°F) decreasing linearly to 50% at 40°C(104°F)

<80%

7000ft. (2000meters) maximum.

3 x 1.5V “AAA” Batteries

~30h (Backlight ON), ~100h (Backlight OFF)

After approx. 15 minutes

For indoor use and in accordance with the requirements for double insulation to

CAT II 1000V, CAT III 600V (EN 61010-

1:2010+A1:2019, EN 61010-2-032:2012, EN 61010-2-

033:2012 Low Voltage Directive 2014/35/EU), Pollution

Degree 2

Weight

Dimensions

10.2 oz (290.6g)

9.4 x 3.0 x 1.5” (238.8 x 76.5 x 38mm)

Warranty Information

Triplett / Jewell Instruments extends the following warranty to the original purchaser of these goods for use. Triplett warrants to the original purchaser for use that the products sold by it will be free from defects in workmanship and material for a period of (1) one year from the date of purchase. This warranty does not apply to any of our products which have been repaired or altered by unauthorized persons in any way or purchased from unauthorized distributors so as, in our sole judgment, to injure their stability or reliability, or which have been subject to misuse, abuse, misapplication, negligence, accident or which have had the serial numbers altered, defaced, or removed. Accessories, including batteries are not covered by this warranty

Copyright © 2020 Triplett www.triplett.com