CEILING CONCEALED TYPE AIR CONDITIONER INDOOR UNIT
INSTRUCTION
MANUAL
H-MRV
Ceiling Concealed Type Room Air Conditioner
AE072FCAKA
AE092FCAKA
AE122FCAKA
AE142FCAKA
AE182FCAKA
AE212FCAKA
AE242FCAKA
AE09~212FCAKA
AE072FCAKA
AE242FCAKA
Contents
Before Application
Cautions
Part Description
Important Points of Safety
Operating Instructions
AUTO,COOL, DRY,HEAT Operation
TIME Operation
Sleep Function
Health Function
Maintenance
Trouble Shooting
When Fault Occurs
Notice to Users
Indoor Unit Installation
Installation Precautions
Installation Procedure
Malfunction
Installation Check and Trial Run
0010573331
Please read this manual carefully before use.
Please keep it attentively for future use.
17-18
19
20
21-22
23-33
34-35
36
1-2
3-8
9-11
12
13-14
15
16
Cautions
1
Cautions
Indoor
DB C
WB C
Cooling outdoor
DB C
WB C
Heating
Rated Maximum Minimum
27 32 18
19 23 14
35 43 -5
Indoor
DB C
WB C
24 26 --
20 27 15
14.5 -- --
7 24 -15 outdoor DB C
WB C
6 18 --
2
D
AE072FCAKA
AE242FCAKA
AE092FCAKA , AE122FCAKA , AE142FCAKA , AE182FCAKA , AE212FCAKA have the Return air box (see the following picture) when shipping from the factory and they are back-side return air. During the installation, also can be changed to Down-side Return air according to the user's need.
AE09~212FCAKA
3
D
SWING
MODE
T E M P
ON
OFF
FAN
SLEEP
HEALTH FRESH
CLOCK
TIMER
SET
RESET
LIGHT LOCK
Left picture is a wired remote controller, which can be used on AE072FCAKA(wired control), AE092FCAKA
(wired control), AE122FCAKA(wired control),
AE142FCAKA(wired control),AE182FCAKA(wired control),AE212FCAKA(wired control), AE242FCAKA
(wired control). The remote controller can be purchased extrally.
Wired remote Controller using method:
1.Use one wired remote controller. See fig (1)
2.Also can buy a remote controller extrally, realize wired remote control + remote control dual control modes.
AUTO
ON
*
OFF
SET
ROOM C
MODE FAN SWING
TEMP HEALTH
CLOCK
TIMER
SET
SLEEP
FILTER RESET
RESET
ON/OFF
Wire remote controlller
Remote controlller (1)
Remote controlller is an accessory, to be ordered extrally
fig(1)
The right figure is a remote controller, which can be used on AE072FCAKA(remote control), AE092FCAKA(remote control), AE122FCAKA(remote control), AE142FCAKA
(remote control),AE182FCAKA(remote control),
AE212FCAKA(remote control), AE242FCAKA(remote control) and the matching remote control receiver
Remote control receiver using method :
Use remote controller control the remote control window of the remote control receiver.
B A
AUTO
OFF
H
HEALTH
MODE
T E M P
ON
OFF
FAN
SWING
TIMER
RESET CODE
LOCK
R
Remote receiver (2)
fig(2)
Remote controlller (2)
4
D
14 15 16 17 18 19
13
12
11
10
9
8
AUTO
MODE FAN SWING
TEMP HEALTH
20
29
22.Setting button
Used to confirm
the time of timer
and clock
23.Sleep button
7
6
SET
CLOCK
TIMER
SET
SLEEP
21
22
26
27
28
21.Clock button
Used to calibrate the time of timer and clock
Used to set Sleep state
5
4
3
2
1
1.ON/OFF button
Used to turn on/off unit
2.Temperature display
3.Clock display
4.Timer ON/OFF display
5.Humidity display
6.Air filter cleaning display
When there is too much dust collected on the air inlet, the wire controller will show this display to remind the user to clean the air inlet.
Auto
Low Fan Med Fan High Fan Auto
11.Fresh air state display
12.Humidifying state display
Working mode
Wire controller
Auto operation
Cooling operation
Dehumidifying operation
16.Electric heating display
17.Operation mode button
* just press the air filter reset button.
7.Super/Soft operation display
8.Fan speed display
9.Auto Swing display
10.Health state display
SUR
FILTER RESET
RESET
ON/OFF
13.Sleep state display
14.Network control display
15.Working mode display
23
24
25
30
25.Reset button
Heating operation
Fan operation
When the wire controller appears abnormal condition, use a sharp-pointed article to press this button to make the wire controller resume normal
26.Air Filter Reset
button
Used to set working mode:
Auto, Cooling, Dehumidifying,
Heating, Fan
18.Fan speed button
Used to set fan speed: Low
Fan, Med Fan, High Fan, Auto
19.Swing button
Used to set Auto Swing or
Fixed air sending direction
20.Temperature Setting button
Used to set temperature, temperature range: 16 C~30
C
24.Time Adjusting
button
Used to adjust the time of timer and clock
After cleaning the air inlet, press this button, the unit can start to operate
27.Timer button
Used to set the mode of timer
28.Lock state display
29.Health
Used to control the generating oxygen function and negative ion-function
Note:
1.This model does not have the following related
display and function
5 6 7 9 11 12 14 16 26
30.Remote control window
Used to receive the remote control signal
2.The outdoor unit no oxygen-bar function or no negative ion
Calibration of clock
When turning on the unit for the first time, the clock should be calibrated. The method of calibration is:
1.Press ìClockî button, the Clock display ìAMî ìPMî will flash.
2.Press or to adjust time. For each press, the time will increase or decrease 1
* minute. If depressing the button, the time will increase or decrease rapidly.
3.After confirming the time, press ìSetî button, ìAMî or ìPMî will stop flashing,the
clock will begin to work.
5
D
Remote LCD display contents and key name and each key function introduction
31
23
22
21
20
19
18
17
16
15
8
1
2
3
SWING
MODE
HEALTH
CLOCK
T E M P
ON
OFF
FRESH
SET
FAN
SLEEP
24
25
26
27
28
29
9
10
11
1.ON/OFF button
Used to turn on/off unit
Note: Wired remote
controller his key have compl
cooling running function.
2.Operation mode button
Used to set working mode:
Auto, Cooling,
Dehumidifying,
Heating, Fan
3.Health
Used to control the generating oxygen function and negative ion-function
4.Clock button
Used to calibrate the time of timer and clock
5.Timer button
13.Setting button
Used to confirm
the time of timer
and clock
14.Lock button
Used to lock the operating key and LCD contents
15.Timer ON/OFF display
16.Fan speed display
Auto
Low Fan Med Fan High Fan Auto
17.Battery energy display
18.Clock display
19.Auto Swing display
20.Humidifying state display
21.Sleep mode display
22.Working mode display
4
12
13
Used to set the mode of timer
Working mode
Remote controller
5
TIMER
6.Time Adjusting button
Auto operation
6
7
RESET
LIGHT LOCK
14
30
7.Reset button
When the wire controller appears abnormal condition, use a sharp-pointed article to press this button to make the wire controller resume normal
8.Swing button
Cooling operation
Dehumidifying operation
Heating operation
Fan operation
23.Health state display
Display when the health running
24.Electric heating display
25.Comfort running display
Used to set Auto Swing or
Fixed air sending direction
26.Fresh air state display
AUTO
ON
*
SET
ROOM
OFF
C
MODE
TEMP
CLOCK
TIMER
FAN
ON/OFF
SWING
HEALTH
SET
SLEEP
FILTER RESET
RESET
9.Temperature Setting button
Used to set temperature, temperature range: 16 C~30 C
10.Fan speed button
Used to set fan speed: Low
Fan, Med Fan, High Fan, Auto
27.Signal launch display
23.Temperature display
Used to display the setting temperature and room temp.
29.Lock state display
11.Sleep button
12.Fresh air
Used to set fresh air function
30.Light button
Used to realize control board
VFD light stable,light weaker, light shut off etc.
31.Signal lauch head
Remote controller
(Operation of remote controller)
Make sure that the remote controller is used within 7 meters from receiver window of the wire controller and there are no obstructions in between.
The remote controller or wire controller should be handled with care.
When operating the remote controller in an area where electronically controlled lights are installed or wireless handsets are used, move closer to the indoor unit as the function of the remote controller might be affected by signals from this equipment.
Note:
3.When using remote controller, first point it to the receiving window of wire controller, and then operate remote controller.A ìtickî tone will be uttered to indicate a right acceptance.
4.All the buttons except the sleeping button is no effective after wire controller received lock signal from remote controller.
6
D
11
12
13
14
Remote LCD display contents and key name and each key function introduction
4
6
21
AUTO ion
OFF
H
HEALTH
MODE
T E M P
ON
OFF
FAN
SWING
TIMER
RESET CODE
B A
LOCK
20
15
16
1.ON/OFF button
Used to turn on/off unit
2.Temperature Setting button
Used to set temperature, temperature range: 16 C~30 C
17
18
19
2
7
3.Health
Used to control the generating oxygen function and negative ion-function
4.Operation mode button
8
9
10
Used to set working mode:
Cooling, Dehumidifying,
Heating
5.Timer button
Used to set the mode of timer
6.Reset button
When the remote controller appears abnormal condition, use a sharp-pointed article to press this button to make the wire controller resume normal
7.Fan speed button
Used to set fan speed
8.Swing button
Used to set Auto Swing or
Fixed air sending direction
9.Time Adjusting button
10.Lock button
Press on time lock all the key sand press another time concel the lock.
11.Working mode display
12.Fan speed display
Used to display the fan speed. After setting
"AUTO" function,air speed can auto change according to the temp. difference between the room temp. and setting temp.
13.Health running display
Used to display healthy running.
14.Timer ON/OFF display
Display Timing mode.
"Blank" No Timing
15.Signal display
Sending out signal to the remote receiver.
16.Temperature display
Display the setting temp.
value.
17.Lock display
Display the key have been locked.
18.Super/Soft operation display
19.Timing time display
Display timing open time or timing close time
20.Signal launch head
Use to send signal to the indoor unit receive window.
21.Code
Select remote control receive code(H-MRV Remote cnotrol type use A code)
Make sure that the remote controller is used within 7 meters from receiver window of the wire controller and there are no obstructions in between.
The remote controller or wire controller should be handled with care.
When operating the remote controller in an area where electronically controlled lights are installed or wireless handsets are used, move closer to the indoor unit as the function of the remote controller might be affected by signals from this equipment.
R
Note:
1.After change the battery, working condition resume as follows:
Working mode:cooling Temp. 26 C
Timming mode: normal Air speed: Auto
2.The units used in this manual no 8 18 functions. The health key can only control the negative generator.
7
D
Clock set
When unit is started for the first time, clock should be adjusted as follows:
Press CLOCK button, "AM"or "PM" flashes.
Press or to set correct time. Each press will increase or decrease 1min. If the button is kept depressed, time will change quickly.
After time setting is confirmed, press SET, "AM "and "PM" stop flashing, while clock starts working.
Battery loading
Batteries are fitted as follows:
* *
* *
Remove the battery compartment lid
Slightly press and disengage the battery compartment lid marked with ì î and then hold the remote controller by the upper section and then remove the battery compartment lid by pressing in the direction of the arrow as shown in the figure above.
Loading the battery
Ensure that batteries are correctly placed in the compartment as required for positive and negative terminals.
Replacing the battery compartment lid
The battery compartment lid is reinstalled in the reverse sequence.
Display review
Press the button to see if batteries are properly fitted. If no display appears, refit the batteries.
Caution:
If the remote controller does not operate as designed after fitting new batteries of the same type, press the Reset button (marked ) with a pointed article.
Note:
It is recommended that the batteries be removed from the compartment if the remote controller is not used for an extended period.
The remote controller is programmed for automatic test of operation mode after the batteries are replaced. When the test is conducted, all icons will appear on the screen and then disappear if the batteries are properly fitted.
When the display become weak, this display no power in the battery, please change the battery.
2
5
4
3
1
1 .Emergency switch
2 .Power lamp
After open the unit, this lamp bright when the unite enter health running, the lamp change from orange to blue lamp.
3 .Timing lamp
When the unit been setting Timing running, this lamp bright.
4 .Running lamp
When the compressor working, this lamp bright.
5 .Indoor temp. sensor
Test the room temperature.
R
8
Important Points of Safety
The following four important points of safety and suggestions should be paid great attention:
!
Warning: Misuse may cause fatal result such as death or serious injury etc.
!
Attention: Misuse may cause human injury or damage of machine, in some case
fatal results.
: Content marked with this ìforbiddenî sign should be absolutely forbid-
den, otherwise may cause damage of machine and human injury of the
user.
!
: Content marked with this ìcompulsoryî sign should be executed comp-
ulsively, otherwise may cause damage of machine and human injury of
the user.
Comply with the following important points of safety.
Put these important points of attention and suggestions nearby and convenient for reference in need.
Hand over this instruction manual to new user if you resell this machine.
!
Entrusted Installation
Installation of the machine should be entrusted to certified person of after service. Unauthorized installation may cause water leakage, electric shock or fire hazard for improper operation.
!
To prevent leakage of refrigerant, let certified person of after service do it.
Leakage of refrigerant over certain consistence may result in shortage of oxygen. Enough precautions
MUST
be done to avoid oxygen shortage in case of refrigerant leaking if the room where the airconditioner is installed is small.
!
Warning
The power supply must be fitted with earth line to ensure valid earthing of the air-conditioner. No or incomplete earthing connection may cause the risk of electric shock.
!
Test run
After indoor units are installed,all cassettes hinded models should be tested.when the units are confirmed to be normal,other fitments can be installed.
!
9
Important Points of Safety
!
Warning
Avoid your body being blown
directly by cold wind for long
period, otherwise your health
may be affected.
Donít extend your fingers or
any other article into the inlet
or outlet during operation of
the machine for touching re-
volving fans may cause human
injury or damage of machine.
If something abnormal (e.g.: burnt
smell etc.) occurs, stop running the
machine, shut down the manual
power switch and contact after
service. Continuous operation in
disorder may cause fire hazard or
electric shock etc.
!
When you have to disassemble
and reinstall the machine, entrust
it to after service. Improper inst-
allation may cause fire hazard,
electric shock or damage of ma-
chine.
!
Unauthorized alteration or repair
work is strictly forbidden. Impr-
oper alteration or maintenance
may cause fire hazard, electric
shock or water leakage. Repair
work should be entrusted to cert-
ified person of after service.
!
Attention
Ensure the drainage hose work
normally during installation.
Improper installation of drainage
can cause water leakage and
damp articles.
!
DO NOT install the machine in
place where flammable gas
releases easily to avoid fire
hazard.
Ensure electric leakage breaker
being installed. Electric leakage
breaker MUST be installed,
otherwise electric shock may be
caused.
!
If the power supply cord is
damaged, call a certified
electrician of the manufacturer
or other maintenance department
to replace it.
1 0
Important Points of Safety
!
Attention
* Ensure ventilation of the room
if the machine is used with
burning facilities. Deficient
ventilation can cause oxygen
shortage.
* DONíT lay any burning facilities
in place where winds produced by
the machine can reach. Incomplete
combustion of burning facility may
be caused otherwise.
* Check whether installation
bench of the machine is
damaged after a long period
of use. Machine on damaged
bench may fall down and cause
human injury or other damage.
* DONíT clean the machine with
water. Electric shock may occur
otherwise.
* In place where winds produced
by the machine can reach, donít
lay any animals or plants which
may be hurt otherwise.
* DONíT put flammable spray
articles nearby or spray them to
the machine. Fire hazard may
occur otherwise.
* Donít put vases containing water
or other else on the unit assembly.
Otherwise, the machine may be
immersed internally and result in
bad electric insulation causing
electric shock.
* DONíT operate switch with wet
hand. Electric shock may occur
otherwise.
* The is machine CANNOT be
used for the purpose of prese-
rving food, animals, plants,
precision instruments and
artwork etc., which may be
destroyed otherwise.
* Stop operation and shut down
manual power switch before
cleaning and maintenance.
* The power supply MUST be of
rated voltage and connected with
special electrical supply circuit.
* DONíT replace fuse with ma-
terial other than fuse of proper
capacity. Replacing fuse with
metal wire or copper etc. can
cause fire hazard or other faults.
11
Operating Instructions
Recommendations
Use COOL in summer.
Use HEAT in winter.
Use DRY in spring,autumn and in damp climate.
AUTO RUN, COOL,HEAT and DRY operation
AUTO
SET
AM
*
MODE FAN SWING
2
TEMP
CLOCK
3
TIMER
SET
SLEEP
FILTER RESET
RESET
ON/OFF
5
1
SWING
MODE
5
T E M P
ON
OFF
FAN
SLEEP
HEALTH FRESH
CLOCK
TIMER
SET
RESET
LIGHT LOCK
(1) Unit start
Press ON/OFF button, unit starts.
Previous operation status appears on display
(Not Timer setting). Power indicator lights up.
(2) Select operation mode
Press MODE button. For each press, operation mode changes as follows:
Press FAN button. For each press, fan speed changes as follows:
Wire controller
LOW
Remote controller
MID HIGH
AUTO
AUTO
A
U
T
O
LOW
MID HIGH
AUTO
AUTO COOL DRY HEAT FAN
Unit will run in operation mode displayed on LCD.
Stop display at your desired mode.
(3) Select temp. setting
Press TEMP button
Every time the button is pressed, temp. setting increases 1 C.
If button is kept depressed, temp.setting will increase quickly.
Every time the button is pressed, temp. setting decreases 1 C.
If button is kept depressed, temp. setting will decrease quickly.
Unit will start running to reach the temp. setting on LCD.
(4) Fan speed selection
Unit runs at the speed displayed on LCD.In HEAT mode, warm air will blow out after a short period of time due to cold-draft prevention function.
In DRY mode, when room temp. becomes 2 C higher than temp. setting, unit will run intermittently at
LOW speed regardless of FAN setting.
(5) Unit stop
Press ON/OFF button.
Only time and room temp remains on LCD.
All indicators go out.
Vertical flap closes automatically.
Hints
Wire controller can memorize each operation status.
When starting it next time, just press ON/OFF button and unit will run in previous status.
Auto running: During the Auto running mode, air conditioning running and can auto-select the cooling, heating, fan mode according to the room temperature.
Fan running: The AC only have air supply running no cooling and heating running at the condition, AC can't have auto air supply running, and can't display the setting temperature value on the LCD.
During the heating running, after start the AC, in order to prevent cooled air, AC can stop for a while before send heat air.
During the dehumification running, when the room temp. setting temp. , not setting condition according to the air speed.
1 2
Operating Instructions
TIMER Operation
MODE FAN SWING
TEMP HEALTH
SET
ON
AM
SET
AM
*
CLOCK
2
TIMER SLEEP
4
FILTER RESET
3
RESET
SWING
MODE
T E M P
ON
OFF
FAN
1
SLEEP
HEALTH FRESH
ON/OFF
1
SET CLOCK
2
TIMER
4
3
LIGHT
LOCK
RESET
Set Clock correctly before starting Timer operation.
You can let unit start or stop automatically at following time: Before you wake up in the morning, or get back from outside or after you
fall asleep at night.
TIMER ON/OFF
(1)After unit start, select your desired operation mode.
Operation mode will be displayed on LCD.
Power indicator lights up.
(2)TIMER mode selection
Press TIMER button to change TIMER mode.
Every time the button is pressed, display changes as follows:
ON OFF
ON
OFF blank
Select your desired TIMER mode (ON or OFF)
To cancel TIMER mode
(3)Timer setting
Press TIME button.
Every time the button is pressed, time increases 10min.
If button is kept depressed, time will change quickly.
Every time the button is pressed, time decreases 10min.
If button is kept depressed, time will change quickly.
Time will be shown on LCD. It can be adjusted within
24hours.
(4)Confirming your setting
After setting correct time, press SET button to confirm
"ON" or "OFF" stops flashing.
Time displayed: Unit starts or stops at x hour x min (ON or OFF).
Timer mode indicator lights up.
Just press TIMER button several times until TIMER mode disappears.
According to the seting timing open, close sequence, can realize first open then colse the unit or first close then open the unit.
Hints:
Wire controller possesses memory function, when use TIMER mode next time, just press SET button after mode selecting if timer setting is the same as previous one.
Wire remote controller or remote controller can memorize each working condition. Next time open the unit, only need to press the ON/OFF key, the AC can work according to last time working condition.(Timing, Sleeping and Swing mode not included.)
From Timing close to timing open, can setting sleep mode.
Please close health function first before setting Timer, then you can do the TIMER ON operation.Please do not use the health function when in TIMER ON state.
1 3
Operating Instructions
TIMER Operation
MODE FAN SWING
SET
ON
PM
OFF
AM
*
CLOCK
2
TIMER
TEMP
HEALTH
3
SET
SLEEP
6
4
FILTER RESET 5
RESET
ON/OFF
1
SWING
MODE
T E M P
ON
OFF
1
FAN
SLEEP
2
HEALTH FRESH
3
CLOCK SET
TIMER
6
RESET
4
5
LIGHT LOCK
TIMER ON-OFF
(1)After unit start, select your desired operation mode
Operation mode will be displayed on LCD.
Power indicator lights up.
(2) Press TIMER button to change TIMER mode
Every time the button is pressed, display changes as follows:
ON OFF
ON
OFF blank
(4) Time confirming for TIMER ON
After time setting, press TIMER button to confirm.
"ON" stops blinking, While "OFF" starts blinking.
Time displayed: Unit starts at Xhour X min.
(3)Time setting for TIMER ON
Press TIME button.
Every time the button is pressed, time increases 10min.
If button is kept depressed, time will change quickly.
Every time the button is pressed, time decreases 10min.
If button is kept depressed, time will change quickly.
Time will be shown on LCD.
It can be adjusted within 24hours.
AM refers to morning and PM to afternoon.
(5)Time setting for TIMER OFF
Follow the same procedures in "Time setting for
TIMER ON".
(6)Time confirming for TIMER OFF
After time setting, press SET button to confirm
"OFF" stops flashing.
Time displayed: Unit stops at X hour X min.
To cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.
According to the Time setting sequence of TIMER ON or TIMER OFF, either Start-Stop or Stop-Start can be achieved.
1 4
Operating Instructions
Note: Before using this function, must adjust the clock, or the sleep function will be disordered.
Comfortable Sleep
At night, before going to bed you can press down the SLEEP button on the controller and the airconditioner will run by the comfortable sleeping mode to make you sleep more comfortable.
SET
AM
OFF
AM
*
MODE FAN
SWING
TEMP HEALTH
CLOCK
TIMER
SET
SLEEP
FILTER RESET
RESET
ON/OFF
Sleep Function
SWING
MODE
T E M P
ON
OFF
FAN
SLEEP
HEALTH FRESH
SET CLOCK
TIMER
RESET
LIGHT LOCK
In cooling, dehumidifying mode
hour the temp. rises 1 and then run continuously for another 6hrs' and then close. The actual temp.
is higher than the setting one which is to prevent from being too cool to your sleep.
In heating mode
close after 3hrs' continuous operation. The actral temperature is lower than the setting one which is to prevent from being too hot to your sleep.
Note:
In AUTO mode, unit will run in SLEEP function according to the operation mode.
After setting SLEEP function, it is forbidden to calibrate clock.
If the set sleep-time does not reach 8 hours, the unit will stop operation automatically after set time is complete.
Set "TIMER-OFF" function first, then set SLEEP, and the sleep-set is performance; set TIMER-
ON function first, the sleep function can only be set before TIMER-ON; if set theSLEEP function first, the TIMER function can not be set.
After setting sleep function, not allowed to adjust the clock. Can't use the remote controller operate the AC. If so, please cancel the sleep function first.
After setting sleep function, can't set the timing function.
SETTING T
1 hr
1 hr decrease 2
C decreases 2 C about 3 hrs
3 hrs
SHUT DOWN increase1
C
SLEEP RUN BEGINS
Heat mode
SLEEP RUN STOPS
SLEEP RUN BEGINS about 6 hrs
SLEEP RUN STOPS
1 hr
1 hr increase 1 increase 1
C
C
SETTING T
SHUT DOWN
Cooling mode
1 5
Operating Instructions
SET
AM
OFF
AM
*
MODE FAN SWING
TEMP HEALTH
CLOCK
TIMER
SET
SLEEP
FILTER RESET
RESET
ON/OFF
SWING
MODE
T E M P
ON
OFF
FAN
SLEEP
HEALTH FRESH
CLOCK
TIMER
SET
RESET
LIGHT LOCK
Health Function
1.How to use the health function (only for units
with this function)
After set the right function mode, press health button,
remote controller or wire controller displays ì î,
oxygen pump or negative ion generator starts up to apply
oxygen or negative ion to indoor unit. Press the button
again,the sign ì î disappeared and negative ion generator
stops working. After all health function of the indoor unit
being fully canceled, oxygen pump stopped.
CAUTION: oxygen pump is automatically stopped, if press health button just then, oxygen pump could not start up. But if the air
On the "Health" mode, if you want to setting timing open mode, should close the health first: On the timing open mode, please don't use health function.
conditioner has the negative ion function simultaneous, when press the health button, negative ion function could still be operated. When the temperature of the outdoor unit to oxygen-make function.
Power Failure Compensation (to be applied for a necessary situation) :
After the power failure compensation is set, if power failure suddenly occurs while the air conditioner is working, it will resume the previous working state when the power is supplied again.
Setting Method:
When the remote controller is on (excluding timer mode and fan mode), press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 4 times, the air conditioner will enter the state of power failure compensation.
Cancel Method:
Press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 2 timer, the power failure compensation mode will be cancelled.
Notes:
When a power failure suddenly occurs during the air conditioner is working after the power failure compensation is set, if the air conditioner will not be used for a long time, please cut off the power supply to prevent its operation from being resumed after the power is supplied again, or press the "Switch On/Off" button after the power comes again.If the controller no sleep key ,use the "swing" key instead the "sleeping" on setting the auto restart function.
Concerning MRV Auto Restart function for H-MRV models
Haier Auto Restart function when the unit power drops down suddenly, the unit microprocessor will store the previous working condition and when the power is on again, the unit will run as this memory.
Auto Restart function is designed basically on the MRV whole system, but it is suitable for each indoor unit individually.
If some of indoor units power cut down, but the outdoor unit and the other indoor units still work, maybe problems will happen such as freezing at cooling mode and overload protection at heating mode on those indoor units without power.
Reason
When one or some indoor units power drops down and the other indoor units are still work, the indoor units without the power, will keep the previous working condition before the power is off. And expansion valve keeps open at a kind of opening rate condition as the previous requirement, so there is refrigerant flowing in the exchanger, but the indoor fan stops working. If the units work at cooling mode, the indoor units without the power will maybe make freezing. If the unit works at heating mode, maybe the outdoor unit compressor will stop because of the pressure or temperature protection. This is our design basically on Auto Restart function currently.
Haier, Herewith, solemnly informs our customers, installers, distributors, etc.
when making installation, please make sure when the power is shut down whether artificially or accidentally, the whole system including outdoor unit and all the indoor units must be off. If you do not make the installation as our indication, Haier will not be responsible for any problem resulting from this.
User Caution
About the remote cnotrol operation, above only take wired remote controller and remote controller (1) as a example about the remote controller (2) and remote receiver use method, it is the same remote controller (1) , please use refer to above method.
No sleep function when use remote (2) and remote receiver.
1 6
Trouble Shooting
The following cases are not troubles.
Water flow sound is heard.
"Hua-Hua
"
A sound of "Pi-Pa " is generated.
Smells are given off.
During operation , mist or steam are blown out.
During operation
,
the air conditioner may sometimes exhibit a sound of "clatter
"
or
"rumble
"
. This is the common sound of refrigerant flow but not a trouble.
This is caused by the thermal expansion or cold shrinkage of plastics.
Sometimes there are smells in the air flow from the indoor unit. This is caused by the smell of cigarettes or paint coatings inside the unit.
During COOL or DRY operation, the unit may blow out a thin mist. This is the condensate water mist caused by sudden cooling of the indoor air blown out from the indoor unit.
During COOL operation changes to FAN mode.
, it automatically
The system couldnt be re-started immediately
after turning off.The unit can
' t start?
In order to prevent frost accumulation on the heat exchanger in the indoor unit
, sometimes it will automatically transfers to FAN mode, but soon will return to
COOL mode.
This is due to the systems self-protection function , which prevents it from restarting in 3 min after stops.
Please wait for 3 min.
1 8
Trouble Shooting
During DRY operation, there is no air sent out or fan speed cant be changed.
In HEAT mode , the outdoor unit generates water or steam.
This occurs during removal of the frost
(in defrosting operation) on the radiator of outdoor unit.
In HEAT mode , the indoor fan still keeps running even the unit operation stops.
Defrost operation
After the unit stops , the indoor fan will continue to run for a while to eliminate
residual heat.
Before asking for after-service to an authorized service center, please check your air conditioner for the following items
The system couldnt start
Is power on/off switched on?
Is the power supply line normal?
Power failure?
ON
OFF
Is current leakage breaker triggered?
The power on/off switch is not at position of "ON
"
.
Please do immediately cut off power supply and contact the authorized service center.
1 8
When Fault Occurs
Poor cooling or heating
Is the operation controller adjusted as required?
Are there any obstructs before the air inlet or outlet?
Is there any door or window left open?
Is there any other heat source in the room?
Poor cooling
Is there any direct sunlight into the room?
Are there too many people in the room?
If , after the above checks and the corresponding corrective actions , the system remains abnormal operation , or the following facts appear, please turn off the air conditioner and then contact the local authorized service center.
Frequent open of fuse or breaker.
There is water leakage during COOL or DRY operation.
The operation is abnormal or abnormal sound is heard.
1 9
Notice to Users
Notice to users
To ensure proper operation of the system
, the user shall follow this instruction manual to install the unit.
When handling the air conditioner
, please be care not to scratch the case surface.
This instruction manual describes the installation method aided with the installation tools specified by manufacturer .
The maximum length of connection pipe is 50 m , and the maximum difference between levels of indoor unit and outdoor unit shall be 30 m.
Please keep the installation instruction manual well for reference in maintenance or changing installation position.
After installed
,
please follow the operational instruction manual to use the air conditioner properly.
Information about application
Adjust your desired air flow direction Avoid direct sunlight and gas flow
Keep appropriate room temperature
Too cool or too warm wont benefit to your health , but causes an increased energy consumption.
Effectively use the timer Using
TIMER mode you can enjoy a comfortable room temperature when wake up or come back home.
Maximum temperature
Caution: After installation
,
please confirm no refrigerant leaks.
2 0
Installation Precautions
Before installing, do read this "Safety precautions" carefully to guarantee the proper installation.
wrong installation occur, it is very possible death and severe injury and other serious accidents will happen. For those items are listed in" Warning"
!
Note" part can also cause serious accidents. Above all, both the two parts are very important contents related to safety, so they must be obeyed.
After finishing the installation work, do test run to verify everything is normal. After that please explain the using and maintenance methods to the user. Additionally, give this installation manual and operation manual to the user and ask them to keep it properly.
!
Warning
The distributing shop, where you bought the air conditioner, or the specified shops shall do the installation work. If you do the installation work by yourself, the improper installation will cause
water leakage, electric shock fire and other accidents.
The installation work shall be in line with what the installation manual specified. If installation is not proper, water leakage, electric shock, fire and other accidents will occur.
Install the air conditioner to a place where can definitely stand its weight. Places not firm enough will cause drop down of unit resulting in body hurt.
The installation work shall be preventive to typhoon and earthquake. If the installation work is not met with the requirements, overturn of the unit will occur resulting in accidents.
The wiring work shall be done by a qualified person and referred to the " technical standard of electric equipment" , "indoor wiring regulation" and what the manual specified. Do use special circuit. If the capacity of the circuit is not enough or bad work, electric shock, fire and other
accidents will happen.
Using the specified cable to do wiring work and connecting firmly and properly. Fix the connecting part of the terminals to prevent it from the external force.Improper connection and fixing will cause
heating and fire etc. accidents.
Wiring shall be kept in correct shape avoiding extrusion. After installation, the electric box cover and the external panel shall not nip the wire. Improper installation will cause heating and fire etc.
accidents.
When setting or moving the air conditioner do not let the air and things alike get into the refrigeration system except the specified refrigerant (R22). If air and other things enter, abnormal high pressure will occur, which easily cause break and body injuries etc. Accidents.
When installing, do use the accessories or specified parts. If not using the parts specified by our company, water leakage, electric shock, fire and refrigerant leakage will occur.
Do not lead the drainpipe to drain where the sulfur gas may be involved. Otherwise, the poisonous gas will enter into the indoor.
During installation, if refrigerant leakage occurs, do the ventilation work immediately. As soon as the refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas enters into room and meet the air blowing heater, heater or stove etc. fire source, the poisonous gas may be produced.
After installation, confirm there is no leakage of refrigerant.
Do not install the unit in a place where the combustible gas may be leaked. In any case the combustible gas leaks and accumulated around the unit, fire accident will occur.
Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose of heat preservation. If the heat insulation measure is not sufficient, water generated by condensing dew will drip leading to wet the floor and indoor articles.
!
Note
Do grounding work.Do not connect the grounding wire to gas pipe,tap,lighting rod or telephone line.Improper grounding will cause electric shock.
After electric installation,power on them to do electric leakage test.
2 1
Installation Precautions
! Attention
This description does not address to all possible cases. For new requirement and query, please consult the regional sales center of Haier Air Conditioner General Co., Ltd.
! Warning
This instruction manual must be read carefully before beginning of installation, improper installation may cause accidents and thus bring about machine damage and personal casualty.
Installing tools
1. Screw driver 6. Pipe cutter 10. Leakage detector or soap water
2. Hacksaw 7. Pipe expander 11. Measuring tape
3. Driller of 70mm diameter 8. Knife 12. Scraper
4. Spanner (diameter 17, 27mm) 9. Pinchers 13. Refrigeration oil
5. Spanner (14, 17, 19, 27mm)
Electrical requirements
The power supply shall be connected from the outdoor side. (For models with electric-aided heating function, the power supply to the indoor unit shall be connected at the indoor side
The power cord size is 3 G(1.0-1.5)mm
2
, type of H05RN-F).
A separate power circuit shall be supplied and connected by a qualified electrician according to the wiring rules specified in the corresponding national standard.
A current leakage breaker must be installed.
The connection method of power cord is " Y " type. If the power flexible cord is damaged, it shall be replaced by the manufacturer or its service department or similar qualified technician so as to avoid risks.
Power cord plug: L should be connected to the live wire, N should be connected to the neutral wire and to the ground wire.
Connection wire size: 3 G (1.0-1.5) mm
2
, type of H05RN-F.
Signal transmission wire size:H05RN-F 2 x (0.75-1.5) mm
2
(shielded wire).
Power cord, connection wire and signal wire shall be provided by the user.
Indoor unit
1. Select suitable places the outlet air can be sent to the
entire room, and convenient to lay out the connection
pipe, connection wire and the drainage pipe to outdoor.
2. The ceiling structure must be strong enough to support
the unit weight.
3. The connecting pipe, drain pipe and connection wire
shall be able to go though the building wall to connect
between the indoor and outdoor units.
Fig 1
4. The connecting pipe between the indoor and outdoor
units as well as the drain pipe shall be as short as possible. (See Figure 1)
5. If its necessary to adjust the filling amount of the refrigerant, please refer to the installation
manual attached with the outdoor unit.
6. The connecting flange should be provided by the user himself.
7. The indoor unit have 2 drainage outlet, one outlet be jamedwith rubber cap, during installation
only use another outlet (In/Out liquid pipe side). When necessary, use the two outlet at the
same time.
8. Not place the TV., equipment, facility, piano etc, expensive goods below the AC, prevent the
water dropping down from the AC and lead to damage to the goods.
22
Installation Procedure
After selecting the unit installation location, proceed the following steps:
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube
purchased locally. The wall hole shall be with a outward down slope of at least 1/100. (See
Figure 2)
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position.
Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. If the base is not firm, it will cause
noise, vibration or leakage (see Figure 6).
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go
through the wall hole easily.
Figure showing installation dimensions: (unit:mm)
Model a
AE092FCAKA 615
AE122FCAKA
AE142FCAKA
AE182FCAKA
AE212FCAKA
770
990 b
648
804
1024 c
452
452
452 d
225
225
225 e
55
55
55 f
125
125
125 g
225
225 i
100
100
225 100 c b
i e f d g a
Fig 2
223
223
500
1249
AE072FCAKA
AE242FCAKA
Notes
1.For electrical heating unit, the air outlet not allowed directly connecting with canvas
etc. easy catching fire goods.
2.This series' indoor unit are all middle static pressure(30 Pa external static pressure ).
3.An access port must be provided during installation of indoor unit for maintenance.
23
Installation Procedure
Installation of indoor unit
When installing the ceiling concealed type indoor unit, a specially designed return air bellows shall be installed, as shown in Figure 3, Figure 4.
Figure 3
Installing building roof
*0.5m or*5m
A
Ceiling
Air supply
Unit
Air outlet duct
Detail A
Figure 4
Air outlet grille
Return air
Return air bellows
Return air bellows
Air supply
No obstacles within 1 m
Unit
Return air
Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to seal the interface closely. Recommend the distance between the air return duct and the wall is more than
150mm.
The distance between air duct outlet and air conditioner outlet is according to the length of actually installed air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air duct is showed below, when connect to short air duct, using low static terminal (terminal color is write), the distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct, using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet could be within 5m at this point.
Figure 5
joint of air diffuser sling dog drain piping air return duct air return shutter
transition
air duct air outlet duct air diffuser
Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover the drain piping of condensed water to keep warmth.
As figure shown, suspend and install the unit.
M8 broad foundation bolt
Figure 6
M8 suspension screw
M8 broad lock ring
M8 nut
Unit
24
Figure 5
Installation Procedure
Installation of indoor unit
Installation for air duct of indoor unit
1
. Installation for air supply duct
This type of unit uses circular air duct with its caliber of 180mm.
An additional transitive air duct is necessary for the circular air duct to connect to the air
supply inlet. It should be also connected to its respective air diffuser separately. See
Fig.1. Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so
as to meet a demand of the air conditioner in the room.
Indoor unit
flexible joint or static pressure box
transitive air duct circular air duct joint of air diffuser
air diffuser
Fig1: Duct connected
2
. Installation for air return duct
Use rivets to connect the air return duct to the air return inlet of the indoor unit. The
other end connects to the air return shutter. as shown in Fig.2.
air return shutter air return duct indoor unit rivet
Fig2: Duct return connected
3
. Air duct insulation
Insulation layer is needed for air supply and return duct. First, paste a glue nail to the
air duct, and then attach the insulation cotton that has a tinfoil layer and use the glue
nail cover to fix. Finally, seal the air duct interface with tinfoil adhesive tape closely.
as shown in Fig3.
galvanized board insulating fabric
tinfoil glue nail glue nail cover adhesive tape
Fig3
25
Installation Procedure
Installation of indoor unit
Installing the suspension screw:
Use M8 or M10 suspension screws (4, prepared in the field) (when the suspension screw height exceeds 0.9 m, M10 size is the only choice). These screws shall be installed as follows with space adapting to air conditioner overall dimensions according to the original building structures.
Wooden structure
A square wood shall be supported by the beams and then set the suspension screws.
Square wood
Suspension screw
New concrete slab
To set with embedded parts, foundation bolts etc.
Beam
Guide plate embedded part
Iron reinforcement
Foundation bolt
Pipe suspension foundation bolt Knife embedded part
Original concrete slab
Use hole hinge, hole plunger or hole bolt.
Steel reinforcement structure
Use steel angle or new support steel angle directly.
Hanging bolt
Suspension screw
Support steel angle
Hanging of the indoor unit l
Fasten the nut on the suspension screw and then hang the suspension screw in the T
slot of the suspension part of the unit.
l
Aided with a level meter, adjust level of the unit within 5 mm.
26
Installation Procedure
1. Remove upper cover of wire controller
Remove upper part of wire controller by press.
PCB is mounted on lower part of wire controller, be careful not to damage it.
Installation of remote controller
Upper cover of wire controller
2. Install the wired remote controller
Please drill two holes on the wall according to the back cover screw hole position of the wire remote
controller, then strike the wood block to the holes respectively, then align the 2 screw hole of the wire controller back cover to the wood block, fasten the wire reote controller to the wall use wood screws.
3. Switch setting
The switchs setting as follows:1.ON 2.OFF 3.ON 4.OFF
Note
Try as far as possible a flat surface for installation.
Don't use excessive force when tightening screws, or lower part might got deformed.
4. Connecting method as the following chart
No Symbol
1 A
2 B colour
White or Green
Red
3 C
Yellow
4 D contents
12V
Gnd
COM
Switch button
Lower cover of wire controller
Screw hole
Back cover of the wire controller
Use shielede wires for telecommunication between wire controller and indoor unit; indoor unit and outdoor unit. Ground the shield on one side.
Otherwise misoperation because of noise may occur.
Signal wire is self-provided by user.
ground
Shielded wire
5. Replace the upper cover of wire controller
Be careful not to hold down the wiring.
Hint
1. Power supply switch and signal wire should be prepaired by the user.
2. Don't touch PCB with hand.
27
Installation Procedure
Installating the Reciever and MP3 equipment MP3
Installation of receive display
Because of the temperature sensitive device, do not install the receive display at straight sunlight place, either in front of air outlet grill, for it is effected greatly from cool air and heat air, the receive display is at least 20mm distance to the air outlet grill.
Since there is light sensitive device which receives wireless remote signal, so do not installed behind the window curtain or other obstacles, in order not to obstruct the signal.
Must fix the remote control wire far from strong electricity (such as the wiring of electric light, air conditioner, etc.) and weak electricity (such as the wiring of telephone, interphone, etc.).
1.Fix the receive display with screws on the selected place
2.Place the panel onto the fixed frame, pay attention that the four claws must be placed into the corresponding four poles on the frame
Connecting wiring method of receiver :
Refer the indoor unit wiring diagram .
safety cautions see the electrical wiring part .
28
Installation Procedure
Drain pipe
! Caution
In order to drain water normally, the drain pipe shall be processed as specified in
the installation manual and shall be thermal insulated to avoid dew generation.
Improper hose connection may cause indoor water leakage.
Requirements
The indoor drain pipe shall be thermal insulated.
The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation.
The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be of S type elbow, otherwise abnormal sound will be produced.
The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5 ñ 2m to prevent wavy form.
Central piping shall be laid out according to the following figure.
Take care not to apply external force onto the drain pipe connection part.
1.5m~2m
Support
Insulation
(supplied by the user)
Down slope above 1/100
S type elbow
To the largest (app. 10cm)
Wall
VP30
Down slope above 1/100
Pipe and insulation material
Outside
Slant
Drain pipe (supplied by the user)
Pipe
Rigid PVC pipe VP31.5mm (internal diameter)
Insulation
Foamed PE with thickness above 7mm
Hose
Drain pipe size: ÿ19.05mm
2
(3/4") PVC pipe
The hose is used for adjusting the off-center and angle of the rigid PVC pipe.
Directly stretch the hose to install without making any deformation.
The soft end of the hose must be fastened with a hose clamp.
Please apply the hose on horizontal part
Hose
sulation treatment:
Hose clamp
Wrap the hose and its clamp until to the
indoor unit without any clearance with
insulating material, as shown in the figure.
Drain confirmation
Subsidiary insulation
Insulation
Rigid PVC pipe
During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.
29
Installation Procedure
R
efrigerant piping
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.
Pipe material and size
Pipe material
Model
Pipe size
(mm)
Phosphorus deoxidized copper seamless pipe (TP
2
M) for air conditioner
AE072FCAKA
AE092FCAKA
AE122FCAKA
AE142FCAKA
AE182FCAKA
AE212FCAKA
AE242FCAKA
Gas side
ÿ9.52
ÿ12.70
ÿ15.88
Liquid side
ÿ6.35
ÿ6.35
ÿ9.52
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant
A
Requirement
Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.
Pipe expander
Connection of refrigerant pipe
Conduct flared connection work to connect all refrigerant pipes.
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
Pipe expansion dimensions as follows:
Pipe diameter
ÿ
Size A (mm)
6.35 mm (1/4
"
) 0.8 ~ 1.5
9.52 mm (3/8
"
) 1.0 ~ 1.8
12.7 mm (1/2
"
) 1.2 ~ 2.0
15.88 mm (5/8
"
) 1.4 ~2.2
1. Pipe cutting 2. Removing burrs
3.Insertion nut 4. Pipe expansion
Correct
Incorrect
Slope Damage Bur Partial Overlong
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe
O.D.(mm)
ÿ6.35
ÿ9.52
ÿ12.70
ÿ15.88
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
Increased installing torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
30
Double-spanner operation
Installation Procedure
R
efrigerant piping
Vacuum pumping
With a vacuum pump, create vacuum from the stop valve of the outdoor unit.
l
Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all valves
Open all the valves on the outdoor unit.
Gas leakage detection
Check with a leakage detector or soap water that if there is gas leakage at the pipe connections and bonnets.
Insulation treatment
Conduct insulation treatment on both the gas side and liquid side of pipes respectively.
During cooling operation, both the liquid and gas sides are cold and thus shall be insulated
so as to avoid dew generation.
l
The insulating material at gas side shall be resistant to a temperature above 120
*
.
l
The indoor unit pipe connection part shall be insulated.
The notch upward (Attached detail view)
Indoor unit
Field piping side
Subsidiary insulation tube
31
Installation Procedure
Electric wiring
! Warning
!
The electric wiring work shall be conducted by qualified electricians according to the installation instructions. A separate power circuit shall be used. Insufficient power cord amperage or improper wiring will cause danger of electric shock or fire.
During wiring connection, the power cord shall be of the specified cable and reliably fastened so that external forces applied to the cable wouldnt transfer to the terminals. Improper connection or fastening will cause danger of heating, fire etc.The power cord must be fitted with a grounding wire.
Grounding shall be made as specified. Unreliable grounding will cause electric shock. The grounding wire shall not be connected to the gas pipeline, water pipeline, thunder arrestor and telephone wire
! Caution
!
A current leakage breaker shall be installed, otherwise it electric shock would happen easily.
If the power cord is damaged, it must be replaced by the manufacturer or its service center or similar personnel to avoid risks. The power supply to the indoor unit shall be laid in complying with the operational instruction manual.
The electric wiring shall avoid contacting with the high temperature part of the piping so as to prevent the cable insulation melts and cause dangers.
After connected on the terminal block, the wires shall be bent to U form and then fastened with wire clip.
The control wiring and refrigerant piping may be laid and fastened together.
Before completion of vacuum pumping of the refrigerant pipe system, do not electrify the indoor unit.
The power cord of the indoor unit and connection wiring between indoor and outdoor units shall be laid out according to the operational instruction manual of the indoor unit.
The connection of the power cord shall comply with the local regulations.
The power supply wiring connection should meet the local regulation.
Wiring connection method : (the wiring diagram is attached inside the machine)
1) Ring terminal connection method
If there is a ring at the end of the connection wire, the wire connection method is as shown in the right figure. Remove the terminal screw and insert it through the ring at the connection wire end, then connect to the terminal board and fasten the screw.
2) Straight terminal connection method
Connection method for ring terminal
If there isnt a ring at the end of the connection wire, the connection method shall be: loosen the terminal screw, insert the connection wire end completely into the terminal board and fasten the screw.
Pull the connection wire outwards slightly to confirm it is clamped tightly.
3) Clamping method of the connection wire
After wire connection is finished, the connection wire must be pressed tightly with wire clips, which shall apply to the outer sheath of the connection wire.
32
Installation Procedure
Electric wiring
Wire connection for built-in indoor unit
Insert from outside the connection wire and signal transmission wire through the wall hole with pipeline already arranged.
Pull out the front ends of connection wire and signal wire and make a circle on the signal wire.
Connect the connection wire according to the connection method and indoor and outdoor wiring diagram.
Pull the connecting conductor outwards slightly to confirm it is clamped tightly.
Connect the plug for connecting the signal wire with the plug of the signal wire connected from the indoor unit.
After wire connection is finished, install wire clips using the same method for connection wire clamping.
Note: When connecting the indoor unit and the outdoor unit, please do connect the wires with the same color terminals.
Notes:
Before connecting the conductors between indoor unit and outdoor unit, check for the number on the indoor and outdoor units connecting terminals. Connect the terminals with the same color and number with a wire.
Wrong connection would damage the controller of the air conditioner or the machine couldnt operate.
Do not connect the connection wire and signal wire with the same cable. They shall be connected respectively to ensure system normal operation.
Field setting
Field setting the unit number
In order to realize central control of the MRV air conditioning system, its necessary to set
the indoor unit number (control address).
Indoor unit number setting
Indoor unit number setting switch and confirmation of the settings.
There is a 4-position dial switch for setting the indoor unit number on the computer board of the indoor unit.
Setting way is as follows:
Before connecting the power supply, please set the indoor unit number manually according to the following table
Matrix of the dial switch and indoor unit number
Example:
1 0 0
Position 1 Position 2 Position 3 Representing unit number
0
1
0
1
0
1
0
0
1
1
0
0
0
0
0
0
1
1
1
2
3
4
5
6
Pos.1 Pos.
2
Pos.
3
Pos.
4
Setting for No. 2 indoor unit
Disabled
: 0
: 1
33
Malfunction
Indoor unit malfunction display code
Indoor unit malfunction
Float switch or water motor abnormal
Outdoor unit abnormal
Setting running mode is different with outdoor running mode
Liquid temperature sensor is abnormal
Gas temperature sensor is abnormal
The communication between indoor 846 chip and communication chip is abnormal
The communication with electronic expansion box is abnormal
The communication between the wire remote controller and indoor unit control board is abnormal
The communication between indoor and outdoor unit is abnormal
Water temp. sensor is abnormal
Display code
E0
E1
E2
E3
E4
E5
E7
E8
E9
EB
Outdoor unit malfunction display code
(When the wire remote controller display E1,can check the indoor unit control board
LED1 or the outdoor unit control board LED1 Outdoor unit control board LED
(ALARMA or ALARMB)).
Outdoor unit malfunction
Outdoor unit defrost temp. sensor is abnormal
Outdoor unit environment temp. sensor is abnormal
Outdoor unit suction temp. sensor is abnormal
Outdoor unit discharge temp. sensor is abnormal
Outdoor unit AC over-current protection
Outdoor unit DC voltage is insufficient protection
IPM protection
Outdoor unit EEPROM abnormal
Compressor Discharge temperature overheat protection
The communication between outdoor unit 857 and communication chip is abnormal
Outdoor unit system over-high pressure protection
LED flashing times flashing once flashing twice flashing 3 times flashing 4times flashing 6times flashing 7times flashing 9times flashing 10times flashing 11times flashing 12times flashing 13 times
34
Malfunction
Remote controller Timer and Operation indicator malfunction code
When the unit running, Timer indicator flash stand for indoor unit malfunction operation indicator flashing stand for outdoor unit malfunction
1. Indoor unit malfunction
Timer indicator
Flashing times
Indoor unit malfunction
Flashing once The liquid tube temperature sensor is abnormal
Flashing twice The gas tube temperature sensor is abnormal
Flashing 3 times The environment temperature sensor is abnormal
Flashing 4 times The communication with outdoor unit is abnormal
Flashing 5 times The ommunication with the electronic expansion valve control board is abnormal
6
The communication between indoor 846 and communication chip is abnormal
Flashing 8 times PMV strong electricity board is abnormal
Flashing 10 times Indoor unit PG fan motor is abnormal
Flashing 11 times Indoor unit water overflow or float switch is abnormal
Flashing 12 times Indoor unit EEPROM data is abnormal
Flashing 13 times Indoor unit is overload
Flashing 14 times The communication between indoor unit and wire remote controller is abnormal
2.Outdoor unit malfunction
Operation indicator flashing times
Flashing once
Flashing twice
Flashing 3 times
Flashing 4 times
Flashing 5 times
Flashing 6 times
Flashing 7 times
Flashing 9 times
Flashing 10 times
Flashing 11 times
Flashing 12 times
Flashing 13 times
Flashing 14 times
Flashing 15 times
Outdoor unit Trouble contents
Outdoor unit defrost temp. sensor is abnormal
Outdoor unit environment temp. sensor is abnormal ction temperature sensor is abnormal
Outdoor unit discharging temperature sensor is abnormal
Outdoor unit evapor ating temperature sensor is abnormal
Outdoor unit AC over-current protection
Outdoor unit DC voltage is insufficient protection
IPM protection
Outdoor unit EEPROM is abnormal
Compressor discharging temperature overheat protection
The communication between the 857&communication chip is abnormal
Outdoor unit high pressure protection
High pressure sensor PD is abnormal
Low pressure sensor PS is abnormal
35