Samwha DSP DSP-DVR Manual

Add to My manuals
22 Pages

advertisement

Samwha DSP DSP-DVR Manual | Manualzz
Digital 3 phase Voltage Relay
<DSP-DVR/DVR-M,DM II Meter>
Contents
1. Abstraction
2. Main Features
3. Operation Time
4.Technical Specification
5.Preset Description
6. The order of Rotated Mode
7.PIN Assignment
8.Indication
9.Control Key Operation
10.Over voltage trip time characteristic
11.Trip Indication
12.Rotated Indication
13.Time-Voltage based Trip Output
14.Application Sequence Diagram
15.Dimension
16.Order Form
Digital 3 phase Voltage Relay
<DSP-DVR/DVR-M,DM II meter>
1.Abstraction
Installation
Panel Mounting
Type
Panel Flush
MountingType
Model
Protection
Indication
DSP-DVR
DSP-DVR-M
Panel Mounting Type
*Over Voltage
*Under Voltage
*Phase Loss
*Reverse Phase
*Line/Average Voltage
*Frequency
Panel Flush Mounting Type
2.Main Features
 MCU based control, 8 Pin Type Compact size
Easy Installation
: Panel Mounting Type → DSP-DVR
: Panel Flush Mounting Type → DSP-DVR-M
 Operation based on direct line voltage detection
: Protection : Over/Under voltage, Phase Loss, Reverse Phase, Voltage Unbalance
: Indication : Voltage[Line/Average], Frequency
:Time-Voltage operational characteristic → Definite / Inverse
 Over/Under Voltage Protection
:Rated Line Voltage → 100 ~ 500VAC
:Over Voltage protection Range → within (+) 20% to line voltage
: Under Voltage protection Range → above (–) 20% to line voltage
 Possible to preset operation time for over/under voltage each, repectively
 Perfect check for initial line state
a)”dt”(trip delay time) mode is preset “OFF”
▸Preset “a” in “out” mode
:Main trip output(95-98) is energized (Open → Close ) in case the rated line voltage with normal
forward phase state is sensed initially
: Main trip output(95-98) is trip(Close → Open) within 0.5sec after energizing(Open→Close)
if the initial state is under phase loss
: Main trip output(95-98) is trip(Close → Open) after operational preset time is elapsed from
instant energizing point(Open→Close) as showing a trip cause if the initial line state is under
over/under voltage,reverse phase, voltage unbalance
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
while the normal operation is doing.
▸Preset “b” in “out” mode
:Main trip output(95-98) is not energized (Open → Open ) even if the rated line voltage with
normal forward phase state is sensed initially
: Main trip output(95-98) is trip(Open → Close) within 0.5sec if the initial state is under phase loss
: Main trip output(95-98) is trip(Open →Close) after operational preset time is elapsed as showing
a trip cause if the initial line state is under over/under voltage,reverse phase, voltage unbalance
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
b)”dt”(trip delay time) mode is preset a value(time)
▸Preset “a” in “out” mode
: Main trip output(95-98) is energized (Open → Close ) after “dt” is elapsed in case the rated line
voltage with normal forward phase state is sensed initially
: Main trip output(95-98) is still opened(not trip) even after “dt” is elapsed if the initial state
is under phase loss,also “PL’ is shown
: Main trip output(95-98) is energized (Open → Close) right after “dt” is elapsed if the initial line
state is under over/under voltage, voltage unbalance, and then it is trip(Close → Open) after
operational preset time is elapsed from energizing point(Open→Close) as showing a trip cause
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
while the normal operation is doing.
:”rP” is shown as main trip output(97-98) is still opened(not trip) after operational trip time
(0.5sec) without concerning with “dt” if reverse state is sensed initially
▸Preset “b” in “out” mode
: Main trip output(95-98) is not energized (Open → Open ) in any case
: Main trip output(95-98) is trip (Open → Close) after “dt” is elapsed if the initial state is under
phase loss as “PL’ is shown
:Main trip output(95-98) is trip (Open → Close) right after “dt”is elapsed as showing a trip cause
if the initial line state is under over/under voltage, voltage unbalance
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
:”rP” is shown as main trip output(97-98) is still closed(not trip) after operational trip time
(0.5sec) without concerning with “dt” if reverse state is sensed initially
 Trip cause is shown by characters and/or numbers
: 4 Digit Window/DVR Type
: 5 Digit Window/DVR-M Type
 3 phase line voltage/average voltage and /or frequency is shown ordery in every 3sec
 Stored the information for latest 8 trip event.
 Reset after a trip : auto or manual
 Self-diagnostics to check if this relay is ready to work or not.
3.Operation Time
Over Voltage
*definite :0.2~20sec
*Inverse :1~10 Class
*ovt” mode
Under Voltage
1~20sec : “uvt” mode
Reverse Phase
Within 0.5sec/initial phase state
Phase Loss
0.5~5sec : “PL” mode
Voltage Unbalance
1~10sec :” v-ut” mode
4.Technical Specification
DIV
Line Voltage
Protection range
Description
Line Input:V1,V2,V3
100 ~500VAC,50/60Hz
Over voltage
Under 20% based on the line voltage
Under voltage
Protection delay time(dt)
Over voltage trip delay
time(ovt)
Over 20% based on the line voltage
1~60 sec/definite
*0.2~20 sec/definite
*1~10 Class/inverse
Under voltage trip delay
time(uvt)
Reverse Phase(RP)
Phase Loss(PL)
Voltage unbalance
Voltage
Allowable tolerance
Time
Time preset
1~20 sec/definite
Within 0.5 sec
0.5~5sec/definite
1~10sec
±3%
*t<=2sec:± 0.2sec, t>2sec:±10%
*Reverse phase:+10%
Control power
*AC 85V∼AC260V,50/60Hz (DC90V∼DC370V)
Trip output relay
*DC24V(Optional)
1c(1-SPDT),5A/Resistive
Application
environment
95-96-98
Operation
-25OC∼+70OC
Storage
-40OC∼+80OC
Temperature
Humidity
30∼85% , relative/non-condensing
Insulation Resistence/IEC-60255-5
Case–Circuit: 10Mohm/500VDC
High Voltage Withstand Test/
IEC-60255-5
*Case–Circuit:AC2000V,60Hz,1 min
*Contact-Contact:AC 1000V,60Hz,1 min
Lightning Impulse Voltage Withstand Test/ IEC*Circuit-Ground,Circuit-Circuit: 1.2/50(uS),5KV
60255-5
*Control Circuits:1.2/50(uS), 5KV
1 MHz Burst Immunity Test:IEC 61000- 4-18
2.5KV,Positive/Negative under 2sec
Electrostatic Discharge:IEC-61000-4-2
Air :Level 3, 8KV,
Contact:Level 3, 6KV
Radiated Electromagnetic Field
Disturbance:IEC-61000-4-3
Level 3, 10V/m
Electric Fast Transient Burst :IEC-61000-4-4
Power,trip output:Level 4,4KV
Surge Immunity test:IEC-61000-4-5
trip output :1.2X50uS,2KV(0O,90O, 180O , 270O)
Conducted Disturbence Test
:IEC-61000-4-6
10V, Level 3
Screw Torque
Max0.6N.m
Consuming power
4W Max
5.Preset description
▶ Main Mode
Press "SET" key to enter into setting mode ,then enter password. The more detail is
described in "Operation of Control key "
Mode
P***
Out/a/b
LInE/OFF/
setting Value
Function
Description
* "P000"(factory default password) is shown
*Move cursor from first digit to right end digit by
pressing "CLR" key,finally press once more if
password is not changed from factory default value, but
if password is changed, then make required digit by
Password input using "UP","DN" key untill operator meets changed
password.
*Make power-on again as keeping both “UP” and
“DN” key pressed under power-off in order to make an
initialization to factory default
* initial state of main trip output is defined as followed
condition.
▸a : main trip output/95-98(1a) is energized
(open→close) in case normal forwarded voltage is
sensed after control power is loaded
▸b : main trip output/95-98(1a) is not energized
(open→open) in case normal forwarded voltage is
to select initial
state of main
sensed after control power is loaded
trip output
* initial trip is happened without concerning with above
definition for initial state if one of over/under
voltage,voltage unbalance,phase loss and reverse
phase is sensed
▸phase loss : trip right after sensing.
▸reverse phase,voltage unbalance,over/under
voltage : trip after preset time is elapsed.
*OFF:the sensed voltage is only shown as trip output is
to select line
not come out
voltage
* to define the value of incoming line voltage:100~
500VAC
Factory
Default
000
a
440
*1P:single phase motor/disable for phase loss & reverse 3P
to select
PhAS/
phase, voltage unbalance /voltage must be loaded
phase of power
1P/3P
between L1 and L2
line
*3P:3 phase motor protection
to select a base
*L : to show line voltage
to display
trAn/L/A
*A : to show average voltage
incoming
voltage
to preset a time *OFF : disable
dt/OFF/setting to stop
*1~60sec/definite,adjustable
value
protection
*all protective function except reverse state is stopped
function
during “dt”,but detected voltage is shown
*OFF : disable
*to protect over voltage according to preset value in
"LInE" mode
*protection range : under 20% based on line input
ov/OFF/setting to protect over voltage
value
voltage
*Auto reset is possible only after a sensed voltage
is dropped under preset valued voltage after a time
of “AUo” mode is elapsed continuously
*Auto reset is done in case line voltage is not loaded
*This mode is not available in case initial PL(phase loss)
is happened
to define
voltage-trip
*dEF : definite
Otc/dEF/Inv
time
*Inv : Inverse
charateristics
to preset trip *to preset trip delay time after sensed voltage is over
ovt/setting
delay time to
preset value
value
protect over
*definite : 0.2∼20sec/adjustable
voltage
*inverse : 1~10 Class
uv/OFF/
to preset trip *OFF : disable
setting
delay time to *to protect under voltage according to preset value in
value
protect ubder
"LInE" mode
voltage
*protection range:over 20% based on line input voltage
*Auto reset is possible only after a sensed voltage is
risen over preset valued voltage after a time of “AUo”
mode is elapsed continuously
*This mode is not available in case initial PL(phase loss)
is happened
to preset trip
*to preset trip delay time after sensed voltage is under
uvt/setting
delay time to
preset value
value
protect under
*1∼20sec/definite,adjustable
voltage
L
OFF
OFF
dEF
1
OFF
10
*OFF : disable
*trip in case voltage unbalance rate is over 45%
:[(max-min)/max]*100[%]
* 0.5 ~ 5 sec/definite,adjustable
to protect phase
*In case 3 phase is normal power-off state, this mode is
PL/oFF/ setting loss by
not worked.
value
incoming line
*This protection is not available for the load such as a
voltage
motor which the reversed voltage can be created by the
internal common point of 3 phase line ,but available for
initial phase loss
*This mode is not available for single phase line.
RP/oFF/ setting to protect
*OFF : disable
value
reverse phase * within 0.5sec
by incoming *In case 3 phase is normal power-off state or phase
line voltage
loss state , this mode is not worked.
*Auto reset is not possible,but manual reset.
*”dt” is not interfaced with this mode
v-Ub/oFF/
setting value
to preset
voltage
unbalance
protection
rate(%)
v-Ut/setting
value
to preset
operating trip * to preset a operating trip time for voltage unbalance
delay time for *Adjustable range: 1~10 sec
voltage
unbalance
rESt/Hr/Er
*trip in case preset rate condition is kept on preset time
or more
*rate:[(Max V-Min V)/Max V]*100 [%]
*adjustable range:5%~30%
to decide how *to decide how to reset in case of trip
to reset trip
*Hr : manual reset by key touch
state
→Password Input :rP ,PL/trip state is still remained
even in case of power OFF-ON,but possible only
by password input
→”CLR” key: OV,UV,v-UB
→ not possibl to preset setting value under trip state
*Er : electrical reset
→ "CLR" Key
→ Control power off
→ Auto reset
: “OV”, “UV”, “v-Ub”
:possible to reset naturally after preset time by
“AUT” mode is elapsed if trip cause is clear
→ not possibl to preset setting value under trip state
OFF
OFF
oFF
3초
Er
caused by “PL” and “RP”,but possible to preset
under trip state caused by “OV”, “UV” and “v-Ub
Aut
to decide auto
reset time
3
*possible to preset auto reset time in case “Er” is preset
in “rESt” mode
*1sec~10 sec
to decide
OFF
*OFF/basic factor : line voltage/average voltage
additional
[L1,L2,L3] to indicate orderly in every 3 sec.
factor besides
rotA/ON/OFF
*ON : frequencty is added to basic factor
basic factor to
*possible to fix one of rotated factor or to release as
indicate value
pressing "CLR" key repeatedly
in the order
*to check latest 8 trip cause
to show latest *press "UP" or "DN" in the "trip" mode, then trip cause
trIP /8 ~1/trip 8 trip cause
and value is shown alternatively
cause / trip
orderly
*press "CLR" or ""SET" to check next event or previous
-value
event
*In order to enter setup state on the way of trip condition
check, press "DN" or "UP"
*oFF : disable for this mode
to preset delay
*preset time:1sec~10sec
time to show
v-ot/oFF/
*”v-ot” is shown initially if voltage is not detected
“v-oFF’ if
setting
during an operation, but finally ”v-oFF’ is shown after
voltage is not
value
preset time is elapsed
detected while
*operational condition for “v-oFF” in “out” mode
working
shall be applied for this mode as well
Test
*to check if this relay is ready to work normally or not.
*"tESt" is appeared in case the operator press "CLR" key for 3 sec or more,
then release pressed "CLR" key when “tESt” is shown
*Trip output(95-98) will be energized after counting down preset ovt-time
*press “CLR” key to reset after test trip
▶ Cab(calibration) Mode
This mode is appeared as pressing "SET" key for 10 sec or more ,and is disappeared
as "SET'key once more
Mode
Function
P***
Password
Input
vrPE
to have a
Description
*need to input password to adjust this mode group so that
authorized person may be able to adjust.
*How to input is aame as it of main mode
*to show present sensed voltage
Factory
Default
000
0
vsPE
vtPE
`
calibration for *Possible to adjust with +,- 1V step size with 100V adjust
phase "L1"
range
voltage
to have a
calibration for
phase "L2"
voltage
to have a
calibration for
phase "L3"
voltage
to change
Password
*Possible to enter new digit by using "UP" or "DN" key
after positioning a cursor on the required digit
*Press both "SET" & "CLR" key in order to come out
setting mode and the changed password is stored.
6. The order of Rotated Mode
0
0
000
7.PIN Assignment
DIV
Input
Output
Socket Pin
2
7
5
4
3
5
4
6-8-1
8. Indication feature
Description
* Control Voltage/AC 85V∼AC260V,50/60Hz
(DC90V∼DC370V)
Phase L1 voltage
3 Phase application
Phase L2 voltage
Phase L3 voltage
Phase L1 voltage
1 phase application
Phase L2 voltage
Main trip/95-96-98,1c(SPDT)
9.Control key Operation
*Note: trip will be occurred after completing preset process if trip condition is happened
during preset process
*Press "SET" Key to enter into setting mode, then "P000"/”P0000” (factory
default password) is shown
*Move cursor from first digit to right end digit by pressing "CLR" key,
finally press once more if password is not changed from factory default
1.”SET” key
value, but if password is changed, then make required digit by using
"UP","DN" key untill operator meets changed password.
*If there is no input for 15sec or pressing both "SET" and "CLR"key, it can
be entered into operating condition.
*After entering into possible state for preset , each key acts its job as
2. Changed
follows :SET→backward direction ,CLR→foward direction ,UP,DN→
feature of Setting able to select number or character in preset mode.
Key
*The previous mode based on setting mode is come out as pressing "SET"
key during doing a prest job
3."SET" Key &
"CLR" Key/ to
*Possible to select Mode by using "SET" or "CLR" key
select MODE
4."UP" key &
*Possible to preset required value as selection a character or number by
"DN"Key/Adjust using UP/DOWN
*The storage for preset data is completed by pressing both SET and CLR
5."SET" &
key in the same time or after 15sec is elapsed
"CLR"Key/
*The character and/or a number that is already preset in the above preset
Store
process is stored in one times.
*While each factor is rotated, one of rotated factor is fixed by pressing
"CLR" key and released as pressing once more
6.“CLR" key
*After fixing a operating factor, the operator is able to rotate manually one
by one as pressing "UP"(forwardly), "DN" (reversely)
*Average voltage is shown without rotating if average voltage is selected.
*possible to check preset and/or change value of each mode as pressing
To check and/or
“SET” key once during operation,
change preset
*”P000”/”P0000” is shown as pressing “SET” key
value of each
*preset value and mode are appeared alternatively and to check an/or change
mode during
preset value
operation
*next mode as pressing “CLR” Key
Self-Test/Reset
: "CLR" Key
*return to operating mode as pressing both “SET” and "CLR" key or waiting
for 15sec without any touch
*to check if this relay is ready to work normally or not.
*"tESt" is appeared in case the operator press "CLR" key for 3 sec or more
only in case control power is loaded,without loading V1,V2,V3 , then
release pressed "CLR" key
*Trip output(95-98) will be trip after counting down preset ovt time as
showing “0-0”
*Make reset a trip as press “CLR” key once more
10.Over voltage trip time characteristic
11.Trip indication
Trip cause and caused value is appeared alternatively
Trip
Display
Cause
Over voltage
*trip caused by over voltage in phase
L1-L2
Under
voltage
*trip caused by under voltage in phase
L1-L2
Reverse
phase
* trip caused initially by reverse phase of
incoming power line
Phase loss
*trip caused by phase loss of incoming power
line, phase L2
*Indication is shown based on “RP” condition if
phase loss is occurred under “RP” state
Volarge
unbalance
*trip caused by voltage unbalance in L1-L2
*The difference value of [max-min] and “vub” is
shown anlternatively
Zero voltage
*to show that voltage is not sensed
*The operation voltage is dropped under 35V
while normal operation is done or zero(0)
initially
12. Rotated indication
▸If line voltage value with normal phase order is sensed after the control power is loaded, then 3
phase line voltage indication is rotated
▸output(95-98) is energized (Open→Close) as normal phase voltage is loaded if out” mode is
preset “a”
▸output(95-98) is not energized (Open→Open) if out” mode is preset “b”
▸however v.oFF is shown if the voltage is not sensed or the voltage is dropped into 0V(Zero Volt)
while normal operation is done
▸If single phase is applied. V-OFF or actual voltage is shown
▸”dt”(trip delay time) mode is preset “OFF”
a)Preset “a” in “out” mode
•Main trip output(97-98) is trip at once in case initial line phase state is phase loss
•Main trip is energized ,then is trip after operational trip time is elapsed in case initial line phase
state is under reverse phase,over/under voltaege and voltage unbalance as each mode is preset
valued condition,also trip cause is shown
b)Preset “b” in “out” mode
•”PL” is shown during “dt” in case initial line phase state is phase loss, consequently main trip
output(97-98) is trip right after “dt” is elapsed
•Main trip output(97-98) is trip after the sum of “dt” and operational time is elapsed in case initial
line phase state is under reverse phase,over/under voltaege and voltage unbalance as each mode
is preset valued condition,also trip cause is shown
▸”rotA” Mode : OFF → voltage of L1, L2, L3
▸”rotA” mode: ON → voltage of L1,L2,L3, Frequency
▸Average voltage : same as a case of line voltage by “rotA” ON,OFF
▸Bar graph indication : DSP-DVR-M Type
 Operational state
The ratio of a sensed voltage to preset “ov” value is shown
e.g. preset value for “ov”:400V, sensed voltage :320V, then bar graph:80%
 Trip state
13.Time-Voltage based trip output
▸Over Voltage : “out” mode/a, trip caused by over-voltage during a normal operation
▸Over Voltage : “out” mode/b, trip caused by over-voltage during a normal operation
▸ Over/Under voltage: “out” mode/a, auto reset after trip during a normal operation
▸ Over/Under voltage: “out” mode/b, auto reset after trip during a normal operation
14.Application Sequence Diagram
15.Dimension
▶DSP-DVR
▶DSP-DVR-M
▪ Converter
▪ Display meter
16.Order form
DIV
1
2
3
Type
Control Power
Frequency
Reference Code
DSP-DVR
DSP-DVR-M
DSP-SOCKET-8P
DSP-DVR
DSP-DVR-M
B
Z
7
Description
Panel Mounting Type
Panel Flush Mounting Type
24VDC(Optional)
85~260VAC(90~370VDC)
50/60Hz
Description
Panel Mounting Type,3Phase incoming voltage,8PIN Socket embedded,
Control power/85~260VAC (90~ 370 VDC), Possible to fix line voltage
in “Line” mode:100~500 VAC
Panel Flush Mounting Type,3Phase incoming voltage, 8PIN Socket
embedded,Control power/85~260VAC(90~ 370VDC),Possible to fix line
voltage in “Line” mode: 100~500 VAC
8PIN Socket